When replacing any part on this appliance use only spare parts that you can be
assured conform to the safety and performance specification that we require. Do not
use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
SE9 RS, SE12 RS, SE15 RS
& SE18 RS
August 2004 UIN 200 547 A04
GENERAL
Table 1 - General Data
Boiler SizeSE9 RSSE12 RSSE15 RSSE18 RS
Gas supply connectionRc
1/2 (1/2) 1/2" (BSP Female)
Flow connection22mm copper
Return connection22mm copper
Maximum static water head m (ft.)30.5 (100)
Minimum static water head m (ft.) 0.45 (1.5)
Electrical supply230 V 50 Hz
Fuse ratingExternal: 3A
Water contentlitre (gal.)3.65 (0.8)4.6 (1.0)
Dry Weight kg (lb.)42.0 (93.0)48.0 (105.0)
Maximum installation weight kg (lb.)34.0 (75.0)40.0 (88.0)
* The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings.
The test data from which it has been calculated have been certified by a notified body.
To obtain gas consumption
3
(a) For l/s: divide heat input (kW) by C.V. of the gas (MJ/m
3
(b) For ft
/h; divide by C.V. of the gas (Btu/ft3).
)
Heat inputs are preset to the highest nominal rating.
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of this
appliance, care should be taken when handling edges of sheet steel components
2
Classic SE RS - Installation & Servicing
GENERAL
Classic SE RS
Data Badge: on top of the controls support
B.G. Certified - P.I. No. 87AP108
Destination Countries: GB & IE Appliance type: C
via ducts to a horizontal terminal, which admits
fresh air to the burner and discharges the products
of combustion to the outside through orifices which,
in this case, are concentric.
= An appliance designed for use on 2nd Family gas,
I
2H
Group H only.
Natural Gas only: I
11
Only
2H
CONTENTS
Air Supply. ...................................................................... 6
Water and Systems ...................................................... 7
For GB, to comply with Building Regulations Part L1 (Part J in Scotland) the boiler should be fitted in accordance with the
manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be
demonstrated by completing and signing the Benchmark log book.
BENCHMARK LOG BOOK DETAILS
BoilerPage
Make and model ....................................................... 3
Appliance serial no. on data badge ..........................8
For all boilers:complete, sign & hand over to customer
For assistance see Technical Helpline on the back page
Page
Classic SE RS - Installation & Servicing
3
GENERAL
INTRODUCTION
The Classic SE9 RS, SE12 RS, SE15 RS and SE18 RS is a range
of automatically fully controlled, wall mounted, balanced flue,
gas boilers.
The boiler casing is of white enamelled mild steel.
The boilers are supplied with a standard flue kit, suitable for rear
outlet applications from 229mm (9") to 305mm (12").
The boilers are suitable for connection to pumped, open vented
central heating systems; pumped central heating combined with
pumped or gravity indirect domestic hot water systems; gravity or
pumped indirect domestic hot water supply systems.
See Frame 1 for details of the correct boiler tappings to use.
The boiler casing has a removable controls pod containing a
drop-down door. The boiler thermostat is located behind the
drop-down door.
This boiler may require 2 operatives to move it to its installation
site, remove it from its packaging base and during movement
into its installation location. Manoeuvring the boiler may include
the use of a sack truck and involve lifting, pushing and pulling.
Caution should be exercised during these operations.
Operatives should be knowledgeable in handling techniques
when performing these tasks and the following precautions
should be considered:
•Grip the boiler at the points shown in Frame 14.
•Split the boiler down to reduce the weight, e.g. remove
casing and hardware pack. Refer to Frame 5.
•Be physically capable.
•Use PPE as appropriate, e.g. gloves, safety footwear.
During all manoeuvres and handling actions, every attempt
should be made to ensure the following unless unavoidable
and/or the weight is light.
•Keep back straight.
•Avoid twisting at the waist.
•Avoid upper body/top heavy bending.
•Always grip with the palm of the hand.
•Use designated hand holds.
•Keep load as close to the body as possible.
