ideal Classic RS 330 User guide

Wall hung, balanced
flue, gas fired boilers
Classic RS 330-360
GENERAL
Table 1 - General Data
Boiler Size RS 330 RS 340 RS 350 RS 360
Gas supply connection Rc 1/2 (1/2) 1/2" (BSP Female) Flow connection 22mm copper Return connection 22mm copper Maximum static water head m (ft.) 30.5 (100) Minimum static water head m (ft.) 0.45 (1.5) Electrical supply 230 V 50 Hz Fuse rating External: 3A Water content litre (gal.) 3.65 (0.8) 4.6 (1.0) Dry Weight kg (lb.) 46.3 (107.1) 54.2 (119.5) Maximum installation weight kg (lb.) 34.7 (76.5) 42.7 (94.2) Boiler size Height mm (in.) 600 (23.6)
Width mm (in.) 380 (15.0) Depth mm (in.) 300 (11
3/4")
Table 2 - Performance Data
Boiler Size RS 330 RS 340 RS 350 RS 360
(Btu/h) (37 200) (49 500) (60 750) (74 000)
3
Gas consumption l/s (ft
/h) 0.28 (36.1) 0.38 (48.2) 0.46 (58.6) 0.56 (71.3)
Boiler output kW 8.8 11.7 14.7 17.6
(Btu/h) (30 000) (40 000) (50 000) (60 000)
Burner setting pressure (HOT) mbar (in.w.g.) 6.4 (2.6) 11.0 (4.4) 13.1 (5.3) 14.1 (5.7)
Seasonal Efficiency (SEDBUK)* Band D [78.4]% [78.9]% [80.3]% [79.0]%
* The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by a notified body.
To obtain gas consumption
3
(a) For l/s: divide heat input (kW) by C.V. of the gas (Btu/ft
3
(b) For ft
/h; divide by C.V. of the gas (Btu/ft3).
)
Heat inputs are preset to the highest nominal rating.
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of this
appliance, care should be taken when handling edges of sheet steel components
2
Classic RS -
Installation & Servicing
GENERAL
Classic RS
Data Badge: on top of the controls support
B.G. Certified - P.I. No. 87AP108 Destination Countries: GB & IE Appliance type: C
Models G.C. Appliance No.
Classic RS 330 .............................41 392 09
Classic RS 340 .............................41 392 10
Classic RS 350 .............................41 392 11
Classic RS 360 .............................41 392 12
Key to symbols IE
= Ireland
GB
= United Kingdom
PMS = Maximum operating pressure of water
= A room sealed appliance designed for connection
C
12
via ducts to a horizontal terminal, which admits fresh air to the burner and discharges the products of combustion to the outside through orifices which, in this case, are concentric.
= An appliance designed for use on 2nd Family gas,
I
2H
Group H only.
Natural Gas only: I
2H
12
CONTENTS
Air Supply. ...................................................................... 6
Boiler Assembly - Exploded view ................................. 8
Boiler Clearances .......................................................... 5
Burner Assembly - Exploded view ............................. 31
Electrical Connections ................................................ 15
Electrical Diagram ....................................................... 15
Electrical Supply ............................................................ 7
Fault Finding .................................................................28
Flue Fitting ....................................................................14
Flue Installation .............................................................. 6
Gas Safety Regulations ................................................. 4
Gas Supply ..................................................................... 6
Health & Safety Document No 635 ............................... 4
Initial Lighting ............................................................... 19
Installation ..................................................................... 8
Mandatory Requirements ............................................. 4
Pump ............................................................................ 10
Servicing ...................................................................... 21
Short List of Parts ....................................................... 29
System Diagrams ........................................................ 16
Terminal Guards. ........................................................... 6
Water and Systems ...................................................... 7
For GB, to comply with Building Regulations Part L1 (Part J in Scotland) the boiler should be fitted in accordance with the manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be demonstrated by completing and signing the Benchmark log book.
