Ideal ND2292 User Manual

2
#61-156 #61-157 #61-158
SureTest®Model ST-1TH D & ST-1THDC Instructions
Introduction
The SureTest®family of Circuit/distortion analyzers identify problems common to electrical circuits and harmonic distortion quickly, easily and accurately. They have a patented voltage drop test, which applies a full 15-ampere load without causing interruption to equipment on the circuit. This family also features 64K of memory to store and recall up to 36 hours of testing.
Product Features
• Identifies and Locates Loose Wire Connections Bad Splices/Receptacles High Resistance Grounds False (Bootleg) Grounds Shared Neutrals
• Verifies Proper GFCI Operation Dedicated Circuit Presence Isolated Ground Presence (with the 61-176 Adapter)
• Measures True RMS Line Voltage Resistance of Hot and Neutral Conductors Ground Impedance % Voltage Drop by Conducting an Actual Full 15 Amp Load Test % Voltage Drop by Simulating a 20 Amp Load Test GFCI Trip Time True RMS Neutral-to-Ground Voltage Estimated Load on Circuit Line Frequency Power Consumption Power Factor % Total Harmonic Distortion (THD) in the Line Voltage (to the 31st
Harmonic)
Product Features
• Measures % THD in the Neutral Current (to the 31st Harmonic) True RMS Current with the 61-181 Clamp Adapter (ST-1THDC)
• Event Recording Captures up to 36 hours of testing Min/Max/Avg/Peak Line Voltage Resistance in Hot, Neutral, and Ground Conductors Min/Max/Avg/Peak Neutral-to-Ground Voltage % THD in the Line Voltage and Neutral Current % THD per Harmonic up to the 31st Harmonic Line Frequency
General Operation
The SureTest Models ST-1THD and ST-1THDC Circuit/Distortion Analyzers take only seconds to test each outlet and circuit under a full load. The ST-1THD features two easy to use operating menus. The Wiring Menu gives access to measurements of line voltage, voltage drop at a full 15 amperes and 20 amperes, ground-to-neutral voltage, resistance of the hot a neutral conductor, ground impedance. A ground fault circuit interrupter (GFCI) test is also performed that will disrupt the electrical supply if a func­tional GFCI is present.
The Wave Form Menu gives access to measurements of % line voltage total harmonic distortion (THD), line voltage harmonics to the 31st harmonic, % neutral current THD, neutral current harmonics to the 31st harmonic and line frequency.
In addition to these two programming menus, the ST-1THDC features a third menu when used with the #61-181 Amp Clamp Adapter. The Clamp Adapter Menu gives access to measurements of True RMS current, THD, and harmonics to the 31st harmonic.
Any discrepancies from a normal reading indicate that a problem has been detected in the circuit.
For use in 3-prong (grounded) outlets, inset the ST-1THD into the recepta­cle with the ground pin extended. For use in 2-prong (non-grounded) out­lets, leave the ground pin retracted. In non-grounded (2-prong) outlets many of the tests will be non-functional due to an absence of ground.
4
WARNING
Do not use on outputs from UPS systems, light dimmers or square wave generating equipment.
Insert the unit into the receptacle; observe test results and then move on to the next receptacle. Allow at least 20 seconds between insertions. Repeatedly inserting the SureTest into a receptacle will exceed its ability to dissipate heat within the unit, resulting in fluctuating readings or damage to the unit.
Wiring Verification
The St-1THD will test the wiring of a receptacle to identify if errors are pre­sent. Error messages will be displayed for polarity reversal, no ground, and false ground conditions.
“E_rP” on the LED display indicates that the hot and neutral wires are reversed.
“E_nG” on the LED display indicates that no ground is present. The ST­1THD will not perform any of the tests involving the ground circuit if a no ground condition is detected.
“E_FG” on the LED display indicates a false ground condition. False ground is defined as a short between the ground and neutral wires very close to the receptacle. A false ground may also be indicated if the recepta­cle is within 15 feet of the neutral-ground bonding point at the panel, or if conduit is being used as the ground conductor.
Specifications
Case Construction: GE Cycolac plastic molded Operating Range: All measurements except voltage drop, FG, drop, FG, conductor resistances: 80-300 Volts AC @ 50-60 Hz Voltage drop, False Ground & Conductor Resistances: 80-150 Volts Harmonic Display: Odd, 3 - 15 + Bal. To 31 All Measurements: True R.M.S.