•Always use assistance if required.
OPTIONAL EXTRA KITS
Programmer kitfits neatly within the casing. Separate
fitting instructions are included with this
kit.
Extension ductsup to 394 mm (15 1/2").
Overheatallows the boiler to be used on sealed
Thermostat Kitsystems.
Sealed System Unit fits on top of the appliance
GAS SAFETY
CURRENT GAS SAFETY (INSTALLATION AND USE)
REGULATIONS OR RULES IN FORCE.
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in accordance with
the relevant requirements of the:
•Gas Safety (Installation and Use) Regulations
•The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (northern Ireland).
•The Water Fittings Regulations or Water byelaws in
Scotland.
•The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent Person
and installed in accordance with the current edition of I.S.813
"Domestic Gas Installations", the current Building Regulations
and reference should be made to the current ETCI rules for
electrical installation.
Detailed recommendations are contained in the following British
Standard Codes of Practice:
BS. 6891Low pressure installation pipes.
BS. 6798Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 5449Forced circulation hot water systems.
BS. 5546Installation of gas hot water supplies for domestic
purposes (2nd Family Gases).
BS. 5440: Part 1 Flues for gas appliances of rated input not
exceeding 60 kW.
BS. 5440: Part 2 Ventilation for gas appliances of rated input
not exceeding 60 kW.
BS 7593Treatment of water in Domestic Hot Water Central
Heating Systems.
Health & Safety Document No. 635.
The Electricity at Work Regulations, 1989.
Manufacturer’s notes must NOT be taken in any way as
overriding statutory obligations.
IMPORTANT. These appliances are certificated by the British
Standards Institution for safety and performance. It is important,
therefore, that no external control devices, e.g. flue dampers,
economisers etc., are directly connected to these appliances
unless covered by these Installation and Servicing instructions
or otherwise recommended by Caradon Ideal Limited in writing.
If in doubt please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited could invalidate the BSI Certification and
the normal appliance warranty. It could also infringe the Gas
Safety Regulations and the above regulations.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation
panels, which can cause irritation to the skin. No asbestos,
mercury or CFCs are included in any part of the boiler.
NOTE TO THE INSTALLER:
LEAVE THESE
INSTRUCTIONS ADJACENT TO THE GAS METER.
ALSO COMPLETE THE BENCHMARK LOG BOOK
AND GIVE THIS TO THE CUSTOMER.
4
Classic SE RS - Installation & Servicing
GENERAL
LOCATION OF BOILER
The boiler must be installed on a flat and vertical wall, capable
of adequately supporting the weight of the boiler and any
ancillary equipment.
The boiler may be fitted on a combustible wall and insulation
between the wall and the boiler is not necessary - unless
required by the local authority.
The boiler must not be fitted outside.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should be
fitted in accordance with the Institute of Gas Engineering document
IGE/UP/7:1998.
1
BOILER WATER CONNECTIONS
1. This appliance is NOT suitable for use in a direct hot
water system.
2. If the boiler is to be used on a sealed system, an
Overheat Thermostat Kit is available and must be
installed in accordance with the instructions supplied with
the kit.
Bathrooms
The boiler may be installed in any room or internal space, although
particular attention is drawn to the requirements of the current
I.E.E. (BS 7671) Wiring Regulations and, in Scotland, the electrical
provisions of the building regulations applicable in Scotland with
respect to the installation of the boiler in a room or internal space
containing a bath or shower. For Ireland reference should be
made to the current ETCI rules for electrical installations and
I.S. 813: 2002.
Where a room-sealed appliance is installed in a room containing
a bath or shower then the appliance and any electrical switch or
appliance control utilising mains electricity should be so situated
that it cannot be touched by a person using the bath or shower.
Where installation will be in an unusual location, special
procedures may be necessary and BS.6798 gives detailed
guidance on this aspect.
......continued on page 6.
3. If the boiler is to be used for gravity domestic hot water
supply then cut off the spun ends of the gravity flow and
return pipes and fit a 22 mm to 28 mm copper connection
at the boiler gravity flow and return connections, in order
to run the gravity circuits in 28 mm pipe.