BENCHMARK LOG BOOK DETAILS
Boiler Page
Make and model .......................................................3
Appliance serial no. on data badge ..........................8
SEDBUK No. % .........................................................2
Controls
Time and temperature control to heating ......... 16/17
Time and temperature control to hot water ...... 16/17
Heating zone valves .......................................... 16/17
TRV's .........................................................................7
Auto bypass ............................................................... 7
Boiler interlock ..........................................................7
For all boilers
Flushing to BS.7593 .................................................7
Inhibitor......................................................................7
Central heating mode
Heat input ................................................. to be calculated
Burner operating pressure ....... measure and record
Central heating flow temp. ........ measure and record
Central heating return temp. ..... measure and record
For combination boilers only
Scale reducer ......................................................... n/a
Hot water mode
Heat input ............................................................... n/a
Max. operating burner pressure ............................n/a
Max. operating water pressure ..............................n/a
Cold water inlet temp ............................................. n/a
Hot water outlet temp. ............................................n/a
Water flow rate at max. setting ...............................n/a
For condensing boilers only
Condensate drain .................................................. n/a
For all boilers:
For assistance see Technical Helpline on the back page
complete, sign & hand over to customer
Page
Classic RS -
Installation & Servicing
3
GENERAL
INTRODUCTION
The Classic RS 330-360 is a range of automatically fully controlled, wall mounted, balanced flue, gas boilers.
The boiler casing is of white enamelled mild steel. The boilers are supplied with a standard flue kit, suitable for
rear outlet applications from 229mm (9") to 305mm (12"). The boilers are suitable for connection to pumped, open
vented central heating systems; pumped central heating combined with pumped or gravity indirect domestic hot water systems; gravity or pumped indirect domestic hot water supply systems.
See Frame 1 for details of the correct boiler tappings to use. The boiler casing has a removable controls pod containing a
drop-down door. The boiler thermostat is located behind the drop-down door.
OPTIONAL EXTRA KITS
Programmer kit fits neatly within the casing. Separate
fitting instructions are included with this kit.
Extension ducts up to 394 mm (15 1/2"). Overheat allows the boiler to be used on sealed
Thermostat Kit systems. Sealed System Unit fits on top of the appliance
GAS SAFETY
CURRENT GAS SAFETY (INSTALLATION AND USE) REGULATIONS OR RULES IN FORCE.
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI Registered Installer. It must be carried out in accordance with the relevant requirements of the:
Gas Safety (Installation and Use) Regulations
The appropriate Building Regulations either The Building Regulations, The Building Regulations (Scotland), Building Regulations (northern Ireland).
The Water Fittings Regulations or Water byelaws in Scotland.
The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent Person and installed in accordance with the current edition of I.S.813 "Domestic Gas Installations", the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
Detailed recommendations are contained in the following British Standard Codes of Practice:
BS. 6891 Low pressure installation pipes. BS. 6798 Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 5449 Forced circulation hot water systems. BS. 5546 Installation of gas hot water supplies for domestic
purposes (2nd Family Gases).
BS. 5440: Part 1 Flues for gas appliances of rated input not
exceeding 60 kW.
BS. 5440: Part 2 Ventilation for gas appliances of rated input
not exceeding 60 kW.
BS 7593 Treatment of water in Domestic Hot Water Central
Heating Systems.
Health & Safety Document No. 635. The Electricity at Work Regulations, 1989. Manufacturer’s notes must NOT be taken in any way as
overriding statutory obligations. IMPORTANT. These appliances are certificated by the British
Standards Institution for safety and performance. It is important, therefore, that no external control devices, e.g. flue dampers, economisers etc., are directly connected to these appliances unless covered by these Installation and Servicing instructions or otherwise recommended by Caradon Ideal Limited in writing. If in doubt please enquire.
Any direct connection of a control device not approved by Caradon Ideal Limited could invalidate the BSI Certification and the normal appliance warranty. It could also infringe the Gas Safety Regulations and the above regulations.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation panels, which can cause irritation to the skin. No asbestos, mercury or CFCs are included in any part of the boiler.
LOCATION OF BOILER
The boiler must be installed on a flat and vertical wall, capable of adequately supporting the weight of the boiler and any ancillary equipment.
The boiler may be fitted on a combustible wall and insulation between the wall and the boiler is not necessary - unless required by the local authority.
The boiler must not be fitted outside. Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should be fitted in accordance with the Institute of Gas Engineering document IGE/UP/7:1998.
Bathrooms
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. (BS 7671) Wiring Regulations and, in Scotland, the electrical provisions of the building regulations applicable in Scotland with respect to the installation of the boiler in a room or internal space containing a bath or shower. For Ireland reference should be made to the current ETCI rules for electrical installations and I.S. 813: 2002.
Where a room-sealed appliance is installed in a room containing a bath or shower then the appliance and any electrical switch or appliance control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
Where installation will be in an unusual location, special procedures may be necessary and BS.6798 gives detailed guidance on this aspect.
