Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the
safety-alert symbol . When you see this symbol on the
unit and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe
Form No. RGV-036-072-02SI Rev. BPg 1 3-24Replaces: RGV-036-072-01SI
Page 2
practices, which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
DANGER
ELECTRICAL SHOCK HAZARD
Failure to follow this warning will result in personal injury
or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lock(s) and lockout tag(s). Ensure electrical service to
rooftop unit agrees with voltage and amperage listed on
the unit rating plate. Unit may have more than one
power switch.
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death,
serious personal injury and/or property damage.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig (3450 Pa). Pressures
greater than 0.5 psig will cause gas valve damage
resulting in hazardous condition. If gas valve is
subjected to pressure greater than 0.5 psig, it must be
replaced before use. When pressure testing fieldsupplied gas piping at pressures of 0.5 psig or less, a
unit connected to such piping must be isolated by
closing the manual gas valve(s).
WARNING
CARBON-MONOXIDE POISONING HAZARD
Failure to follow instructions could result in severe
personal injury or death due to carbon-monoxide
poisoning, if combustion products infiltrate into the
building.
Check that all openings in the outside wall around the
vent (and air intake) pipe(s) are sealed to prevent
infiltration of combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are
not obstructed in any way during all seasons.
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE
CARBONE
Si ces directives ne sont pas suivies, cela peut entraîner
des blessures graves ou une intoxication au monoxyde
de carbone pouvant causer la mort, si des produits de
combustion s’infiltrent dans le bâtiment.
Vérifier que toutes les ouvertures pratiquées dans le mur
extérieur autour du ou des tuyaux d’évent (et de la prise
d’air) sont scellées de manière à empêcher l’infiltration
de produits de combustion dans le bâtiment.
Veiller à ce que la ou les sorties de l’évent de l’appareil
de chauffage (et la prise d’air) ne soient, en aucune
façon, obstruées, quelle que soit la saison.
WARNING
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
R-410A refrigerant systems operate at higher pressures
than standard R-22 systems. Do not use R-22 service
equipment or components on R-410A refrigerant
equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury
or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in
personal injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning equipment.
FIRE HAZARD
Failure to follow this warning could result in severe
personal injury and/or property damage.
Inlet pressure tap set screw must be tightened and
1/8 in. NPT pipe plug must be installed to prevent gas
leaks.
Gas Valve
Inlet Pressure
Tap Set Screw
2
Page 3
WARNING
FIRE HAZARD
Failure to follow this warning could result in severe
personal injury and/or property damage.
Manifold pressure tap set screw must be tightened and
1/8 in. NPT pipe plug must be installed to prevent gas
leaks.
Manifold Pressure
Tap Set Screw
Manifold
Gas Valve
MODEL NUMBER NOMENCLATURE AND
DIMENSIONS
See Fig. 1 for RGV model number nomenclature. See
Fig. 2 for unit dimensional drawings. Figure 2 also shows
service clearance dimensions.
Rated Indoor Airflow
Table 1 lists the rated indoor airflow used for the AHRI
efficiency rating for the units covered in this document.
Table 1 — Rated Indoor Airflow
MODEL NUMBERRATED INDOOR AIRFLOW (cfm)
RGV036/0371050
RGV048/0491500
RGV0602000
RGV0611875
RGV0722400
3
Page 4
MODEL SERIES
RGV0 6 0 LDDA0AAA
Position Number
12345678910111213
14
Type
Voltage
Heating Capacity
Outdoor Air Options / Control
0A = No Options
4B = Non-Fused Disconnect Switch
AA = Hinged Access Panels
AT = Un-Powered Convenience Outlet
BB = Powered Convenience Outlet
BP = Return Air Smoke Detector
BR = Supply Air Smoke Detector
CJ = Condensate Overflow SwitchFactory-Installed Options⁵
A = Aluminum / Copper Cond & Evap Coil
B = Precoat Alum/Copper Cond with Alum / Copper Evap (3 phase only)
C = E-Coated Alum/Copper Cond with Alum / Copper Evap (3 phase only)
D = E-Coated Alum / Copper Cond & Evap (3 phase only)
E = Copper/Copper Cond & Alum/Copper Evap (3 phase only)
F = Copper/Copper Cond & Evap (3 phase only)
Condenser / Evaporator Coil Configuration
A = Standard Controls for Factory-Installed W7212 (036-061 sizes) and All Field-Installed Economizers
B = Factory-Installed EconoMi$er
®
X with W7220 Economizer Controller
C = Factory-Installed EconomizerONE with POL224 Economizer Controller
Economizer Control
1
Units meet Department of Energy 2023 SEER2 requirements.
2
For units meeting SEER2 requirements, choose 037/049/061. For units meeting SEER requirements, choose 036/048/060.
3
The following are not available as factory-installed options for models with this voltage code: coated or copper fin coils, economizers and
two-position damper, powered convenience outlet, and Hot Gas Re-Heat.
4
Hot Gas Re-Heat system includes Low Ambient controller.
5
FIOPs installed in combination use different codes. Contact your sales representative for details.
D = Low Heat
E = Medium Heat
F = High Heat
L = Low NOx, Low Heat (sizes 036-061 only), includes Stainless Steel HX
S = Low Heat, Stainless Steel Heat Exchanger
R = Medium Heat, Stainless Steel Heat Exchanger
T = High Heat, Stainless Steel Heat Exchanger
D = Direct Drive X-Vane™ Fan – Standard Static
E = Direct Drive X-Vane Fan – High Static
F = Direct Drive X-Vane Fan – Medium Static
G = Direct Drive X-Vane Fan – High Static with Hot Gas Re-Heat
4
A = None
B = Economizer with Barometric relief, OA Temp sensor
E = Economizer with Barometric relief + CO sensor, OA Temp sensor
H = Economizer with Barometric relief, enthalpy sensor
L = Economizer with Barometric relief + CO sensor, enthalpy sensor
P = Two-Position Damper (036-061 models only)
U = Temp Ultra Low Leak Economizer with Barometric relief
W = Enthalpy Ultra Low Leak Economizer with Barometric relief
R = Rooftop
G = Gas Heat / Electric Cooling
V = Standard Efficiency 1
4 SEER and 13.4 SEER2
Nominal
Cooling
Capacity²
037 = 36,000 BTUH = 3 Tons SEER2
1
049 = 48,000 BTUH = 4 Tons SEER2
1
061 = 60,000 BTUH = 5 Tons SEER2
1
Fig. 1 — RGV036-072 Model Number Nomenclature
4
Page 5
5
Fig. 2 — Unit Dimensional Drawing
Page 6
6
Fig. 2 — Unit Dimensional Drawing (cont)
Page 7
7
Fig. 2 — Unit Dimensional Drawing (cont)
Page 8
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb
or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings.
See Fig. 2 on page 6.
NOTE: Consider also the effect of adjacent units.
Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion
and ventilation air must be provided in accordance with
Section 5.3 (Air for Combustion and Ventilation) of the
National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation
must be in accordance with the CAN1-B149 installation
codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
Locate mechanical draft system flue assembly at least
4 ft (1.2 m) from any opening through which combustion
products could enter the building, and at least 4 ft (1.2 m)
from any adjacent building (or per local code). Locate the
flue assembly at least 10 ft (3.05 m) from an adjacent
unit’s fresh air intake hood if within 3 ft (0.91 m) of same
elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least
7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate
height to allow installation of condensate trap per requirements. Refer to Install External Condensate Trap and Line
on page 17 for required trap dimensions.
ROOF MOUNT
Check building codes for weight distribution requirements.
Unit operating weights are shown in Table 2.
Table 2 — Operating Weights
RGV
Base Unit482 (219) 543 (246)556 (252)607 (275)
Economizer
Hot Gas Re-Heat
Cu Fins25 (11) 43 (20) 56 (25) 56 (25)
Powered Outlet35 (16)35 (16)35 (16)35 (16)
Curb
14 in. (356 mm)115 (52)115 (52)115 (52)115 (52)
24 in. (610 mm)197 (89)197 (89)197 (89)197 (89)
System50 (23)50 (23)80 (3680 (36)
036/037048/049060/061072
UNIT lb (kg)
Step 2 — Plan for Sequence of Unit
Installation
The support method used for this unit will dictate different
sequences for the steps of unit installation. For example, on
curb-mounted units, some accessories must be installed on
the unit before the unit is placed on the curb. Review the
following for recommended sequences for installation steps.
CURB-MOUNTED INSTALLATION
1. Install curb.
2. Install field-fabricated ductwork inside curb.
3. Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details).
4. Prepare bottom condensate drain connection to suit
planned condensate line routing (refer to Install
External Condensate Trap and Line on page 17 for
details).
5. Rig and place unit.
6. Install outdoor air hood.
7. Install flue hood.
8. Install gas piping.
9. Install condensate line trap and piping.
10. Make electrical connections.
11. Install other accessories.
PAD-MOUNTED INSTALLATION
1. Prepare pad and unit supports.
2. Check and tighten the bottom condensate drain
connection plug.
3. Rig and place unit.
4. Convert unit to side duct connection arrangement.
5. Install field-fabricated ductwork at unit duct openings.
6. Install outdoor air hood.
7. Install flue hood.
8. Install gas piping.
9. Install condensate line trap and piping.
10. Make electrical connections.
11. Install other accessories.
FRAME-MOUNTED INSTALLATION
Frame-mounted applications generally follow the sequence
for a curb installation. Adapt the sequence as required to
suit specific installation plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with
transportation agency.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.
On units with hinged panel option, check to be sure all latches are snug and in closed position.
Locate the carton containing the outside air hood parts. Do
not remove carton until unit has been rigged and located in
final position.
Step 4 — Provide Unit Support
ROOF CURB MOUNT
Accessory roof curb details and dimensions are shown in
Fig. 3 (on page 9). Assemble and install accessory roof curb
in accordance with instructions shipped with the curb.
8
Page 9
E
E
7/16"
[11]
4 9/16"
[115.5]
1/4"
[7.0]
5' 7-3/8"
[1711.3]
1' 4-13/16"
[427] INSIDE
1-3/4"
[44.4]
2-3/8"
[61]
1-3/4"
[44.5]
1.00"
[25.4]
"A"
1-3/4"
[44.4]
21.74"
[552.2]
5.42"
[137.7]
11.96"
[303.8]
4.96"
[126.0]
70.87"
[1800.2]
40.69"
[1033.5]
21.84"
[554.7]
16.03"
[407.2]
1.75"
[44.5]
20.41"
[518.3]
3.00"
[76.2]
13.78"
[350.0]
14.00"
[355.6]
3.00"
[76.2]
15.19"
[385.8]
32.19"
[817.6]
3'-1 3/16"
[944.6]
"A"
1-3/4"
[44.5]
CRBTMPWR001A013/4" [19] NPT
3/4" [19] NPT
1/2" [12.7] NPT
CRRFCURB002A01
CONNECTOR PKG. ACC. GAS CONNECTION TYPEGAS FITTING
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
TYPICAL (4) SIDES
SUPPLY AIRRETURN AIR
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
UNIT
GASKET
(SUPPLIED WITH CURB)
RIGID INSULATION
(FIELD SUPPLIED)
DUCT
(FIELD SUPPLIED)
NAIL (FIELD SUPPLIED)
VIEW "B"
CORNER DETAIL
SEE VIEW "B"
RETURN AIR
SUPPLY AIR
SUPPLY AIR
OPENING
RETURN AIR
OPENING
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
SEE NOTE #2
11 3/4"[298.5] WIDE
INSULATED DECK PANELS
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
1/3/4"[44.5]
SCALE 0.250
E-ESECTION
48TC400427
9
Fig. 3 — Roof Curb Details
Page 10
NOTE: The gasketing of the unit to the roof curb is critical
A
Maximum Allowable
Difference, in. (mm)
A-BB-CA-C
0.5 (13)1.0 (25) 1.0 (25)
for a watertight seal. Install gasket supplied with the roof
curb as shown in Fig. 3. Improperly applied gasket can
also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are shown in
Fig. 4. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb
and not to the unit. The accessory thru-the-base power
and gas connection package must be installed before the
unit is set on the roof curb. If field-installed thru-the-roof
curb gas connections are desired, use factory-supplied
duct opening dimensions for the first 18 in. (458 mm) of
duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
A minimum clearance is not required around ductwork.
Step 6 — Rig and Place Unit
1/2 in. pipe coupling and gas plate assembly to mount
the thru-the-roof curb connection to the roof curb. Gas
connections and power connections to the unit must be
field-installed after the unit is installed on the roof curb.
NOTE: If electric and control wiring is to be routed
through the basepan, attach the accessory thru-the-base
service connections to the basepan in accordance with
the accessory installation instructions.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to
roofing materials.
Membrane roofs can be cut by sharp sheet metal edges.
Be careful when placing any sheet metal parts on such
CAUTION
roof.
Keep unit upright and do not drop. Spreader bars are required. Rollers may be used to move unit across a roof.
Rigging materials under unit (cardboard or wood) must
be removed PRIOR to placing the unit on the roof curb.
Level by using unit frame as a reference. See Table 2
C
and Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
Rigging materials under unit (cardboard or wood to pre-
vent basepan damage) must be removed PRIOR to placing the unit on the roof curb.
When using the standard side drain connection, ensure
B
the red plug in the alternate bottom connection is tight.
Do this before setting the unit in place. The red drain plug
can be tightened with a 1/2 in. square socket drive extension. For further details, see “Install External Condensate
Fig. 4 — Unit Leveling Tolerances
SLAB MOUNT (HORIZONTAL UNITS ONLY)
Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
Trap and Line” on page 17.
Before setting the unit onto the curb, recheck gasketing
on curb.
POSITIONING ON CURB
in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
CAUTION
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
SLAB MOUNT)
A non-combustible sleeper rail can be used in the unit
curb support area. If sleeper rails cannot be used,
support the long sides of the unit with a minimum of
3 equally spaced 4 in. x 4 in. (102 mm x 102 mm) pads
on each side.
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof
curb and building structure. Do not connect ductwork to
unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck when packaging
is removed.
If using top crate as spreader bar, once unit is set,
carefully lower wooden crate off building roof top to
ground. Ensure that no people or obstructions are below
prior to lowering the crate.
Position unit on roof curb so that the following clearances
are maintained: 1/4 in. (6.4 mm) clearance between the
roof curb and the base rail inside the front and rear,
0.0 in. clearance between the roof curb and the base rail
inside on the duct end of the unit. This will result in the
distance between the roof curb and the base rail inside
on the condenser end of the unit being approximately
1/4 in. (6.4 mm).
10
Page 11
Fig. 5 — Rigging Details
Required
Spreader
Bars
"B"
36-54 in.
(914-1371 mm)
"C"
"A"
See Detail "A"
Place all seal strips
in place before
placing unit
on roof curb
Duct End
Detail "A"
Fan
Side
NOTE(S):
1. SPREADER BARS ARE REQUIRED. Top damage will occur if spreader bars are not used.
2. Hook rigging shackles through holes in base rail, as shown in Detail A. Holes in base rails are centered around the unit center
of gravity. Use wooden top to prevent rigging straps from damaging unit.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal
clearance of 4 ft (1220 mm) from electric and gas meters,
gas regulators, and gas relief equipment. Minimum
distance between unit and other electrically live parts is
48 in. (1220 mm).
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials. Locate mechanical draft system flue assembly at least 48 in.
(1220 mm) from an adjacent building or combustible
material.
NOTE: Installation of accessory flue discharge deflector kit
will reduce the minimum clearance to combustible material
to 18 in. (460 mm).
After unit is in position, remove rigging skids and shipping
materials.
