ICP RGV-036-072-02SI User Manual

Page 1
RGV036-072
Single Package Rooftop
Gas Heating/Electric Cooling Unit
with R-410A Refrigerant
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE AND
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Rated Indoor Airflow . . . . . . . . . . . . . . . . . . . . . 3
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 1 — Plan for Unit Location . . . . . . . . . . . . 8
• ROOF MOUNT
Step 2 — Plan for Sequence of Unit
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• CURB-MOUNTED INSTALLATION
• PAD-MOUNTED INSTALLATION
• FRAME-MOUNTED INSTALLATION
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . 8
Step 4 — Provide Unit Support . . . . . . . . . . . . . 8
• ROOF CURB MOUNT
• SLAB MOUNT (HORIZONTAL UNITS ONLY)
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
SLAB MOUNT)
Step 5 — Field Fabricate Ductwork . . . . . . . . . 10
Step 6 — Rig and Place Unit . . . . . . . . . . . . . . 10
• POSITIONING ON CURB
Step 7 — Convert to Horizontal and Connect
Ductwork (When Required) . . . . . . . . . . . . . 11
Step 8 — Install Outside Air Hood . . . . . . . . . 12
• ECONOMIZER AND TWO-POSITION DAMPER
HOOD PACKAGE REMOVAL AND SETUP
(FACTORY OPTION)
• ECONOMIZER AND 2-POSITION HOOD
Step 9 — Units with Hinged Panels Only . . . . 13
Step 10 — Install Flue Hood . . . . . . . . . . . . . . 13
Step 11 — Install Gas Piping . . . . . . . . . . . . . . 13
• FACTORY OPTION THRU-BASE CONNECTIONS
(GAS CONNECTIONS)
Step 12 — Install External Condensate Trap and
Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Step 13 — Make Electrical Connections . . . . . 17
• FIELD POWER SUPPLY
• UNITS WITH FACTORY-INSTALLED NON-FUSED
DISCONNECT
• UNITS WITHOUT FACTORY-INSTALLED
NON-FUSED DISCONNECT
• ALL UNITS
• CONVENIENCE OUTLETS
• FACTORY-OPTION THRU-BASE CONNECTIONS
(ELECTRICAL CONNECTIONS)
• UNITS WITHOUT THRU-BASE CONNECTIONS
(ELECTRICAL CONNECTIONS)
• FIELD CONTROL WIRING
• THERMOSTAT
• HEAT ANTICIPATOR SETTINGS
• HOT GAS RE-HEAT CONTROL CONNECTIONS
• TYPICAL UNIT WIRING DIAGRAMS
Integrated Gas Controller . . . . . . . . . . . . . . . . 27
Hot Gas Re-Heat Dehumidification System
(Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
• NORMAL COOLING
• DEHUM/MECH COOLING (SUBCOOLING) MODE
• DEHUMIDIFICATION (HOT GAS REHEAT) MODE
• REHEAT CONTROL
EconomizerONE (Factory Option) . . . . . . . . . 32
• ECONOMIZER SETTINGS
•WIRING
• SETUP AND CONFIGURATION
• INSTALLING OPTIONAL 1196582 SINGLE OUTSIDE AIR ENTHALPY SENSOR
•CHECKOUT
• TROUBLESHOOTING
Controller Options . . . . . . . . . . . . . . . . . . . . . . 53
• LOW AMBIENT
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . 53
Step 14 — Adjust Factory-Installed Options . 54
•SMOKE DETECTORS
• ECONOMIZERONE OCCUPANCY SWITCH
Step 15 — Install Accessories . . . . . . . . . . . . 54
Step 16 — Fan Speed Set Up . . . . . . . . . . . . . 55
• UNITS WITH ELECTROMECHANICAL CONTROLS
START-UP CHECKLIST. . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe
Form No. RGV-036-072-02SI Rev. B Pg 1 3-24 Replaces: RGV-036-072-01SI
Page 2
practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
DANGER
ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury
or death. Before performing service or maintenance operations
on unit, turn off main power switch to unit and install lock(s) and lockout tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
WARNING
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death,
serious personal injury and/or property damage. Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field­supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
WARNING
CARBON-MONOXIDE POISONING HAZARD Failure to follow instructions could result in severe
personal injury or death due to carbon-monoxide poisoning, if combustion products infiltrate into the building.
Check that all openings in the outside wall around the vent (and air intake) pipe(s) are sealed to prevent infiltration of combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not obstructed in any way during all seasons.
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE
Si ces directives ne sont pas suivies, cela peut entraîner des blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort, si des produits de combustion s’infiltrent dans le bâtiment.
Vérifier que toutes les ouvertures pratiquées dans le mur extérieur autour du ou des tuyaux d’évent (et de la prise d’air) sont scellées de manière à empêcher l’infiltration de produits de combustion dans le bâtiment.
Veiller à ce que la ou les sorties de l’évent de l’appareil de chauffage (et la prise d’air) ne soient, en aucune façon, obstruées, quelle que soit la saison.
WARNING
WARNING
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal
injury, death and/or equipment damage. R-410A refrigerant systems operate at higher pressures
than standard R-22 systems. Do not use R-22 service equipment or components on R-410A refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
CAUTION
PERSONAL INJURY HAZARD Failure to follow this caution may result in
personal injury. Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
FIRE HAZARD Failure to follow this warning could result in severe
personal injury and/or property damage. Inlet pressure tap set screw must be tightened and
1/8 in. NPT pipe plug must be installed to prevent gas leaks.
Gas Valve
Inlet Pressure
Tap Set Screw
2
Page 3
WARNING
FIRE HAZARD Failure to follow this warning could result in severe
personal injury and/or property damage. Manifold pressure tap set screw must be tightened and
1/8 in. NPT pipe plug must be installed to prevent gas leaks.
Manifold Pressure
Tap Set Screw
Manifold
Gas Valve
MODEL NUMBER NOMENCLATURE AND
DIMENSIONS
See Fig. 1 for RGV model number nomenclature. See Fig. 2 for unit dimensional drawings. Figure 2 also shows service clearance dimensions.

Rated Indoor Airflow

Table 1 lists the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
Table 1 — Rated Indoor Airflow
MODEL NUMBER RATED INDOOR AIRFLOW (cfm)
RGV036/037 1050 RGV048/049 1500
RGV060 2000 RGV061 1875 RGV072 2400
3
Page 4
MODEL SERIES
RGV0 6 0 LDDA0AAA
Position Number
12345678910111213
14
Type
Voltage
Heating Capacity
Outdoor Air Options / Control
0A = No Options 4B = Non-Fused Disconnect Switch AA = Hinged Access Panels AT = Un-Powered Convenience Outlet BB = Powered Convenience Outlet BP = Return Air Smoke Detector BR = Supply Air Smoke Detector CJ = Condensate Overflow Switch Factory-Installed Options⁵
A = Aluminum / Copper Cond & Evap Coil B = Precoat Alum/Copper Cond with Alum / Copper Evap (3 phase only) C = E-Coated Alum/Copper Cond with Alum / Copper Evap (3 phase only) D = E-Coated Alum / Copper Cond & Evap (3 phase only) E = Copper/Copper Cond & Alum/Copper Evap (3 phase only) F = Copper/Copper Cond & Evap (3 phase only)
Condenser / Evaporator Coil Configuration
A = Standard Controls for Factory-Installed W7212 (036-061 sizes) and All Field-Installed Economizers B = Factory-Installed EconoMi$er
®
X with W7220 Economizer Controller
C = Factory-Installed EconomizerONE with POL224 Economizer Controller
Economizer Control
1
Units meet Department of Energy 2023 SEER2 requirements.
2
For units meeting SEER2 requirements, choose 037/049/061. For units meeting SEER requirements, choose 036/048/060.
3
The following are not available as factory-installed options for models with this voltage code: coated or copper fin coils, economizers and
two-position damper, powered convenience outlet, and Hot Gas Re-Heat.
4
Hot Gas Re-Heat system includes Low Ambient controller.
5
FIOPs installed in combination use different codes. Contact your sales representative for details.
Unit Efficiency
Motor Option (Indoor Fan)
036 = 36,000 BTUH = 3 Tons SEER 048 = 48,000 BTUH = 4 Tons SEER 060 = 60,000 BTUH = 5 Tons SEER 072 = 72,000 BTUH = 6 Tons
H = 208/230-3-60 K = 208/230-1-60
3
L = 460-3-60 S = 575-3-60
D = Low Heat E = Medium Heat F = High Heat L = Low NOx, Low Heat (sizes 036-061 only), includes Stainless Steel HX S = Low Heat, Stainless Steel Heat Exchanger R = Medium Heat, Stainless Steel Heat Exchanger T = High Heat, Stainless Steel Heat Exchanger
D = Direct Drive X-Vane™ Fan – Standard Static E = Direct Drive X-Vane Fan – High Static F = Direct Drive X-Vane Fan – Medium Static G = Direct Drive X-Vane Fan – High Static with Hot Gas Re-Heat
4
A = None B = Economizer with Barometric relief, OA Temp sensor E = Economizer with Barometric relief + CO sensor, OA Temp sensor H = Economizer with Barometric relief, enthalpy sensor L = Economizer with Barometric relief + CO sensor, enthalpy sensor P = Two-Position Damper (036-061 models only) U = Temp Ultra Low Leak Economizer with Barometric relief W = Enthalpy Ultra Low Leak Economizer with Barometric relief
R = Rooftop
G = Gas Heat / Electric Cooling
V = Standard Efficiency 1
4 SEER and 13.4 SEER2
Nominal
Cooling
Capacity²
037 = 36,000 BTUH = 3 Tons SEER2
1
049 = 48,000 BTUH = 4 Tons SEER2
1
061 = 60,000 BTUH = 5 Tons SEER2
1
Fig. 1 — RGV036-072 Model Number Nomenclature
4
Page 5
5
Fig. 2 — Unit Dimensional Drawing
Page 6
6
Fig. 2 — Unit Dimensional Drawing (cont)
Page 7
7
Fig. 2 — Unit Dimensional Drawing (cont)
Page 8

INSTALLATION

Jobsite Survey

Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (curb or other) that provides for the minimum clearances re­quired for safety. This includes the clearance to combus­tible surfaces, unit performance and service access be­low, around and above unit as specified in unit drawings. See Fig. 2 on page 6.
NOTE: Consider also the effect of adjacent units. Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet. Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminat­ed air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American Nation­al Standards Institute) and NFPA (National Fire Protec­tion Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adja­cent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per require­ments. Refer to Install External Condensate Trap and Line on page 17 for required trap dimensions.
ROOF MOUNT Check building codes for weight distribution requirements.
Unit operating weights are shown in Table 2.
Table 2 — Operating Weights
RGV
Base Unit 482 (219) 543 (246) 556 (252) 607 (275) Economizer
Vertical 50 (23) 50 (23) 50 (23) 50 (23) Horizontal 80 (36) 80 (36) 80 (36) 80 (36)
Hot Gas Re-Heat Cu Fins 25 (11) 43 (20) 56 (25) 56 (25) Powered Outlet 35 (16) 35 (16) 35 (16) 35 (16) Curb
14 in. (356 mm) 115 (52) 115 (52) 115 (52) 115 (52) 24 in. (610 mm) 197 (89) 197 (89) 197 (89) 197 (89)
System 50 (23) 50 (23) 80 (36 80 (36)
036/037 048/049 060/061 072
UNIT lb (kg)

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.

