It is essential that the instructions in this booklet are strictly
followed, for safe and economical operation of the boiler.
Current Gas Safety (Installation and Use) Regulations or
rules in force. In your own interest, and that of safety, it is the
law that this boiler must be installed by a CORGI registered
installer, in accordance with the above regulations.
Tampering with sealed components or incorrect use of the
boiler will invalidate the boiler guarantee.
CAUTION.
To avoid the possibility of injury during the installation, servicing
or cleaning of this appliance care should be taken when handling
edges of sheet steel components.
Electricity Supply
This appliance must be connected to the supply via a doublepole switch, fused at 3 A.
Minimum Clearances
The minimum clearances given below must be complied with in
order to maintain the safe running of the boiler and to facilitate
servicing.
Above the boiler -160 mm (6 1/4")
At LH side of the boiler -15 mm(
At RH side of the boiler -35 mm (1 3/8")
Underneath the boiler casing:
for service -150 mm(6")
Front of the boiler:
for service -450 mm(18")
5/8")
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components.
2
C80 FF and C95 FF - User's
Supplied By www.heating spares.co Tel. 0161 620 6677
Important Notes
1. THIS APPLIANCE MUST NOT BE OPERATED WITHOUT
THE INNER FRONT SEALING PANEL BEING CORRECTLY
FITTED.
2. Compartment Installations
If the boiler is installed in a compartment then the
compartment MUST NOT be used for storage purposes.
Ventilation provided for boilers installed in compartments
MUST NOT be blocked, and a check should be made
periodically that the ventilation areas are free from any
obstruction.
3. If it is known or suspected that a fault exists on the boiler then
it MUST NOT BE USED until the fault has been corrected by
a CORGI registered installer.
Control of water temperature
DOMESTIC HOT WATER
The domestic hot water draw-off temperature is normally limited
by the modulating gas control to approximately 60
minimum water draw-off rate of about 3.5 litre/min. (0.75 g.p.m.).
It can be varied between 60
water temperature control (C).
CENTRAL HEA TING
The boiler modulating control automatically maintains the central
heating radiator temperature between 84 oC and 40 oC by
adjusting the variable heating temperature control (B).
If your system includes a room thermostat the heating
temperature control (B) may be left in its maximum position.
If your household includes very young or elderly people you may,
however, reduce this setting, for safety reasons.
o
C and 35 oC by adjusting the hot
o
C at the
Escape of gas
Should a gas leak or fault be suspected contact your local gas
supplier without delay.
Do NOT search for gas leaks with a naked flame.
Cleaning
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains use a damp cloth and mild
detergent.
DO NOT use abrasive cleaning materials.
Maintenance
The appliance should be serviced at least once a year by a
CORGI registered installer.
IMPORT ANT - DRAINING THE SYSTEM
It is not good practice to drain off radiators to decorate behind
them. In the case of sealed system boilers, such as this, it will
lower the system pressure AND MAY CAUSE THE BOILER TO
STOP WORKING.
BOILER CONTROLS
LEGEND
A Main switch
B Heating temperature control
C Hot water temperature control
To light the boiler
Summer Conditions - Domestic Hot Water Only
Set the main switch (A) to HOT WATER .
Note. Whenever domestic hot water is drawn off, the boiler will
fire to provide hot water at the tap.
Winter Conditions - Central Heating & Domestic Hot Water
Set the main switch (A) to HEATING & HOT WATER
The boiler will fire and supply heat to the radiators but will give
priority to domestic hot water when required.
D Overheat thermostat reset button
E System water pressure gauge
F Programmer (optional)
(see illustration )
.
AB
C
D
NOTE TO THE INSTALLER: LEAVE THESE INSTRUCTIONS WITH THE HOUSEHOLDER
C80 FF and C95 FF - User's
E
F
Rap 1387
3
Supplied By www.heating spares.co Tel. 0161 620 6677
To shut down the boiler
Set the main switch (A) to OFF (O).
When heating is again required, restore the switch to the HOT
WATER or HEATING & HOT WATER.
Frost
If no frost protection is provided and frost is likely during a short
absence from home, leave the heating control (B) at a reduced
temperature setting.
For longer periods, the entire system should be drained including the domestic water supply .
If the system includes a frost thermostat then, during cold
weather, the boiler should be turned OFF by selecting the OFF
programme at the time control.
Faults
A. No heating or hot water
Check that gas and electricity are available at the boiler and
that all switches are on.
Check that the system water pressure gauge (F) reads atleast 0.5 bar.
Check that the overheat thermostat has not tripped.
Remove cover and press button (D) to reset.
Turn the main switch (A) to OFF (O) position,wait 5seconds
and return to desired setting.
B. Hot water but no heating
Check that the programmer and room thermostat (if fitted)
are both calling for heat.
The mains supply should be left switched ON.
If in doubt, ask your installer.
To relight the boiler
Repeat the procedure detailed in 'To light the boiler'.
The code of practice for the installation,
commissioning & servicing of central heating systems
C. Heating but no hot water
Check that cold water does flow out of the hot taps at a
minimum rate of 3.5 litres per minute (or 1 pint in 10
seconds or less).
If not, look for stop valves not fully open.
If these simple checks fail to solve the problem, or the
problem recurs, consult your service engineer.
Caradon Plumbing Limited, P.O. Box 103,
National Ave, Kingston upon Hull, HU5 4JN.
T elephone: 01482 492 251 Fax: 01482 448 858.
Registration No. London 322 137. Registered
Office: National Avenue, Kingston upon Hull, HU5
4JN. A subsidiary of Caradon p.l.c
Caradon Plumbing Limited pursues a policy of continuing
improvement in the design and performance of its products. The
right is therefore reserved to vary specification without notice.
Caradon Plumbing Ltd. is a member of the Benchmark
initiative and fully supports the aims of the programme.
Benchmark has been introduced to improve the
standards of installation and commissioning of central
heating systems in the UK and to encourage the
regular servicing of all central heating systems to
ensure safety and efficiency .
I
deal Consumer Helpline: 01482 498 660
September 2000155 553A01