Specifications (continued)
Crest Factor: Peak / True R.M.S. Memory Hold/Recall: 36 Hours Power Use: 2 Watts continuous, 1800 W peak Digital Display: Seven segment L.E.D., 3” Accuracy, Display: 1% of full scale +/- 1 digit Operating Temp: 0º C to 50º C Storage Temp: -20º C to +65º C Dimensions: 7” X 3” X 1.5” Weight: 7 ounces #61-181 Amp Clamp Adapter: 3 to 500 Amps, Jaw opening -1.3 inches
Test Procedures
The programming menus feature a simple single button operation to advance between various measurements. The programming set the mea­surements in a series of menu and submenu options to make navigation through the menu structure easier.
3
®
1
2
LED Display Display Advance Button
1 2
SureTest
Circuit/Harmonics Analyzer
L
P
A
S
I
Y
D
A
E
D
C
V
N
A
61-156 ST-1THD
WIRING MENU
L = Line Volts (True RMS) 15 = % Volt Drop 15 Amp. Gn = Volts Ground - Neutral (True RMS) rES = Ohms Resistance GFCI = Exact Trip Point rCL = Recall Memory
WAVE FORM MENU
(HOLD BUTTON & INSERT) LT = Line Voltage % THD LH = Line Harmonics % nT = Neutral Current % THD nH = Neutral Harmonic % F = Line Frequency rCL = Recall Memory
Press Button for 3 Seconds to Access Sub Menu
65
Menu Structure for Outlet Circuit Testing
Submenu
Display Menu Display Measurement
L- Line Voltage True RMS Line Voltage
Hi= Highest Line Voltage Lo= Lowest Line Voltage A= Average Line Voltage P= Peak Line Voltage
15= Voltage Drop % Voltage Drop at 15 Ampere Load
20= % Voltage Drop at 20 Ampere Load
Gn= Ground-to-Neutral Voltage TRMS Ground-to-Neutral Voltage
Hi= Highest Ground-to-Neutral Voltage Lo= Lowest Ground-to-Neutral Voltage A= Average Ground-to-Neutral Voltage P= Peak Ground-to-Neutral Voltage ELL= Estimated Load on Circuit Ld= Load (Watts) PF= Power Factor of Load
rES= Resistance
rn= Neutral Conductor Resistance rH= Hot Conductor Resistance rG= Ground Impedance
GFCI= GFCI Trip time
Countdown of Trip Time Testing GFCI Time to Trip
rCL= Recall Memory
Blinking rCL SureTest is Recording Data Sto Recording Completed
Outlet Circuit Testing
Unless a wiring error exists, the ST-1THD will show "Out" in the LED dis­play. This indicates that the unit is calibrating itself prior to testing. After this calibration is performed, the ST-1THD automatically enters into the out­let circuit testing programming menu. The LED display cycles between the menu heading, and the measurement every four seconds. Press and hold the display advance button for one second to move to the menu. To enter the submenu, press the display advance button for three seconds. To navi­gate from measurement to measurement within the submenu, press the dis­play advance button. While in the submenu, pressing and holding the dis­play advance button for three seconds brings the unit back to the menu structure.
1. Insert the ST-1THD into the receptacle
2. The LED display shows Out indicating self-calibration of the unit
3. The LED display cycles between L_, indicating that True RMS Line Voltage is being measured, and the Line Voltage measurement every four seconds.
4. Press and hold the display advance button for three seconds to access the Line Voltage submenu.
5. The LED display alternates between Hi, indicating that the highest line voltage is being measured, and the measurement every four seconds
6. Press the display advance button for one second to move to the next test within the Line Voltage submenu.
7. Press and hold the display advance button for three seconds to return to the main menu.
87
Line Voltage Menu
Menu Heading - L-
Measurement at Menu Heading - True RMS Line Voltage
Submenu - yesHi= - Highest Line VoltageLo= - Lowest Line VoltageA= - Average Line VoltageP= - Peak Line Voltage
The submenu values are the highest, lowest, average and peak values taken since the SureTest was plugged in.
Voltage Drop Menu
Menu Heading - Gn-
Measurement at Menu Heading - % Voltage Drop under a full 15 Amp
Load
Submenu - yes20= - Voltage Drop under 20 Amp Load
The test results for the 20 Amp load test are simulated based on an actual 15 Amp load.