2
BOILER CLEARANCES
The following minimum clearances must be maintained for
operation and servicing. Additional space will be required for
installation, depending upon site conditions.
If using the Classic Sealed System Unit then refer to the
instructions packed with the unit for the necessary
clearances.
Gravity flow pipe
Pumped return pipe
FRONT VIEWSIDE VIEW
380 (15")
332 (13")
232 (9
1/8
")
Gravity
return
pipe
Pumped
flow pipe
300 (12")
31
(1
1/4"
Front clearance: 450mm
(17
3/4") from the front of
the boiler casing.
Minimum front clearance
when built in to cupboard is
75mm (3")
)
Flue terminal
Gas conn.
Cla 6035
130 (5
1/8
")
600
(24")
Classic SE RS - Installation & Servicing
(1
30
1/8
")
Gas
conn.
(1
48
7/8
200
(8")
")
5
GENERAL
Compartment Installations
A compartment used to enclose the boiler MUST be designed and
constructed specially for this purpose. An existing cupboard or
compartment may be used, providing it is modified for the purpose.
In both cases details of essential features of cupboards/
compartment design, including airing cupboard installation, are
to conform to the following:
!!
BS. 6798.
!
!!
!!
The position selected for installation MUST allow adequate
!
!!
space for servicing in front of the boiler and for air circulation
around the boiler; see section on 'Air Supply'.
! For the minimum clearances required for safety and
subsequent service, see Frame 2. In addition, sufficient
boiler clearance may be required to allow lifting access to
the wall mounting plate.
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an adequate
supply of gas. An existing service pipe must NOT be used without
prior consultation with the local gas supplier.
A gas meter can only be connected by the local gas supplier or by
a local regional contractor.
An existing meter should be checked, preferably by the gas supplier,
to ensure that the meter is adequate to deal with the rate of gas
supply required. A minimum gas pressure of 20 mbar MUST be
available at the boiler inlet, with the boiler operating.
Installation pipes MUST be fitted in accordance with BS. 6891. In
IE refer to I.S. 813:2002. Pipework from the meter to the boiler
MUST be of an adequate size.
The complete installation MUST be tested for gas soundness and
purged as described in the above code.
FLUE INSTALLATION
Pluming may occur at the terminal so terminal positions which
would cause a nuisance should be avoided.
The flue must be installed in accordance with the
recommendations of BS. 5440-1:2000. In IE refer to I.S. 813:2002.
The following notes are intended for general guidance:-
1. The boiler MUST be installed so that the terminal is exposed
to external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Table
3.
4. Where the lowest part of the terminal is fitted less than 2m
(6' 6") above a balcony, above ground or above a flat roof to
which people have access then the terminal MUST be protected
by a purpose designed guard.
Terminals guards are available from boiler suppliers. Ask for
TFC Flue Guard, Model A. In case of difficulty seek advice from:
2. Below guttering, drain pipes or
soil pipes300 mm (12")
3. Below eaves300 mm (12")
4. Below balconies or a car port roof600 mm (24")
5. From vertical drain pipes or300 mm (12")
soil pipes
6. From an internal or external corner or
to a boundary alongside the terminal600 mm (24")
7. Above adjacent ground, roof or
balcony level300 mm (12")
8. From a surface or a boundary
facing the terminal600 mm (24")
9. From a terminal facing a terminal600 mm (24")
10. From an opening in a car port
(e.g. door or window) into dwelling1200 mm (48")
11. Vertically from a terminal on the
same wall1500 mm (60")
12. Horizontally from a terminal on
the wall300 mm (12")
5. If a natural draught terminal is fitted less than 1m below a
plastic gutter or less than 0.5m below painted eaves or any
other painted surface a suitable shield at least 1m long
should be fitted to protect the surface.
6. The air inlet/products outlet duct and the terminal of the boiler
MUST NOT be closer than 25mm (1") to combustible material.