......continued on page 6.
NOTE TO THE INSTALLER:
LEAVE THESE
INSTRUCTIONS ADJACENT TO THE GAS METER.
ALSO COMPLETE THE BENCHMARK LOG BOOK
AND GIVE THIS TO THE CUSTOMER.
4
Classic RS -
Installation & Servicing
1
BOILER WATER CONNECTIONS
1. This appliance is NOT suitable for use in a direct hot
water system.
2. If the boiler is to be used on a sealed system, an Overheat Thermostat Kit is available and must be
installed in accordance with the instructions supplied with the kit.
3. If the boiler is to be used for gravity domestic hot water supply then cut off the spun ends of the gravity flow and return pipes and fit a 22 mm to 28 mm copper connection at the boiler gravity flow and return connections, in order to run the gravity circuits in 28 mm pipe.
2
BOILER CLEARANCES
The following minimum clearances must be maintained for operation and servicing. Additional space will be required for installation, depending upon site conditions.
GENERAL
Front clearance: 450mm
3/4") from the front of
(17 the boiler casing.
Minimum front clearance when built in to cupboard is 75mm (3")
If using the Classic Sealed System Unit then refer to the instructions packed with the unit for the necessary clearances.
Gravity flow pipe
Pumped return pipe
FRONT VIEW SIDE VIEW
Gravity
380 (15")
332 (13")
232 (9
1/8
")
return
pipe
Pumped
flow pipe
300 (12")
31
(1
1/4"
)
Classic RS -
Flue terminal
Gas conn.
Cla 6035
Installation & Servicing
130 (5
1/8
600
(24")
200 (8")
")
Gas
conn.
(1
48
7/8
")
30
(1
1/8
")
5
GENERAL
Compartment Installations
A compartment used to enclose the boiler MUST be designed and constructed specially for this purpose. An existing cupboard or compartment may be used, providing it is modified for the purpose.
In both cases details of essential features of cupboards/ compartment design, including airing cupboard installation, are to conform to the following:
!!
! BS. 6798.
!!
!!
! The position selected for installation MUST allow adequate
!!
space for servicing in front of the boiler and for air circulation around the boiler; see section on 'Air Supply'.
! For the minimum clearances required for safety and
subsequent service, see Frame 2. In addition, sufficient boiler clearance may be required to allow lifting access to the wall mounting plate.
GAS SUPPLY
The local gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. An existing service pipe must NOT be used without prior consultation with the local gas supplier.
A gas meter can only be connected by the local gas supplier or by a local regional contractor.
An existing meter should be checked, preferably by the gas supplier, to ensure that the meter is adequate to deal with the rate of gas supply required. A minimum gas pressure of 20 mbar MUST be available at the boiler inlet, with the boiler operating.
Installation pipes MUST be fitted in accordance with BS. 6891. In IE refer to I.S. 813:2002. Pipework from the meter to the boiler MUST be of an adequate size.
The complete installation MUST be tested for gas soundness and purged as described in the above code.
FLUE INSTALLATION
Pluming may occur at the terminal so terminal positions which would cause a nuisance should be avoided.
The flue must be installed in accordance with the recommendations of BS. 5440-1:2000. In IE refer to I.S. 813:2002.
The following notes are intended for general guidance:-
1. The boiler MUST be installed so that the terminal is exposed
to external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Table
3.
4. Where the lowest part of the terminal is fitted less than 2m
(6' 6") above a balcony, above ground or above a flat roof to which people have access then the terminal MUST be protected by a purpose designed guard.
Terminals guards are available from boiler suppliers. Ask for TFC Flue Guard, Model A. In case of difficulty seek advice from:
Grasslin (UK) Ltd., Tower House, Vale Rise, Tonbridge, Kent TN9 1TB. Tel: +44 (0) 1732 359 888. Fax: +44 (0) 1732 354 445 www.tfc-group.co.uk
Ensure that the guard is fitted centrally.