Ground-to-Neutral Voltage Menu
Ground-to-neutral voltage results from current flowing in the neutral con­ductor from other equipment on the circuit. High ground-to-neutral voltage indicates that the circuit may be loaded near its capacity or the neutral con­ductor may be shared or carrying harmonic distortion. A reading of less than 2 volts usually indicates a usable outlet. An excessive ground-to-neu­tral voltage may result in inconsistent or intermittent equipment performance
This test can also be used to verify a dedicated circuit. A measurement greater than 0.1 volts indicates that the receptacle under test is not on a dedicated circuit.
Menu Heading - Gn-
Measurement at Menu Heading - True RMS Voltage, Ground-to-Neutral
Submenu - yesHi= - Highest Ground-to-Neutral VoltageLo= - Lowest Ground-to-Neutral VoltageA= - Average Ground-to-Neutral VoltageP= - Peak Ground-to-Neutral VoltageELL= - Estimated Load on CircuitLd= - Load (Watts)PF= - Power Factor of Load
The submenu values are the highest, lowest, average and peak values taken since the SureTest was plugged in.
After the display is advanced to Ld in the submenu, it will cycle between the load and power factor measurements. Pressing the display button will not advance the unit through the programming sequence. After these mea­surements are taken, the unit must be removed from the receptacle and re­inserted.
Resistance Menu
Menu Heading - rES-
Measurement at Menu Heading - None
Submenu - yesrn= - Resistance of Neutral Conductor rH= - Resistance of Hot ConductorrG= - Ground Impedance
The St-1THD checks ground impedance by pulsing 15 amperes from hot-to­ground to ensure that the resistance is less than 1 Ohm.
GFCI Menu
The ST-1D applies 6mA to ground through a fixed resistor to trip the GFCI. A functional GFCI will disconnect the power. The reset may be at the outlet or at the panel.
WARNING
When testing 3-wire outlets, do not proceed with the GFCI test if the Wiring Indicator lights indicate a No Ground condition exists. Repair the ground circuit first.
109
GFCI Menu (continued)
Menu Heading - GFC=
Measurement at Menu Heading - None
Submenu - No
Pressing the display advance button for three seconds will activate the GFCI test. The ST-1THD applies 6mA to ground through a fixed resistor to trip the GFCI. A functional GFCI will disconnect the power. The reset may be at the outlet or at the panel. The tester will display the calculated time to trip, apply the current and count up to the calculated time.
If the GFCI is functioning properly, the circuit will disconnect, and the LED display on the ST-1THD will go out. When the circuit is reset, and power is returned, the LED display will show the actual time to trip.
If the GFCI fails to trip, the LED display will show "bAd", which indicates that the GFCI may be installed incorrectly, or the GFCI may be defective.
WARNING
In order to test GFCIs in a 2-wire system (no ground wire), the #61-175 ground continuity adapter must be used. Connect the ground lead on the adapter to a ground, such as a metal water or gas pipe.
Recall Memory Menu (Event Recording)
Stored data can be viewed from the Recall Memory menu. Pressing the dis­play advance button for three seconds enters the submenu. The submenu is identified by a blinking rCL on the LED display. Once in the submenu, pressing the display advance button gives access to the stored values from memory. These values are accessed through the outlet circuit testing menu. While stored values are being displayed, the LED will blink to differentiate these values from the live values being captured in standard testing mode. Navigating through the outlet circuit testing menu while in recall memory mode is identical to navigation through the menu in standard operation.
While the ST-1THD is in operation, the unit will analyze and store data on the various measurements. These values can be permanently stored into the memory from the Recall Memory submenu. Pressing the display advance button for three seconds when a blinking rCL is shown on the display will store all of the data into memory, overwriting any previous data in memory.
It is important to note that pressing the blinking "rCL" to exit viewing recorded data stores new data into permanent memory. If you wish to main­tain the stored data, but want to return to standard operation mode, unplug the SureTest and re-insert it into the receptacle. The SureTest will return to operation mode.
Menu Heading - rCL-
Measurement at Menu Heading - None
Submenu - yes Blinking rCL - Allows access to stored values from memory Sto - Stores values into memory
Harmonic Wave Form Testing
To access the harmonic wave form programming menu, press the display advance button and insert the ST-1THD into the receptacle. "HAr" will be shown on the LED display . The LED display cycles between the menu heading, and the measurement every four seconds. Press and hold the dis­play advance button for one second to move to the menu. To enter the sub­menu, press the display advance button for three seconds. To navigate from measurement to measurement within the submenu, press the display advance button. While in the submenu, pressing and holding the display advance button for three seconds brings the unit back to the menu structure.