Detailed recommendations on the protection of combustible
material are given in BS.5440-1:2000. In IE refer to I.S. 813:2002.
IMPORTANT. It is absolutely ESSENTIAL to ensure, in practice,
that products of combustion discharging from the terminal cannot
re-enter the building or any other adjacent building through
ventilators, windows, doors, other sources of natural air infiltration
or forced ventilation/air conditioning.
If this should occur, the appliance MUST be turned OFF, labelled
'unsafe' and corrective action taken.
Minimum Spacing
SE9, SE12 SE15, SE18
TERMINAL
The terminal assembly can be adapted to accommodate various
wall thicknesses. Refer to Frame 4 - Unpacking.
AIR SUPPLY
Detailed recommendations for air supply are given in BS.5440:2.
In IE refer to I.S. 813:2002.
The following notes are for general guidance:
1. It is NOT necessary to have a purpose provided air vent in the
room or internal space in which the boiler is installed.
2. If the boiler is to be installed in a cupboard or compartment,
permanent air vents are required (for cooling purposes) in the
cupboard/compartment, at both high and low levels. The air
vents must either communicate with room/internal space, or
be direct to outside air. The minimum effective areas of the
permanent air vents, required in the cupboard/compartment,
are specified in Table 4 and are related to maximum rated heat
input.
6
Classic SE RS - Installation & Servicing
GENERAL
3. Both air vents MUST communicate with the same room or
internal space or MUST be on the same wall to outside air.
4. In siting the air vents care must be taken to avoid the freezing of
pipework.
Table 4 - High and low vent areas
BoilerAir from room/internalAir direct
Space cm
SE9 RS102 (16)51 (8)
SE12 RS135 (21)68 (11)
SE15 RS170 (26)83 (13)
SE18 RS198 (31)102 (16)
2
(in.2)Outside cm2 (in.2)
WATER CIRCULATION SYSTEM
The boiler must NOT be used for direct hot water supply. For the
types of system and correct piping procedure refer to 'Introduction'
and Frame 1.
The central heating system should be in accordance with
BS. 6798 and, in addition, for smallbore and microbore systems,
BS. 5449.
The domestic hot water system, if applicable, should be in
accordance with the relevant recommendations of BS. 5546.
Copper tubing to BS. 2871:1 is recommended for water carrying
pipework.
The hot water storage cylinder MUST be of the indirect type and
should preferably be manufactured of copper.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The hot water cylinder and ancillary pipework not forming part of
the useful heating surface should be lagged to prevent heat loss
and any possible freezing - particularly where pipes run through
roof spaces and ventilated underfloor spaces.
IMPORTANT. The boiler must be vented (not on sealed systems.)
For sealed system installations copper tubing to BS2871:1 MUST
be used throughout the heating system
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler and
hot water storage vessel. They should be at least 1/2" BSP nominal
size and be in accordance with BS. 2879.
The boiler is fitted with a special drain plug (provided) to drain the
BOILER ONLY, in the event of the system drain plug being unable
to do so. The hydraulic resistance of the boilers, at MAXIMUM
OUTPUT with an 11
in Table 5.
Table 5 - Water flow rate and pressure loss
Boiler SizeSE9 RS SE12 RS SE15 RS SE18 RS
0
C (20 0F) temperature differential, are shown
Caradon Ideal Limited recommend Water Treatment in
accordance with the Benchmark Guidance Notes on Water
Treatment in Central Heating Systems.
Caradon Ideal Limited recommend the use of Fernox, GE Betz
Sentinel or Salamander water treatment products, which must
be used on accordance with the manufacturers instructions.
G E Betz Ltd, Sentinel Division, Foundry Lane, Widnes, Cheshire,
WA8 8UD. Tel. +44 (0) 151 424 5351
or
Salamander Engineering Ltd, Unit 24, Reddicap Trading Estate,
Sutton Coldfield, West Midlands B75 7BU. Tel. +44 (0) 121 378 0952
Notes.
1. It is most important that the correct concentration of the water
treatment products is maintained in accordance with the
manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing.