Table 3 - Balanced flue terminal position
Terminal Position
1a. Directly BELOW an opening, 600mm 1500mm
air brick, opening window etc. (24") (60")
1b. Directly ABOVE an opening, 300mm 300mm
air brick, opening window etc. (12") (12")
1c. HORIZONTALLY to an opening, 400mm 600mm
air brick, opening window etc. (16") (24")
2. Below guttering, drain pipes or
soil pipes 300 mm (12")
3. Below eaves 300 mm (12")
4. Below balconies or a car port roof 600 mm (24")
5. From vertical drain pipes or 300 mm (12")
soil pipes
6. From an internal or external corner or
to a boundary alongside the terminal 600 mm (24")
7. Above adjacent ground, roof or
balcony level 300 mm (12")
8. From a surface or a boundary
facing the terminal 600 mm (24")
9. From a terminal facing a terminal 600 mm (24")
10. From an opening in a car port
(e.g. door or window) into dwelling 1200 mm (48")
11. Vertically from a terminal on the
same wall 1500 mm (60")
12. Horizontally from a terminal on
the wall 300 mm (12")
5. If a natural draught terminal is fitted less than 1m below a
plastic gutter or less than 0.5m below painted eaves or any other painted surface a suitable shield at least 1m long should be fitted to protect the surface.
6. The air inlet/products outlet duct and the terminal of the boiler
MUST NOT be closer than 25mm (1") to combustible material. Detailed recommendations on the protection of combustible material are given in BS.5440-1:2000. In IE refer to I.S. 813:2002.
IMPORTANT. It is absolutely ESSENTIAL to ensure, in practice, that products of combustion discharging from the terminal cannot re-enter the building or any other adjacent building through ventilators, windows, doors, other sources of natural air infiltration or forced ventilation/air conditioning.
If this should occur, the appliance MUST be turned OFF, labelled 'unsafe' and corrective action taken.
Minimum Spacing
330-340 350-360
TERMINAL
The terminal assembly can be adapted to accommodate various wall thicknesses. Refer to Frame 4 - Unpacking.
AIR SUPPLY
Detailed recommendations for air supply are given in BS.5440:2. In IE refer to I.S. 813:2002.
The following notes are for general guidance:
1. It is NOT necessary to have a purpose provided air vent in the
room or internal space in which the boiler is installed.
2. If the boiler is to be installed in a cupboard or compartment,
permanent air vents are required (for cooling purposes) in the cupboard/compartment, at both high and low levels. The air vents must either communicate with room/internal space, or be direct to outside air. The minimum effective areas of the permanent air vents, required in the cupboard/compartment, are specified in Table 4 and are related to maximum rated heat input.
6
Classic RS -
Installation & Servicing
GENERAL
3. Both air vents MUST communicate with the same room or
internal space or MUST be on the same wall to outside air.
4. In siting the air vents care must be taken to avoid the freezing of
pipework.
Table 4 - High and low vent areas
Boiler Air from room/internal Air direct
Space cm
RS 330 102 (16) 51 (8) RS 340 135 (21) 68 (11) RS 350 170 (26) 83 (13) RS 360 198 (31) 102 (16)
2
(in.2) Outside cm2 (in.2)
WATER CIRCULATION SYSTEM
The boiler must NOT be used for direct hot water supply. For the types of system and correct piping procedure refer to 'Introduction' and Frame 1.
The central heating system should be in accordance with BS. 6798 and, in addition, for smallbore and microbore systems, BS. 5449.
The domestic hot water system, if applicable, should be in accordance with the relevant recommendations of BS. 5546. Copper tubing to BS. 2871:1 is recommended for water carrying pipework.
The hot water storage cylinder MUST be of the indirect type and should preferably be manufactured of copper.
Single feed, indirect cylinders are not recommended and MUST NOT be used on sealed systems.
The hot water cylinder and ancillary pipework not forming part of the useful heating surface should be lagged to prevent heat loss and any possible freezing - particularly where pipes run through roof spaces and ventilated underfloor spaces.
IMPORTANT. The boiler must be vented
For sealed system installations copper tubing to BS2871:1 MUST be used throughout the heating system
Draining taps MUST be located in accessible positions, which permit the draining of the whole system - including the boiler and hot water storage vessel. They should be at least 1/2" BSP nominal size and be in accordance with BS. 2879.
The boiler is fitted with a special drain plug (provided) to drain the BOILER ONLY, in the event of the system drain plug being unable to do so. The hydraulic resistance of the boilers, at MAXIMUM OUTPUT with an 110C (20 0F) temperature differential, are shown in Table 5.
Table 5 - Water flow rate and pressure loss
Boiler Size RS 330 RS 340 RS 350 RS 360
(not on sealed systems.)
Caradon Ideal Limited recommend Water Treatment in accordance with the Treatment in Central Heating Systems.
