Ideal ND2396 User Manual

2
#61-802
800 Series
Power Clamp Meter
1. Transformer Jaw
2. Transformer Trigger
3. Data Hold Button
4. Rotary Function Switch
5. LCD Display
6. Function Buttons
7. Input Terminals
1
3
4
5
6
7
2
61-802
Power Clamp
OLD
F
3ØP
C
A
0
0
2
0
0
2
KVARKVA
D
+
0 0
H
C
F
OF
W
K
W
K
F
P
A
V
H
VA
3Ø3W
3Ø4W
True RMS
61-802
Power Clamp
OLD
HzV
VA
3Ø4W
PFKW
H
OFF
3ØPF AC+DC 2000KW 2000A
KVARKVA
3Ø3W
True RMS
Ø
3
DC A/W
ZERO
READ
KVAR
REC
XT
E
N
KVA
CAT III - 600V
Ø
3
C
D /W
A
O
R
E
Z
C
D
A
E
R
C
VAR
E
K
R
T
X
E
N
VA
K
V
0
III - 60
T
A
43
WARNING!
1. DO NOT UNDER ANY CIRCUMSTANCES EXCEED THESE RATINGS:
- Voltage is not to exceed 800 Volts.
- Wattage, Resistance and Continuity functions are not to be performed on circuits capable of delivering greater than 600 Volts.
- Current measurements are not to be performed on cir­cuits capable of delivering greater than 500 Volts
2. To avoid electrical shock hazards and/or damage to the meter:
- Do not exceed the voltage ratings for the meter. Use caution when measuring voltage.
- Do not use during electrical storms. AC power sources with inductive loads or electrical storms may result in high voltage. High energy transients can damage meter and pre­sent a dangerous shock hazard.
- Turn off power to the circuit or device being measured before taking resistance and capacitance measurements. Fully discharge all capacitors before measuring.
3. Ensure meter is in proper working order before using. Visually inspect meter for damage. Performing a continuity check can verify proper operation. If the meter reading goes from overload to zero, this typically means the meter is in proper working order.
4. Visually inspect leads for damage before using. Replace if insulation is damaged or leads appear suspect.
5. Never ground yourself when taking electrical measurements. Do not touch exposed metal pipes, outlets, fixtures etc. Keep your body isolated from ground by using dry clothing, rubber shoes, mats, or any other approved insulating mater­ial. Keep your fingers behind the finger guards on the probes. Work with others.
6. Before beginning all unknown measurements, set meter to highest possible range.
7. Before breaking a circuit for testing, turn off the power to the circuit. When disconnecting from a circuit, disconnect the hot lead first, then the common lead.
8. Disconnect the meter from the circuit before turning off any indicator, including motors, transformers, and solenoids.
Data Hold Button
The data hold button is used to capture and hold a reading on the LCD display.
Press the button again to release the reading.
LCD Display
3-3/4 digit display with maximum indication of 3999.
Function symbols, units, analog bargraph, low battery sym-
bol, min/max symbols, relative symbol, and zero symbol are included.
Function Buttons DC A/W ZERO Button
The DC A/W Zero button is used to zero out the DCA resid­ual value.
Press this button until the LCD displays a zero value and the zero symbol.
This button does not force the meter into manual range mode.
Press and hold the DC A/W Zero button for 2 seconds to disable this function.
REC Button
The meter can store 4 data points in memory.
Pressing the REC button will store the current value into
memory.
The data point number (1-4) will be shown on the upper display, and the stored data will be shown on the main dis­play for approximately 3 seconds.
After all four data points have been stored, the meter will display FULL on the secondary display when the REC but­ton is pressed.
When data is stored in memory, the REC symbol is shown on the LCD display.
This data can be viewed by pressing the READ NEXTbutton.
This data is stored until the meter is turned off.
5
3φKVAR KVA Button
The 3φKVAR KVA button toggles between the KVAR/KVA measurements and the PF/kW measurements in the 3φ3W or 3φ4W functions.
Toggling between these measurements can only be done after the power clamp has calculated the power factor and kW measurement.
Read Next Button
In 3φ3W Function
Pressing the read next button stores the measured values for kW
RS(L1L2)
/kVA
RS(L1L2)
and moves to the next measurement.
Pressing read next after the kW
TS(L2L3)
/kVAR
TS(L2L3)
stores the values and calculates the kW and PF values for the 3φ3W system.
After these values have been calculated, press the 3φKVAR KVA button to display the KVAR and KVA values for the sys­tem.