CURB-MOUNTED INSTALLATION

1. Install curb.
2. Install field-fabricated ductwork inside curb.
3. Install accessory thru-base service connection pack­age (affects curb and unit) (refer to accessory instal­lation instructions for details).
4. Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Install External Condensate Trap and Line on page 17 for details).
5. Rig and place unit.
6. Install outdoor air hood.
7. Install flue hood.
8. Install gas piping.
9. Install condensate line trap and piping.
10. Make electrical connections.
11. Install other accessories.

PAD-MOUNTED INSTALLATION

1. Prepare pad and unit supports.
2. Check and tighten the bottom condensate drain connection plug.
3. Rig and place unit.
4. Convert unit to side duct connection arrangement.
5. Install field-fabricated ductwork at unit duct openings.
6. Install outdoor air hood.
7. Install flue hood.
8. Install gas piping.
9. Install condensate line trap and piping.
10. Make electrical connections.
11. Install other accessories.
FRAME-MOUNTED INSTALLATION Frame-mounted applications generally follow the sequence
for a curb installation. Adapt the sequence as required to suit specific installation plan.

Step 3 — Inspect Unit

Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latch­es are snug and in closed position.
Locate the carton containing the outside air hood parts. Do not remove carton until unit has been rigged and located in final position.

Step 4 — Provide Unit Support

ROOF CURB MOUNT Accessory roof curb details and dimensions are shown in
Fig. 3 (on page 9). Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
8
Page 9
E
E
7/16" [11]
4 9/16" [115.5]
1/4"
[7.0]
5' 7-3/8"
[1711.3]
1' 4-13/16" [427] INSIDE
1-3/4" [44.4]
2-3/8" [61]
1-3/4" [44.5]
1.00" [25.4]
"A"
1-3/4" [44.4]
21.74"
[552.2]
5.42"
[137.7]
11.96"
[303.8]
4.96"
[126.0]
70.87"
[1800.2]
40.69"
[1033.5]
21.84"
[554.7]
16.03"
[407.2]
1.75"
[44.5]
20.41"
[518.3]
3.00" [76.2]
13.78"
[350.0]
14.00"
[355.6]
3.00" [76.2]
15.19"
[385.8]
32.19"
[817.6]
3'-1 3/16"
[944.6]
"A"
1-3/4" [44.5]
CRBTMPWR001A01 3/4" [19] NPT
3/4" [19] NPT
1/2" [12.7] NPT
CRRFCURB002A01
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
POWER WIRING
FITTING
CONTROL WIRING
FITTING
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
THRU THE CURB
1/2" [12.7] NPT 1/2" [12.7] NPT
CRBTMPWR003A01 THRU THE BOTTOM
ROOF CURB
ACCESSORY #
A
CRRFCURB001A01
14"
[356]
24"
[610]
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAUGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
TYPICAL (4) SIDES
SUPPLY AIR RETURN AIR
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
UNIT
GASKET
(SUPPLIED WITH CURB)
RIGID INSULATION
(FIELD SUPPLIED)
DUCT
(FIELD SUPPLIED)
NAIL (FIELD SUPPLIED)
VIEW "B"
CORNER DETAIL
SEE VIEW "B"
RETURN AIR
SUPPLY AIR
SUPPLY AIR OPENING
RETURN AIR OPENING
GAS SERVICE PLATE THRU THE CURB DRILL HOLE 2" [50.8] @ ASSEMBLY (IF REQUIRED) (SEE NOTE #8)
SEE NOTE #2
11 3/4"[298.5] WIDE INSULATED DECK PANELS
8 9/16"[217.5] WIDE INSULATED DECK PANEL
1/3/4"[44.5]
SCALE 0.250
E-ESECTION
48TC400427
9
Fig. 3 — Roof Curb Details
Page 10
NOTE: The gasketing of the unit to the roof curb is critical
A
Maximum Allowable Difference, in. (mm)
A-B B-C A-C
0.5 (13) 1.0 (25) 1.0 (25)
for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig. 4. Refer to Accessory Roof Curb Installation Instruc­tions for additional information as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. The accessory thru-the-base power and gas connection package must be installed before the unit is set on the roof curb. If field-installed thru-the-roof curb gas connections are desired, use factory-supplied
duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be in­sulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.

Step 6 — Rig and Place Unit

1/2 in. pipe coupling and gas plate assembly to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field-installed after the unit is installed on the roof curb.
NOTE: If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the basepan in accordance with the accessory installation instructions.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to
roofing materials. Membrane roofs can be cut by sharp sheet metal edges.
Be careful when placing any sheet metal parts on such
CAUTION
roof.
Keep unit upright and do not drop. Spreader bars are re­quired. Rollers may be used to move unit across a roof. Rigging materials under unit (cardboard or wood) must be removed PRIOR to placing the unit on the roof curb. Level by using unit frame as a reference. See Table 2
C
and Fig. 5 for additional information. Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit. Rigging materials under unit (cardboard or wood to pre-
vent basepan damage) must be removed PRIOR to plac­ing the unit on the roof curb.
When using the standard side drain connection, ensure
B
the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain plug can be tightened with a 1/2 in. square socket drive exten­sion. For further details, see “Install External Condensate
Fig. 4 — Unit Leveling Tolerances
SLAB MOUNT (HORIZONTAL UNITS ONLY) Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
Trap and Line” on page 17. Before setting the unit onto the curb, recheck gasketing
on curb.

POSITIONING ON CURB

in front of condenser coil air inlet to prevent grass and fo­liage from obstructing airflow.
CAUTION
NOTE: Horizontal units may be installed on a roof curb if required.

ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)

A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4 in. x 4 in. (102 mm x 102 mm) pads on each side.

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer. For vertical ducted applications, secure all ducts to roof
curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional di­mensions are equal to or greater than the unit supply
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage. All panels must be in place when rigging. Unit is not
designed for handling by fork truck when packaging is removed.
If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
Position unit on roof curb so that the following clearances are maintained: 1/4 in. (6.4 mm) clearance between the roof curb and the base rail inside the front and rear,
0.0 in. clearance between the roof curb and the base rail
inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately 1/4 in. (6.4 mm).
10
Page 11
Fig. 5 — Rigging Details
Required Spreader
Bars
"B"
36-54 in.
(914-1371 mm)
"C"
"A"
See Detail "A"
Place all seal strips
in place before
placing unit on roof curb
Duct End
Detail "A"
Fan
Side
NOTE(S):
1. SPREADER BARS ARE REQUIRED. Top damage will occur if spreader bars are not used.
2. Hook rigging shackles through holes in base rail, as shown in Detail A. Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
UNIT
MAXIMUM WEIGHT
DIMENSIONS
ABC
lb kg in. mm in. mm in. mm
RGV036/037 784 356 74.5 1890 37.6 955 33.5 850 RGV048/049 890 404 74.5 1890 36.5 925 33.5 850 RGV060/061 903 410 74.5 1890 36.5 925 33.5 850
RGV072 1020 463 74.5 1890 36.0 915 41.5 1055
Removable Horizontal Supply Duct Opening Cover
Removable Horizontal Return Duct Opening Cover
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 4 ft (1220 mm) from electric and gas meters, gas regulators, and gas relief equipment. Minimum distance between unit and other electrically live parts is 48 in. (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate me­chanical draft system flue assembly at least 48 in. (1220 mm) from an adjacent building or combustible material.
NOTE: Installation of accessory flue discharge deflector kit will reduce the minimum clearance to combustible material to 18 in. (460 mm).
After unit is in position, remove rigging skids and shipping materials.

Step 7 — Convert to Horizontal and Connect Ductwork (When Required)

Unit is shipped in the vertical duct configuration. Unit without
Fig. 6 — Horizontal Conversion Panels
Notches
factory-installed economizer or return-air smoke detector option may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers (see Fig. 6) and remove covers. Use the screws to install the covers on vertical duct openings with the insulation-side down. The panels must be inserted into the notches on the basepan to properly seal. The notches are covered by the tape used to secure the insulation to the basepan and are not easily seen. See Fig. 7 for position of the notches in the basepan. Seals around duct openings must be tight. Secure with
Basepan
screws as shown in Fig. 8. Cover seams with foil duct tape. Field-supplied flanges should be attached to horizontal duct
openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
Fig. 7 — Location of Notches
11
Notches
Page 12

Step 8 — Install Outside Air Hood

Screws
Duct Covers Sheet Metal Face Up
Basepan
Filter Access Panel
Outdoor-Air Opening and Indoor Coil Access Panel
Compressor Access Panel
Hood Parts
Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)

ECONOMIZER AND TWO-POSITION DAMPER HOOD PACKAGE REMOVAL AND SETUP (FACTORY OPTION)

NOTE: Economizer and two-position damper are not avail­able as factory installed options for single phase (-K voltage code) models. Two-position damper is not available for 072 models.
The hood is shipped in knock-down form and must be field assembled. The indoor coil access panel is used as the hood top while the hood sides, divider and filter are pack­aged together, attached to a metal support tray using plastic stretch wrap, and shipped in the return air compartment be­hind the indoor coil access panel. The hood assembly’s metal tray is attached to the basepan and also attached to the damper using 2 plastic tie-wraps.
1. To gain access to the hood, remove the filter access panel. See Fig. 9.
2. Locate the (2) screws holding the metal tray to the basepan and remove. Locate and cut the (2) plastic tie-wraps securing the assembly to the damper. See Fig. 10. Be careful to not damage any wiring or cut tie-wraps securing any wiring.
3. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps outlined in the Economizer Hood and 2­Position Hood section.
Fig. 8 — Horizontal Duct Panels In Place
Fig. 9 — Typical Access Panel Locations
Fig. 10 — Economizer and Two-Position Damper
Hood Parts Location
ECONOMIZER AND 2-POSITION HOOD NOTE: If the power exhaust accessory is to be installed on
the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 11.
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 12.
3. Remove the shipping tape holding the economizer barometric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See Fig. 12 and 13. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom fil­ter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 13.
6. Caulk the ends of the joint between the unit top panel and the hood top.
7. Replace the filter access panel.
12
Page 13
Fig. 11 — Indoor Coil Access Panel Relocation
Top Panel
Indoor Coil Access Panel
Indoor
Coil
Access
Panel
Caulk Here
Top Panel
To p Panel
Indoor Coil Access Panel
Screw
Left Hood Side
Hood Divider
33-3/8 in. (848mm)
33-3/8 in. (848mm)
19-1/16 in.
(483mm)
19-1/16 in.
(483mm)
Blower Access Panel
Flue Opening
Compressor Door
Outdoor Coil
Latch
Fig. 14 — Compressor Door Latch Location

Step 10 — Install Flue Hood

Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 15.
Fig. 12 — Economizer Hood Construction
Divider
Outside Air
Hood
Cleanable Aluminum Filter
Barometric Relief
Fig. 13 — Economizer Filter Installation

Step 9 — Units with Hinged Panels Only

If the unit does not have hinged panels, skip this step and
Filter
Filter Clip
continue at Step 10 below. Relocate latch shipped inside the compressor compartment
behind the hinged compressor door to location shown in Fig. 14 after unit installation.
Fig. 15 — Flue Hood Details