1. Press the display advance button and insert the ST-1THD into the recep­tacle
2. The LED display shows HAr indicating self-calibration of the unit
3. The LED display cycles between Lt_, indicating that % Line Voltage Total Harmonic Distortion (THD) is being measured, and the THD mea­surement every four seconds.
4. Press and hold the display advance button for three seconds to access the Line Voltage submenu.
5. The LED display alternates between Hi, indicating that the highest dis­tortion is being measured, and the measurement every four seconds
6. Press the display advance button for one second to move to the next test within the % Line Voltage THD submenu.
7. Press and hold the display advance button for three seconds to return to the main menu.
12
11
Menu Structure for Wiring Harmonic Distortion Testing
Submenu
Display Menu Display Measurement
Lt- % Line Voltage THD Line Voltage THD
Hi= Highest Line Voltage THD Lo= Lowest Line Voltage THD A= Average Line Voltage THD LC= Crest Factor
LH- Line Voltage Harmonics
h3= %THD at 3rd Harmonic h5=...h15= % THD for each odd numbered
Harmonic through the 15th Harmonic
bAL= Total of the remaining % THD from
17th Harmonic to 31st Harmonic
nt- % Neutral Current THD Neutral Current THD
Hi= Highest Neutral Current THD Lo= Lowest Neutral Current THD A= Average Neutral Current THD nC= Crest Factor
nH- Neutral Current Harmonics
h3= %THD at 3rd Harmonic h5=Öh15= Hot Conductor Resistance bAL= Total of the remaining % THD from
17th Harmonic to 31st Harmonic
Frequency Value Line Frequency
rCL= Recall Memory
Blinking rCL SureTest is Recording Data Sto Recording Completed
% Line Voltage THD Menu
Menu Heading - LT-
Measurement at Menu Heading - % Line Voltage THD
Submenu - yesHI= - Highest % THDLo= - Lowest % THDA= - Average % THD LC= - Crest factor of the line voltage
The submenu values are the highest, lowest, and average values taken since the SureTest was plugged in.
Line Voltage Harmonics Menu
Menu Heading - LH-
Measurement at Menu Heading - None
Submenu - yesh3= - % THD at 3rd harmonich5= - % THD at 5th harmonich7=”...”h15 - % THD is given for every odd harmonic to the 15th
harmonic bAL= - Total of the remaining %THD from the 17th to 31st harmonic
% Neutral Current THD Menu
Menu Heading - nt-
Measurement at Menu Heading - % Neutral Current THD
Submenu - yesHi= - Highest % THDLo= - Lowest % THDA= - Average % THD nC= - Crest factor of the neutral current
Neutral Current Harmonics Menu
Menu Heading - nC-
Measurement at Menu Heading - None
Submenu - yesh3= - % THD at 3rd harmonich5= - % THD at 5th harmonich7=”...”h15 - % THD is given for every odd harmonic to the 15th harmonicbAL= - Total of the remaining %THD from the 17th to 31st harmonic
1413
Line Frequency
Within this menu selection, the ST-1THD displays the line frequency of the current. There is no submenu for this menu selection.
Recall Memory Menu (Event Recording)
Stored data can be viewed from the Recall Memory menu. Pressing the display advance button for three seconds enters the submenu. The sub­menu is identified by a blinking rCL on the LED display. Once in the sub­menu, pressing the display advance button gives access to the stored val­ues from memory. These values are accessed through the outlet circuit testing menu. While stored values are being displayed, the LED will blink to differentiate these values from the "live" values being captured in stan­dard testing mode. Navigating through the outlet circuit testing menu while in recall memory mode is identical to navigation through the menu in stan­dard operation.
While the ST-1THD is in operation, the unit will analyze and store data on the various measurements. These values can be permanently stored into the memory from the Recall Memory submenu. Pressing the display advance button for three seconds when a blinking rCL is shown on the display will store all of the data into memory, overwriting any previous data in memory.
It is important to note that pressing the blinking “rCL” to exit viewing recorded data stores new data into permanent memory. If you wish to maintain the stored data, but want to return to standard operation mode, unplug the SureTest and re-insert it into the receptacle. The SureTest will return to operation mode.