To start another calculation, press the read next button again to return and take a measurement for the kW
RS(L1L2)
/kVARS
(L1L2)
values.
In 3φ4W Function
Pressing the read next button stores the measured values for W
R(L1)
/PF
R(L1)
and moves to the next measurement.
Pressing read next after the W
S(L2)
/PF
S(L2)
stores the values
and moves on to the next measurement.
Pressing read next after the W
T(L3)
/PF
T(L3)
stores the values
and calculates the kW and PF values for the 3φ4W system.
After these values have been calculated, press the 3φKVAR KVA button to display the KVAR and KVA values for the sys­tem.
To start another calculation, press the read next button again to return and take a measurement for the W
R(L1)
/PF
R(L1)
values.
6
In any other function
Pressing the read next button in any other function displays the measurement values stored with the REC button.
The REC NO. symbol will be shown on the LCD display and the record number will flash on the secondary display to noti­fy the user of what values are being displayed.
Pressing this button after the meter displays last stored data point returns to the first stored data point.
To exit the read next mode, turn the function switch to any other function. This will exit without losing the stored data.
Kilowatt/Power Factor Measurements
Kilowatt Range Resolution Accuracy Voltage/Current (AC+DC True Power) Range
0-99.99kW 0.01kW ±(2.0% +0.05) 600VAC, 800VDC 100-999.9kW 0.1kW 2000A AC/DC 1000-1600kW 1kW ±(2.0% +5)
Power Factor 0.2-1.0 for 1φ2W, 1φ3W, 3φ3W, and 3φ4W
Autoranging Table 0-200VAC 200-600VAC
0-200VDC 200-800VDC
0-200A 0.00-40.00kW 0.00-99.99kW
100.0-160.0kW
200-2000A 0.0-400.0kW 0.0-999.9kW
1000-1600kW
61-802
Power Clamp
HOLD
F
3ØP
C
D
+
C
A
F
OF
W
K
0
0
0
2
W
K
F
P
A
0
0
0
2
V
z
H
VA
KVARKVA
3Ø3W
3Ø4W
True RMS
Ø
3
C
D
D
A
E
R
R
A
C
V
E
K
R
W
/
A
T
NEX A
V
K
O
R
E
Z
V
0
0
6
-
I
I
I
T
A
C
To measure Kilowatts and Power Factor in a single phase 2-wire system
Set rotary switch to PF/kW without jaws clamping onto any wire
If the watt reading is not zero, press the DC A/W ZERO button once to zero out the watt reading.
Insert the black test lead into the COM terminal and the red test lead into the + terminal.
Connect the black test probe to the neutral conductor and the red test probe to the hot conductor.
Using the trigger to open the jaws, fully enclose the hot conductor within the clamp.
Release the trigger and be sure that the jaws have closed completely.
The power clamp selects the appropriate range based on the Autoranging table.
Power Factor (PF) is a calculated value based on the formula
PF=_______
The kW value is shown on the main display and the PF value is shown on the upper display.
Positive PF (+) indicates an inductive load, while negative PF (-) indicates a capacitive load.
8
To measure Kilowatts and Power Factor in a single phase 3-wire system
See section on 1φ3W AC+DC Power Measurements
AC+DC Voltage/Frequency Measurements
Voltage Resolution Accuracy Accuracy Input Range (50/60Hz) (40-400Hz) Impedance
0-200V 0.1V ±(1.5% +5) ±(2.0% +5) 10M 200-500V 500-600VAC 1V 500-800VDC
Overload Protection: 800V TRMS Measurements Accuracies specified at Crest Factor <3.5
Frequency Range Accuracy Sensitivity
50/60Hz ±(0.5% + 2) >5V 10-400Hz
To Measure Voltage and Frequency
Set the rotary switch to V/Hz
Insert the black test lead into the COM terminal and the red
test lead into the + terminal.
Connect the test probes in parallel with the load or circuit.
The power clamps automatically selects the proper range.
Note: The “+” sign on the jaw must face the power source for correct measurement.
kW
kVA
3ØPF AC+DC 2000KW 2000A
OFF
PFKW
HzV
3Ø3W
3Ø4W
KVARKVA
VA
D
C A
/
W
Z
E
R
O
R
E
C
3
Ø
K
V
A
R K
V
A
R
E
A
D
NEX
T
HOLD
CAT III - 600V
P
o
w
e
r
C
l
a
m
p
True
R
M
S
6
1
-
8
0
2
7
Loading...
+ 8 hidden pages