Step 11 — Install Gas Piping

Installation of the gas piping must be accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installa­tion codes for gas burning appliances.
This unit is factory equipped for use with Natural Gas (NG) fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.
Furnace gas input rate on rating plate is for installation up to 2000 ft (610 m) above sea level. The input rating for alti­tudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level.
For natural gas applications, gas pressure at unit gas con­nection must not be less than 4 in. wg (996 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. On RGV size 048-072 high-heat units, the gas pressure at unit gas connection must not be less than 5 in. wg (1245 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating, see Table 3. For liquefied petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or great­er than 13 in. wg (3240 Pa) at the unit connection, see Table 4.
13
Page 14
Table 3 — Natural Gas Supply Line Pressure Ranges
NOTE(S):
NOTE(S):
STEEL PIPE
NOMINAL DIAMETERS (in.)
SPACING OF SUPPORTS
X DIMENSION (ft)
1/2 6
3/4 or 1 8
1-1/4 or larger 10
UNIT MODEL UNIT SIZE MINIMUM MAXIMUM
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
036/037, 048/049,
060/061, 072
048/049,
060/061, 072
4.0 in. wg (996 Pa)
5.0 in. wg
(1245 Pa)
13.0 in. wg (3240 Pa)
13.0 in. wg (3240 Pa)
Table 4 — Liquid Propane Supply Line Pressure
Ranges
UNIT MODEL UNIT SIZE MINIMUM MAXIMUM
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
036/037, 048/049,
060/061, 072
048/049,
060/061, 072
11.0 in. wg (2740 Pa)
11.0 in. wg (2740 Pa)
13.0 in. wg (3240 Pa)
13.0 in. wg (3240 Pa)
The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at the bottom of the access panel. The gas connection to the unit is made to the 1/2 in. FPT gas inlet port on the unit gas valve.
Manifold pressure is factory-adjusted for natural gas fuel use. Adjust as required to obtain best flame characteristics. See Table 5.
Manifold pressure for LP fuel use must be adjusted to spec­ified range. Follow instructions in the accessory kit to make initial readjustment. See Table 6.
Table 5 — Natural Gas Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
036/037, 048/049,
060/061, 072
048/049,
060/061, 072
3.5 in. wg (872 Pa)
3.5 in. wg (872 Pa)
See Table
Footnote
See Table
Footnote
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe size smaller than 1/2 in. Size the gas supply line to allow for a maximum pressure drop of
0.5 in. wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high-fire flow rate.
The gas supply line can approach the unit in 3 ways: hori­zontally from outside the unit (across the roof), thru­curb/under unit basepan (accessory kit required), or through unit basepan (factory option or accessory kit required). Con­sult accessory kit installation instructions for details on these installation methods. Observe clearance to gas line compo­nents per Fig. 16.
X
9 in. Minimum Clearance
For Panel Removal
Manual Gas
Base Unit
Base Rail
From Gas Meter
a
LEGEND NFGC — National Fuel Gas Code
NOTE: Follow all local codes. *Field-installed.
Roof Curb
Shutoff Valve
48 in. Minimum
Drip Leg Per NFGC
Gas
Regulator
*
*
Field-Fabricated
Support
*
*
a Low Fire, 1.7 in. wg (423 Pa), applies to the following 3-phase voltage units
only: RGV036*E and RGV048/060/072*F.
Table 6 — Liquid Propane Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
RGV****D/E/S/R
(Low or Medium Heat)
RGV****F/T
(High Heat Units Only)
a Low Fire, 5.0 in. wg (1245 Pa), applies to the following 3-phase voltage units
only: RGV036*E and RGV048/060/072*F.
036/037, 048/049,
060/061, 072
048/049,
060/061, 072
10 in. wg
(2490 Pa)
10 in. wg
(2490 Pa)
See Table
Footnote
See Table
Footnote
CAUTION
EQUIPMENT DAMAGE Failure to follow this caution may result in equipment
damage. When connecting the gas line to the unit gas valve, the
installer MUST use a backup wrench to prevent damage to the valve.
a
(with Accessory Thru-the-Curb Service Connections)
Fig. 16 — Gas Piping Guide

FACTORY OPTION THRU-BASE CONNECTIONS (GAS CONNECTIONS)

This service connection kit consists of a 1/2 in. electrical bulkhead connector and a 3/4 in. electrical bulkhead connector, connected to an “L” bracket covering the embossed (raised) section of the unit basepan in the condenser section (see Fig. 17 for shipping position).
The 3/4 in. bulkhead connector enables the low-voltage control wires to pass through the basepan. The 1/2 in. bulkhead connector allows the high-voltage power wires to pass through the basepan. See Fig. 18.
14
Page 15
between the “L” bracket and the connector plate
Brass Fitting
For Gas Piping
Support Bracket
Embossment
assembly).
NOTE: Take care not to damage the gasket, as it is reused in the following step.
3. Place the gasket over the embossed area in the basepan, aligning the holes in the gasket to the holes in the basepan. See Fig. 18.
4. Install the connector plate assembly to the basepan using 8 of the washer head screws.
The thru-base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas piping.
Install a 1/2 in. NPT street elbow on the thru-base gas fitting. Attach a 1/2 in. pipe nipple with minimum length of 16 in. (406 mm) (field-supplied) to the street elbow and extend it through the access panel at the gas support bracket. See Fig. 19.
Fig. 17 — Thru-the-Base Fitting Assembly (Shown in
Shipping Position)
High Voltage Conduit Connector
Auxiliary Power Supply (Optional)
Brass Fitting for 3 to 6 Ton Units
Low Voltage Conduit Connector
Fig. 18 — Thru-Base Connection Fittings
To prepare the unit for thru-base connections:
1. Remove the “L” bracket assembly from the unit.
2. Remove connector plate assembly from the “L” bracket and discard the “L” bracket, but retain the washer head screws and the gasket (located
Fig. 19 — Gas Line Piping for 3 to 6 Ton Units
Other hardware required to complete the installation of the gas supply line includes a manual shutoff valve, a sediment trap (drip leg) and a ground-joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6 ft (1.83 m) of the unit. The union, located in the final leg entering the unit, must be located at least 9 in. (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4 ft (1220 mm) away from the unit’s flue outlet. Some municipal codes re­quire that the manual shutoff valve be located upstream of the sediment trap. See Fig. 20 and 21 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 22 for typical piping arrangement when thru-base is used. Ensure that all piping does not block access to the unit’s main control box or limit the required working space in front of the control box.
15
Page 16
9 in. (229 mm) Minimum
Shut Off
Valve
Union
9 in. (229 mm) Minimum
Unit
Base
Rail
Burner Access Panel
Thru-Curb Adapter
Drip Leg
Thru-Curb Adapter
Shut Off
Valve
Drip Leg
Union
Unit
Base
Rail
Fig. 20 — Gas Piping, Typical Curb Sidewall Piping
(Example 1)
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. per every 15 ft (7 mm per every 5 m) to pre­vent traps. Grade all horizontal runs downward to ris­ers. Use risers to connect to heating section and to meter.
Protect all segments of piping system against physi­cal and thermal damage. Support all piping with ap­propriate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than 1/2 in., follow recommendations of national codes.
Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connec­tions. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If using PTFE (Teflon
®1
) tape, ensure the material is Double Density type and is la­beled for use on gas lines. Apply tape per manufac­turer’s instructions.
Pressure-test all gas piping in accordance with local and national plumbing and gas codes before con­necting piping to unit.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply pip­ing must be disconnected from the gas valve during the testing of the piping systems when test pressure is in ex­cess of 0.5 psig (3450 Pa). Pressure test the gas supply pip­ing system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union.
Check for gas leaks at the field-installed and factory­installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method speci­fied by local codes and/or regulations).
Fig. 21 — Gas Piping, Typical Curb Sidewall Piping
(Example 2)
Fig. 22 — Gas Piping, Typical Thru-Base
Connections
WARNING
Failure to follow this warning could result in personal injury, death and/or property damage.
Connect gas pipe to unit using a backup wrench to avoid damaging gas controls.
Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
Use proper length of pipe to avoid stress on gas control manifold.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics. See Fig. 23.
1. Third-party trademarks and logos are the property of their respective owners.
16
Page 17
Step 12 — Install External Condensate Trap and
Burner
Orifice
Standard Side Drain
Condensate Pan (Side View)
Drain Plug (Factory-Installed)
Alternate Bottom Drain
Minimum Pitch 1 in. (25 mm) Per 10 ft (3 m) of Line
To Roof Drain
Base Rail
Open Vent
3 in. (76 mm)
See Note
Roof Curb
Drain Plug
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4 in. (102 mm) trap is recommended.
Min
Line
The unit has one 3/4 in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 24. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a 1/2 in. square socket drive extension.
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a 1/2 in. square socket drive extension) and install it in the side drain connection.
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 25.
All units must have an external trap for condensate drain­age. Install a trap at least 4 in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft (25 mm per 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4 in.).
Fig. 23 — Orifice Hole
Fig. 24 — Condensate Drain Pan (Side View)
Fig. 25 — Condensate Drain Pan Piping Details

Step 13 — Make Electrical Connections

WARNING
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
NOTE: Field-supplied wiring shall conform with the limita­tions of minimum 63°F (33°C) rise.
FIELD POWER SUPPLY If equipped with optional powered convenience outlet: the
power source leads to the convenience outlet’s transform­er primary are not factory connected. Installer must con­nect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C pressure lugs with unit field power leads. See Convenience Outlets on page 19 for power transformer connections.
The field power wires are connected to the unit at line-side pressure lugs on compressor contactor C (see wiring dia­gram label for control box component arrangement) or at factory-installed option non-fused disconnect switch. Maxi­mum wire size is No. 2ga AWG (copper only) per pole on contactors and No. 2ga AWG (copper only) per pole on op­tional disconnect. See Fig. 26 and unit label diagram for field power wiring connections.
17
Page 18
NOTE: Unit may be equipped with short test leads (pig-
Units Without Non-Fused Disconnect Option
TB TB
11 12 11 12 1 3
Disconnect
per
NEC
208/230-1-60
L1 L2 L3
208/230-3-60
460-3-60 575-3-60
Units With Non-Fused Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory Wiring
Disconnect
per
NEC
Copper
Wire Only
Electric
Disconnect
Switch
Aluminum
Wire
BLK
YEL
BLU
tails) on the field line connection points on contactor C or optional disconnect switch. These leads are for factory­run test purposes only; remove and discard before con­necting field power wires to unit connection points. Make field power connections directly to line connection pres­sure lugs only. See Fig. 27.
WARNING
FIRE HAZARD Failure to follow this warning could result in personal
injury, death, or property damage. Do not connect aluminum wire between disconnect
switch and unit. Use only copper wire.
Field-Install the NFD Shaft and Handle
1. Remove the Control Box access panel. The NFD
enclosure is located below the Control Box (see Fig. 28).
2. Remove 3 cap head screws that secure the NFD
enclosure front cover — 2 on the face of the cover and 1 on the left side cover. See Fig. 29.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at
OFF position (the arrow on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the
shaft in the horizontal position. See Fig. 29.
6. Measure from the tip of the shaft to the top surface of
the black pointer; the measurement should be 3.75 to
3.88 in. (95 to 99 mm).
7. Tighten the locking screw to secure the shaft to the
NFD.
8. Turn the handle to the OFF position with red arrow
pointing at OFF.
9. Install the handle on to the painted cover horizontally
with the red arrow pointing to the left.
10. Secure the handle to the painted cover with 2 screws
and lock washers supplied.
11. Engaging the shaft into the handle socket, re-install
3 hex screws on the NFD enclosure.
12. Re-install the unit front panel.
Fig. 26 — Power Wiring Connections
Fig. 27 — Disconnect Switch and Unit

UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT

The factory-installed option non-fused disconnect (NFD) switch is located in a weatherproof enclosure located under the main control box. The manual switch handle and shaft are shipped in the disconnect enclosure. Assemble the shaft and handle to the switch at this point. Discard the fac­tory test leads (see Fig. 26).
Connect field power supply conductors to LINE side termi­nals when the switch enclosure cover is removed to attach the handle.
Fig. 28 — NFD Enclosure Location
Fig. 29 — NFD Handle and Shaft Assembly
18
Page 19
UNITS WITHOUT FACTORY-INSTALLED NON-FUSED
A
B
C
MOTOR
DISCONNECT When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
ALL UNITS All field wiring must comply with NEC and all local codes.
Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 26 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is No. 2ga AWG (copper only) per pole on contactors. See Fig. 26 and unit label diagram for field power wiring connections.
Provide a ground fault and short circuit over-current protec­tion device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-Current Protection) device size.
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to
be connected to a 208-v power supply, the control trans­former must be rewired by moving the black wire with the 1/4 in. female spade connector from the 230-v connection and moving it to the 200-v 1/4 in. male terminal on the pri­mary side of the transformer. Refer to unit label diagram for additional information. Field power wires will be connected at line-side pressure lugs on the power terminal block or at factory-installed option non-fused disconnect.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the example below to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable unit warranty.