Menu Heading - rCL
Measurement at Menu Heading - None
Submenu - yes Blinking rCL - Allows access to stored values from memory Sto - Stores values into memory
Testing with the #61-181 Clamp Adapter
These tests can only be accessed by using the #61-181 amp clamp adapter with the model ST-1THDC. Power must be supplied to the unit by an exten­sion cord or battery pack to test the unit with the clamp adapter.
When the adapter is plugged into the ST-1THDC, the LED display will show Ct indicating that the adapter is correctly plugged into the unit. The ST­1THDC will then automatically enter into the current probe programming menu. The LED display cycles between the menu heading, and the measure­ment every four seconds. Press the display advance button for one second to move to the menu. To enter the submenu, press the display advance but­ton for three seconds. To navigate from measurement to measurement with­in the submenu, press the display advance button. While in the submenu, pressing and holding the display advance button for three seconds brings the unit back to the menu structure.
1. Insert the #61-181 adapter into the ST-1THDC
2. The LED display shows Ct indicating recognition of the adapter
3. The LED display cycles between cA, indicating that True RMS current is being measured through the amp clamp adapter, and the current mea­surement every four seconds.
4. Press and hold the display advance button for three seconds to access the Current submenu.
5. The LED display alternates between Hi, indicating that the highest cur­rent is being measured, and the measurement every four seconds
6. Press the display advance button for one second to move to the next test within the Current submenu.
7. Press and hold the display advance button for three seconds to return to the main menu.
1615
Menu Structure for Current Probe Menu Testing (ST-1THDC Only)
Submenu
Display Menu Display Measurement
cA- Current Current
Hi= Highest Current Lo= Lowest Current A= Average Current
ct- % Current THD % Current THD
Hi= Highest Current THD Lo= Lowest Current THD A= Average Current THD P= Peak Current THD
cH- Current Harmonics
h3= %THD at 3rd Harmonic H5=...H15= % THD for each odd numbered
Harmonic through the 15th Harmonic
bAL= Total of the remaining % THD from
17th Harmonic to 31st Harmonic
Optional Accessories
#61-175 Ground Continuity Adapter
This adapter allows the operator to verify that a cabinet or equipment chas­sis has been properly connected to the power system ground. Plugging into the #61-175 adapter will isolate the SureTest from the power source ground. The LED display of the ST-1THD will read E-nG. If the equip­ment is properly grounded, then touching the alligator clip from the ground continuity adapter to the cabinet or equipment chassis should return the cir­cuit to a Normal condition.
WARNING
This is a static test and will not confirm the current carrying capacity
With the ST-1D, this adapter can be used to check the ground impedance of a cabinet or equipment chasis. See section 3.4 for test instructions.
This adapter can also be used to test GFCI receptacles on 2-wire circuits. Connect the ground lead on the adapter to a ground, such as a metal water or gas pipe, prior to GFCI testing.
#61-176 Isolated Ground Adapter
This adapter allows the operator to verify that a receptacle is completely iso­lated from the other grounds between the receptacle and the entry panel.
WARNING
The receptacle should be tested for proper grounding prior to testing for ground insulation.
Test the ground impedance of the receptacle and make a note of the results. See the section on outlet circuit testing for details. Remove the SureTest from the receptacle and plug it into the #61-176 adapter. Clip the ground wire to the metal outlet, center receptacle screw, or the metal outlet box. Re-insert the ST-1THD into the receptacle and retest for ground impedance. Make a note of the result.
If the two resistance readings are the same, then the receptacle is not isolat­ed. If the receptacle is isolated, the reading with the #61-176 will be lower. A reading of half when the adapter is used is common, because a parallel ground path has been introduced by attaching the ground wire to the grounding point of the receptacle.
#61-177 Extension Cord
The ST-1THD is supplied with an extension cord to make testing easier on hard-to-reach outlets. Replacement extension cords can be purchased from your authorized IDEAL distributor.
#61-179 CARRYING CASE
The ST-1THD is supplied with a lightweight carrying case to protect the units and store the instruction sheet and accessories. Replacement cases can be purchased from your authorized IDEAL distributor.
1817
#61-181 500AAC Clamp Adapter
This adapter can only be used with the ST-1THDC. This adapter is used for True RMS current measurements up to 500-amperes. #61-158 Circuit/Harmonics Analyzer kit includes both the #61-157 Circuit/Harmonics Analyzer and the #61-181 500AAC Clamp Adapter in one convenient pack­age.