Step 7 — Convert to Horizontal and Connect
Ductwork (When Required)
Unit is shipped in the vertical duct configuration. Unit without
Fig. 6 — Horizontal Conversion Panels
Notches
factory-installed economizer or return-air smoke detector
option may be field-converted to horizontal ducted
configuration. To convert to horizontal configuration, remove
screws from side duct opening covers (see Fig. 6) and
remove covers. Use the screws to install the covers on
vertical duct openings with the insulation-side down. The
panels must be inserted into the notches on the basepan to
properly seal. The notches are covered by the tape used to
secure the insulation to the basepan and are not easily
seen. See Fig. 7 for position of the notches in the basepan.
Seals around duct openings must be tight. Secure with
Basepan
screws as shown in Fig. 8. Cover seams with foil duct tape.
Field-supplied flanges should be attached to horizontal duct
openings and all ductwork should be secured to the flanges.
Insulate and weatherproof all external ductwork, joints, and
roof or building openings with counter flashing and mastic in
accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when insulating horizontal ductwork.
Fig. 7 — Location of Notches
11
Notches
Page 12
Step 8 — Install Outside Air Hood
Screws
Duct Covers
Sheet Metal
Face Up
Basepan
Filter Access Panel
Outdoor-Air Opening and
Indoor Coil Access Panel
Compressor
Access Panel
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for
Metal Tray
Qty (2)
ECONOMIZER AND TWO-POSITION DAMPER HOOD
PACKAGE REMOVAL AND SETUP (FACTORY
OPTION)
NOTE: Economizer and two-position damper are not available as factory installed options for single phase (-K voltage
code) models. Two-position damper is not available for
072 models.
The hood is shipped in knock-down form and must be field
assembled. The indoor coil access panel is used as the
hood top while the hood sides, divider and filter are packaged together, attached to a metal support tray using plastic
stretch wrap, and shipped in the return air compartment behind the indoor coil access panel. The hood assembly’s
metal tray is attached to the basepan and also attached to
the damper using 2 plastic tie-wraps.
1. To gain access to the hood, remove the filter access
panel. See Fig. 9.
2. Locate the (2) screws holding the metal tray to the
basepan and remove. Locate and cut the (2) plastic
tie-wraps securing the assembly to the damper. See
Fig. 10. Be careful to not damage any wiring or cut
tie-wraps securing any wiring.
3. Carefully lift the hood assembly (with metal tray)
through the filter access opening and assemble per
the steps outlined in the Economizer Hood and 2Position Hood section.
Fig. 8 — Horizontal Duct Panels In Place
Fig. 9 — Typical Access Panel Locations
Fig. 10 — Economizer and Two-Position Damper
Hood Parts Location
ECONOMIZER AND 2-POSITION HOOD
NOTE: If the power exhaust accessory is to be installed on
the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the
power exhaust hood assembly.
1. The indoor coil access panel will be used as the top
of the hood. Remove the screws along the sides and
bottom of the indoor coil access panel. See Fig. 11.
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the
screws provided to attach the hood sides to the hood
top. Use screws provided to attach the hood sides to
the unit. See Fig. 12.
3. Remove the shipping tape holding the economizer
barometric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See
Fig. 12 and 13. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 13.
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
12
Page 13
Fig. 11 — Indoor Coil Access Panel Relocation
Top
Panel
Indoor
Coil
Access
Panel
Indoor
Coil
Access
Panel
Caulk
Here
Top
Panel
To p
Panel
Indoor Coil
Access Panel
Screw
Left
Hood
Side
Hood Divider
33-3/8 in.
(848mm)
33-3/8 in.
(848mm)
19-1/16 in.
(483mm)
19-1/16 in.
(483mm)
Blower
Access
Panel
Flue Opening
Compressor Door
Outdoor Coil
Latch
Fig. 14 — Compressor Door Latch Location
Step 10 — Install Flue Hood
Flue hood is shipped screwed to the basepan beside the
burner compartment access panel. Remove from shipping
location and using screws provided, install flue hood and
screen in location shown in Fig. 15.
Fig. 12 — Economizer Hood Construction
Divider
Outside
Air
Hood
Cleanable
Aluminum
Filter
Barometric
Relief
Fig. 13 — Economizer Filter Installation
Step 9 — Units with Hinged Panels Only
If the unit does not have hinged panels, skip this step and
Filter
Filter
Clip
continue at Step 10 below.
Relocate latch shipped inside the compressor compartment
behind the hinged compressor door to location shown in
Fig. 14 after unit installation.
Fig. 15 — Flue Hood Details
Step 11 — Install Gas Piping
Installation of the gas piping must be accordance with local
building codes and with applicable national codes. In
U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas
Code (NFGC). In Canada, installation must be accordance
with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.
This unit is factory equipped for use with Natural Gas (NG)
fuel at elevations up to 2000 ft (610 m) above sea level. Unit
may be field converted for operation at elevations above
2000 ft (610 m) and/or for use with liquefied petroleum fuel.
See accessory kit installation instructions regarding these
accessories.
Furnace gas input rate on rating plate is for installation up to
2000 ft (610 m) above sea level. The input rating for altitudes above 2000 ft (610 m) must be derated by 4% for
each 1000 ft (305 m) above sea level.
For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg (996 Pa) or greater
than 13 in. wg (3240 Pa) while the unit is operating. On
RGV size 048-072 high-heat units, the gas pressure at unit
gas connection must not be less than 5 in. wg (1245 Pa) or
greater than 13 in. wg (3240 Pa) while the unit is operating,
see Table 3. For liquefied petroleum applications, the gas
pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection, see
Table 4.
13
Page 14
Table 3 — Natural Gas Supply Line Pressure Ranges
NOTE(S):
NOTE(S):
STEEL PIPE
NOMINAL DIAMETERS (in.)
SPACING OF SUPPORTS
X DIMENSION (ft)
1/26
3/4 or 18
1-1/4 or larger10
UNIT MODELUNIT SIZEMINIMUMMAXIMUM
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
036/037,
048/049,
060/061, 072
048/049,
060/061, 072
4.0 in. wg
(996 Pa)
5.0 in. wg
(1245 Pa)
13.0 in. wg
(3240 Pa)
13.0 in. wg
(3240 Pa)
Table 4 — Liquid Propane Supply Line Pressure
Ranges
UNIT MODELUNIT SIZEMINIMUMMAXIMUM
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
036/037,
048/049,
060/061, 072
048/049,
060/061, 072
11.0 in. wg
(2740 Pa)
11.0 in. wg
(2740 Pa)
13.0 in. wg
(3240 Pa)
13.0 in. wg
(3240 Pa)
The gas supply pipe enters the unit at the burner access
panel on the front side of the unit, through the long slot at
the bottom of the access panel. The gas connection to the
unit is made to the 1/2 in. FPT gas inlet port on the unit gas
valve.
Manifold pressure is factory-adjusted for natural gas fuel
use. Adjust as required to obtain best flame characteristics.
See Table 5.
Manifold pressure for LP fuel use must be adjusted to specified range. Follow instructions in the accessory kit to make
initial readjustment. See Table 6.
Table 5 — Natural Gas Manifold Pressure Ranges
UNIT MODELUNIT SIZEHIGH FIRE LOW FIRE
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
036/037,
048/049,
060/061, 072
048/049,
060/061, 072
3.5 in. wg
(872 Pa)
3.5 in. wg
(872 Pa)
See Table
Footnote
See Table
Footnote
Install a gas supply line that runs to the unit heating section.
Refer to the NFPA 54/NFGC or equivalent code for gas pipe
sizing data. Do not use a pipe size smaller than 1/2 in. Size
the gas supply line to allow for a maximum pressure drop of
0.5 in. wg (124 Pa) between gas regulator source and unit
gas valve connection when unit is operating at high-fire flow
rate.
The gas supply line can approach the unit in 3 ways: horizontally from outside the unit (across the roof), thrucurb/under unit basepan (accessory kit required), or through
unit basepan (factory option or accessory kit required). Consult accessory kit installation instructions for details on these
installation methods. Observe clearance to gas line components per Fig. 16.
X
9 in. Minimum Clearance
For Panel Removal
Manual Gas
Base Unit
Base Rail
From
Gas Meter
a
LEGEND
NFGC — National Fuel Gas Code
NOTE: Follow all local codes.
*Field-installed.
Roof
Curb
Shutoff Valve
48 in. Minimum
Drip Leg
Per NFGC
Gas
Regulator
*
*
Field-Fabricated
Support
*
*
a Low Fire, 1.7 in. wg (423 Pa), applies to the following 3-phase voltage units
only: RGV036*E and RGV048/060/072*F.
Table 6 — Liquid Propane Manifold Pressure Ranges
UNIT MODELUNIT SIZEHIGH FIRE LOW FIRE
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
a Low Fire, 5.0 in. wg (1245 Pa), applies to the following 3-phase voltage units
only: RGV036*E and RGV048/060/072*F.
036/037,
048/049,
060/061, 072
048/049,
060/061, 072
10 in. wg
(2490 Pa)
10 in. wg
(2490 Pa)
See Table
Footnote
See Table
Footnote
CAUTION
EQUIPMENT DAMAGE
Failure to follow this caution may result in equipment
damage.
When connecting the gas line to the unit gas valve, the
installer MUST use a backup wrench to prevent damage
to the valve.
a
(with Accessory Thru-the-Curb Service Connections)
This service connection kit consists of a 1/2 in. electrical
bulkhead connector and a 3/4 in. electrical bulkhead
connector, connected to an “L” bracket covering the
embossed (raised) section of the unit basepan in the
condenser section (see Fig. 17 for shipping position).
The 3/4 in. bulkhead connector enables the low-voltage
control wires to pass through the basepan. The 1/2 in.
bulkhead connector allows the high-voltage power wires to
pass through the basepan. See Fig. 18.
14
Page 15
between the “L” bracket and the connector plate
Brass Fitting
For Gas Piping
Support
Bracket
Embossment
assembly).
NOTE: Take care not to damage the gasket, as it is reused
in the following step.
3. Place the gasket over the embossed area in the
basepan, aligning the holes in the gasket to the holes
in the basepan. See Fig. 18.
4. Install the connector plate assembly to the basepan
using 8 of the washer head screws.
The thru-base gas connector has male and female threads.
The male threads protrude above the basepan of the unit;
the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting
gas piping.
Install a 1/2 in. NPT street elbow on the thru-base gas fitting.
Attach a 1/2 in. pipe nipple with minimum length of 16 in.
(406 mm) (field-supplied) to the street elbow and extend it
through the access panel at the gas support bracket. See
Fig. 19.
Fig. 17 — Thru-the-Base Fitting Assembly (Shown in
Shipping Position)
High Voltage
Conduit
Connector
Auxiliary
Power
Supply
(Optional)
Brass Fitting for
3 to 6 Ton Units
Low Voltage
Conduit
Connector
Fig. 18 — Thru-Base Connection Fittings
To prepare the unit for thru-base connections:
1. Remove the “L” bracket assembly from the unit.
2. Remove connector plate assembly from the “L”
bracket and discard the “L” bracket, but retain the
washer head screws and the gasket (located
Fig. 19 — Gas Line Piping for 3 to 6 Ton Units
Other hardware required to complete the installation of the
gas supply line includes a manual shutoff valve, a sediment
trap (drip leg) and a ground-joint union. A pressure regulator
valve may also be required (to convert gas pressure from
pounds to inches of pressure). The manual shutoff valve
must be located within 6 ft (1.83 m) of the unit. The union,
located in the final leg entering the unit, must be located at
least 9 in. (230 mm) away from the access panel to permit
the panel to be removed for service. If a regulator valve is
installed, it must be located a minimum of 4 ft (1220 mm)
away from the unit’s flue outlet. Some municipal codes require that the manual shutoff valve be located upstream of
the sediment trap. See Fig. 20 and 21 for typical piping
arrangements for gas piping that has been routed through
the sidewall of the curb. See Fig. 22 for typical piping
arrangement when thru-base is used. Ensure that all piping
does not block access to the unit’s main control box or limit
the required working space in front of the control box.
15
Page 16
9 in. (229 mm) Minimum
Shut Off
Valve
Union
9 in. (229 mm) Minimum
Unit
Base
Rail
Burner
Access
Panel
Thru-Curb Adapter
Drip
Leg
Thru-Curb Adapter
Shut Off
Valve
Drip
Leg
Union
Unit
Base
Rail
Fig. 20 — Gas Piping, Typical Curb Sidewall Piping
(Example 1)
When installing the gas supply line, observe local codes
pertaining to gas pipe installations. Refer to the NFPA
54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA
B149.1). In the absence of local building codes, adhere to
the following pertinent recommendations:
•Avoid low spots in long runs of pipe. Grade all pipe
1/4 in. per every 15 ft (7 mm per every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to
meter.
•Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one
hanger every 6 ft (1.8 m). For pipe sizes larger than
1/2 in., follow recommendations of national codes.
•Apply joint compound (pipe dope) sparingly and only
to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of
liquefied petroleum gases as specified by local
and/or national codes. If using PTFE (Teflon
®1
) tape,
ensure the material is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer’s instructions.
•Pressure-test all gas piping in accordance with local
and national plumbing and gas codes before connecting piping to unit.
NOTE: Pressure test the gas supply system after the gas
supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the
testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig
(3450 Pa). The unit heating section must be isolated from
the gas piping system by closing the external main manual
shutoff valve and slightly opening the ground-joint union.
Check for gas leaks at the field-installed and factoryinstalled gas lines after all piping connections have been
completed. Use soap-and-water solution (or method specified by local codes and/or regulations).
Fig. 21 — Gas Piping, Typical Curb Sidewall Piping
(Example 2)
Fig. 22 — Gas Piping, Typical Thru-Base
Connections
WARNING
Failure to follow this warning could result in personal
injury, death and/or property damage.
•Connect gas pipe to unit using a backup wrench
to avoid damaging gas controls.
•Never purge a gas line into a combustion
chamber.
•Never test for gas leaks with an open flame. Use a
commercially available soap solution made
specifically for the detection of leaks to check all
connections.
•Use proper length of pipe to avoid stress on gas
control manifold.
NOTE: If orifice hole appears damaged or it is suspected to
have been redrilled, check orifice hole with a numbered drill
bit of correct size. Never redrill an orifice. A burr-free and
squarely aligned orifice hole is essential for proper flame
characteristics. See Fig. 23.
1. Third-party trademarks and logos are the property of their respective
owners.
16
Page 17
Step 12 — Install External Condensate Trap and
Burner
Orifice
Standard
Side Drain
Condensate Pan (Side View)
Drain Plug
(Factory-Installed)
Alternate
Bottom
Drain
Minimum Pitch
1 in. (25 mm) Per
10 ft (3 m) of Line
To Roof
Drain
Base Rail
Open
Vent
3 in. (76 mm)
See Note
Roof
Curb
Drain Plug
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4 in. (102 mm) trap is recommended.
Min
Line
The unit has one 3/4 in. condensate drain connection on the
end of the condensate pan and an alternate connection on
the bottom. See Fig. 24. Unit airflow configuration does not
determine which drain connection to use. Either drain
connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, ensure the
red plug in the alternate bottom connection is tight. Do this
before setting the unit in place. The red drain pan can be
tightened with a 1/2 in. square socket drive extension.
To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a 1/2 in.
square socket drive extension) and install it in the side
drain connection.
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 25.
All units must have an external trap for condensate drainage. Install a trap at least 4 in. (102 mm) deep and protect
against freeze-up. If drain line is installed downstream
from the external trap, pitch the line away from the unit at
1 in. per 10 ft (25 mm per 3 m) of run. Do not use a pipe
size smaller than the unit connection (3/4 in.).
Fig. 23 — Orifice Hole
Fig. 24 — Condensate Drain Pan (Side View)
Fig. 25 — Condensate Drain Pan Piping Details
Step 13 — Make Electrical Connections
WARNING
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground.
Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of electrical wire connected to unit ground lug in
control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical
codes.
NOTE: Field-supplied wiring shall conform with the limitations of minimum 63°F (33°C) rise.
FIELD POWER SUPPLY
If equipped with optional powered convenience outlet: the
power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the
convenience outlet. If an always-energized convenience
outlet operation is desired, connect the source leads to the
line side of the unit-mounted disconnect. (Check with local
codes to ensure this method is acceptable in your area.) If
a de-energize via unit disconnect switch operation of the
convenience outlet is desired, connect the source leads to
the load side of the unit disconnect. On a unit without a
unit-mounted disconnect, connect the source leads to
compressor contactor C pressure lugs with unit field power
leads. See Convenience Outlets on page 19 for power
transformer connections.
The field power wires are connected to the unit at line-side
pressure lugs on compressor contactor C (see wiring diagram label for control box component arrangement) or at
factory-installed option non-fused disconnect switch. Maximum wire size is No. 2ga AWG (copper only) per pole on
contactors and No. 2ga AWG (copper only) per pole on optional disconnect. See Fig. 26 and unit label diagram for
field power wiring connections.
17
Page 18
NOTE: Unit may be equipped with short test leads (pig-
Units Without Non-Fused Disconnect Option
TBTB
111211121 3
Disconnect
per
NEC
208/230-1-60
L1L2L3
208/230-3-60
460-3-60
575-3-60
Units With Non-Fused Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
Disconnect
per
NEC
Copper
Wire Only
Electric
Disconnect
Switch
Aluminum
Wire
BLK
YEL
BLU
tails) on the field line connection points on contactor C or
optional disconnect switch. These leads are for factoryrun test purposes only; remove and discard before connecting field power wires to unit connection points. Make
field power connections directly to line connection pressure lugs only. See Fig. 27.
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not connect aluminum wire between disconnect
switch and unit. Use only copper wire.
Field-Install the NFD Shaft and Handle
1. Remove the Control Box access panel. The NFD
enclosure is located below the Control Box (see
Fig. 28).
2. Remove 3 cap head screws that secure the NFD
enclosure front cover — 2 on the face of the cover
and 1 on the left side cover. See Fig. 29.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at
OFF position (the arrow on the black handle knob is
at OFF).
5. Insert the shaft with the cross pin on the top of the
shaft in the horizontal position. See Fig. 29.
6. Measure from the tip of the shaft to the top surface of
the black pointer; the measurement should be 3.75 to
3.88 in. (95 to 99 mm).
7. Tighten the locking screw to secure the shaft to the
NFD.
8. Turn the handle to the OFF position with red arrow
pointing at OFF.
9. Install the handle on to the painted cover horizontally
with the red arrow pointing to the left.
10. Secure the handle to the painted cover with 2 screws
and lock washers supplied.
11. Engaging the shaft into the handle socket, re-install
3 hex screws on the NFD enclosure.
12. Re-install the unit front panel.
Fig. 26 — Power Wiring Connections
Fig. 27 — Disconnect Switch and Unit
UNITS WITH FACTORY-INSTALLED NON-FUSED
DISCONNECT
The factory-installed option non-fused disconnect (NFD)
switch is located in a weatherproof enclosure located under
the main control box. The manual switch handle and shaft
are shipped in the disconnect enclosure. Assemble the
shaft and handle to the switch at this point. Discard the factory test leads (see Fig. 26).
Connect field power supply conductors to LINE side terminals when the switch enclosure cover is removed to attach
the handle.
Fig. 28 — NFD Enclosure Location
Fig. 29 — NFD Handle and Shaft Assembly
18
Page 19
UNITS WITHOUT FACTORY-INSTALLED NON-FUSED
A
B
C
MOTOR
DISCONNECT
When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size.
Disconnect sizing data is provided on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative plate
if mounting the disconnect on the unit cabinet.
ALL UNITS
All field wiring must comply with NEC and all local codes.
Size wire based on MCA (Minimum Circuit Amps) on the
unit informative plate. See Fig. 26 and the unit label diagram
for power wiring connections to the unit power terminal
blocks and equipment ground. Maximum wire size is
No. 2ga AWG (copper only) per pole on contactors. See
Fig. 26 and unit label diagram for field power wiring
connections.
Provide a ground fault and short circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local
codes). Refer to unit informative data plate for MOCP
(Maximum Over-Current Protection) device size.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is to
be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the
1/4 in. female spade connector from the 230-v connection
and moving it to the 200-v 1/4 in. male terminal on the primary side of the transformer. Refer to unit label diagram for
additional information. Field power wires will be connected
at line-side pressure lugs on the power terminal block or at
factory-installed option non-fused disconnect.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. On
3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula
shown in the example below to determine the percent of
voltage imbalance. Operation on improper line voltage or
excessive phase imbalance constitutes abuse and may
cause damage to electrical components. Such operation
would invalidate any applicable unit warranty.
CONVENIENCE OUTLETS
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status
before opening unit for service. Locate its disconnect
switch, if appropriate, and open it. Lock-out and tag-out
this switch, if necessary.
Two types of convenience outlets are offered on RGV models: non-powered and unit-powered. Both types provide a
125-v GFCI (ground-fault circuit interrupter) duplex receptacle rated at 15A behind a hinged waterproof access cover,
located on the end panel of the unit. See Fig. 30.
Figure 31 shows the Convenience Outlet Utilization label,
which is located below the convenience outlet.
Convenience
Outlet GFCI
PWD-CO
Transformer
Fig. 30 — Convenience Outlet Location
PWD-CO Fuse
Switch
% Voltage
Imbalance
Example: Supply voltage is 230-3-60
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227-224 = 3-v
(BC) 231-227 = 4-v
(AC) 227-226 = 1-v
Maximum deviation is 4-v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
= 100 x
AB = 224-v
BC = 231-v
AC = 226-v
max voltage deviation from average voltage
(224 + 231 + 226)
average voltage
681
33
4
227
=
= 1.76%
=227
Fig. 31 — Convenience Outlet Utilization
Notice Label
NOTE: Unit powered convenience outlets are not available
as factory-installed options for single phase (-K voltage
code models).
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory-installed
convenience outlets is now required by UL standards. This
cover cannot be factory-mounted due its depth; it must be
installed at unit installation. For shipment, the convenience
outlet is covered with a blank cover plate.
On units with electromechanical controls the weatherproof
cover kit is shipped in the unit’s control box. The kit includes
the hinged cover, a backing plate, and gasket.
19
Page 20
WARNING
Cover — While-In-Use
Weatherproof
Baseplate For
GFCI Receptacle
Gasket
GFCI Receptacle
Not Included
UNIT
VOLTAGE
CONNECT
AS
PRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208, 230240
L1: RED + YEL
L2: BLU + GRA
H1 + H3
H2 + H4
460480
L1: RED
Splice BLU + YEL
L2: GRA
H1
H2 + H3
H4
575600
L1: RED
L2: GRA
H1
H2
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Using unit-mounted convenience outlets: Units with unit-
mounted convenience outlet circuits will often require
that two disconnects be opened to de-energize all power
to the unit. Treat all units as electrically energized until
the convenience outlet power is also checked and deenergization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of
convenience outlets.
1. Remove the blank cover plate at the convenience
outlet; discard the blank cover.
2. Loosen the 2 screws at the GFCI duplex outlet, until
approximately 1/2 in. (13 mm) under screw heads is
exposed. Press the gasket over the screw heads.
3. Slip the backing plate over the screw heads at the
keyhole slots and align with the gasket; tighten the
2 screws until snug (do not over-tighten).
4. Mount the weatherproof cover to the backing plate as
shown in Fig. 32.
5. Remove 2 slot fillers in the bottom of the cover to
permit service tool cords to exit the cover.
6. Check for full closing and latching.
the unit-mounted non-fused disconnect switch; this will
provide service power to the unit when the unit disconnect
switch is open. Other connection methods will result in the
convenience outlet circuit being de-energized when the unit
disconnect switch is open. See Fig. 33.
Fig. 32 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-purpose
125-v 15A circuit powered from a source elsewhere in the
building. Observe national and local codes when selecting
wire size, fuse or breaker requirements, and disconnect
switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex
receptacle.
Unit-Powered Convenience Outlet
A unit-mounted transformer is factory-installed to step down
the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch
with fuse, located inside the control box and mounted on the
vertical bracket; access is through the unit’s control box access panel. (See Fig. 30.)
The primary leads to the convenience outlet transformer are
not factory-connected. Selection of primary power source is
a customer option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on
Fig. 33 — Powered Convenience Outlet Wiring
Fuse On Power Type
The factory fuse is a Bussmann
™1
Fusetron™1 T-15,
non-renewable screw-in (Edison base) type plug fuse.
Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires and power line phasing if
the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condition.
Using Unit-Mounted Convenience Outlets
Units with unit-mounted convenience outlet circuits will often
require that 2 disconnects be opened to de-energize all
power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and
de-energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
This service connection kit consists of a 1/2 in. NPT gas
adapter fitting (brass), a 1/2 in. electrical bulkhead connector, and a 3/4 in. electrical bulkhead connector, all factoryinstalled in the embossed (raised) section of the unit basepan in the condenser section. The 3/4 in. bulkhead connector enables the low-voltage control wires to pass through the
basepan. The 1/2 in. electrical bulkhead connector allows
the high-voltage power wires to pass through the basepan.
See Fig. 18 on page 15.
1. Third-party trademarks and logos are the property of their respective
owners.
20
Page 21
NOTE: If electrical connections are not going to occur at this
Note 2: Y2 to Y2 connection required on single-stage cooling units when
integrated economizer function is desired.
Field Wiring
Unit
Control
Board
Typical
Thermostat
Connections
C
C
time, tape or otherwise cover the fittings so that moisture
does not get into the building or conduit in the interim.
Check tightness of connector lock nuts before connecting
electrical conduits.
Field-supplied and field-installed liquid tight conduit connectors and conduit may be attached to the connectors on the
basepan. Pull correctly rated high voltage and low voltage
through appropriate conduits. Connect the power conduit to
the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A hole must be
field cut in the main control box bottom on the left side so
the 24-v control connections can be made. Connect the
control power conduit to the unit control box at this hole.
UNITS WITHOUT THRU-BASE CONNECTIONS
(ELECTRICAL CONNECTIONS)
1. Install power wiring conduit through side panel open-
2. Install power lines to terminal connections as shown
FIELD CONTROL WIRING
The RGV unit requires an external temperature control de-
vice. This device can be a thermostat (field-supplied) or a
thermostat emulation device provided as part of a third-party
Building Management System.
All low-voltage wiring should be routed through the provided
raceway built into the corner post of the unit or secured to
the unit control box with the electrical conduit in order to provide UL-required clearance between high and low-voltage
wiring.
THERMOSTAT
Install a field-installed accessory thermostat according to in-
stallation instructions included with the accessory. For complete economizer function, select a 2-stage cooling thermostat. Locate the thermostat accessory on a solid wall in the
conditioned space to sense average temperature in
accordance with the thermostat installation instructions.
Typical low-voltage connections are shown in Fig. 34.
If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of
different colors with minimum of 7 leads. If the thermostat
does not require a 24-v source (no “C” connection required),
use a thermostat cable or equivalent with minimum of
6 leads. Check the thermostat installation instructions for
additional features which might require additional conductors in the cable.
For wire runs up to 50 ft (15 m), use No. 18 AWG (American
Wire Gauge) insulated wire [95°F (35°C) minimum]. For 50
to 75 ft (15 to 23 m), use No. 16 AWG insulated wire [95°F
(35°C) minimum]. For over 75 ft (23 m), use No. 14 AWG insulated wire [95°F (35°C) minimum]. Wire sizes larger than
No. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
ings. Install conduit between disconnect and control
box.
in Fig. 26 on page 18.
Fig. 34 — Low-Voltage Thermostat Connections
Thermostat Wiring, Units Without Thru-Base
Connection Kit
Pass the thermostat control wires through the hole provided
in the corner post; then feed the wires through the raceway
built into the corner post to the control box. Pull the wires
over to the terminal strip on the upper-left corner of the Unit
Control Board. See Fig. 35.
NOTE: If thru-the-bottom connections accessory is used,
refer to the accessory installation instructions for information
on routing power and control wiring.
Raceway
Hole In End Panel (Hidden)
Fig. 35 — Field Control Wiring Raceway
HEAT ANTICIPATOR SETTINGS
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second-stage heating, when available.
21
Page 22
HOT GAS RE-HEAT CONTROL CONNECTIONS
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT
RRS
S RTN
HUM
D1
D2
V+
Vg
C
HUM
G
W2
W1
Y2
Y1
R
Programmable
Thermostat
Unit Control Board
Thermostat Connections
Hot Gas Re-Heat Space RH Controller
NOTE: The Hot Gas Re-Heat system is a factory-installed
option. The Hot Gas Re-Heat system is not available for single phase (-K voltage code) models.
The Hot Gas Re-Heat dehumidification system requires a
field-supplied and field-installed space relative humidity control device. This device may be a separate humidistat control (contact closes on rise in space RH above control set
point) or a combination thermostat-humidistat control device
such as programmable thermostat device with isolated contact set for dehumidification control. The humidistat is normally used in applications where a temperature control is already provided (such as a third-party Building Management
System).
Connecting a Field-Installed Humidistat
1. Route the humidistat 2-conductor cable (field-supplied) through the hole provided in the unit corner
post.
2. Feed wires through the raceway built into the corner
post (see Fig. 35) to the 24-v barrier located on the
left side of the control box. The raceway provides the
UL-required clearance between high-voltage and
low-voltage wiring.
3. Connect one of the leads from the 2-conductor cable
to the HUM terminal on the UCB (Unit Control
Board). Connect the other lead to the R terminal on
the UCB. See Fig. 36.
Unit Control
Board
C
HUM
G
Humidistat
Thermostat
W2
W1
Y2
Y1
R
Fig. 36 — Humidistat Connections to UCB
Connecting at Field-Installed Thermidistat Device
1. Route the thermidistat multi-conductor thermostat
cable (field-supplied) through the hole provided in the
unit corner post.
2. Feed wires through the raceway built into the corner
post (see Fig. 35) to the 24-v barrier located on the
left side of the control box. The raceway provides the
UL-required clearance between high-voltage and
low-voltage wiring.
3. The thermidistat has dry contacts at terminals D1 and
D2 for dehumidification operation (see Fig. 37). Connect D1 to the R terminal on the UCB. Connect D2 to
the HUM terminal on the UCB. Refer to the installation
instructions included with the field-installed thermidistat device for more information.
TYPICAL UNIT WIRING DIAGRAMS
See Fig. 38-41 for examples of typical unit control and pow-
er wiring diagrams. These wiring diagrams are mounted on
the inside of the unit control box cover.
Fig. 37 — Typical Rooftop Unit with Hot Gas Re-Heat Dehumidification System
and Programmable Thermostat
22
Page 23
23
Fig. 38 — Typical RGV036-060 Control Wiring Diagram with Electromechanical and POL224,
208/230-3-60 Unit Shown
Page 24
24
Fig. 39 — Typical RGV072 Control Wiring Diagram with Electromechanical and POL224,
208/230-3-60 Unit Shown
Page 25
T
Fig. 40 — Typical RGV036-072 Power Wiring Diagram, 208/230-3-60 Unit Shown
25
Page 26
T
Fig. 41 — Typical RGV036-072 Power Wiring Diagram, 460-3-60 Unit Shown
26
Page 27
Integrated Gas Controller
Locking
Tab Connector
Overcurrent Fuse
Protection
Redundant Gas
Valve Relay
Locking
Tab Connector
Spade
Connect Ignitor
Status
LED
This unit contains an Integrated Gas Controller (IGC) board.