CONVENIENCE OUTLETS

WARNING
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal
injury or death. Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Lock-out and tag-out this switch, if necessary.
Two types of convenience outlets are offered on RGV mod­els: non-powered and unit-powered. Both types provide a 125-v GFCI (ground-fault circuit interrupter) duplex recepta­cle rated at 15A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 30.
Figure 31 shows the Convenience Outlet Utilization label, which is located below the convenience outlet.
Convenience Outlet GFCI
PWD-CO Transformer
Fig. 30 — Convenience Outlet Location
PWD-CO Fuse Switch
% Voltage Imbalance
Example: Supply voltage is 230-3-60
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227-224 = 3-v
(BC) 231-227 = 4-v
(AC) 227-226 = 1-v
Maximum deviation is 4-v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
= 100 x
AB = 224-v BC = 231-v AC = 226-v
max voltage deviation from average voltage
(224 + 231 + 226)
average voltage
681
33
4
227
=
= 1.76%
= 227
Fig. 31 — Convenience Outlet Utilization
Notice Label
NOTE: Unit powered convenience outlets are not available as factory-installed options for single phase (-K voltage code models).
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.
On units with electromechanical controls the weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate, and gasket.
19
Page 20
WARNING
Cover — While-In-Use
Weatherproof
Baseplate For
GFCI Receptacle
Gasket
GFCI Receptacle
Not Included
UNIT
VOLTAGE
CONNECT
AS
PRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208, 230 240
L1: RED + YEL L2: BLU + GRA
H1 + H3 H2 + H4
460 480
L1: RED Splice BLU + YEL L2: GRA
H1
H2 + H3
H4
575 600
L1: RED L2: GRA
H1 H2
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal
injury or death. Using unit-mounted convenience outlets: Units with unit-
mounted convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de­energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
1. Remove the blank cover plate at the convenience outlet; discard the blank cover.
2. Loosen the 2 screws at the GFCI duplex outlet, until approximately 1/2 in. (13 mm) under screw heads is exposed. Press the gasket over the screw heads.
3. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the 2 screws until snug (do not over-tighten).
4. Mount the weatherproof cover to the backing plate as shown in Fig. 32.
5. Remove 2 slot fillers in the bottom of the cover to permit service tool cords to exit the cover.
6. Check for full closing and latching.
the unit-mounted non-fused disconnect switch; this will provide service power to the unit when the unit disconnect switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect switch is open. See Fig. 33.
Fig. 32 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-purpose 125-v 15A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements, and disconnect switch size and location. Route 125-v power supply conduc­tors into the bottom of the utility box containing the duplex receptacle.
Unit-Powered Convenience Outlet
A unit-mounted transformer is factory-installed to step down the main power supply voltage to the unit to 115-v at the du­plex receptacle. This option also includes a manual switch with fuse, located inside the control box and mounted on the vertical bracket; access is through the unit’s control box ac­cess panel. (See Fig. 30.)
The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer option. If local codes permit, the transformer pri­mary leads can be connected at the line-side terminals on
Fig. 33 — Powered Convenience Outlet Wiring
Fuse On Power Type
The factory fuse is a Bussmann
™1
Fusetron™1 T-15,
non-renewable screw-in (Edison base) type plug fuse. Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
Using Unit-Mounted Convenience Outlets
Units with unit-mounted convenience outlet circuits will often require that 2 disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized un­til the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.

FACTORY-OPTION THRU-BASE CONNECTIONS (ELECTRICAL CONNECTIONS)

This service connection kit consists of a 1/2 in. NPT gas adapter fitting (brass), a 1/2 in. electrical bulkhead connec­tor, and a 3/4 in. electrical bulkhead connector, all factory­installed in the embossed (raised) section of the unit base­pan in the condenser section. The 3/4 in. bulkhead connec­tor enables the low-voltage control wires to pass through the basepan. The 1/2 in. electrical bulkhead connector allows the high-voltage power wires to pass through the basepan. See Fig. 18 on page 15.
1. Third-party trademarks and logos are the property of their respective owners.
20
Page 21
NOTE: If electrical connections are not going to occur at this
HUM
G
W2
W2
G
W1
O/B/Y2
Y2
R
W1
R
Y1
Y1

T H E R M O S T A T

(Note 1) (Note 2)
Note 1: Typical multi-function marking. Follow manufacturer’s configuration Instructions to select Y2.
Note 2: Y2 to Y2 connection required on single-stage cooling units when integrated economizer function is desired.
Field Wiring
Unit
Control
Board
Typical
Thermostat
Connections
C
C
time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
Check tightness of connector lock nuts before connecting electrical conduits.
Field-supplied and field-installed liquid tight conduit connec­tors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the ex­ternal disconnect (through unit side panel). A hole must be field cut in the main control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole.

UNITS WITHOUT THRU-BASE CONNECTIONS (ELECTRICAL CONNECTIONS)

1. Install power wiring conduit through side panel open-
2. Install power lines to terminal connections as shown
FIELD CONTROL WIRING The RGV unit requires an external temperature control de-
vice. This device can be a thermostat (field-supplied) or a thermostat emulation device provided as part of a third-party Building Management System.
All low-voltage wiring should be routed through the provided raceway built into the corner post of the unit or secured to the unit control box with the electrical conduit in order to pro­vide UL-required clearance between high and low-voltage wiring.
THERMOSTAT Install a field-installed accessory thermostat according to in-
stallation instructions included with the accessory. For com­plete economizer function, select a 2-stage cooling thermo­stat. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions. Typical low-voltage connections are shown in Fig. 34.
If the thermostat contains a logic circuit requiring 24-v pow­er, use a thermostat cable or equivalent single leads of different colors with minimum of 7 leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of 6 leads. Check the thermostat installation instructions for additional features which might require additional conduc­tors in the cable.
For wire runs up to 50 ft (15 m), use No. 18 AWG (American Wire Gauge) insulated wire [95°F (35°C) minimum]. For 50 to 75 ft (15 to 23 m), use No. 16 AWG insulated wire [95°F (35°C) minimum]. For over 75 ft (23 m), use No. 14 AWG in­sulated wire [95°F (35°C) minimum]. Wire sizes larger than No. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
ings. Install conduit between disconnect and control box.
in Fig. 26 on page 18.
Fig. 34 — Low-Voltage Thermostat Connections
Thermostat Wiring, Units Without Thru-Base Connection Kit
Pass the thermostat control wires through the hole provided in the corner post; then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Unit Control Board. See Fig. 35.
NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring.
Raceway
Hole In End Panel (Hidden)
Fig. 35 — Field Control Wiring Raceway
HEAT ANTICIPATOR SETTINGS Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second-stage heating, when available.
21
Page 22

HOT GAS RE-HEAT CONTROL CONNECTIONS

Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT RRS
S RTN
HUM
D1 D2
V+ Vg
C
HUM
G
W2
W1
Y2
Y1
R
Programmable
Thermostat
Unit Control Board
Thermostat Connections
Hot Gas Re-Heat Space RH Controller
NOTE: The Hot Gas Re-Heat system is a factory-installed option. The Hot Gas Re-Heat system is not available for sin­gle phase (-K voltage code) models.
The Hot Gas Re-Heat dehumidification system requires a field-supplied and field-installed space relative humidity con­trol device. This device may be a separate humidistat con­trol (contact closes on rise in space RH above control set point) or a combination thermostat-humidistat control device such as programmable thermostat device with isolated con­tact set for dehumidification control. The humidistat is nor­mally used in applications where a temperature control is al­ready provided (such as a third-party Building Management System).
Connecting a Field-Installed Humidistat
1. Route the humidistat 2-conductor cable (field-sup­plied) through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see Fig. 35) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring.
3. Connect one of the leads from the 2-conductor cable to the HUM terminal on the UCB (Unit Control Board). Connect the other lead to the R terminal on the UCB. See Fig. 36.
Unit Control
Board
C HUM G
Humidistat
Thermostat
W2
W1
Y2 Y1
R
Fig. 36 — Humidistat Connections to UCB
Connecting at Field-Installed Thermidistat Device
1. Route the thermidistat multi-conductor thermostat cable (field-supplied) through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see Fig. 35) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring.
3. The thermidistat has dry contacts at terminals D1 and D2 for dehumidification operation (see Fig. 37). Con­nect D1 to the R terminal on the UCB. Connect D2 to the HUM terminal on the UCB. Refer to the installation instructions included with the field-installed thermidi­stat device for more information.
TYPICAL UNIT WIRING DIAGRAMS See Fig. 38-41 for examples of typical unit control and pow-
er wiring diagrams. These wiring diagrams are mounted on the inside of the unit control box cover.
Fig. 37 — Typical Rooftop Unit with Hot Gas Re-Heat Dehumidification System
and Programmable Thermostat
22
Page 23
23
Fig. 38 — Typical RGV036-060 Control Wiring Diagram with Electromechanical and POL224,
208/230-3-60 Unit Shown
Page 24
24
Fig. 39 — Typical RGV072 Control Wiring Diagram with Electromechanical and POL224,
208/230-3-60 Unit Shown
Page 25
T
Fig. 40 — Typical RGV036-072 Power Wiring Diagram, 208/230-3-60 Unit Shown
25
Page 26
T
Fig. 41 — Typical RGV036-072 Power Wiring Diagram, 460-3-60 Unit Shown
26
Page 27