Caradon Ideal Limited recommend the use of Fernox, GE Betz Sentinel or Salamander water treatment products, which must be used on accordance with the manufacturers instructions.
For further information contact: Fernox Manufacturing Co. Ltd, Cookson Electronics, Forsyth Road,
Sheerwater, Woking, Surrey. GU21 5RZ. Tel. +44 (0) 1799 521133 or
G E Betz Ltd, Sentinel Division, Foundry Lane, Widnes, Cheshire, WA8 8UD. Tel. +44 (0) 151 424 5351
or Salamander Engineering Ltd, Unit 24, Reddicap Trading Estate,
Sutton Coldfield, West Midlands B75 7BU. Tel. +44 (0) 121 378 0952
Notes.
Benchmark
Guidance Notes on Water
1. It is most important that the correct concentration of the water
treatment products is maintained in accordance with the manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing. BS7593:1992 details the steps necessary to clean a domestic heating system.
3. In hard water areas, treatment to prevent limescale may be
necessary - however the use of artificially softened water is NOT permitted.
4. Under no circumstances should the boiler be fired before the
system has been thoroughly flushed.
BOILER CONTROL INTERLOCKS
Caradon Ideal Limited recommend that heating systems utilising
full thermostatic radiator valve control of temperature in individual rooms should also be fitted with a room thermostat controlling the temperature in a space served by radiators not fitted with such a valve as stated in BS. 5449.
Central heating systems controls should be installed to ensure the boiler is switched off when there is no demand for heating or hot water.
When thermostatic radiator valves are used, the space heating temperature control over a living / dining area or hallway having a heating requirement of at least 10% of the boiler heat output should be achieved using a room thermostat, whilst other rooms are individually controlled by thermostatic radiator valves. However, if the system employs thermostatic radiator valves on all radiators, or two port valves without end switches, then a bypass circuit must be fitted with an automatic bypass valve to ensure a flow of water should all valves be in the closed position.
Boiler kW 8.8 11.7 14.7 17.6 Output Btu/h 30 000 40 000 50 000 60 000 Water flow l/min 11.4 15.2 19.0 22.9 Rate gal/h 150 200 250 300 Pressure mbar 16.5 22.0 37.5 45 Loss in wg 6.6 9.0 15 18
WATER TREATMENT
These boilers incorporate a cast iron heat exchanger. IMPORTANT. The application of any other treatment to this
product may render the guarantee of Caradon Ideal Limited INVALID.
Classic RS -
Installation & Servicing
ELECTRICAL SUPPLY
Wiring external to the appliance MUST be in accordance with the current I.E.E. (BS. 7671) Wiring Regulations and any local regulations which apply. For Ireland reference should be made to the current ETCI rules for electrical installations.
The point of connection to the mains should be readily accessible and adjacent to the boiler, except for bathroom installations; the point of connection to the mains MUST be situated outside of the bathroom.
Where a room sealed appliance is installed in a room
Note.
containing a bath or shower then the appliance and any electrical switch or appliance control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
7
3
BOILER ASSEMBLY - Exploded View
Classic RS 330 shown
INSTALLATION
INSTALLATION
34
4.2
4.3
5
4.1
47
34
6
2
53
22
25
3
7
LEGEND
1. Heat exchanger
2. Flue baffles
3. Hook bolt kit assy.
4.1 Pipe - RH flow
1
Programmer
18.1
12
5. Pipe - Return assy.
6. Collector hood
7. Combustion chamber
12. Main burner
26
Controls support
Data badge
Clas 1998
25. Boiler thermostat
26. Control thermostat knob
34. Balanced flue terminal
44B. Programmer (optional)
4.2 Pipe - LH flow
4.3 Pipe - Return
8
18.1. Detection electrode
22. Thermostat pocket
47. Gasket, grommet & bush kit
53. Wall mounting plate
Classic RS -
Installation & Servicing
4
UNPACKING
INSTALLATION
The boiler is supplied fully assembled in Pack A, together with a standard flue assembly for lengths up to 305mm (12") in Pack B.
Unpack and check the contents.
FLUE PACKS Note.
PACK B - contains a balanced flue terminal suitable for wall thicknesses from 229mm (9") to 305mm (12") PACK B1 - contains a balanced flue terminal suitable for wall thicknesses from 318mm (12 PACK C - contains a balanced flue terminal suitable for wall thicknesses from 114mm (4 1/2") to 191mm (7 1/2")
All flue packs contain 2 sachets of sealant
Pack A Contents
- Hardware Pack (listed below)
- Installation & Servicing Instructions
- User's Instructions.