T
roubleshooting
Locating Loose (High Resistance) Connectors and Splices
Loose connections, splices and bad connections can be isolated by using the SureTest to test receptacles in sequence along the branch circuit.
For example if the voltage drop at receptacle 5 is unacceptable, checking the other receptacles in the branch can help isolate the problem. If receptacles 1 through 4 and 6 through 8 check out OK, than further investigation should take place at the connection to receptacle 5. The additional resistance could be due to a loose connection/splice. If receptacles 6 through 8 are also unacceptable, chances are that the problem is in either the hot or neutral conductor in the wall between receptacles 4 and 5.
If all of the branch receptacles have unacceptable voltage drops, the problem is most likely in the circuit between the panel and the first receptacle or at the panel. If all branches are in high resistance, the problem may be in the cir­cuit from the meter, or from the transformer to the service entrance.
Using the SureTest will help identify problem areas for further investigation of the receptacles and/or branch circuit.
Troubleshooting Tips
Problem Possible Causes/Solutions High/Low Line Voltage Too much load on branch - also causing
excessive voltage drop
Poor connection at receptacle
Supply voltage too high/low
Clean and tighten receptacle connections
Consult power company
High Voltage Drop Too much load on branch (5% recommended by NEC) Too many outlets on branch
Diameter of wire too small
Check and tighten connection at
receptacle
Clean any corroded wires
Replace outlet, switch
Replace circuit breaker
High Ground-to-Neutral Current flowing in the neutral conductor Voltage (Greater than Locate/repair source 2 Volts) Install surge suppression High Ground Impedance Loose ground connection (Greater than 1 Ohm) Check and tighten ground connections
Clean any corroded wires Failure of GFCI Test GFCI may be installed incorrectly (GFCI will not trip) GFCI may be defective
Check for proper connections
Replace outlet
19
Other Sur
eTest Models from IDEAL
SureTest Circuit Analyzers
SureTest Circuit/Harmonics Analyzers
Warranty limited solely to repair or replacement; no warranty of mer­chantability, fitness for a particular purpose or consequential damages.
IDEAL INDUSTRIES, INC.
Sycamore, IL 60178, U.S.A. 800-435-0705 Customer Assistance www.idealindustries.com
ND 2292-1 Made in U.S.A.
SureTest®Selection Guide
Identifies and Locates
Loose Wire Connections •••• Bad Splices/Receptacles •••• High Resistance Grounds •••• False (Bootleg) Grounds ••• Shared Neutrals ••
Indicates
Proper Wiring in 3-Wire Receptacles •••• Min/Max Line Voltage •• Pass/Fail Voltage Drop •• Pass/Fail Ground Impedance Pass/Fail Neutral-to-Ground Voltage
Verifies
Dedicated Circuit Presence •• Isolated Ground Presence (with #61-176 Adapter) ••• Proper GFCI Operation ••••
Measures
Line Voltage ••• Ground Impedance (Ohms) •• % Voltage Drop under 15 ampere load ••• % Voltage Drop under 20 ampere load •• GFCI Trip Time ••• Neutral-to-Ground Voltage •• Estimated Load on Circuit (Amps) ••
Additional Features
220 VAC Operation
61-150
ST-1
61-151
ST-1P+
61-152
ST-1D
61-153
ST-1D
SureTest®Selection Guide
Identifies and Locates
Loose Wire Connections ••• Bad Splices/Receptacles •• • High Resistance Grounds ••• False (Bootleg) Grounds ••• Shared Neutrals •••
Verifies
Dedicated Circuit Presence ••• Isolated Ground Presence (with #61-176 Adapter) •• Proper GFCI Operation •• •
Measures
Line Voltage ••• Ground Impedance (Ohms) ••• % Voltage Drop under 15 ampere load ••• % Voltage Drop under 20 ampere load ••• GFCI Trip Time ••• Neutral-to-Ground Voltage ••• Estimated Load on Circuit (Amps) ••• True RMS Measurements (Voltage) •• True RMS Measurements (Current)
(with #61-181 Adapter) Line Frequency ••• Power Consumption (Watts) ••• Distortion to 31st Harmonic •••
Additional Features
220 VAC Operation For use with #61-181 500AAC Adaptor •• Included with #61-181 500AAC Adaptor Event recording •• •
61-156
ST-1THD
61-157
ST-1THDC
61-158
ST-1THDC
Loading...