Integrated Gas Controller

Locking
Tab Connector
Overcurrent Fuse Protection
Redundant Gas Valve Relay
Locking
Tab Connector
Spade
Connect Ignitor
Status
LED
This unit contains an Integrated Gas Controller (IGC) board. The IGC control board uses a flue gas pressure switch that senses pressure drop in the heat exchanger due to the combustion inducer. See Fig. 42.
Flue Gas Pressure
Switch
Flue Gas Pressure
Sense Tube
Fig. 42 — Flue Gas Pressure Switch and Pressure
Sense Tube (Typical Location)
When the thermostat calls for heating, power is sent to W on the Integrated Gas Controller (IGC) board. An LED (light emitting diode) on the IGC board turns on and remains on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed, and that the pressure switch is open. If the check was successful, the in­duced draft motor is energized. When the pressure in the heat exchanger is low enough to close the pressure switch, the ignition activation period begins. Once ignition occurs, the IGC board will continue to monitor the condition of the rollout switch, the limit switches, the pressure switch, and the flame sensor. Assuming the unit is controlled through a room thermostat set for “fan auto,” 45 seconds after ignition occurs, the indoor fan motor will energize, and the outdoor air dampers will open to their minimum position. If the “over temperature limit” opens prior to the start of the indoor fan blower, the IGC will shut down the burners, and the control will shorten the 45 second delay to 5 seconds less than the time to trip the limit. For example, if the limit trips at 37 seconds, the control will change the “fan on delay” from 45 seconds to 32 seconds. Once the “fan on delay” has been modified, it will not change back to 45 seconds unless power is reset to the control. On units with 2 stages of heat, W2 closes and initiates power to the second stage of the main gas valve when additional heat is required.
When the thermostat is satisfied, W1 and W2 open and the gas valve closes, interrupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto, the indoor fan motor will con­tinue to operate for an additional 45 seconds and then stop. An LED indicator is provided on the IGC to monitor operation.
See Fig. 43 for IGC board component layout. Figure 44 is a typical IGC control wiring diagram and Table 7 for IGC Board LED Alarm Codes.
Fig. 43 — IGC Board Component Layout
27
Page 28
Fig. 44 — Typical IGC Control Wiring Diagram
UNIT CONTROL
BOARD
NOTE(S):
Table 7 — IGC Board LED Alarm Codes
a,b,c
LED FLASH
CODE
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET METHOD PROBABLE CAUSE
On Normal Operation
Off Hardware Failure No gas heating.
1 Flash Indoor Fan On/Off Delay
Modified
5 seconds subtracted from On delay. 5 seconds added to Off
Power reset. High temperature limit switch opens during heat
delay (3 minute maximum)
2 Flashes Limit Switch Fault Gas valve and igniter Off.
Indoor fan and inducer On.
Limit switch closed, or heat call (W) Off.
3 Flashes Flame Sense Fault Indoor fan and inducer On. Flame sense normal.
Power reset for LED reset.
4 Flashes 4 Consecutive Limit
Switch Fault
5 Flashes Ignition Fault No gas heating. Heat call (W) Off.
6 Flashes Induced Draft Motor
Fault
No gas heating. Heat call (W) Off.
Power reset for LED reset.
Power reset for LED reset.
If heat off: no gas heating. If heat on: gas valve Off and inducer On.
Inducer sense normal, or heat call (W) Off.
Loss of power to the IGC. Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, transformer, and wiring to the IGC.
exchanger warm-up period before fan-on delay expires. High temperature limit switch opens within 10 minutes of heat call (W) Off. See Limit Switch Fault.
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is within the range on the unit nameplate. Check wiring and limit switch operation.
The IGC sensed a flame when the gas valve should be closed. Check wiring, flame sensor, and gas valve operation.
4 consecutive limit switch faults within a single call for heat. See Limit Switch Fault.
Unit unsuccessfully attempted ignition for 15 minutes. Check igniter and flame sensor electrode spacing, gaps, etc. Check flame sense and igniter wiring. Check gas valve operation and gas supply.
Inducer sense On when heat call Off, or inducer sense Off when heat call On. Check wiring, voltage, and operation of IGC motor. Check speed sensor wiring to IGC.
7 Flashes Rollout Switch Lockout Gas valve and igniter Off.
Indoor fan and inducer On.
Power reset. Rollout switch has opened. Check gas valve
operation. Check induced-draft blower wheel is properly secured to motor shaft.
8 Flashes Internal Control Lockout No gas heating. Power reset. IGC has sensed internal hardware or software
error. If fault is not cleared by resetting 24-v power, replace the IGC.
9 Flashes Temporary Software
Lockout
No gas heating. 1 hour auto reset, or power
reset.
Electrical interference is disrupting the IGC software.
a There is a 3-second pause between alarm code displays. b If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence. c Alarm codes on the IGC will be lost if power to the unit is interrupted.
LEGEND
IGC — Integrated Gas Unit Control LED — Light-Emitting Diode
28
Page 29

Hot Gas Re-Heat Dehumidification System (Optional)

Units with the factory-installed Hot Gas Re-Heat system op­tion are capable of providing multiple modes of improved dehumidification as a variation of the normal cooling cycle. The Hot Gas Re-Heat system option includes additional valves in the liquid line and discharge line of the refrigerant circuit and a reheat coil downstream of the evaporator. Hot Gas Re-Heat system operation requires the installation and configuration of a relative humidity switch input or a space relative humidity sensor. These provide the dehumidification demand to the control.
With Hot Gas Re-Heat system units, there are two addition­al HVAC modes available for the user: Dehumidification and Dehum/Mech Cooling. Selection of the Dehum/Mech Cool­ing mode is determined by the dehumidification demand and the cooling demand. Table 8 shows the corresponding circuit mode and output status for the different demand combinations.
NORMAL COOLING This mode is the standard rated cooling system perfor-
mance, and occurs when there is cooling demand without dehumidification demand.
For RGV036-061 units, refrigerant flows through the out­door condenser and is diverted away from the reheat coil with the open Cooling Liquid Valve (CLV) into the expansion device. Figure 45 shows the complete refrigerant flow. The Reheat Discharge Valve (RDV) is closed.
For RGV072 units, refrigerant flows through the outdoor condenser and is diverted away from the reheat coil with the closed Reheat Liquid Valve (RLV) and open CLV into the expansion device. Figure 46 shows the complete refrigerant flow. The RDV is closed.
DEHUM/MECH COOLING (SUBCOOLING) MODE This mode increases the latent heat removal and decreases
sensible cooling compared to normal cooling. This occurs when there is a cooling and dehumidification demands.
For RGV036-061 units, refrigerant flows through the out­door condenser and is diverted through the reheat coil with the closed CLV into the expansion device. Figure 47 shows the complete refrigerant flow. The RDV is closed.
For RGV072 units, refrigerant flows through the outdoor condenser and is diverted through the reheat coil with the open RLV and closed CLV into the expansion device. Figure 48 shows the complete refrigerant flow. The RDV is closed.
DEHUMIDIFICATION (HOT GAS REHEAT) MODE This mode provides maximum latent cooling with little to no
sensible capacity. This occurs when there is a dehumidifica­tion demand and no cooling demand.
For RGV036-072 units, this is the same as the Subcooling mode but the RDV is open, which provides some compres­sor discharge gas to the reheat condenser to further in­crease the reheat of the evaporator air stream. (See Fig. 49 and 50.)
REHEAT CONTROL When there is only a cooling demand, the unit will operate
in normal cooling mode. When there is only dehumidifica­tion demand, the unit will operate in Dehumidification mode (Hot Gas Reheat). When there is both cooling de­mand and dehumidification demand, the unit will operate in Dehum/Mech Cooling mode (Subcooling). During Dehu­midification and Dehum/Mech cooling mode, the unit will run all cooling stages.
Table 8 — Hot Gas Re-Heat System Control Modes
DEMAND AND MODE OUTPUTS
Dehumidification
Demand
No Power No Power No power Off
No No Off Off
No Yes COOL On
Yes No
Yes Yes DEHUM On
Cooling Demand Mode Compressor RDV CLV
DEHUM/MECH
COOL
On
De-energized
(no flow)
De-energized
(no flow)
De-energized
(no flow)
De-energized
(no flow)
Energized
(flow)
De-energized
(flow)
De-energized
(flow)
De-energized
(flow)
Energized
(no flow)
Energized
(no flow)
RLV
(RGV072 only)
De-energized
(flow)
Energized
(no flow)
Energized
(no flow)
De-energized
(flow)
De-energized
(flow)
29
Page 30
Hot Gas Reheat Coil
Compressor
Outdoor Air
Indoor
Supply Air
Indoor
Return Air
RLV
Valve
Expansion
Valve (TXV)
= Closed Valve = Open Valve
RDV
Valve
Evaporator Coil
Condenser Coil
CLV
Valve
RDV
Valve
Indoor
Leaving Air
Reheat Mode
Metering
Device (TXV)
Condenser Coil
Hot Gas Reheat Coil
Outdoor Air
CLV
Valve
Compressor
Evaporator Coil
= Closed Valve = Open Valve
Indoor
Entering Air
Fig. 45 — Normal Cooling Mode – Hot Gas Re-Heat System with Single Stage Cooling, RGV036-061
Fig. 46 — Normal Cooling Mode – Hot Gas Re-Heat System with 2 Stage Cooling, RGV072
Condenser Coil
Outdoor Air
Compressor
= Closed Valve = Open Valve
RDV
Valve
CLV
Valve
Indoor
Leaving Air
Hot Gas Reheat Coil
Evaporator Coil
Indoor
Entering Air
Reheat Mode
Metering
Device (TXV)
Fig. 47 — Subcooling Mode – Hot Gas Re-Heat System with Single Stage Cooling, RGV036-061
30
Page 31
RDV
Valve
CLV
Valve
Condenser Coil
Hot Gas Reheat Coil
Evaporator Coil
Compressor
Outdoor Air
Indoor
Leaving Air
Indoor
Entering Air
Reheat Mode
Metering
Device (TXV)
= Closed Valve = Open Valve
RDV
Valve
Indoor
Supply Air
Condenser Coil
Hot Gas Reheat Coil
RLV
Valve
Outdoor Air
CLV
Valve
Compressor
Expansion
Valve (TXV)
Evaporator Coil
= Closed Valve = Open Valve
Indoor
Return Air
Fig. 48 — Subcooling Mode – Hot Gas Re-Heat System with 2 Stage Cooling, RGV072
Fig. 49 — Hot Gas Reheat Mode – Hot Gas Re-Heat System with Single Stage Cooling, RGV036-061
RDV
Valve
Condenser Coil
RLV
Valve
Outdoor Air
CLV
Compressor
Valve
= Closed Valve = Open Valve
Fig. 50 — Hot Gas Reheat Mode – Hot Gas Re-Heat System with 2 Stage Cooling, RGV072
31
Indoor
Supply Air
Hot Gas Reheat Coil
Expansion
Valve (TXV)
Evaporator Coil
Indoor
Return Air
Page 32

EconomizerONE (Factory Option)

12 3
4
5
6
NOTE: QR codes in this image are for reference only.
NO. DESCRIPTION
1 USB port for Wi-Fi/WLAN stick. 2 QR code to download Climatix
mobile application.
3
One-line LCD. After a period of inactivity, the controller displays the default: HMI screen (free cooling status, 1FREECOOL YES or 1FREECOOL NO)
4
Operation button (Up button) - Move to the previous value, step or category.
5
Operation button (Down button) - Move to the next value, step or category.
6
Operation button (Enter button):
• Press to edit the current value or option.
• Press to confirm a newly selected value or option.
• Press Enter + Up to jump up one entire category.
• Press Enter + Down to jump down one entire category.