BS7593:1992 details the steps necessary to clean a
domestic heating system.
3. In hard water areas, treatment to prevent limescale may be
necessary - however the use of artificially softened water is
NOT permitted.
4. Under no circumstances should the boiler be fired before the
system has been thoroughly flushed.
BOILER CONTROL INTERLOCKS
Caradon Ideal Limited recommend that heating systems utilising
full thermostatic radiator valve control of temperature in individual
rooms should also be fitted with a room thermostat controlling the
temperature in a space served by radiators not fitted with such a
valve as stated in BS. 5449.
Central heating systems controls should be installed to ensure the
boiler is switched off when there is no demand for heating or hot water.
When thermostatic radiator valves are used, the space heating
temperature control over a living / dining area or hallway having a
heating requirement of at least 10% of the boiler heat output should
be achieved using a room thermostat, whilst other rooms are
individually controlled by thermostatic radiator valves. However, if
the system employs thermostatic radiator valves on all radiators,
or two port valves without end switches, then a bypass circuit must
be fitted with an automatic bypass valve to ensure a flow of water
should all valves be in the closed position.
BoilerkW8.811.714.717.6
OutputBtu/h 30 00040 00050 00060 000
Water flowl/min11.415.219.022.9
Rategal/h150200250300
Pressurembar16.522.037.545
Lossin wg6.69.01518
WATER TREATMENT
These boilers incorporate a cast iron heat exchanger.
IMPORTANT. The application of any other treatment to this
product may render the guarantee of Caradon Ideal Limited
INVALID.
Classic SE RS - Installation & Servicing
ELECTRICAL SUPPLY
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS. 7671) Wiring Regulations and any local
regulations which apply. For Ireland reference should be made to
the current ETCI rules for electrical installations.
The point of connection to the mains should be readily accessible
and adjacent to the boiler, except for bathroom installations; the
point of connection to the mains MUST be situated outside of the
bathroom.
Note. Where a room sealed appliance is installed in a room
containing a bath or shower then the appliance and any electrical
switch or appliance control utilising mains electricity should be so
situated that it cannot be touched by a person using the bath or
shower.
7
3
BOILER ASSEMBLY - Exploded View
Classic SE9 RS shown
INSTALLATION
INSTALLATION
34
4.2
5
4.3
4.1
47
34
6
2
53
22
25
3
7
LEGEND
1.Heat exchanger
2.Flue baffles
3.Hook bolt kit assy.
4.1Pipe - RH flow
1
Programmer
18.1
12
5.Pipe - Return assy.
6.Collector hood
7.Combustion chamber
12.Main burner
26
Controls support
Data badge
Clas 1998
25.Boiler thermostat
26.Control thermostat knob
34.Balanced flue terminal
44B. Programmer (optional)
4.2Pipe - LH flow
4.3Pipe - Return
8
18.1. Detection electrode
22.Thermostat pocket
47.Gasket, grommet & bush kit
53.Wall mounting plate
Classic SE RS - Installation & Servicing
4
UNPACKING
INSTALLATION
The boiler is supplied fully assembled in Pack A, together with a
standard flue assembly for lengths up to 305mm (12") in Pack B.
Unpack and check the contents.
Pack A Contents
- Hardware Pack (listed below)
- Installation & Servicing Instructions
- User's Instructions.
Hardware Pack
! 50mm x No. 14 wood screw - 3 off
! 50mm x No. 10 wood screw - 3 off
! Wall plug - 6 off
! Cover plate, painted
FLUE PACKSNote. All flue packs contain 2 sachets of sealant
PACK B - contains a balanced flue terminal suitable for wall thicknesses from 229mm (9") to 305mm (12")
PACK B1 - contains a balanced flue terminal suitable for wall thicknesses from 318mm (12
PACK C - contains a balanced flue terminal suitable for wall thicknesses from 114mm (4
1/2") to 394mm (15 1/2")
1/2") to 191mm (7 1/2")
INSTALLATION
Note.
