IDEAL 30-1033, 30-1034 Installation Instructions

Page 1
In-Sure™ Push-In Wire Connectors
European rating: 0.75mm²-2.5mm² solid
EN60998-1 450V 24A 40º
EN60998-2-2 1.5mm²-2.5mm² rigid stranded
Installation Instructions:
1. Wiring and installation must comply with applicable electrical regulations
3. Turn off power before removing or installing connectors
4. Strip wires back 13mm
5. Grip wire firmly and push conductor into open port. Use only one conductor per port
6. One time use only. Do not reuse
7. Do not use on aluminium wire
! WARNING !
Contact with electricity can cause serious injury or death. Shut off power at the circuit breaker or remove fuse before using this product.
ISO 9001 Registered Quality Management System.
CUSTOMER SAFETY NOTICE
Please be advised that these connectors are not designed for use with flexible stranded wire cables. The use of stranded wire is limited to 1.5mm2 - 2.5mm2 rigid stranded ( 7 strands) only.
Light gauge stranded wires of the kind typically used in lighting applications (flex with 7 strands) do not have sufficient rigidity to allow proper insertion into the connector body. Incorrect use of these connectors can be dangerous and may cause electrical fires.
To the extent permitted by law, Ideal Industries Inc. excludes its liability for any use of these connectors other than in accordance with the instructions and this customer safety notice.