ECONOMIZER SETTINGS

Interface Overview
EconomizerONE This option consists of the following:
Low Leak Economizer Assembly
1193547 OA (Outdoor Air) Dry Bulb Sensor
1193547 Mixed Air Sensor
POL224 Controller
1203458 Harness POL224 Economizer Module Wiring The economizer controller used on electromechanical units
is a Siemens POL224, which is to be located in the RTU base unit’s control box. See Fig. 51 for button description of the POL224 controller. Refer to the unit dimensional draw­ing for the location of the control box access panel.
The POL224 controller provides the following:
1. One-line LCD (Liquid Crystal Display) — After a
period of inactivity, the controller displays the default HMI (Human Machine Interface) screen (free cooling status, 1FREE-COOL YES or 1FREE COOL NO). See Fig. 51-55.
2. Operation button (Up button) — Move to the previous
value, step, or category.
3. Operation button (Down Button) — Move to the next
value, step, or category.
4. Operation Button (Enter Button):
a. Press Enter to edit the current value or option. b. Press Enter to confirm a newly selected value or
option. c. Press Enter + Up to jump up one entire category. d. Press Enter + Down to jump down one entire
category.
User Interface and Keypad The controller user interface consists of an LCD display and
a 3-button keypad for input. The LCD is a 16 character by 1-line dot matrix display. The keypad is used to navigate and change the desired menu items on the display. See Fig. 51.
The Climatix commissioning, and servicing. Scanning a QR code on the controller allows users to download the mobile application on Android Wi-Fi/WLAN stick is needed. See Fig. 51 and 52. Plug Wi-Fi/WLAN stick into controller USB port for temporary connection for mobile application setup. The Wi-Fi/WLAN stick can be used for multiple units.
Menu Structure Menus are displayed in the economizer controller via
categories. There are eight first-level menus, each of which is represented by a number at the beginning of the line on the LCD. Pressing Enter + Up or Down can toggle between different first-level menus. Submenus follow the numbered first-level menus closely. Pressing Up or Down can toggle between different submenus.
At the end of the line, the LCD displays the value of the cur­rent submenu (if any). If the value is editable, pressing Enter will put the terminal in Edit mode. The value is then high­lighted for change. After making a change by pressing Up or
1. Third-party trademarks and logos are the property of their respective owners.
™1
mobile application allows for installation,
™1
or Apple iOS®1, but a
Down, press Enter to confirm the change and exit the Edit mode. See Fig. 54.
Powering the Economizer Controller The POL224 controller power connections are made
through the economizer harness (P/N 1203458). Con­nections from the harness are made to the C (24 vac common) and R (24 vac power) terminals of the econo­mizer controller. See Fig. 53.
LED Indication NOTE: If different faulty events occur at the same time, then
sensor/DAC LED lights up following the priority below: Red Yellow Off. For example, if there is a humidity sensor error and air temperature failure at the same time, then the sensor LED turns red rather than yellow. See Fig. 55 and Table 9.
IMPORTANT: After the Economizer controller enters the running state, it may take one minute for peripheral devic­es to complete initialization. Before that, LED indication might be unstable.
Fig. 51 — POL224 Controller
32
Page 33
NOTE: QR codes in this image are for reference only.
Power
No. Description
1 Number representing the first-level menu of Status Display. Different
numbers represent different menus:
1: Status Display 2: Basic Settings 3: Advanced Settings 4: Alarms 5: Enter Configuration State and Reset 6: I/O Config 7: Testing 8: Enter Running State
2 Submenu*
3 Value of the current submenu*
12 3
*See “Setup and Configuration” on page 42 for detailed submenus together with possible values or ranges.
NO. DESCRIPTION
1 Free Cooling LED 2 Sensor LED 3 DAC LED
123
Table 9 — LED Indication
On
Off
ShutOff SP OAT
DB
LEGEND
OAT — Outside Air Temperature DB — Deadband SP — Set Point
Fig. 52 — Wi-Fi/WLAN Stick
Fig. 53 — Powering the EconomizerONE Controller
STATUS
Commissioning mode
Power start up Yellow On Yellow On Yellow On Free cooling is running Green On Free cooling is available
but not running Not economizing when it
should Economizing when it
should not Sensor working okay Green On Humidity sensor error —Yellow On— CO
sensor error —LED Off—
2
Air temperature fault/failure Red On
Excess outdoor air
Damper working okay Green On Damper not modulating Red On
Damper slippage ——
Damper unplugged ——
Terminal ACT-FB is configured but no available feedback signal
FREE
COOLING
LED
Yellow
Blinking
Green
Blinking
Red Blinking
Red On
——LED Off
SENSOR
LED
Yellow
Blinking
——
Red
Blinking
DAC LED
Yellow
Blinking
Red
Blinking
Fast Red
Blinking
Functions
Free Cooling Economizing Free cooling uses unconditioned outside air to cool the
space directly. The economizer controller enables or dis­ables free cooling after it judges which control mode is ac­tive. It also uses hysteresis to ensure a smooth switchover.
Depending on the sensors that are used, there are four dif­ferent control modes. In different control modes, the as­sessed conditions are different. See Table 10.
Default Hysteresis Setting Hysteresis setting (DB) defaults to 2°F (–17°C). See Fig. 56.
Fig. 54 — Menu Structure Descriptions
Fig. 55 — LED Indication
Fig. 56 — Hysteresis Settings
33
Page 34
Table 10 — Free Cooling Functions
CONTROL MODE SENSORS USED ENABLE FREE COOLING?
Control Mode 1
• Fixed Dry bulb
Control Mode 2
• Differential Dry bulb (Dual Dry bulbs)
Control Mode 3
• Combination Fixed Enthalpy and Fixed Dry bulb Control
Control Mode 4
• Combination of Differential Enthalpy and Fixed Dry bulb
OA (outside air) temperature sensor and MA (Mixed Air) temperature sensor
OA temperature sensor, RA (Return Air) temperature sensor and MA temperature sensor
OA temperature and humidity sensor, and MA temperature sensor
OA temperature and humidity sensor, RA temperature and humidity sensor, and MA temperature sensor
The outside air dry bulb temperature is compared with the set temperature shutoff setpoint. If the outside air dry bulb temperature is below the temperature shutoff setpoint, then the outside air is used to meet all or part of the cooling demand.
The outside-air dry bulb temperature is compared with the return air dry bulb temperature. If both OAT and RAT are higher than the temperature high limitation, then free cooling is prohibited. If OAT or RAT is lower than the temperature high limitation and the outside air dry bulb temperature is lower than the return air dry-bulb temperature, then the outside air is used to meet all or part of the cooling demand.
The outside air dry bulb temperature and enthalpy are compared with the set temperature and enthalpy shutoff setpoints. If the outside air enthalpy is lower than the set enthalpy shutoff setpoint, and the outside air dry bulb temperature is lower than the temperature shutoff setpoint, then the outside air can be used for economizing.
The outside air dry bulb temperature and enthalpy are compared with the temperature shutoff setpoint and return air enthalpy. If both OA enthalpy and RA enthalpy are higher than the enthalpy high limitation, then free cooling is prohibited. If OA enthalpy or RA enthalpy is lower than the enthalpy high limitation, outside air enthalpy is lower than the return-air enthalpy, and the outside air dry bulb temperature is lower than the set temperature shutoff setpoint, then outside air can be used for economizing.
Damper Modulation During Free Cooling Once outside air is suitable for free cooling, the controller
modulates the damper based on MAT (mixed air tempera­ture, default) or OAT (outside air temperature). Refer to Table 10.
If MAT is used when free cooling is enabled, MAT setpoint (3MAT SET, configurable in “Parameter Settings — Ad- vanced” on page 45) is used for MAT modulating. When MAT falls below the anti-freeze setpoint (3FRZ PROT), the damper either fully closes or opens to the minimum position (configurable in “Parameter Settings — Advanced” on page 45).
1. If MAT is lower than MAT setpoint, then the damper is modulated to maintain MAT setpoint, towards fully closed or open to the minimum position based on occupancy status if MAT continues dropping.
2. If MAT is in the range [MAT setpoint, (MAT setpoint + neutral zone band [1°F by default])], then the damper position does not change.
3. If MAT is higher than (MAT setpoint + neutral zone band), then the damper opens towards fully open.
4. If MAT is 10°F higher than MAT setpoint, then the damper fully opens to 100%.
If OAT is used when there is a cooling demand, the damper can be opened to different positions depending on different outside air temperatures:
1. If outside air is higher than 50°F but lower than the temperature shutoff setpoint, then the damper is fully open.
2. If outside air is higher than OAT lockout setpoint but lower than 50°F, then linear modulation is applied when only Cooling Stage 1 input (Y1I) is ON. Result
of the following formula indicates the damper’s open position:
([OAT - OAT Lockout Setpoint] / [50 - OAT Lockout Setpoint]) * (80% - MIN POS) + MIN POS
NOTE: When both free cooling and mechanical cooling are on, damper remains fully open regardless of the
modulating logic. Location-Based Shutoff Setpoints The economizer controller can get location-based tempera-
ture and enthalpy shutoff setpoints automatically if it is con­nected to the Climatix
mobile application. Once a Wi-Fi/WLAN stick is plugged in, the economizer controller can establish network connection with the mobile applica­tion. The temperature and enthalpy shutoff setpoints ob­tained via the phone or tablet’s GPS functionality can then be synchronized to the economizer controller.
Cooling Stage Operation The economizer controller accepts inputs for 1 and 2-stage
cooling inputs and reroutes to the RTU through the relay connection Y1 and Y2.
The operation of the cooling stages is determined by the availability of Free Cooling provided by the economizer op­eration mode. See Cooling Stage I/O Logic Tables 11-12. Based on the use of Free Cooling, the operating modes are as follows:
Y1 is Stage 1 Cooling Demand.
Y2 is Stage 2 Cooling Demand.
Free Cooling is always the first cooling stage.
Cooling Stage 1 call from the Commercial Thermo­stat (Y1) energizes the Y1 input to the economizer controller.
Cooling Stage 2 call from the Commercial Thermo­stat (Y2) energizes the Y2 input to the economizer controller.
34
Page 35
Table 11 — 1 and 2-Stage Cooling Stage I/O Logic
NOTE(S):
NOTE(S):
NOTE(S):
NOTE(S):
ECONOMIZER
CONDITION MET
Y1 Y2
NO On On On On NO On Off On Off
NO Off Off Off Off YES On On On On/Off YES On Off Off Off YES Off Off Off Off
COOLING
STAGE 1
COOLING
STAGE 2
Table 14 — Different Fan Speeds with Different
Configured Outputs
FAN TYPE 1-SPEED COOLING
1-SPEED
FAN
a
2-SPEED
FAN
• Spd H (regardless of
c
c
cooling demand, OCC=Yes)
• Spd L (0 or 1 cooling demand)
• Spd H (2 cooling demands)
b
a
2-STAGE COOLING
• Spd H (regardless of cooling demand, OCC=Yes)
• Spd L (0 or 1 cooling demand)
• Spd H (2 cooling demands)
b
aIf OAT MAT setpoint (3MAT SET), then Relay 2 is always OFF to disable
Cooling Stage 2. Otherwise, if both stages of cooling (Y1 and Y2) are ON for more than a set time (15 minutes by default), Y2 remains ON, and the OAT is higher than MAT setpoint, then Relay 2 energizes to allow Y2 pass-through to enable Cooling Stage 2.