Hardware Pack
! 50mm x No. 14 wood screw - 3 off ! 50mm x No. 10 wood screw - 3 off ! Wall plug - 6 off ! Cover plate, painted
1/2") to 394mm (15 1/2")
INSTALLATION
Note.
Wall thicknesses outside those specified cannot be accommodated. An overlap of at least 50mm at any duct joint must be allowed.
5
PACKAGING AND CASING REMOVAL
1. Unpack the boiler
2. Remove the casing as follows and place to one
side to avoid damage.
a. Release the controls pod fixing screws (a) 3 full
turns only. Remove the pod by pulling it forward to disengage from the keyhole slots.
b. Undo the 3 screws (b), retaining the casing to
the back panel.
c. Remove the casing in the direction of the
arrows.
3. Remove the boiler from its packaging base. The
boiler may now be stood on its controls support protection frame to ease handling and installation
4. Unpack the boiler terminal box and, if applicable,
the extension flue box(es).
Classic RS -
Installation & Servicing
9
INSTALLATION
6
OPEN VENT SYSTEM REQUIREMENTS - Fully pumped
The system should be vented directly off the boiler flow pipe, as close to the boiler as possible. The cold feed entry should be inverted and MUST be positioned between the pump and the vent, and not more than 150mm (6") away from the vent connection.
There should be a minimum height - 450mm (18") - of open vent above the cistern water level. If this is impossible refer below.
The vertical distance between the highest point of the system and the feed/ expansion cistern water level MUST not be less than 450mm (18").
The pump MUST be fitted on the flow side of the boiler. A suitable pump is a domestic circulator capable of providing an 11°C (20°F)
temperature differential (e.g. Grundfos UPS 15/50 or equivalent). The vertical distance between the pump and feed/expansion cistern MUST comply with the
INSTALLATION
pump manufacturer's minimum requirements to avoid cavitation. Should these conditions not apply, either lower the pump position or raise the cistern above the minimum requirement specified by Caradon Ideal Limited.
A cold water feed must be available back to the boiler when all automatic
Note.
valves are in the closed position (refer to BS. 6798) and, when close coupled, the feed must not be in a vertical leg.
7
LOW HEAD INSTALLATIONS
The Classic range of boilers can be installed in low head situations by fitting a 'surge arrester' in the expansion pipe, as shown.
The following conditions MUST be observed:
1. The surge arrester must be at least 42mm in diameter x
150mm long, thus ensuring a MINIMUM air gap and a MINIMUM depth of water below the static water level (cold) of 75mm.
2. The static water level (cold) must be at least 200mm
above the top of the horizontal flow pipe, fitted as shown. The vent connection MUST NOT be made immediately off the top of the boiler, as venting is made less efficient.
3. The maximum practical length of 15mm cold feed pipe
should be used in order to reduce the effective volume of system water expanding into the feed/expansion cistern to a minimum.
Note.
manufacturers minimum requirements must be complied with.
450 (18) Min.
Return
The pump
75 (3) Min.
200 (8) Min.
Feed / expansion cistern
Water level (cold)
22mm Open vent
System return
Surge arrester
75 (3) Min.
Flow
Highest point of flow or return
Connections to boiler
15mm Cold feed
Inverted cold feed entry
Feed / expansion
cistern
22 (3/4)
Open vent
150
(6)
Max
Max. practical
length
Minimum Requirements
All dimensions in mm (in.)
NB: Imperial dimensions are approximate
450 (18") Mimimum
450 (18") Mimimum
150 (6") Max
System flow to pump
Cold
water
level
To pump
8
REQUIREMENTS FOR CORRECT GRAVITY HOT WATER PERFORMANCE
NOTE.
Gravity horizontal pipes should be ABOVE ceiling level and as SHORT as possible. A MINIMUM inclination of 25mm per 3m run (1" per 10') is required to avoid air locks. If these conditions cannot be met, pumped primaries MUST be used.
The above graph assumes 8 elbows in the gravity circuit. For each elbow in excess of 8, (R) must be reduced by 300 mm (12 in.) or (H) increased by 100 mm (4 in.)
10
Classic RS -
Installation & Servicing
Loading...
+ 22 hidden pages