The IGC control board uses a flue gas pressure switch that
senses pressure drop in the heat exchanger due to the
combustion inducer. See Fig. 42.
Flue Gas
Pressure
Switch
Flue Gas
Pressure
Sense Tube
Fig. 42 — Flue Gas Pressure Switch and Pressure
Sense Tube (Typical Location)
When the thermostat calls for heating, power is sent to W
on the Integrated Gas Controller (IGC) board. An LED (light
emitting diode) on the IGC board turns on and remains on
during normal operation. A check is made to ensure that the
rollout switch and limit switch are closed, and that the
pressure switch is open. If the check was successful, the induced draft motor is energized. When the pressure in the
heat exchanger is low enough to close the pressure switch,
the ignition activation period begins. Once ignition occurs,
the IGC board will continue to monitor the condition of the
rollout switch, the limit switches, the pressure switch, and
the flame sensor. Assuming the unit is controlled through a
room thermostat set for “fan auto,” 45 seconds after ignition
occurs, the indoor fan motor will energize, and the outdoor
air dampers will open to their minimum position. If the “over
temperature limit” opens prior to the start of the indoor fan
blower, the IGC will shut down the burners, and the control
will shorten the 45 second delay to 5 seconds less than the
time to trip the limit. For example, if the limit trips at
37 seconds, the control will change the “fan on delay” from
45 seconds to 32 seconds. Once the “fan on delay” has
been modified, it will not change back to 45 seconds unless
power is reset to the control. On units with 2 stages of heat,
W2 closes and initiates power to the second stage of the
main gas valve when additional heat is required.
When the thermostat is satisfied, W1 and W2 open and
the gas valve closes, interrupting the flow of gas to the
main burners. If the call for W1 lasted less than 1 minute,
the heating cycle will not terminate until 1 minute after W1
became active. If the unit is controlled through a room
thermostat set for fan auto, the indoor fan motor will continue to operate for an additional 45 seconds and then
stop. An LED indicator is provided on the IGC to monitor
operation.
See Fig. 43 for IGC board component layout. Figure 44 is a
typical IGC control wiring diagram and Table 7 for
IGC Board LED Alarm Codes.
Fig. 43 — IGC Board Component Layout
27
Page 28
Fig. 44 — Typical IGC Control Wiring Diagram
UNIT CONTROL
BOARD
NOTE(S):
Table 7 — IGC Board LED Alarm Codes
a,b,c
LED FLASH
CODE
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET METHODPROBABLE CAUSE
OnNormal Operation———
OffHardware FailureNo gas heating.
1 FlashIndoor Fan On/Off Delay
Modified
5 seconds subtracted from
On delay.
5 seconds added to Off
Power reset.High temperature limit switch opens during heat
—
delay (3 minute maximum)
2 Flashes Limit Switch FaultGas valve and igniter Off.
Indoor fan and inducer On.
Limit switch closed, or
heat call (W) Off.
3 Flashes Flame Sense FaultIndoor fan and inducer On. Flame sense normal.
Power reset for LED reset.
4 Flashes 4 Consecutive Limit
Switch Fault
5 Flashes Ignition FaultNo gas heating.Heat call (W) Off.
6 Flashes Induced Draft Motor
Fault
No gas heating.Heat call (W) Off.
Power reset for LED reset.
Power reset for LED reset.
If heat off: no gas heating.
If heat on: gas valve Off
and inducer On.
Inducer sense normal, or
heat call (W) Off.
Loss of power to the IGC. Check 5 amp fuse on
IGC, power to unit, 24-v circuit breaker,
transformer, and wiring to the IGC.
exchanger warm-up period before fan-on delay
expires.
High temperature limit switch opens within 10
minutes of heat call (W) Off.
See Limit Switch Fault.
High temperature limit switch is open. Check the
operation of the indoor (evaporator) fan motor.
Ensure that the supply-air temperature rise is
within the range on the unit nameplate. Check
wiring and limit switch operation.
The IGC sensed a flame when the gas valve
should be closed. Check wiring, flame sensor, and
gas valve operation.
4 consecutive limit switch faults within a single call
for heat. See Limit Switch Fault.
Unit unsuccessfully attempted ignition for 15
minutes.
Check igniter and flame sensor electrode spacing,
gaps, etc. Check flame sense and igniter wiring.
Check gas valve operation and gas supply.
Inducer sense On when heat call Off, or inducer
sense Off when heat call On. Check wiring,
voltage, and operation of IGC motor. Check speed
sensor wiring to IGC.
7 Flashes Rollout Switch LockoutGas valve and igniter Off.
Indoor fan and inducer On.
Power reset.Rollout switch has opened. Check gas valve
operation. Check induced-draft blower wheel is
properly secured to motor shaft.
8 Flashes Internal Control Lockout No gas heating.Power reset.IGC has sensed internal hardware or software
error. If fault is not cleared by resetting 24-v
power, replace the IGC.
9 Flashes Temporary Software
Lockout
No gas heating.1 hour auto reset, or power
reset.
Electrical interference is disrupting the IGC
software.
a There is a 3-second pause between alarm code displays.
b If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.
c Alarm codes on the IGC will be lost if power to the unit is interrupted.
LEGEND
IGC — Integrated Gas Unit Control
LED — Light-Emitting Diode
28
Page 29
Hot Gas Re-Heat Dehumidification System
(Optional)
Units with the factory-installed Hot Gas Re-Heat system option are capable of providing multiple modes of improved
dehumidification as a variation of the normal cooling cycle.
The Hot Gas Re-Heat system option includes additional
valves in the liquid line and discharge line of the refrigerant
circuit and a reheat coil downstream of the evaporator. Hot
Gas Re-Heat system operation requires the installation and
configuration of a relative humidity switch input or a space
relative humidity sensor. These provide the dehumidification
demand to the control.
With Hot Gas Re-Heat system units, there are two additional HVAC modes available for the user: Dehumidification and
Dehum/Mech Cooling. Selection of the Dehum/Mech Cooling mode is determined by the dehumidification demand
and the cooling demand. Table 8 shows the corresponding
circuit mode and output status for the different demand
combinations.
NORMAL COOLING
This mode is the standard rated cooling system perfor-
mance, and occurs when there is cooling demand without
dehumidification demand.
For RGV036-061 units, refrigerant flows through the outdoor condenser and is diverted away from the reheat coil
with the open Cooling Liquid Valve (CLV) into the expansion
device. Figure 45 shows the complete refrigerant flow. The
Reheat Discharge Valve (RDV) is closed.
For RGV072 units, refrigerant flows through the outdoor
condenser and is diverted away from the reheat coil with the
closed Reheat Liquid Valve (RLV) and open CLV into the
expansion device. Figure 46 shows the complete refrigerant
flow. The RDV is closed.
DEHUM/MECH COOLING (SUBCOOLING) MODE
This mode increases the latent heat removal and decreases
sensible cooling compared to normal cooling. This occurs
when there is a cooling and dehumidification demands.
For RGV036-061 units, refrigerant flows through the outdoor condenser and is diverted through the reheat coil with
the closed CLV into the expansion device. Figure 47 shows
the complete refrigerant flow. The RDV is closed.
For RGV072 units, refrigerant flows through the outdoor
condenser and is diverted through the reheat coil with the
open RLV and closed CLV into the expansion device.
Figure 48 shows the complete refrigerant flow. The RDV is
closed.
DEHUMIDIFICATION (HOT GAS REHEAT) MODE
This mode provides maximum latent cooling with little to no
sensible capacity. This occurs when there is a dehumidification demand and no cooling demand.
For RGV036-072 units, this is the same as the Subcooling
mode but the RDV is open, which provides some compressor discharge gas to the reheat condenser to further increase the reheat of the evaporator air stream. (See Fig. 49
and 50.)
REHEAT CONTROL
When there is only a cooling demand, the unit will operate
in normal cooling mode. When there is only dehumidification demand, the unit will operate in Dehumidification
mode (Hot Gas Reheat). When there is both cooling demand and dehumidification demand, the unit will operate
in Dehum/Mech Cooling mode (Subcooling). During Dehumidification and Dehum/Mech cooling mode, the unit will
run all cooling stages.
Table 8 — Hot Gas Re-Heat System Control Modes
DEMAND AND MODE OUTPUTS
Dehumidification
Demand
No Power No Power No power Off
NoNoOffOff
NoYesCOOLOn
YesNo
YesYesDEHUMOn
Cooling Demand Mode Compressor RDV CLV
DEHUM/MECH
COOL
On
De-energized
(no flow)
De-energized
(no flow)
De-energized
(no flow)
De-energized
(no flow)
Energized
(flow)
De-energized
(flow)
De-energized
(flow)
De-energized
(flow)
Energized
(no flow)
Energized
(no flow)
RLV
(RGV072 only)
De-energized
(flow)
Energized
(no flow)
Energized
(no flow)
De-energized
(flow)
De-energized
(flow)
29
Page 30
Hot Gas Reheat Coil
Compressor
Outdoor Air
Indoor
Supply Air
Indoor
Return Air
RLV
Valve
Expansion
Valve
(TXV)
= Closed Valve
= Open Valve
RDV
Valve
Evaporator Coil
Condenser Coil
CLV
Valve
RDV
Valve
Indoor
Leaving Air
Reheat Mode
Metering
Device (TXV)
Condenser Coil
Hot Gas Reheat Coil
Outdoor Air
CLV
Valve
Compressor
Evaporator Coil
= Closed Valve
= Open Valve
Indoor
Entering Air
Fig. 45 — Normal Cooling Mode – Hot Gas Re-Heat System with Single Stage Cooling, RGV036-061
Fig. 46 — Normal Cooling Mode – Hot Gas Re-Heat System with 2 Stage Cooling, RGV072
Condenser Coil
Outdoor Air
Compressor
= Closed Valve
= Open Valve
RDV
Valve
CLV
Valve
Indoor
Leaving Air
Hot Gas Reheat Coil
Evaporator Coil
Indoor
Entering Air
Reheat Mode
Metering
Device (TXV)
Fig. 47 — Subcooling Mode – Hot Gas Re-Heat System with Single Stage Cooling, RGV036-061
30
Page 31
RDV
Valve
CLV
Valve
Condenser Coil
Hot Gas Reheat Coil
Evaporator Coil
Compressor
Outdoor Air
Indoor
Leaving Air
Indoor
Entering Air
Reheat Mode
Metering
Device (TXV)
= Closed Valve
= Open Valve
RDV
Valve
Indoor
Supply Air
Condenser Coil
Hot Gas Reheat Coil
RLV
Valve
Outdoor Air
CLV
Valve
Compressor
Expansion
Valve
(TXV)
Evaporator Coil
= Closed Valve
= Open Valve
Indoor
Return Air
Fig. 48 — Subcooling Mode – Hot Gas Re-Heat System with 2 Stage Cooling, RGV072
Fig. 49 — Hot Gas Reheat Mode – Hot Gas Re-Heat System with Single Stage Cooling, RGV036-061
RDV
Valve
Condenser Coil
RLV
Valve
Outdoor Air
CLV
Compressor
Valve
= Closed Valve
= Open Valve
Fig. 50 — Hot Gas Reheat Mode – Hot Gas Re-Heat System with 2 Stage Cooling, RGV072
31
Indoor
Supply Air
Hot Gas Reheat Coil
Expansion
Valve
(TXV)
Evaporator Coil
Indoor
Return Air
Page 32
EconomizerONE (Factory Option)
123
4
5
6
NOTE: QR codes in this image are for reference only.
NO.DESCRIPTION
1USB port for Wi-Fi/WLAN stick.
2QR code to download Climatix
™
mobile application.
3
One-line LCD. After a period of inactivity, the controller
displays the default:
HMI screen (free cooling status, 1FREECOOL YES or
1FREECOOL NO)
4
Operation button (Up button) - Move to the previous
value, step or category.
5
Operation button (Down button) - Move to the next
value, step or category.
6
Operation button (Enter button):
• Press to edit the current value or option.
• Press to confirm a newly selected value or option.
• Press Enter + Up to jump up one entire category.
• Press Enter + Down to jump down one entire
category.
ECONOMIZER SETTINGS
Interface Overview
EconomizerONE
This option consists of the following:
•Low Leak Economizer Assembly
•1193547 OA (Outdoor Air) Dry Bulb Sensor
•1193547 Mixed Air Sensor
•POL224 Controller
•1203458 Harness
POL224 Economizer Module Wiring
The economizer controller used on electromechanical units
is a Siemens POL224, which is to be located in the RTU
base unit’s control box. See Fig. 51 for button description of
the POL224 controller. Refer to the unit dimensional drawing for the location of the control box access panel.
The POL224 controller provides the following:
1. One-line LCD (Liquid Crystal Display) — After a
period of inactivity, the controller displays the default
HMI (Human Machine Interface) screen (free cooling
status, 1FREE-COOL YES or 1FREE COOL NO).
See Fig. 51-55.
2. Operation button (Up button) — Move to the previous
value, step, or category.
3. Operation button (Down Button) — Move to the next
value, step, or category.
4. Operation Button (Enter Button):
a. Press Enter to edit the current value or option.
b. Press Enter to confirm a newly selected value or
option.
c. Press Enter + Up to jump up one entire category.
d. Press Enter + Down to jump down one entire
category.
User Interface and Keypad
The controller user interface consists of an LCD display and
a 3-button keypad for input. The LCD is a 16 character by
1-line dot matrix display. The keypad is used to navigate
and change the desired menu items on the display. See
Fig. 51.
The Climatix
commissioning, and servicing. Scanning a QR code on
the controller allows users to download the mobile
application on Android
Wi-Fi/WLAN stick is needed. See Fig. 51 and 52. Plug
Wi-Fi/WLAN stick into controller USB port for temporary
connection for mobile application setup. The Wi-Fi/WLAN
stick can be used for multiple units.
Menu Structure
Menus are displayed in the economizer controller via
categories. There are eight first-level menus, each of
which is represented by a number at the beginning of the
line on the LCD. Pressing Enter + Up or Down can toggle
between different first-level menus. Submenus follow the
numbered first-level menus closely. Pressing Up or Down
can toggle between different submenus.
At the end of the line, the LCD displays the value of the current submenu (if any). If the value is editable, pressing Enter
will put the terminal in Edit mode. The value is then highlighted for change. After making a change by pressing Up or
1. Third-party trademarks and logos are the property of their respective
owners.
™1
mobile application allows for installation,
™1
or Apple iOS®1, but a
Down, press Enter to confirm the change and exit the Edit
mode. See Fig. 54.
Powering the Economizer Controller
The POL224 controller power connections are made
through the economizer harness (P/N 1203458). Connections from the harness are made to the C (24 vac
common) and R (24 vac power) terminals of the economizer controller. See Fig. 53.
LED Indication
NOTE: If different faulty events occur at the same time, then
sensor/DAC LED lights up following the priority below:
Red → Yellow → Off. For example, if there is a humidity
sensor error and air temperature failure at the same time,
then the sensor LED turns red rather than yellow. See
Fig. 55 and Table 9.
IMPORTANT: After the Economizer controller enters the
running state, it may take one minute for peripheral devices to complete initialization. Before that, LED indication
might be unstable.
Fig. 51 — POL224 Controller
32
Page 33
NOTE: QR codes in this image are for reference only.
Power
No. Description
1Number representing the first-level menu of Status Display. Different
numbers represent different menus:
1: Status Display
2: Basic Settings
3: Advanced Settings
4: Alarms
5: Enter Configuration State and Reset
6: I/O Config
7: Testing
8: Enter Running State
2Submenu*
3Value of the current submenu*
123
*See “Setup and Configuration” on page 42 for detailed submenus together
with possible values or ranges.