Table 12 — 2-Stage Cooling Stage I/O Logic
ECONOMIZER
CONDITION MET
Y1 Y2
COOLING
STAGE 1
NO On On On On NO On On On On NO On Off On Off
NO Off Off Off Off YES On On On On YES On On On On/Off YES On Off Off Off YES Off Off Off Off
COOLING
STAGE 2
IMPORTANT: The economizer controller can tolerate ther­mostat wiring mismatch, e.g. Thermostat Y1 → Economiz- er Y2-In, Thermostat Y2 Economizer Y1-In. The han­dling logic is Stage =Y1I + Y2I. For example, Y1O =1 if Stage > =1, Y2O =1 if Stage > = 2.
Multi-Speed Fan Support The economizer controller supports connection to 2-speed
fans. When the unit is equipped with a multi-speed fan, the damper responds to multiple fan speeds via multiple mini­mum positions (MIN POS) to keep minimum airflow. See Tables 13-15.
Table 13 — Damper MIN POS for 2-Speed Fan
Y1 Y2
X——X — X — XX—— X — X
—— X— X — X
W1 OR
O/B
SPD L SPD H POS L POS H
a
a If a single-speed fan connects to the Controller, it opens directly on the call of
cooling/heating. The damper position is Pos H. b Configured by Y1O or Y2O. c Configured by 6FAN.
LEGEND
Spd L — Low Speed (Fan) Spd H — High Speed (Fan)
Table 15 — Different Damper Minimum Positions with
Different Configured Outputs
FAN TYPE 1-SPEED COOLING
1-SPEED
FAN
2-SPEED
FAN
a Configured by Y1O or Y2O. b Configured by 6FAN.
LEGEND
Pos L — Damper MIN POS for Low-Speed Fan Pos H — Damper MIN POS for High-Speed Fan
• Pos H (regardless of
b
b
cooling demand, OCC=Yes)
• Pos H (regardless of cooling demand, OCC=Yes)
a
2-STAGE COOLING
• Pos H (regardless of cooling demand, OCC=Yes)
• Pos L (0 or 1 cooling demand)
•Pos H (2 cooling demands)
b
If DCV (demand controlled ventilation) is enabled, each fan speed corresponds to two damper position ventilation set­points (VENT MIN, VENT MAX), e.g., Pos L corresponds to 2VENTMIN L... 2VENTMAX L. See Table 16 for Different Damper Position Setting with Different Configured Outputs with DCV enabled.
If CO
sensor is connected but DCV is disabled, then each
2
fan speed corresponds to one minimum damper position ventilation setpoint. See Table 17 for Different Damper Posi­tion Setting with Different Configured Outputs with DCV dis­abled.
a A multi-speed fan is not controlled by the economizer controller but by an ex-
ternal logic board.
LEGEND
POS L — Damper MIN POS for Low-Speed Fan POS H — Damper MIN POS for High-Speed Fan SPD L — Low-Speed (Fan) SPD H — High-Speed (Fan)
35
Page 36
Table 16 — Different Damper Position Settings with Different Configured Outputs (DCV is Enabled)
NOTE(S):
NOTE(S):
FAN TYPE 1-STAGE COOLING
1-SPEED FAN
2-SPEED FAN
a Configured by Y1O or Y2O. b Configured by 6FAN.
a
b
b
• 2VENTMIN H to 2VENTMAX H (regardless of cooling demand, OCC=Yes)
• 2VENTMIN H to 2VENTMAX H (regardless of cooling demand, OCC=Yes)
• 2VENTMIN H to 2VENTMAX H (regardless of cooling demand, OCC=Yes)
• 2VENTMIN L to 2VENTMAXL (0 or 1 cooling demand)
• 2VENTMIN H to 2VENTMAX H (2 cooling demands)
2-STAGE COOLING
a
Table 17 — Different Damper Position Settings with Different Configured Outputs
(DCV is Disabled, CO2 sensor is connected)
FAN TYPE 1-STAGE COOLING
1-SPEED FAN
2-SPEED FAN
a Configured by Y1O or Y2O. b Configured by 6FAN.
b
b
• 2VENTMIN H (regardless of cooling demand, OCC=Yes)
• 2VENTMIN H (regardless of cooling demand, OCC=Yes)
Cooling Delay via Increasing Fan Speed If there is cooling demand while outside air is suitable for
economizing, then the economizer controller tries to in­crease fan speed to maximize the use of outside air first. If the cooling demand is not reached within a set time, then mechanical cooling will be enabled.
Typical field application:
1. Prerequisites:
Outside air is suitable for economizing and free cool­ing is ON.
Fan connected to the controller supports multiple speeds. Cooling delay function does not work if only a one-speed fan is connected to the controller.
2. If it is a 2-speed fan and there are two cooling demand inputs/outputs and Y1-Input is called, then the controller sets fan speed to Speed Low. Damper is fully open (100%).
If Y2-Input is also called, then the controller increases fan speed to Speed High and starts fan delay (2FAN DLY) time. After the delay time runs out, the controller starts Y1-Output.
Demand Controlled Ventilation (DCV) If a field-installed CO2 sensor is connected to the
EconomizerONE controller, then a demand controlled venti­lation strategy will operate automatically. As the CO
level in
2
the space increases above the setpoint (on the EconomizerONE controller), the minimum position of the dampers will be increased proportionally until the Maximum Ventilation setting is reached. As the space CO
level de-
2
creases because of the increase in fresh air, the outdoor damper will follow the higher demand condition from the DCV mode or from the free cooling mode.
The controller modulates the outside air damper based on the CO
level through the ppm value selected between the
2
range of 500 and 2000 ppm. The measured CO2 concentra­tion value is compared with the set DCV setpoint. If the measured CO
concentration value is below the DCV
2
setpoint, then keep the damper to the minimum position. Otherwise, enable DCV. Once DCV is enabled, the DCV PID starts to run to control the indoor CO
concentration
2
value towards the DCV setpoint. The damper opens to the maximum position.
a
• 2VENTMIN H (regardless of cooling demand, OCC=Yes)
• 2VENTMIN L (0 or 1 cooling demand)
• 2VENTMIN H (2 cooling demands)
2-STAGE COOLING
a
NOTE: DCV is disabled if the controller receives no occu­pancy signal.
DCV operation is available in Occupied and Unoccupied periods with the EconomizerONE system. However, a con­trol modification will be required on the unit system to imple­ment the Unoccupied period function. Refer to controller ac­cessory installation instruction manual for further controls and command operation information.
High Humidity Limitation The economizer controller applies high limit of humidity to
enthalpy-based economizing. When the OA dew point is below the dew point setpoint, enthalpy-based economiz­ing is available. Otherwise, enthalpy-based economizing is unavailable.
Anti-Freeze Protection The economizer controller initiates the anti-freeze protection
if MAT or OAT temperature falls below the anti-freeze setpoint.
MAT-Based Anti-Freeze Protection
1. If MAT temperature falls below the anti-freeze set­point (3FRZ PROT), then:
The controller closes both damper and compressor if unit type is conventional unit and cooling/heating conventional operation mode is enabled.
The controller closes the damper if unit type is heat pump and heat pump operation mode is enabled.
2. If the MAT sensor fails, MAT is substituted by OAT to continue the anti-freeze assessment. If OAT fails too, the controller closes the damper immediately.
OAT-Based Anti-Freeze Protection If OAT temperature falls below the OAT lockout setpoint
(3OAT LOCK):
1. The controller stops the compressor from running if unit type is conventional unit and cooling/heating conventional operation mode is enabled.
2. The controller compressor is bypassed if unit type is heat pump and heat pump operation mode is enabled.
36
Page 37
Exhaust Fan Operation Up to two exhaust fans can be connected to the econo-
mizer controller.
If Exhaust Fan 1 is connected and configured, then Exhaust Fan 1 parameter group (L, M and H) is avail­able, depending on fan configuration.
If Exhaust Fan 2 is connected and configured, then Exhaust Fan 2 parameter group (L, M and H) is avail­able, depending on fan configuration.
The controller energizes Exhaust Fan Relay 1 and Exhaust Fan Relay 2 if the damper position reaches Exhaust Fan 1 parameter setting and Exhaust Fan Relay 2 parameter setting respectively. The selection of L, M, or H matches the current fan speed.
NOTE: If terminal ACT-FB is configured, then the damper position is the damper feedback position. If feedback signal is unavailable, it is the simulated position.
Occupancy Input The economizer controller can receive an occupancy sig-
nal from the connected thermostat or work under Occu­pied mode all the time. This is configurable in the Ther­mostat setup from the Climatix
mobile application or un­der the I/O Configuration menu on the inbuilt display. See “Parameter Settings — I/O Configurations” on page 45 for more information.
IMPORTANT: On the call of cooling, when the controller is configured to receive signal from the thermostat but the thermostat is working under the Unoccupied mode, the damper is fully closed if outside air is not suitable for econ­omizing. If outside air is suitable for economizing, the damper is fully open.
Pre-occupancy Purge The pre-occupancy purge demand comes from the configu-
ration of the Auxiliary features in the Climatix
mobile appli­cation or 6AUX2-I under the I/O Configuration menu on the inbuilt display.
During pre-occupancy purge on the call of heating or when there is no cooling/heating demand, the damper position is MIN POS.
During pre-occupancy purge on the call of cooling, the damper position is MIN POS if outside air is not suitable for economizing. If outside air is suitable for economizing, then the damper is fully open.
Airflow Commissioning Airflow measurement station (differential pressure signal)
can connect to the controller temporarily to run airflow commissioning to calculate, calibrate, and store 4 fan speed characteristic curves automatically at damper positions 40%, 60%, 80%, and 100%. The controller places the damper to a proper position to meet minimum or any other
airflow requests in cfm. Users can enable this function only from the Climatix
mobile application if the related function
is available in the current mobile application version. Fault Detection and Diagnostics The economizer controller can detect and diagnose free
cooling faults, sensor operation faults, and damper modulat­ing faults. It can also report anti-freeze and shutdown notifi­cations and actuator errors. Following is a list of all detect­able or reportable information:
Sensor disconnected or has no signal.
Sensor short or high signal (under range or over range).
Not economizing.
Unexpected economizing.
Excess outdoor air.
Damper not modulating.
Input power monitor and brownout. After detecting brownout, the economizer controller enters the brownout protection mode and disables all of the re­lay outputs.
Anti-freeze notifications.
Shutdown notifications.
Actuator errors.
Too low or too high leaving air temperature.
Cooling/heating error.
Damper actuator cycle count. Parameter 1ACT CNT indicates number of times actuator has cycled. It is resettable via HMI item 8ACT CNT RESET.
IMPORTANT: The first 6 faults are detectable via LEDs or alarm reports on the LCD. See LED Indication on page 33 and Alarms on page 46 for fault indications. These faults can also be displayed in the Operating section of the
Climatix
mobile application.
Firmware Update NOTE: Back up configurations before firmware update. All
the previous configuration data are erased after firmware update. NOTE: Contact Application Engineering for more in­formation on support for firmware.
IMPORTANT: If the controller enters the configuration state for the convenience of I/O configurations, then users can manually switch to the running state after finishing configurations. To do so, press Enter + Up at the same time, and then press Enter to confirm the switch after 8RUN STATE appears on the LCD.
37
Page 38

