Ideal ESCGRID1001 User Manual

Product Manual
Qty
Description
1
ESCGRID1001 Smart Connector
ESCGRID1001 – LVDC Grid Luminaire Controller
PRODUCT DESCRIPTION
The LVDC Grid Luminaire Controller is a wireless device which provides electrical connectivity between the light fixture (load) and 24V DC power and provides on/off power control and 0-10V based dimming to the load. The information that tells the controller to power on/off/dim the fixture is acquired via wireless signals that originate from a building automation system or room controls, based on environmental conditions and/or predetermined programs.
KEY FEATURES
FCC and IC approved Small form factor Integrated Wire Antenna RoHS compliant
Audacy®, Smart Connector® and Smart Switch® are registered trademarks of IDEAL INDUSTRIES.
All other trademarks are the property of their respective owners.
PRODUCT CONTENTS
The following items are included inside the package:
IDEAL Model ESCGRID1001 LVDC Luminaire Controller Installation
ND xxxx-x 04/2017 Users Manual – ESCGRID1001 LVDC Grid Luminaire Controller Page 1 www.idealindustries.com
Instructions
Product Manual
24V DC Bus
LOAD
Fig. 1
0-10V Dimming
ESCGRID1001 – LVDC Grid Luminaire Controller
WARNING: This is a current rated device. Use in applications involving
Amperage beyond its rating can be dangerous and cause electrical fires.
Wiring must comply with all applicable electrical codes.
TERMINOLOGY
24V Input: Incoming power feed from 24V source (DC Flex-Zone) LOAD: Power output from Luminaire Controller to 24V DC LED Fixture input
DIM: 0-10 VDC dimming control output from Smart Connector to ballast
dimming input
Power and Load Connections
Power The 24V Input power is applied to the device once clipped onto the DC Flexzone grid. Place the device in the desired location on an energized rail. LOAD Connector The LOAD Connector accepts 18 AWG copper conductors, solid or stranded (16 strands
or less).
Use only one conductor per port and ensure that no copper is exposed on any of the
wires after installation.
ND xxxx-x 04/2017 Users Manual – ESCGRID1001 LVDC Grid Luminaire Controller Page 2 www.idealindustries.com
Product Manual
ESCGRID1001 – LVDC Grid Luminaire Controller
1. Strip the wires to 3/8”.
2. Grip the LOAD +24V wire and firmly push conductor into the port marked with the black stripe. See Fig. 2.
3. Grip the LOAD -24V wire and firmly push conductor into the unmarked port. See Fig. 2.
4. After LOAD wire installation, the load can safely be disconnected and re-connected without re-installing the wires. To disconnect the load, firmly grip the LOAD connector and pull to separate it from the main body of the Smart Connector. To re-connect, simply push the LOAD connector into the corresponding port on the Smart Connector.
DIM Connector The DIM Connector accepts 18 AWG copper conductors, solid or stranded (16 strands or less). Use only one conductor per port and ensure that no copper is exposed on any of the wires after installation.
1. Strip wires to 3/8”.
2. Grip positive/(+)/purple DIM conductor and firmly push into the port marked “1”. See Fig. 3.
3. Grip negative/(-)/gray DIM conductor and firmly push into the port marked “2”. See Fig. 3.
4. After DIM wire installation, the DIM connector can safely be disconnected and re-connected without re-installing the wires. To disconnect the DIM connector, firmly grip the DIM connector and pull to separate it from the main body of the Smart Connector. To re-connect, simply push the DIM connector into the corresponding port on the Smart Connector.
PROGRAMMING
Refer to the Audacy™ system configuration manual to associate smart connectors to other devices and to set up operating parameters for the Audacy™ lighting control system
ND xxxx-x 04/2017 Users Manual – ESCGRID1001 LVDC Grid Luminaire Controller Page 3 www.idealindustries.com