NO.DESCRIPTION
1Free Cooling LED
2Sensor LED
3DAC LED
123
Table 9 — LED Indication
On
Off
ShutOff SPOAT
DB
LEGEND
OAT — Outside Air Temperature
DB — Deadband
SP — Set Point
Fig. 52 — Wi-Fi/WLAN Stick
Fig. 53 — Powering the EconomizerONE Controller
STATUS
Commissioning mode
Power start upYellow OnYellow On Yellow On
Free cooling is runningGreen On——
Free cooling is available
but not running
Not economizing when it
should
Economizing when it
should not
Sensor working okay—Green On—
Humidity sensor error—Yellow On—
CO
sensor error—LED Off—
2
Air temperature fault/failure—Red On—
Excess outdoor air—
Damper working okay——Green On
Damper not modulating——Red On
Damper slippage——
Damper unplugged——
Terminal ACT-FB is
configured but no available
feedback signal
FREE
COOLING
LED
Yellow
Blinking
Green
Blinking
Red Blinking——
Red On——
——LED Off
SENSOR
LED
Yellow
Blinking
——
Red
Blinking
DAC LED
Yellow
Blinking
—
Red
Blinking
Fast Red
Blinking
Functions
Free Cooling Economizing
Free cooling uses unconditioned outside air to cool the
space directly. The economizer controller enables or disables free cooling after it judges which control mode is active. It also uses hysteresis to ensure a smooth switchover.
Depending on the sensors that are used, there are four different control modes. In different control modes, the assessed conditions are different. See Table 10.
Default Hysteresis Setting
Hysteresis setting (DB) defaults to 2°F (–17°C). See Fig. 56.
Fig. 54 — Menu Structure Descriptions
Fig. 55 — LED Indication
Fig. 56 — Hysteresis Settings
33
Page 34
Table 10 — Free Cooling Functions
CONTROL MODESENSORS USEDENABLE FREE COOLING?
Control Mode 1
• Fixed Dry bulb
Control Mode 2
• Differential Dry bulb
(Dual Dry bulbs)
Control Mode 3
• Combination Fixed
Enthalpy and Fixed
Dry bulb Control
Control Mode 4
• Combination of
Differential
Enthalpy and Fixed
Dry bulb
OA (outside air) temperature sensor
and
MA (Mixed Air) temperature sensor
OA temperature sensor, RA (Return Air)
temperature sensor and MA temperature
sensor
OA temperature and humidity sensor, and MA
temperature sensor
OA temperature and humidity sensor, RA
temperature and humidity sensor,
and MA temperature sensor
The outside air dry bulb temperature is compared with the set temperature
shutoff setpoint.
If the outside air dry bulb temperature is below the temperature shutoff
setpoint, then the outside air is used to meet all or part of the cooling demand.
The outside-air dry bulb temperature is compared with the return air dry
bulb temperature.
If both OAT and RAT are higher than the temperature high limitation, then
free cooling is prohibited.
If OAT or RAT is lower than the temperature high limitation and the outside
air dry bulb temperature is lower than the return air dry-bulb temperature,
then the outside air is used to meet all or part of the cooling demand.
The outside air dry bulb temperature and enthalpy are compared with the
set temperature and enthalpy shutoff setpoints.
If the outside air enthalpy is lower than the set enthalpy shutoff setpoint,
and the outside air dry bulb temperature is lower than the temperature
shutoff setpoint, then the outside air can be used for economizing.
The outside air dry bulb temperature and enthalpy are compared with the
temperature shutoff setpoint and return air enthalpy.
If both OA enthalpy and RA enthalpy are higher than the enthalpy high
limitation, then free cooling is prohibited.
If OA enthalpy or RA enthalpy is lower than the enthalpy high limitation,
outside air enthalpy is lower than the return-air enthalpy, and the outside
air dry bulb temperature is lower than the set temperature shutoff setpoint,
then outside air can be used for economizing.
Damper Modulation During Free Cooling
Once outside air is suitable for free cooling, the controller
modulates the damper based on MAT (mixed air temperature, default) or OAT (outside air temperature). Refer to
Table 10.
If MAT is used when free cooling is enabled, MAT setpoint
(3MAT SET, configurable in “Parameter Settings — Ad-
vanced” on page 45) is used for MAT modulating. When
MAT falls below the anti-freeze setpoint (3FRZ PROT), the
damper either fully closes or opens to the minimum position
(configurable in “Parameter Settings — Advanced” on
page 45).
1. If MAT is lower than MAT setpoint, then the damper
is modulated to maintain MAT setpoint, towards fully
closed or open to the minimum position based on
occupancy status if MAT continues dropping.
2. If MAT is in the range [MAT setpoint, (MAT setpoint +
neutral zone band [1°F by default])], then the damper
position does not change.
3. If MAT is higher than (MAT setpoint + neutral zone
band), then the damper opens towards fully open.
4. If MAT is 10°F higher than MAT setpoint, then the
damper fully opens to 100%.
If OAT is used when there is a cooling demand, the damper
can be opened to different positions depending on different
outside air temperatures:
1. If outside air is higher than 50°F but lower than the
temperature shutoff setpoint, then the damper is fully
open.
2. If outside air is higher than OAT lockout setpoint but
lower than 50°F, then linear modulation is applied
when only Cooling Stage 1 input (Y1I) is ON. Result
of the following formula indicates the damper’s open
position:
([OAT - OAT Lockout Setpoint] / [50 - OAT Lockout
Setpoint]) * (80% - MIN POS) + MIN POS
NOTE: When both free cooling and mechanical cooling
are on, damper remains fully open regardless of the
modulating logic.
Location-Based Shutoff Setpoints
The economizer controller can get location-based tempera-
ture and enthalpy shutoff setpoints automatically if it is connected to the Climatix
™
mobile application. Once a
Wi-Fi/WLAN stick is plugged in, the economizer controller
can establish network connection with the mobile application. The temperature and enthalpy shutoff setpoints obtained via the phone or tablet’s GPS functionality can then
be synchronized to the economizer controller.
Cooling Stage Operation
The economizer controller accepts inputs for 1 and 2-stage
cooling inputs and reroutes to the RTU through the relay
connection Y1 and Y2.
The operation of the cooling stages is determined by the
availability of Free Cooling provided by the economizer operation mode. See Cooling Stage I/O Logic Tables 11-12.
Based on the use of Free Cooling, the operating modes are
as follows:
•Y1 is Stage 1 Cooling Demand.
•Y2 is Stage 2 Cooling Demand.
•Free Cooling is always the first cooling stage.
•Cooling Stage 1 call from the Commercial Thermostat (Y1) energizes the Y1 input to the economizer
controller.
•Cooling Stage 2 call from the Commercial Thermostat (Y2) energizes the Y2 input to the economizer
controller.
34
Page 35
Table 11 — 1 and 2-Stage Cooling Stage I/O Logic
NOTE(S):
NOTE(S):
NOTE(S):
NOTE(S):
ECONOMIZER
CONDITION MET
Y1Y2
NOOnOnOnOn
NOOnOffOnOff
NOOffOffOffOff
YESOnOn On On/Off
YESOnOffOffOff
YESOffOffOffOff
COOLING
STAGE 1
COOLING
STAGE 2
Table 14 — Different Fan Speeds with Different
Configured Outputs
FAN TYPE1-SPEED COOLING
1-SPEED
FAN
a
2-SPEED
FAN
• Spd H (regardless of
c
c
cooling demand,
OCC=Yes)
• Spd L
(0 or 1 cooling
demand)
• Spd H
(2 cooling demands)
b
a
2-STAGE COOLING
• Spd H (regardless of
cooling demand,
OCC=Yes)
• Spd L
(0 or 1 cooling demand)
• Spd H
(2 cooling demands)
b
aIf OAT ≤ MAT setpoint (3MAT SET), then Relay 2 is always OFF to disable
Cooling Stage 2. Otherwise, if both stages of cooling (Y1 and Y2) are ON for
more than a set time (15 minutes by default), Y2 remains ON, and the OAT is
higher than MAT setpoint, then Relay 2 energizes to allow Y2 pass-through to
enable Cooling Stage 2.
IMPORTANT: The economizer controller can tolerate thermostat wiring mismatch, e.g. Thermostat Y1 → Economiz-
er Y2-In, Thermostat Y2 → Economizer Y1-In. The handling logic is Stage =Y1I + Y2I. For example, Y1O =1 if
Stage > =1, Y2O =1 if Stage > = 2.
Multi-Speed Fan Support
The economizer controller supports connection to 2-speed
fans. When the unit is equipped with a multi-speed fan, the
damper responds to multiple fan speeds via multiple minimum positions (MIN POS) to keep minimum airflow. See
Tables 13-15.
Table 13 — Damper MIN POS for 2-Speed Fan
Y1Y2
X——X — X —
XX—— X — X
—— X— X — X
W1 OR
O/B
SPD LSPD HPOS LPOS H
a
a If a single-speed fan connects to the Controller, it opens directly on the call of
cooling/heating. The damper position is Pos H.
b Configured by Y1O or Y2O.
c Configured by 6FAN.
LEGEND
Spd L — Low Speed (Fan)
Spd H — High Speed (Fan)
Table 15 — Different Damper Minimum Positions with
Different Configured Outputs
FAN TYPE1-SPEED COOLING
1-SPEED
FAN
2-SPEED
FAN
a Configured by Y1O or Y2O.
b Configured by 6FAN.
LEGEND
Pos L — Damper MIN POS for Low-Speed Fan
Pos H — Damper MIN POS for High-Speed Fan
• Pos H (regardless of
b
b
cooling demand,
OCC=Yes)
• Pos H (regardless of
cooling demand,
OCC=Yes)
a
2-STAGE COOLING
• Pos H (regardless of
cooling demand,
OCC=Yes)
• Pos L
(0 or 1 cooling demand)
•Pos H
(2 cooling demands)
b
If DCV (demand controlled ventilation) is enabled, each fan
speed corresponds to two damper position ventilation setpoints (VENT MIN, VENT MAX), e.g., Pos L corresponds to
2VENTMIN L... 2VENTMAX L. See Table 16 for Different
Damper Position Setting with Different Configured Outputs
with DCV enabled.
If CO
sensor is connected but DCV is disabled, then each
2
fan speed corresponds to one minimum damper position
ventilation setpoint. See Table 17 for Different Damper Position Setting with Different Configured Outputs with DCV disabled.
a A multi-speed fan is not controlled by the economizer controller but by an ex-
ternal logic board.
LEGEND
POS L — Damper MIN POS for Low-Speed Fan
POS H — Damper MIN POS for High-Speed Fan
SPD L — Low-Speed (Fan)
SPD H — High-Speed (Fan)
35
Page 36
Table 16 — Different Damper Position Settings with Different Configured Outputs (DCV is Enabled)
NOTE(S):
NOTE(S):
FAN TYPE1-STAGE COOLING
1-SPEED FAN
2-SPEED FAN
a Configured by Y1O or Y2O.
b Configured by 6FAN.
a
b
b
• 2VENTMIN H to 2VENTMAX H (regardless of
cooling demand, OCC=Yes)
• 2VENTMIN H to 2VENTMAX H (regardless of
cooling demand, OCC=Yes)
• 2VENTMIN H to 2VENTMAX H (regardless of
cooling demand, OCC=Yes)
• 2VENTMIN L to 2VENTMAXL
(0 or 1 cooling demand)
• 2VENTMIN H to 2VENTMAX H
(2 cooling demands)
2-STAGE COOLING
a
Table 17 — Different Damper Position Settings with Different Configured Outputs
(DCV is Disabled, CO2 sensor is connected)
FAN TYPE1-STAGE COOLING
1-SPEED FAN
2-SPEED FAN
a Configured by Y1O or Y2O.
b Configured by 6FAN.
b
b
• 2VENTMIN H (regardless of cooling demand,
OCC=Yes)
• 2VENTMIN H (regardless of cooling demand,
OCC=Yes)
Cooling Delay via Increasing Fan Speed
If there is cooling demand while outside air is suitable for
economizing, then the economizer controller tries to increase fan speed to maximize the use of outside air first. If
the cooling demand is not reached within a set time, then
mechanical cooling will be enabled.
Typical field application:
1. Prerequisites:
•Outside air is suitable for economizing and free cooling is ON.
•Fan connected to the controller supports multiple
speeds. Cooling delay function does not work if only
a one-speed fan is connected to the controller.
2. If it is a 2-speed fan and there are two cooling
demand inputs/outputs and Y1-Input is called, then
the controller sets fan speed to Speed Low. Damper
is fully open (100%).
If Y2-Input is also called, then the controller increases
fan speed to Speed High and starts fan delay (2FAN
DLY) time. After the delay time runs out, the controller
starts Y1-Output.
Demand Controlled Ventilation (DCV)
If a field-installed CO2 sensor is connected to the
EconomizerONE controller, then a demand controlled ventilation strategy will operate automatically. As the CO
level in
2
the space increases above the setpoint (on the
EconomizerONE controller), the minimum position of the
dampers will be increased proportionally until the Maximum
Ventilation setting is reached. As the space CO
level de-
2
creases because of the increase in fresh air, the outdoor
damper will follow the higher demand condition from the
DCV mode or from the free cooling mode.
The controller modulates the outside air damper based on
the CO
level through the ppm value selected between the
2
range of 500 and 2000 ppm. The measured CO2 concentration value is compared with the set DCV setpoint. If the
measured CO
concentration value is below the DCV
2
setpoint, then keep the damper to the minimum position.
Otherwise, enable DCV. Once DCV is enabled, the DCV
PID starts to run to control the indoor CO
concentration
2
value towards the DCV setpoint. The damper opens to the
maximum position.
a
• 2VENTMIN H (regardless of cooling demand,
OCC=Yes)
• 2VENTMIN L
(0 or 1 cooling demand)
• 2VENTMIN H
(2 cooling demands)
2-STAGE COOLING
a
NOTE: DCV is disabled if the controller receives no occupancy signal.
DCV operation is available in Occupied and Unoccupied
periods with the EconomizerONE system. However, a control modification will be required on the unit system to implement the Unoccupied period function. Refer to controller accessory installation instruction manual for further controls
and command operation information.
High Humidity Limitation
The economizer controller applies high limit of humidity to
enthalpy-based economizing. When the OA dew point is
below the dew point setpoint, enthalpy-based economizing is available. Otherwise, enthalpy-based economizing
is unavailable.
Anti-Freeze Protection
The economizer controller initiates the anti-freeze protection
if MAT or OAT temperature falls below the anti-freeze
setpoint.
MAT-Based Anti-Freeze Protection
1. If MAT temperature falls below the anti-freeze setpoint (3FRZ PROT), then:
•The controller closes both damper and compressor if
unit type is conventional unit and cooling/heating
conventional operation mode is enabled.
•The controller closes the damper if unit type is heat
pump and heat pump operation mode is enabled.
2. If the MAT sensor fails, MAT is substituted by OAT to
continue the anti-freeze assessment. If OAT fails too,
the controller closes the damper immediately.
OAT-Based Anti-Freeze Protection
If OAT temperature falls below the OAT lockout setpoint
(3OAT LOCK):
1. The controller stops the compressor from running if
unit type is conventional unit and cooling/heating
conventional operation mode is enabled.
2. The controller compressor is bypassed if unit type is
heat pump and heat pump operation mode is
enabled.
36
Page 37
Exhaust Fan Operation
Up to two exhaust fans can be connected to the econo-
mizer controller.
•If Exhaust Fan 1 is connected and configured, then
Exhaust Fan 1 parameter group (L, M and H) is available, depending on fan configuration.
•If Exhaust Fan 2 is connected and configured, then
Exhaust Fan 2 parameter group (L, M and H) is available, depending on fan configuration.