Wall thicknesses outside those specified cannot be accommodated. An overlap of at least 50mm at any duct joint
must be allowed.
5
PACKAGING AND CASING REMOVAL
1. Unpack the boiler
2. Remove the casing as follows and place to one
side to avoid damage.
a. Release the controls pod fixing screws (a) 3 full
turns only.
Remove the pod by pulling it forward to
disengage from the keyhole slots.
b. Undo the 3 screws (b), retaining the casing to
the back panel.
c. Remove the casing in the direction of the
arrows.
3. Remove the boiler from its packaging base. The
boiler may now be stood on its controls support
protection frame to ease handling and installation
4. Unpack the boiler terminal box and, if applicable,
the extension flue box(es).
Classic SE RS - Installation & Servicing
9
INSTALLATION
6
OPEN VENT SYSTEM REQUIREMENTS - Fully pumped
The system should be vented directly off the boiler flow pipe, as close to the boiler
as possible. The cold feed entry should be inverted and MUST be positioned
between the pump and the vent, and not more than 150mm (6") away from the
vent connection.
There should be a minimum height - 450mm (18") - of open vent above the cistern
water level. If this is impossible refer below.
The vertical distance between the highest point of the system and the feed/
expansion cistern water level MUST not be less than 450mm (18").
The pump MUST be fitted on the flow side of the boiler.
A suitable pump is a domestic circulator capable of providing an 11°C (20°F)
temperature differential (e.g. Grundfos UPS 15/50 or equivalent). The vertical
distance between the pump and feed/expansion cistern MUST comply with the
INSTALLATION
pump manufacturer's minimum requirements to avoid cavitation. Should these
conditions not apply, either lower the pump position or raise the cistern above the
minimum requirement specified by Caradon Ideal Limited.
Note. A cold water feed must be available back to the boiler when all automatic
valves are in the closed position (refer to BS. 6798) and, when close coupled, the
feed must not be in a vertical leg.
7
LOW HEAD INSTALLATIONS
The Classic SE range of boilers can be installed in low
head situations by fitting a 'surge arrester' in the expansion
pipe, as shown.
The following conditions MUST be observed:
1. The surge arrester must be at least 42mm in diameter
x 150mm long, thus ensuring a MINIMUM air gap and a
MINIMUM depth of water below the static water level
(cold) of 75mm.
2. The static water level (cold) must be at least 200mm
above the top of the horizontal flow pipe, fitted as shown.
The vent connection MUST NOT be made immediately
off the top of the boiler, as venting is made less efficient.
3. The maximum practical length of 15mm cold feed pipe
should be used in order to reduce the effective volume of
system water expanding into the feed/expansion cistern
to a minimum.
Return
Note. The pump
manufacturers minimum
requirements must be
complied with.
450
(18)
Min.
75 (3)
Min.
200
(8)
Min.
Feed / expansion
cistern
Water
level
(cold)
22mm
Open vent
System
return
Surge
arrester
75 (3) Min.
Flow
Highest
point of
flow or
return
Connections
to boiler
15mm
Cold
feed
Inverted cold
feed entry
Feed / expansion
cistern
22 (3/4)
Open vent
150
(6)
Max
Max. practical
length
Minimum Requirements
All dimensions in mm (in.)
NB: Imperial dimensions are approximate
450 (18")
Mimimum
450 (18")
Mimimum
150 (6")
Max
System
flow to
pump
Cold
water
level
To pump
8
REQUIREMENTS FOR CORRECT GRAVITY HOT WATER PERFORMANCE
NOTE. Gravity horizontal pipes should be ABOVE ceiling level and as SHORT as
possible. A MINIMUM inclination of 25mm per 3m run (1" per 10') is required to
avoid air locks. If these conditions cannot be met, pumped primaries MUST be used.
The above graph assumes 8 elbows in the gravity circuit. For each elbow in excess
of 8, (R) must be reduced by 300 mm (12 in.) or (H) increased by 100 mm (4 in.)
10
Classic SE RS - Installation & Servicing
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.