•The controller energizes Exhaust Fan Relay 1 and
Exhaust Fan Relay 2 if the damper position reaches
Exhaust Fan 1 parameter setting and Exhaust Fan
Relay 2 parameter setting respectively. The selection
of L, M, or H matches the current fan speed.
NOTE: If terminal ACT-FB is configured, then the damper
position is the damper feedback position. If feedback signal
is unavailable, it is the simulated position.
Occupancy Input
The economizer controller can receive an occupancy sig-
nal from the connected thermostat or work under Occupied mode all the time. This is configurable in the Thermostat setup from the Climatix
™
mobile application or under the I/O Configuration menu on the inbuilt display. See
“Parameter Settings — I/O Configurations” on page 45
for more information.
IMPORTANT: On the call of cooling, when the controller is
configured to receive signal from the thermostat but the
thermostat is working under the Unoccupied mode, the
damper is fully closed if outside air is not suitable for economizing. If outside air is suitable for economizing, the
damper is fully open.
Pre-occupancy Purge
The pre-occupancy purge demand comes from the configu-
ration of the Auxiliary features in the Climatix
™
mobile application or 6AUX2-I under the I/O Configuration menu on the
inbuilt display.
During pre-occupancy purge on the call of heating or when
there is no cooling/heating demand, the damper position is
MIN POS.
During pre-occupancy purge on the call of cooling, the
damper position is MIN POS if outside air is not suitable for
economizing. If outside air is suitable for economizing, then
the damper is fully open.
Airflow Commissioning
Airflow measurement station (differential pressure signal)
can connect to the controller temporarily to run airflow
commissioning to calculate, calibrate, and store 4 fan speed
characteristic curves automatically at damper positions
40%, 60%, 80%, and 100%. The controller places the
damper to a proper position to meet minimum or any other
airflow requests in cfm. Users can enable this function only
from the Climatix
™
mobile application if the related function
is available in the current mobile application version.
Fault Detection and Diagnostics
The economizer controller can detect and diagnose free
cooling faults, sensor operation faults, and damper modulating faults. It can also report anti-freeze and shutdown notifications and actuator errors. Following is a list of all detectable or reportable information:
•Sensor disconnected or has no signal.
•Sensor short or high signal (under range or over
range).
•Not economizing.
•Unexpected economizing.
•Excess outdoor air.
•Damper not modulating.
•Input power monitor and brownout. After detecting
brownout, the economizer controller enters the
brownout protection mode and disables all of the relay outputs.
•Anti-freeze notifications.
•Shutdown notifications.
•Actuator errors.
•Too low or too high leaving air temperature.
•Cooling/heating error.
•Damper actuator cycle count. Parameter 1ACT CNT
indicates number of times actuator has cycled. It is
resettable via HMI item 8ACT CNT RESET.
IMPORTANT: The first 6 faults are detectable via LEDs or
alarm reports on the LCD. See LED Indication on page 33
and Alarms on page 46 for fault indications. These faults
can also be displayed in the Operating section of the
Climatix
™
mobile application.
Firmware Update
NOTE: Back up configurations before firmware update. All
the previous configuration data are erased after firmware
update. NOTE: Contact Application Engineering for more information on support for firmware.
IMPORTANT: If the controller enters the configuration
state for the convenience of I/O configurations, then users
can manually switch to the running state after finishing
configurations. To do so, press Enter + Up at the same
time, and then press Enter to confirm the switch after
8RUN STATE appears on the LCD.
37
Page 38
WIRING
WARNING
Failure to follow this caution may result in damage to
equipment. Be sure to allow enough time for compressor
startup and shutdown between checkout tests so that the
compressors do not short-cycle.
Mounting Devices Connected to the Economizer
Controller
Devices like damper actuators, sensors (temperature
sensor, humidity sensor, combination temperature and
humidity sensor, CO
fans can be connected to the economizer controller. For
information on how to mount the devices, see the
device’s installation instructions. See Fig. 57 and Table 18
for economizer controller wiring details.
sensor), thermostats, and exhaust
2
Fig. 57 — EconomizerONE Control Wiring
38
Page 39
Table 18 — EconomizerONE Control Wiring Settings
NO.LABELTYPEDESCRIPTION
1+RS485 Modbus ALine A
2-RS485 Modbus BLine B
3¬GND_ISOEarth Ground
4MATType II NTC 10K or 0-10 vdcMixed or Discharge Air Temperature Sensor
5COMCOMMixed or Discharge Air Temperature Sensor Common
6OATType II NTC 10K or 0-10 vdcOutside Air Temperature Sensor
7OAH0-10 vdc or 4-20mAOutside Air Relative Humidity Sensor
8COMCOM
9AUX-AI0-10 vdc, 2-10 vdc or 0-5 vdcAir Quality Sensor or Pressure Sensor
10RATType II NTC 10K or 0-10 vdcReturn Air Temperature Sensor
11RAH0-10 vdc or 4-20mAReturn Air Relative Humidity Sensor
12S-COMCOM24 vac Common
13S-24V24 vac24 vac Power Out to Sensors
14ACT-FB2-10 vdcDamper Actuator Feedback
15ACT2-102-10 vdcDamper Actuator Output
16ACT-COM COMDamper Actuator Output Common
17ACT-24V24 vac24 vac Power Out to Damper Actuator
18AUX2-O24 vac OUT
19COMCOM24 vac Common
20AUX2-I24 vac IN
21AUX1-O24 vac OUT
22COMCOM24 vac Common
23AUX1-I24 vac IN
24OCC24 vac INOccupancy Input
25Y2O24 vac OUTCooling Stage 2 Output to Stage 2 Mechanical Cooling
26Y2I24 vac INCooling Stage 2 Input from Commercial Thermostat
27Y1O24 vac OUTCooling Stage 1 Output to Stage 1 Mechanical Cooling
28Y1I24 vac INCooling Stage 1 Input from Commercial Thermostat
29CCOM24 vac Common
30R24 vac24 vac Power
Outside Air Temperature Sensor or
Outside Air Relative Humidity Sensor Common
Configurable:
• Exhaust Fan (1 or 2)
• System Alarm output (Title 24)
Configurable:
• Shut Down
• Heat Conventional (W1)
• Heat Pump Changeover (reversing valve OB)
• Pre-occupancy
Configurable:
• Exhaust Fan (1 or 2)
• System Alarm output (Title 24)
Configurable:
• Shut Down
• Heat Conventional (W1)
• Heat Pump Changeover (reversing valve OB)
• Pre-occupancy
39
Page 40
Connecting Peripheral Devices to the Economizer
•
Outside Air:
Connect to the
OAT and COM
terminals of the
device.
•
Return Air
(Differential):
and S-COM
terminals of the
device.
•
Mixed Air: Connect
to the MAT and
COM terminals of
the device.
Mixed or Discharge Air Temperature Sensor
Outside Air Temperature Sensor
Return Air Temperature Sensor
Outside Air
Relative Humidity:
Connect to the
OAH and COM
terminals of the
device.
Return Air Relative
Humidity: Connect
to the RAH and
S-COM terminals of
the device.
Combination
Temperature/
Humidity: Connect
to the OAT, COM,
and OAH terminals
of the device.
Return
Combination
Temperature/
Humidity: Connect
to the RAT, S-COM,
and RAH terminals
of the device.
•
•
Combo Temperature and Humidity Sensor
Combo Temperature and Humidity Sensor
Connect to the
AUX-AI, S-COM,
and S-24V terminals
of the device.
•
Air Quality Sensor or
Pressure Sensor
Connect to the
ACT 2-10,
ACT-COM, and
ACT-24V terminals
of the device.
•
Damper Actuator:
Power and 2-10 Vdc
Fig. 61 — CO
Fig. 62 — Damper Actuator Connection
/Pressure Sensor Connection
2
41
Page 42
SETUP AND CONFIGURATION
NOTE(S):
IMPORTANT: Before setup and configuration, it is recommended to obtain some location-based values, such as
shutoff points, or utilize the location services in the
Climatix
™
mobile application.
Set up and configure the economizer controller before putting it into usage. This can be accomplished by using the
Climatix
™
mobile application or the inbuilt display. After
sensor, compressor, thermostat, or actuator is connected to
the economizer controller, values/statuses are displayed in
the Operating section of the mobile application and on the
LCD. Users can manually change basic and advanced settings, configure I/Os, and test the damper operation and any
configured outputs by modifying the corresponding parameter values in the local device or mobile application. See
Tables 19-26 for complete list of all parameters available on
the LCD display. Refer to it during the setup and configuration process.
NOTE: For all units, the Climatix application login is:
Administrator. For units coming from the factory with CO
configuration or single enthalpy (control mode 3), the
controller password is OneBT2.1. For all other units, use the
controller password OneBT.
NOTE: Parameters and display menus may display
differently/dynamically if different applications are configured. See Tables 19-26.
IMPORTANT: Not all operations are available on the local
POL224. For example, users can only obtain shutoff
setpoints and perform cfm commissioning via the
Climatix
™
mobile application. Setup and configuration on
the local device are only recommended if operations from
the mobile application are unavailable. Check the mobile
application for all operations that can be performed from
the mobile application end.
IMPORTANT: By connecting the RS485 port to a PC, all
parameters are also readable or writable from PC tools
such as Modbus Poll.exe via Modbus
BACnet™
a
MSTP (Bps 38400 [default], Bps 9600, Bps
®a
and Yabe.exe via
19200, Bps 115200). Note that an external End of Line
(EOL) element is required to achieve Baud Rate 115200 at
2
a maximum cable length of 4000 ft (1.2 km).
a Third-party trademarks and logos are the property of their respective owners.
42
Page 43
Table 19 — Status Display
PARAMETERDESCRIPTIONVALUE
1FREECOOLIndicates whether the system can use outdoor air for free cooling.
1ECON ENABIndicates whether outdoor air is being used for the first stage of cooling.
Indicates whether the space is occupied. If users choose ALWAYS for 6OCC when
1OCCUPIED
configuring I/Os, then the parameter value is YES; if users keep the default selection
T-STAT for 6OCC and the controller receives 24-v signal from OCC input, then the value is
YES. Otherwise, the value is NO.
1Y1-INY1-In call from thermostat for Cooling Stage 1.
1Y1-OUTY1-Out signal to compressor for Cooling Stage 1.
1Y2-INY2-In call from thermostat for Cooling Stage 2.
1Y2-OUT
1AUX1-I
1AUX1-O
1AUX2-I
1AUX2-O
Y2-Out signal to compressor for Cooling Stage 2.
Dynamic item: Appears only if Y2-Out terminal is configured.
Aux1-In signal
Dynamic item: Appears only if Aux1-In terminal is configured.
Aux1-Out signal
Dynamic item: Appears only if Aux1-Out terminal is configured.
Aux2-In signal
Dynamic item: Appears only if Aux2-In terminal is configured.
Aux2-Out signal
Dynamic item: Appears only if Aux2-Out terminal is configured.
1COMP STAGEIndicates compressor current stage.
1HEAT ENABIndicates whether heating is enabled.
1MIX AIR LOW
Indicates whether the anti-freeze protection function is enabled for a mixed air temperature
sensor. If the detected air temperature is lower than the anti-freeze protection setpoint
(3FRZ PROT), then the parameter value is YES. Otherwise, it is NO.
Indicates the present value of the mixed air temperature (MAT) sensor.
1MAT PRES
1LAT PRES
1OAT PRES
1OAH PRES
1RAT PRES
1RAH PRES
1CO2 PRES
Dynamic item: Appears only if MAT or AUTO is selected for
3DIF T LOC under Parameter Settings — Advanced on page 45.
Indicates the present value of the leaving air temperature (LAT) sensor.
Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC.
Indicates the present value of the outdoor air temperature (OAT) sensor.
Dynamic item: Appears only if an OAT sensor is configured.
Indicates the present value of the outdoor air relative humidity (OAH) sensor.
Dynamic item: Appears only if an OAH sensor is configured.
Indicates the present value of the return air temperature (RAT) sensor.
Dynamic item: Appears only if a RAT sensor is configured.
Indicates the present value of the return air relative humidity (RAH) sensor.
Dynamic item: Appears only if a RAH sensor is configured.
Indicates the present value of the CO
Dynamic item: Appears only if a CO2 sensor is configured.
sensor.
2
The corresponding detected
value is displayed on the LCD.
Indicates the demand controlled ventilation (DCV) status.
1DCV STATUS
1FAN SPD LV
Dynamic item: Appears only if a CO
Displays ON if the measured CO2 concentration value is above the DCV setpoint and OFF
if below the DCV setpoint.
Indicates the current fan speed status (low, medium, or high). If a one-speed fan is
connected and configured, then this item is invisible.
Dynamic item: Appears only if “6FAN” is configured as “2SPEED” under Parameter
sensor is configured.
2
Settings — I/O Configurations on page 45.
1ACT OUTIndicates current position of damper actuator in V.
1ACT FBIndicates feedback signal of damper actuator in V.
1ACT POSIndicates current position of damper actuator in % Open.
1ACT CNT
Indicates number of times actuator has cycled (1 cycle = 180 degrees of movement in any
direction). Resettable via HMI item 8ACT CNT RESET under Enter Running State on
The corresponding detected
value is displayed on the LCD.
page 47.
1EQUIP
Indicates the equipment type. If HP(O) or HP(B) is chosen for 6AUX1-I, then the parameter
value is HP(O) or HP(B) respectively. If neither is chosen, then the value is CON RTU.
1OAT LOCKIndicates status of the OAT cooling lockout function.
1INS
Indicates the installation date of the economizer controller. If the installation date is
incorrect, press Enter to change and confirm month, date, and year.
YES
NO
ON
OFF
Off
1
2
3
YES
NO
ON
OFF
L
H
HP(O)
HP(B)
CON RTU
NO
LCKOUT
OVRD
—
43
Page 44
Table 20 — Parameter Settings — Basic
PARAMETERDESCRIPTIONRANGEDEFAULT
Temperature shutoff setpoint can be obtained automatically if a smartphone
2 TEMP OFF
or tablet with the mobile application installed on it is connected to the
network provided by a Wi-Fi/WLAN stick plugged into the economizer
controller. This can also be a manually defined setpoint.
Enthalpy shutoff setpoint can be obtained automatically if a smartphone or
2ENTH OFF
tablet with the mobile application installed on it is connected to the network
provided by a Wi-Fi/WLAN stick plugged into the economizer controller. This
can also be a manually defined setpoint.
Dynamic item: Appears only if an OAH sensor is configured.
Demand controlled ventilation setpoint can be obtained automatically if a
2DVC
2FAN L ACT
2FAN H ACT
2VENTMAX L
2VENTMAX H
2VENTMIN L
2VENTMIN H
CFM COMM
smartphone or tablet with the mobile application installed on it is connected
to the network provided by a Wi-Fi/WLAN stick plugged into the economizer
controller. This can also be a manually defined setpoint.
Dynamic item: Appears only if a CO
Damper minimum position when fan runs at a low speed.
Dynamic item: Appears only if “6FAN” is configured as “2SPEED” under
Parameter Settings — I/O Configurations on page 45.
Damper minimum position when fan runs at a high speed.
Dynamic item: Appears only if “6FAN” is configured as “1SPEED” or
“2SPEED”.
DCV maximum position when fan runs at a low speed.
Dynamic item: Appears only if a CO
configured as “2SPEED”.
DCV maximum position when fan runs at a high speed.
Dynamic item: Appears only if a CO
configured as “1SPEED” or “2SPEED”.
DCV minimum position when fan runs at a low speed.
Dynamic item: Appears only if a CO
configured as “2SPEED”.
DCV minimum position when fan runs at a high speed.
Dynamic item: Appears only if a CO
configured as “1SPEED” or “2SPEED”.
Air Flow Chart: CFM commissioning can only be initiated from the mobile
application. When CFM commissioning is in progress, the local device
sensor is configured.
2
sensor is configured and “6FAN” is
2
sensor is configured and “6FAN” is
2
sensor is configured and “6FAN” is
2
sensor is configured and “6FAN” is
2
reads “CFM COMM”.
2DEGREESTemperature unit (°F or °C).—°F
2FANFan cfm.
Exhaust Fan 1 low-speed parameter setting.
2EX1 L
Dynamic item: Appears only if:
• Exhaust Fan 1 is configured.
•“6FAN” is configured as “2SPEED”.
Exhaust Fan 1 high-speed parameter setting.
2EX1 H
2EX2 L
Dynamic item: Appears only if:
• Exhaust Fan 1 is configured.
•“6FAN” is configured as “1SPEED” or “2SPEED”.
Exhaust Fan 2 low-speed parameter setting.
Dynamic item: Appears only if:
• Exhaust Fan 2 is configured.
•“6FAN” is configured as “2SPEED”.
Exhaust Fan 2 high-speed parameter setting.
2EX2 H
2THL
2EHL
Dynamic item: Appears only if:
• Exhaust Fan 2 is configured.
•“6FAN” is configured as “1SPEED” or “2SPEED”.
Temperature high limitation.
Dynamic item: Appears only if an RAT sensor is configured.
Enthalpy high limitation.
Dynamic item: Appears only if an RAH sensor is configured.
2FAN DLYCooling delay via increasing fan speed.0...30 min; increment by 15 min.
48...80°F; increment by 163°F
22...30 Btu/lbm; increment by 128 Btu/lbm
300...2000PPM;
increment by 100
1100PPM
2...10V; increment by 0.13.6V
2...10V; increment by 0.12.8V
2...10V; increment by 0.13.6V
2...10V; increment by 0.13.6V
2...10V; increment by 0.13.1V
2...10V; increment by 0.12.3V
——
100...50,000cfm;
increment by 100
5000cfm
0...100%; increment by 165%
0...100%; increment by 150%
0...100%80%
0...100%; increment by 175%
0...100%; increment by 1 83%
30...50 Btu/lbm; increment by 133 Btu/lbm
44
Page 45
Table 21 — Parameter Settings — Advanced
PARAMETERDESCRIPTIONVALUE/RANGEDEFAULT
3FREEZE POSAnti-freeze protection damper position (closed or minimum).
3SD ACT POSDamper position during shutdown (open or closed).
MAT sensor location:
3DIF T LOC
3LAT LOW
3LAT HIGH
3OAT CALOAT sensor calibration.–2.5...2.5°F; increment by 0.50°F
3RAT CAL
3OAH CAL
3RAH CAL
3MAT CALMAT or LAT sensor calibration.–2.5...2.5°F; increment by 0.50°F
3MAT SETSetpoint of MAT or LAT sensor.38...70°F; increment by 153°F
3FRZ PROTAnti-freeze protection setpoint of MAT sensor.35...55°F; increment by 145°F
3ACT TOLR
3OAT LOCKOAT lockout set point for anti-freeze protection.–45...80°F; increment by 132°F
3OAT LCKOVRD
3OAT LOCKODLY Indicates the overridden time if “YES” is selected for “3OAT LCKOVRD”.0...300 min; increment by 145 min.
• Choose MAT if the sensor is installed before the DX (Direct Expansion) coil.
• Choose LAT if the sensor is installed after the DX coil.
• Choose AUTO to let the economizer controller automatically detect the location.
Low limit of leaving air temperature.
Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC.
High limit of leaving air temperature.
Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC.
RAT sensor calibration.
Dynamic item: Appears only if an RAT sensor is configured.
OAH sensor calibration.
Dynamic item: Appears only if an OAH sensor is configured.
RAH sensor calibration.
Dynamic item: Appears only if an RAH sensor is configured.
Actuator tolerance setpoint between output (in percent) and feedback (in
percent).
When OAT LOCKOUT is enabled, choose to override the cooling lockout
function or not.
• Alarm output to thermostat (Title 24).
NOTE: Except for Exhaust Fan, whichever is chosen for 6AUX1-O does not
appear in the list of 6AUX2-O.
COOL 2
NONE
NONE
ALARM
EXHAUST
NONE
ALARM
EXHAUST
MSTP
MODBUSSLV
COOL 2
EXHAUST
ALARM
MSTP
Table 23 — Alarm Parameters
PARAMETERDESCRIPTION
NO ALARMNo alarm is activated.
4MAT SEN ALARMMAT sensor has failed, gone out of range, or become disconnected.
4CO2 SEN ALARMCO
4OAT SEN ALARMOAT sensor has failed, gone out of range, or become disconnected.
4OAH SEN ALARMOAH sensor has failed, gone out of range, or become disconnected.
4RAT SEN ALARMRAT sensor has failed, gone out of range, or become disconnected.
4RAH SEN ALARMRAH sensor has failed, gone out of range, or become disconnected.
4FREEZE ALARMAnti-freeze notification when MAT sensor is below anti-freeze protection setpoint.
4RTU SHUTDOWNNotification of Shutdown Active when SHUTDWN is chosen for 6AUX1-I or 6AUX2-I.
4ACTUATOR ALARMActuator gets disconnected or has failed.
4ACT UNDER VVoltage received by the actuator is below expected range.
4ACT OVER VVoltage received by the actuator is above expected range.
4ACT STALLEDDamper actuator stopped before achieving commanded position.
4ACT SLIPPINGDamper actuator slips after reaching commanded position.
4NOT ECONNot economizing when it should.
4ECON SHOULDNTEconomizing when it should not.
4EXCESS OAExcess outdoor air. Outside air intake is significantly higher than it should be.
4LLA ALARMLeaving air temperature is lower than the low limit (3LAT LOW).
4HLA ALARMLeaving air temperature is higher than the high limit (3LAT HIGH).
a All alarms are dynamic items. An alarm appears only if a related symptom mentioned above is detected.
b An alarm activation triggers a general alarm and then the configured system alarm output (AUX1-O or AUX2-O) is activated. If there is no alarm, then NO ALARM is
displayed on the HMI.
sensor has failed, gone out of range, or become disconnected.
2
a,b
Table 24 — Test Commands
PARAMETERDESCRIPTION
7DAMPER MIN POSPress Enter to test whether the economizer controller can drive damper to minimum position.
7DAMPER CLOSEPress Enter to test whether the economizer controller can drive damper to 100% Closed.
7DAMPER OPEN Press Enter to test whether the economizer controller can drive damper to 100% Open.
7DAMPER ALL Press Enter to perform all the above tests.
7DAMPERPress Enter to test whether the economizer controller can drive damper to the selected voltage.
7Y1OPress Enter to test whether the economizer controller can turn on or off the first stage of cooling (close or open relay Y1O).
7Y2O
7AUX1-OPress Enter to test AUX1-O connection (close or open relay AUX1-O).
7AUX2-OPress Enter to test AUX2-O connection (close or open relay AUX2-O).
Press Enter to test whether the economizer controller can turn on or off the second stage of cooling (close or open relay
Y2O).
46
Page 47
Table 25 — Enter Running State
PARAMETERDESCRIPTION
8RUN STATEChange to Running State. Press Enter to confirm the change.
8ENTER RUN? Confirm the change to Running State.
8FACTORY DEF
8DEF CONFIRM?Confirm the factory resetting.
8ACT CNT RESETDamper count reset.
8VER x.x.xFirmware version information such as 0.1.10.
Perform factory reset. Press Enter to confirm the reset. (This action resets the controller
password to default: OneBT.)
Table 26 — Enter Configuration State and Restart
PARAMETERDESCRIPTION
5CONFIG STATEChange to Configuration State. Press Enter to confirm the change.
5ENTER CONFIG?Confirm the change to Configuration State.
5RESTARTRestart the economizer controller. Press Enter to confirm the restart.
5CONF RESTARTConfirm the restart.
INSTALLING OPTIONAL 1196582 SINGLE
OUTSIDE AIR ENTHALPY SENSOR
When using the 1196582 enthalpy sensor (see Fig. 63) for
outside air changeover, the existing 1193547 dry bulb sensor (see Fig. 64) must be removed. The enthalpy sensor will
be mounted in the same location as the dry bulb sensor
(see Fig. 65). When the enthalpy sensor’s OA (Outside Air)
temperature, enthalpy, and dew point are below their respective setpoints, the outside air can be used for free cooling. When any of these are above the setpoint, free cooling
will not be available. Enthalpy setpoints are configurable
and create an enthalpy boundary according to the user’s input. For additional details, see Fig. 66-67 and Table 27.
Harness 1201876 is required to be connected between the
EconomizerONE harness in the return air chamber. Harness 1201876 has a 5-pin plug that connects directly to the
1196582 enthalpy sensor.
Enthalpy Control Sensor Configuration
The optional enthalpy control sensor (P/N: 1196582) communicates with the POL224 economizer controller using the
5-wire harness, 1201876. The 1196582 sensor can be used
as a single outside air enthalpy, a differential return enthalpy, or a differential return temperature sensor. Refer to the
base unit control wiring diagrams found earlier in this book
to wire the 1196582 enthalpy sensor for each option. Use
Fig. 63 and Table 29 on page 50 to locate the wiring terminals for each enthalpy control sensor.
47
Page 48
Fig. 63 — 1196582 Dimensional, Connection and Switching Information
Actuator
HH79NZ039
Outside Air
Temperature
Sensor
Outside Air
Damper
Wiring
Harness
16
16
16
15
15
14
14
10
7
8
9
6
5
4
3
13
12
11
2
1
Fig. 64 — 1193547 Dry Bulb and Mixed Air Sensor Wiring
Fig. 65 — EconomizerONE Component Locations
(CRECOMZR108A00 Shown)
Fig. 66 — California Title 24 Zones
48
Page 49
NOTE(S):
U.S. and Canada I-Codes / ASHRAE Zones
Climate Zone 1
Climate Zone 2
Climate Zone 3
Climate Zone 4 (Except Marine)
Climate Zone 5 and Marine
Climate Zone 6
Climate Zone 7 and 8
Fig. 67 — U.S. and Canada Climate Zones
Table 27 — Enthalpy Manual Entry Setpoints for EconomizerONE Per Climate Zone
a See Fig. 67 for map of U.S. and Canada climate zones.
b See Fig. 66 for map of California Title 24 zones.
49
Page 50
Economizers are shipped standard with an 1193547 outside
NOTE(S):
air dry bulb sensor (see Fig. 64). System default setting
(high temp limit) is 63°F (17°C) and has a range of 48°F to
80°F (9°C to 27°C). Sensor is factory installed on
economizer.
NOTE: A second 1193547 sensor is provided for mixed air
temperature.
NOTE: California high temperature setting requirements by
region are shown in Table 28.
Enthalpy Settings (Enthalpy Option)
If installing the optional 1196582 enthalpy sensor, the
1193547 dry bulb outside air sensor must first be removed.
Wire sensor to harness 1201876 and the (5) wires from the
harness to the EconomizerONE harness in the return air
chamber. Harness 1201876 has a 5-pin plug that connects
directly to the 1196582 enthalpy sensor. Refer to the base
unit control wiring diagrams earlier in this book for wiring
connections. Refer to Fig. 63 and Table 29.
California’s Title 24 High Temperature
Limit Settings
California’s Title 24 code requires a high temperature limit setting for all dry bulb outside air economizer changeover. The temperatures vary by the region within California. See Table 28 for high limit settings.
Table 28 — California Title 24 Regional High Limit
Dry Bulb Temperature Settings
CLIMATE
DEVICE TYPE
FIXED DRY
BULB
DIFFERENTIAL
DRY BULB
FIXED
ENTHALPY
+ FIXED DRY
BULB
a This table sourced from 2019 California Energy Code, Title 24, Part 6, Table
140.4-E Air Economizer High Limit Shut Off Control Requirements.
b Only the high limit control devices listed are allowed to be used and at the set
points listed. Others such as Dew Point, Fixed Enthalpy, Electronic Enthalpy,
and Differential Enthalpy Controls, may not be used in any climate zone for
compliance with Section 140.4(e)1 unless approval for use is provided by the
Energy Commission Executive Director.
c At altitudes substantially different than sea level, the Fixed Enthalpy limit value
shall be set to the enthalpy value at 75°F and 50% relative humidity. As an example, at approximately 6,000 foot elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb.
b
ZONES
1, 3, 5, 11-16OAT exceeds 75°F (23.8°C)
2, 4, 10OAT exceeds 73°F (22.7°C)
6, 8, 9OAT exceeds 71°F (21.6°C)
7OAT exceeds 69°F (20.5°C)
1, 3, 5, 11-16
2, 4, 10
6, 8, 9
7
c
All
REQUIRED HIGH LIMIT
(ECONOMIZER OFF WHEN):
DESCRIPTION
OAT exceeds
RA temperature
OAT exceeds return air temperature
OAT exceeds return air temperature
OAT exceeds return air temperature
OAT exceeds 28 Btu/lb of dry airb or
–2°F (–18.8°C)
–4°F (–20°C)
–6°F (–21.1°C)
OAT exceeds 75°F (23.8°C)
a
LEGEND
OAT —Outdoor-air Thermostat
RA —Return Air
Table 29 — 1196582 Sensor Wiring Terminations
TERMINAL
NUMBERLABEL
1TCOMNTC 10kOutside Air Temperature Sensor Output
2TSIGNTC 10kOutside Air Temperature Sensor Output
3HSIG0-10 vdcOutside Air Relative Humidity Sensor Output
4HCOMCOMMONSensor 24-v Common Input
5H24V24 vacSensor 24-v Operating Voltage Input
TYPEDESCRIPTION
50
Page 51
CHECKOUT
Inspect all wiring connections at the economizer module’s
terminals, and verify compliance with the installation wiring
diagrams. For checkout, review the Status of each configured parameter and perform the Test Commands tests (refer to Table 24).
For information about menu navigation and use of the keypad see Interface Overview on page 32.
WARNING
ELECTRIC SHOCK HAZARD
Failure to follow this warning could result in personal
injury, property damage, or death.
Before performing service or maintenance operations on
unit, always turn off main power switch to unit and install
lock(s) and lockout tag(s). Unit may have more than one
power switch. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
If any wiring changes are required, first be sure to
remove power from the economizer module before
starting work. Pay particular attention to verifying the
power connection (24 vac).
Power Up
After the POL224 module is mounted and wired, apply
power.
Initial Menu Display
On initial start up, “Welcome” displays on the economizer
HMI screen. After a brief pause, the Parameter Settings —
I/O Configuration (refer to Table 22) of the software appears, allowing the user to check that presets and default
values are configured correctly.
Power Loss (Outage or Brownout)
All set points and advanced settings are restored after any
power loss or interruption.
NOTE: All settings are stored in non-volatile flash memory.
Status
Use the Status menu (refer to Table 19) to check the parameter values for the various devices and sensors configured.
NOTE: For information about menu navigation and use of
the keypad, see Interface Overview on page 32.
Checkout Tests
Use the Test Commands menu (refer to Table 24) to test the
damper operation and any configured outputs. Only items
that are configured are shown in the Test Commands menu.
NOTE: For information about menu navigation and use of
the keypad, see Interface Overview on page 32.
To perform a Test Command test:
1. Scroll to the desired test in Test Command menu 7
using the Up and Down buttons.
2. Press the Enter button to select the item. RUN?
appears.
3. Press the Enter button to start the test. The unit
pauses and then displays IN PROGRESS. When the
test is complete, DONE appears.
4. When all desired parameters have been tested,
press Enter + Up to end the test.
The Checkout tests can all be performed at the time of installation or at any time during the operation of the system
as a test that the system is operable.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Be sure to allow enough time for compressor start-up
and shutdown between checkout tests so that you do
not short-cycle the compressors.
51
Page 52
TROUBLESHOOTING
NOTE(S):
For EconomizerONE troubleshooting issues see Table 30.
Table 30 — Operating Issues and Concerns
SYMPTOMREASONSOLUTION
An alarm is displayed on the
LCD
DAC LED is blinking REDDamper slippageCheck whether the damper works properly.
DAC LED is blinking
RED quickly
DAC LED is OFF
Economizer controller has
no alarm, but the Free
Cooling LED will not turn on
when the OA seems to be
suitable for Free Cooling
Economizer
controller/mechanical
cooling is not operating
Firmware update failure
Free Cooling LED is solid
RED
Free Cooling LED is blinking
RED
Incorrect controller
password error on mobile
application
RS485 communication
failure
Sensor LED is blinking RED Excess outdoor airCheck the whole economizer working system, such as the sensor, damper, and thermostat.
Sensor LED is solid RED
Sensor LED is OFFCO
Sensor LED is YELLOWHumidity sensor error
Wi-Fi connection failure
Sensor, damper, or the whole working
system may not work properly
Damper unpluggedCheck whether the damper is connected.
Terminal ACT-FB is configured but there is
no available feedback signal
Shutoff SP setting error
OA temp is too low
OA temp is too high or too humid
No input power
Brownout
Y1/Y2 signal is missing from the
thermostat
24 vac~ and 24 vac ⊥
are incorrectly wired
Application file is damaged, operation is
incorrect, and/or USB flash disk does not
work properly
Sensor, damper, or whole working system
may not work properly
Not economizing when it shouldCheck the whole economizer working system, such as the sensor, damper, and thermostat.
and single enthalpy (control
For CO
2
mode 3) configurations from the factory,
the password has changed
RS485 signal or configuration error
Mixed Air (MA) sensor errorCheck the MA sensor. It must be either a Type II NTC 10K or 0-10 vdc sensor.
Outside Air (OA)/Return Air (RA) sensor
error
Air temperature failure/fault
sensor error
2
Wi-Fi/WLAN stick error or wrong user
name and password
Check sensor, damper, or the whole working system following the detailed alarm information.
Check whether the feedback signal is connected; check if ACT-FB is faulty.
Shutoff temperature and/or enthalpy set point is incorrectly set up. Consult an HVAC
professional to set up the shutoff set point correctly.
The OA temperature is too low; therefore, there is no cooling demand. This could possibly
enable anti-freeze protection.
In DIFF mode, even though OA temperature is lower than RA temperature, if both OA and RA
temperatures exceed the high limit, then Free Cooling turns off.
In Differential Enthalpy control mode, even though OA enthalpy is lower than RA enthalpy, if
both OA and RA enthalpy exceed the high limit, then Free Cooling turns off.
Use a multi-meter to check whether there is 24 vac ± 25% (18-30 vac) at the POWER
terminals. If there is no voltage or if the voltage is significantly low, then check the transformer
output voltage at the RTU. If 24-v is not present at the transformer secondary side, then check
the primary line voltage to the transformer. If the line voltage is not present at the transformer
primary side, then check the primary power to the RTU, fuses, circuit breaker, and so on.
If voltage is below 17-v, then the economizer controller may be in Brownout Protection mode.
This mode disables all of the relay outputs. When the power is 19 vac or higher, the
economizer controller and RTU operate normally.
Mechanical cooling does not run until there is cooling demand (Y1/Y2 Active). Check the wiring
from Y1I and Y2I terminals to the commercial thermostat. 24-v should be present between
Y1I/Y2I and Y1O/Y2O respectively.
24 vac power supply has polarity when all devices are powered by the same 24 vac
transformer; reversing polarity may cause a short circuit that can damage the system.
Follow the transformer polarity mark, check the wiring of 24-v~ (or G or 24-v+), and ensure that
they are tied to the same polar of 24 vac power supply; while checking the wiring of ⊥ (or G0 or
24-v- or COM), ensure that they are all tied to another polar of 24 vac power supply.
a
Reload a BIN file, restart the controller, update firmware
service provider if failure still exists.
Check sensor, damper, or the whole working system following the detailed alarm information.
For units coming from the factory with CO
use the controller password OneBT2.1.
For all other units, use the controller password OneBT.
Performing a factory reset on the controller will also reset the password to OneBT.
Check wiring, configuration, Baud Rate (using mobile application), and other network
communication parameters.
Check the wiring and signal of the OA sensor. If in Differential (DIFF) mode, also check the RA
sensor. The following sensor signals are valid:
Type II NTC 10K or 0-10 vdc temperature.
0-10 vdc or 4-20 mA humidity.
Check the air temperature sensor signal. The valid signal must be Type II NTC 10K or 0-10
vdc.
Check CO
type.
Check humidity sensor connection, sensor signal (under range or over range), and sensor
signal type.
Unplug and re-plug in the Wi-Fi/WLAN stick, enter a correct user name and password, restart
the controller, or replace the Wi-Fi/WLAN stick. If the Wi-Fi/WLAN stick is POL903.00/100, then
the default user name and password are Siemens-WLAN-Stick and SIBPAdmin. DNS name is
siemens.wlanstick. Contact Application Engineering for information on this accessory.
sensor connection, sensor signal (under range or over range), and sensor signal
2
configuration or single enthalpy (control mode 3),
2
, or change a USB flash disk. Contact
a Back up configurations before firmware update. All the previous configuration data is erased after firmware update. Contact Application Engineering for more information
on support for firmware.
IMPORTANT: If the controller enters the configuration state for the convenience of I/O configurations, then users can manually switch to the running state after finishing
configurations. To do so, press Enter + Up at the same time, then press Enter to confirm the switch after 8RUN STATE appears on the LCD.
52
Page 53
Controller Options
Return Air
Smoke Detector
(As Shipped)
Step 1Step 2Step 3
LOW AMBIENT
If the unit comes with electromechanical (EM) controls, then
no adjustment is necessary.
Smoke Detectors
Smoke detectors are available as factory-installed options
on RGV models. Smoke detectors may be specified for
supply air only, for return air without or with economizer, or
in combination of supply air and return air. Return-air smoke
detectors are arranged for vertical return configurations only. All components necessary for operation are factoryprovided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be
necessary to complete the unit and smoke detector configuration to meet project requirements.
Units equipped with factory-optional return-air smoke detectors require a relocation of the sensor module at unit
installation. See Fig. 68 for the as-shipped location.
Completing Return Air Smoke Sensor Installation
1. Unscrew the 2 screws holding the return air smoke
detector assembly. See Fig. 69, Step 1. Save the
screws.
2. Turn the assembly 90 degrees and then rotate end to
end. Make sure that the elbow fitting is pointing
down. See Fig. 69, Step 2.
3. Screw the sensor and detector plate into its operating
position using screws from Step 1. See Fig. 69,
Step 3.
4. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Additional Application Data
Refer to the application data document “Factory Installed
Smoke Detectors for Small and Medium Rooftop Units 2 to
25 Tons” for discussions on additional control features of
these smoke detectors including multiple unit coordination.
Fig. 68 — Return Air Smoke Detector,
Shipping Position
Fig. 69 — Completing Installation of Return Air Smoke Sensor
53
Page 54
Step 14 — Adjust Factory-Installed Options
SMOKE DETECTORS
Smoke detector(s) will be connected at the Unit Control
Board (UCB), at terminals marked “Smoke Shutdown.” Detach the jumper covering the Smoke Shutdown terminals on
the UCB and then attach the wiring harness from the smoke
detector.
ECONOMIZERONE OCCUPANCY SWITCH
External occupancy control is managed through a connec-
tion on the Unit Control Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked OCCUPANCY. Detach the jumper covering the “Occupancy”
terminals on the UCB and then attach the required
connections.
Step 15 — Install Accessories
Available accessories include:
•Roof curb
•Thru-base connection kit (must be installed before
unit is set on roof curb)
•LP conversion kit
•Flue discharge deflector
•Manual outside air damper
•Two-position motorized outside air damper
•EconomizerONE (with POL224 controller)
•Power Exhaust
•Differential dry-bulb sensor (EconomizerONE)
•Outdoor enthalpy sensor
•Differential enthalpy sensor
•CO
•Louvered hail guard
•Phase monitor control
Refer to separate installation instructions for information on
installing these accessories.
sensor
2
54
Page 55
Step 16 — Fan Speed Set Up
Fan Speed Set Up Controls
Fan Speed Set Up Controls
Switch 1
5-Pin DIP
UNITS WITH ELECTROMECHANICAL CONTROLS
The fan speed set up controls are located on the lower sec-
tion of the Unit Control Board (UCB). See Fig. 70 for the location on 3-phase voltage units or Fig. 71 for the location on
single phase voltage units.
1. Check the job specifications for the cfm (cubic feet
per minute) and ESP (external static pressure)
required.
2. Using the chart on the Fan Speed Set Up labels (see
Fig. 73), calculate the vdc from the cfm and ESP for
the base unit. Then add vdc for any accessories
installed per the “Field Accessories” section of the
label.
NOTE: The Fan Speed Set Up labels are located on the
High Voltage cover in the Control Box.
3. Connect a multimeter to the vdc terminals on the
UCB.
4. Set the Range Switch to either A, B, or C per the
Switch Range table.
5. Using a straight blade screwdriver, turn the vdc control dial to fine tune the vdc reading.
6. Record the reading in the Field Setting field.
NOTE: Fan set-up vdc is not affected by the operating stage
of the unit.
Fig. 71 — UCB Fan Speed Controls —
Single Phase Units
NOTE: On single phase units, the approximate static
pressure of the ductwork must be set for optimal unit efficiency. The unit is factory set for greater than 1.0 in. wg. If
the external static pressure is less than 1.0 in. wg, slide
switch 1 on the 5-pin DIP to the “ON” position. See Fig. 72.
Fig. 72 — Detail — 5-Pin DIP Switch
Fig. 70 — UCB Fan Speed Controls — 3-Phase Units
55
Page 56
VDCCalculator
NOTE: Values in the Field Accessories section are vdc adders.
1500
1625
1750
1875
2000
CFM
2125
2250
2375
UNIT MODEL NUMBER
2500
Field Accessories:
Fig. 73 — Example of Fan Speed Set Up Labels for Electromechanical Controls
0.2
6.0
6.3
6.7
7.1
7.5
7.9
8.3
8.7
9.1
0.1
0.4
6.7
7.1
7.4
7.7
8.1
8.4
8.8
9.2
9.5
0.1
0.6
7.4
7.7
8.0
8.3
8.7
9.0
9.4
9.7
0.1
ESP in. wg
0.8
8.0
8.3
8.6
8.9
9.2
9.5
9.9
0.1
1.0
8.5
8.8
9.1
9.4
9.7
0.1
1.2
9.0
9.3
9.5
9.8
0.1
1.4
9.5
9.7
10.0
0.1
1.61.82.0
9.9
0.1Economizer
Factory Setting:
9.0 V
DC
Field Setting:
Record field setting here
V
Switch Range:
B
A
A
4.1 - 7.5
6.9 - 8.7
B
7.7 - 10.0
C
* Overlap in A, B, C switch range
designed for maximum field
adjustment potential. For example
Form No. RGV-036-072-02SI Rev. BPg 58 3-24Replaces: RGV-036-072-01SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 59
START-UP CHECKLIST FOR RGV036-072 SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNIT
(Remove and use for job file)
NOTE: To avoid injury to personnel and damage to equipment or
property when completing the procedures listed in this start-up
checklist, use good judgment, follow safe practices, and adhere to
the safety considerations/information as outlined in preceding
sections of this document.
I. PRELIMINARY INFORMATION
MODEL NO. _____________________________________________
JOB NAME ______________________________________________
SERIAL NO. _____________________________________________
ADDRESS _______________________________________________
START-UP DATE ________________________________________
TECHNICIAN NAME _____________________________________
ADDITIONAL ACCESSORIES
_____________________________________________________________________________________________________
II. PRE-START-UP
Verify that all packaging materials have been removed from unit. (Y/N) _____
Verify installation of outdoor air hood. (Y/N) _____
Verify installation of flue exhaust and inlet hood. (Y/N) _____
Verify that condensate connection is installed per instructions. (Y/N) _____
Verify that all electrical connections and terminals are tight. (Y/N) _____
Verify ground integrity with a continuity test. (Y/N) _____
Verify gas pressure to unit gas valve is within specified range. (Y/N) _____
Check gas piping for leaks. (Y/N) _____
Check that indoor-air filters are clean and in place. (Y/N) _____
Check that outdoor air inlet screens are in place.(Y/N) _____
Verify that unit is level. (Y/N) _____
Verify that fan assembly is free of obstructions and rotor spins freely. (Y/N) _____
Verify that scroll compressors are rotating in the correct direction. (Y/N) _____
Verify installation of thermostat.(Y/N) _____
Verify that crankcase heaters have been energized for at least 24 hours. (Y/N) _____
Outdoor-Air Temperature _____________ °F DB (Dry Bulb)
Return-Air Temperature _____________ °F DB _____________ °F WB (Wet Bulb)
Cooling Supply Air Temperature_____________ °F
Gas Heat Supply Air _____________ °F
Form No. RGV-036-072-02SI Rev. BPg CL-1 3-24Replaces: RGV-036-072-01SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 60
PRESSURES
Gas Inlet Pressure in. wg _____________ in. wg
Gas Manifold PressureSTAGE 1 _____________ in. wg
STAGE 2 _____________ in. wg
Refrigerant Suction_____________ PSIG
Refrigerant Discharge _____________ PSIG
Verify Refrigerant Charge using Charging Charts. (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped). (Y/N) _____
Verify smoke detector unit shutdown by utilizing magnet test. (Y/N) _____
Verify outdoor fan operation. On units with head pressure controls, verify outdoor fan ramps up.(Y/N) _____
IV. HOT GAS RE-HEAT SYSTEM START-UP
STEPS
1.Check UCB (Unit Control Board) for jumper 1, 2, 3 (Jumper 1, 2, 3 must be cut and open). (Y/N) _____
2.Open humidistat contacts. (Y/N) _____
3.Start unit In cooling (Close Y1). (Y/N) _____
OBSERVE AND RECORD
a. Suction pressure ______________ PSIG
b. Discharge pressure ______________ PSIG
c. Entering air temperature ______________ °F
d. Liquid line temperature at outlet or reheat coil ______________ °F
e. Confirm correct rotation for compressor. (Y/N) _____
f. Check for correct ramp-up of outdoor fan motor as condenser coil warms. (Y/N) _____
4.Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed. (Y/N) _____
5.Check unit charge per charging chart. (Y/N) _____
OBSERVE
a. Reduction in suction pressure (5 to 7 psi expected). (Y/N) _____
b. Discharge pressure unchanged. (Y/N) _____
c. Liquid temperature drops to 50 to 55°F range. (Y/N) _____
d. LSV solenoid energized (valve closes). (Y/N) _____
6.Switch unit to dehumid (reheat) by opening Y1. (Y/N) _____
OBSERVE
a. Suction pressure increases to normal cooling level.(Y/N) _____
b. Discharge pressure decreases (35 to 50 psi). (Limited by head pressure control.)(Y/N) _____
c. Liquid temperature returns to normal cooling level.(Y/N) _____
d. LSV solenoid energized (valve closes).(Y/N) _____
e. DSV solenoid energized, valve opens.(Y/N) _____
7.With unit in dehumid mode, close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized. (Y/N) _____
8.Open W1 restore unit to dehumid mode. (Y/N) _____
9.Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized. (Y/N) _____
10. Restore set points for thermostat and humidistat. (Y/N) _____