WIRING

WARNING
Failure to follow this caution may result in damage to equipment. Be sure to allow enough time for compressor startup and shutdown between checkout tests so that the compressors do not short-cycle.
Mounting Devices Connected to the Economizer Controller
Devices like damper actuators, sensors (temperature sensor, humidity sensor, combination temperature and humidity sensor, CO fans can be connected to the economizer controller. For information on how to mount the devices, see the device’s installation instructions. See Fig. 57 and Table 18 for economizer controller wiring details.
sensor), thermostats, and exhaust
2
Fig. 57 — EconomizerONE Control Wiring
38
Page 39
Table 18 — EconomizerONE Control Wiring Settings
NO. LABEL TYPE DESCRIPTION
1 + RS485 Modbus A Line A 2 - RS485 Modbus B Line B 3 ¬ GND_ISO Earth Ground 4 MAT Type II NTC 10K or 0-10 vdc Mixed or Discharge Air Temperature Sensor 5 COM COM Mixed or Discharge Air Temperature Sensor Common 6 OAT Type II NTC 10K or 0-10 vdc Outside Air Temperature Sensor 7 OAH 0-10 vdc or 4-20mA Outside Air Relative Humidity Sensor
8 COM COM
9 AUX-AI 0-10 vdc, 2-10 vdc or 0-5 vdc Air Quality Sensor or Pressure Sensor 10 RAT Type II NTC 10K or 0-10 vdc Return Air Temperature Sensor 11 RAH 0-10 vdc or 4-20mA Return Air Relative Humidity Sensor 12 S-COM COM 24 vac Common 13 S-24V 24 vac 24 vac Power Out to Sensors 14 ACT-FB 2-10 vdc Damper Actuator Feedback 15 ACT2-10 2-10 vdc Damper Actuator Output 16 ACT-COM COM Damper Actuator Output Common 17 ACT-24V 24 vac 24 vac Power Out to Damper Actuator
18 AUX2-O 24 vac OUT
19 COM COM 24 vac Common
20 AUX2-I 24 vac IN
21 AUX1-O 24 vac OUT
22 COM COM 24 vac Common
23 AUX1-I 24 vac IN
24 OCC 24 vac IN Occupancy Input 25 Y2O 24 vac OUT Cooling Stage 2 Output to Stage 2 Mechanical Cooling 26 Y2I 24 vac IN Cooling Stage 2 Input from Commercial Thermostat 27 Y1O 24 vac OUT Cooling Stage 1 Output to Stage 1 Mechanical Cooling 28 Y1I 24 vac IN Cooling Stage 1 Input from Commercial Thermostat 29 C COM 24 vac Common 30 R 24 vac 24 vac Power
Outside Air Temperature Sensor or Outside Air Relative Humidity Sensor Common
Configurable:
• Exhaust Fan (1 or 2)
• System Alarm output (Title 24)
Configurable:
• Shut Down
• Heat Conventional (W1)
• Heat Pump Changeover (reversing valve OB)
• Pre-occupancy Configurable:
• Exhaust Fan (1 or 2)
• System Alarm output (Title 24)
Configurable:
• Shut Down
• Heat Conventional (W1)
• Heat Pump Changeover (reversing valve OB)
• Pre-occupancy
39
Page 40
Connecting Peripheral Devices to the Economizer
Outside Air:
Connect to the OAT and COM terminals of the device.
Return Air
(Differential):
and S-COM terminals of the device.
Mixed Air: Connect
to the MAT and COM terminals of the device.
Mixed or Discharge Air Temperature Sensor
Outside Air Temperature Sensor
Return Air Temperature Sensor
Outside Air
Relative Humidity: Connect to the OAH and COM terminals of the device.
Return Air Relative
Humidity: Connect to the RAH and S-COM terminals of the device.
Outside Air Relative Humidity Sensor
Return Air Relative Humidity Sensor
Controller
See Fig. 58-62 for wiring details.
Connect to the RAT
Fig. 58 — Temperature Sensor Connection
Fig. 59 — Relative Humidity Sensor Connection
40
Page 41
Fig. 60 — Combination Temperature/Humidity Sensor Connection
Outside
Combination Temperature/ Humidity: Connect to the OAT, COM, and OAH terminals of the device.
Return
Combination Temperature/ Humidity: Connect to the RAT, S-COM, and RAH terminals of the device.
Combo Temperature and Humidity Sensor
Combo Temperature and Humidity Sensor
Connect to the
AUX-AI, S-COM, and S-24V terminals of the device.
Air Quality Sensor or Pressure Sensor
Connect to the
ACT 2-10, ACT-COM, and ACT-24V terminals of the device.
Damper Actuator: Power and 2-10 Vdc
Fig. 61 — CO
Fig. 62 — Damper Actuator Connection
/Pressure Sensor Connection
2
41
Page 42

SETUP AND CONFIGURATION

NOTE(S):
IMPORTANT: Before setup and configuration, it is recom­mended to obtain some location-based values, such as shutoff points, or utilize the location services in the Climatix
mobile application.
Set up and configure the economizer controller before put­ting it into usage. This can be accomplished by using the Climatix
mobile application or the inbuilt display. After sensor, compressor, thermostat, or actuator is connected to the economizer controller, values/statuses are displayed in the Operating section of the mobile application and on the LCD. Users can manually change basic and advanced set­tings, configure I/Os, and test the damper operation and any configured outputs by modifying the corresponding parame­ter values in the local device or mobile application. See Tables 19-26 for complete list of all parameters available on the LCD display. Refer to it during the setup and configura­tion process.
NOTE: For all units, the Climatix application login is: Administrator. For units coming from the factory with CO configuration or single enthalpy (control mode 3), the
controller password is OneBT2.1. For all other units, use the controller password OneBT.
NOTE: Parameters and display menus may display differently/dynamically if different applications are config­ured. See Tables 19-26.
IMPORTANT: Not all operations are available on the local POL224. For example, users can only obtain shutoff setpoints and perform cfm commissioning via the Climatix
mobile application. Setup and configuration on the local device are only recommended if operations from the mobile application are unavailable. Check the mobile application for all operations that can be performed from the mobile application end.
IMPORTANT: By connecting the RS485 port to a PC, all parameters are also readable or writable from PC tools such as Modbus Poll.exe via Modbus BACnet™
a
MSTP (Bps 38400 [default], Bps 9600, Bps
®a
and Yabe.exe via
19200, Bps 115200). Note that an external End of Line (EOL) element is required to achieve Baud Rate 115200 at
2
a maximum cable length of 4000 ft (1.2 km).
a Third-party trademarks and logos are the property of their respective owners.
42
Page 43
Table 19 — Status Display
PARAMETER DESCRIPTION VALUE
1FREECOOL Indicates whether the system can use outdoor air for free cooling. 1ECON ENAB Indicates whether outdoor air is being used for the first stage of cooling.
Indicates whether the space is occupied. If users choose ALWAYS for 6OCC when
1OCCUPIED
configuring I/Os, then the parameter value is YES; if users keep the default selection T-STAT for 6OCC and the controller receives 24-v signal from OCC input, then the value is
YES. Otherwise, the value is NO. 1Y1-IN Y1-In call from thermostat for Cooling Stage 1. 1Y1-OUT Y1-Out signal to compressor for Cooling Stage 1. 1Y2-IN Y2-In call from thermostat for Cooling Stage 2.
1Y2-OUT
1AUX1-I
1AUX1-O
1AUX2-I
1AUX2-O
Y2-Out signal to compressor for Cooling Stage 2.
Dynamic item: Appears only if Y2-Out terminal is configured.
Aux1-In signal
Dynamic item: Appears only if Aux1-In terminal is configured.
Aux1-Out signal
Dynamic item: Appears only if Aux1-Out terminal is configured.
Aux2-In signal
Dynamic item: Appears only if Aux2-In terminal is configured.
Aux2-Out signal
Dynamic item: Appears only if Aux2-Out terminal is configured.
1COMP STAGE Indicates compressor current stage.
1HEAT ENAB Indicates whether heating is enabled.
1MIX AIR LOW
Indicates whether the anti-freeze protection function is enabled for a mixed air temperature
sensor. If the detected air temperature is lower than the anti-freeze protection setpoint
(3FRZ PROT), then the parameter value is YES. Otherwise, it is NO.
Indicates the present value of the mixed air temperature (MAT) sensor.
1MAT PRES
1LAT PRES
1OAT PRES
1OAH PRES
1RAT PRES
1RAH PRES
1CO2 PRES
Dynamic item: Appears only if MAT or AUTO is selected for
3DIF T LOC under Parameter Settings — Advanced on page 45.
Indicates the present value of the leaving air temperature (LAT) sensor.
Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC.
Indicates the present value of the outdoor air temperature (OAT) sensor.
Dynamic item: Appears only if an OAT sensor is configured.
Indicates the present value of the outdoor air relative humidity (OAH) sensor.
Dynamic item: Appears only if an OAH sensor is configured.
Indicates the present value of the return air temperature (RAT) sensor.
Dynamic item: Appears only if a RAT sensor is configured.
Indicates the present value of the return air relative humidity (RAH) sensor.
Dynamic item: Appears only if a RAH sensor is configured.
Indicates the present value of the CO
Dynamic item: Appears only if a CO2 sensor is configured.
sensor.
2
The corresponding detected
value is displayed on the LCD.
Indicates the demand controlled ventilation (DCV) status.
1DCV STATUS
1FAN SPD LV
Dynamic item: Appears only if a CO
Displays ON if the measured CO2 concentration value is above the DCV setpoint and OFF
if below the DCV setpoint.
Indicates the current fan speed status (low, medium, or high). If a one-speed fan is
connected and configured, then this item is invisible.
Dynamic item: Appears only if “6FAN” is configured as “2SPEED” under Parameter
sensor is configured.
2
Settings — I/O Configurations on page 45.
1ACT OUT Indicates current position of damper actuator in V. 1ACT FB Indicates feedback signal of damper actuator in V. 1ACT POS Indicates current position of damper actuator in % Open.
1ACT CNT
Indicates number of times actuator has cycled (1 cycle = 180 degrees of movement in any
direction). Resettable via HMI item 8ACT CNT RESET under Enter Running State on
The corresponding detected
value is displayed on the LCD.
page 47.
1EQUIP
Indicates the equipment type. If HP(O) or HP(B) is chosen for 6AUX1-I, then the parameter
value is HP(O) or HP(B) respectively. If neither is chosen, then the value is CON RTU.
1OAT LOCK Indicates status of the OAT cooling lockout function.
1INS
Indicates the installation date of the economizer controller. If the installation date is
incorrect, press Enter to change and confirm month, date, and year.
YES
NO
ON
OFF
Off
1 2 3
YES
NO
ON
OFF
L
H
HP(O) HP(B)
CON RTU
NO
LCKOUT
OVRD
43
Page 44
Table 20 — Parameter Settings — Basic
PARAMETER DESCRIPTION RANGE DEFAULT
Temperature shutoff setpoint can be obtained automatically if a smartphone
2 TEMP OFF
or tablet with the mobile application installed on it is connected to the network provided by a Wi-Fi/WLAN stick plugged into the economizer controller. This can also be a manually defined setpoint.
Enthalpy shutoff setpoint can be obtained automatically if a smartphone or
2ENTH OFF
tablet with the mobile application installed on it is connected to the network provided by a Wi-Fi/WLAN stick plugged into the economizer controller. This can also be a manually defined setpoint. Dynamic item: Appears only if an OAH sensor is configured.
Demand controlled ventilation setpoint can be obtained automatically if a
2DVC
2FAN L ACT
2FAN H ACT
2VENTMAX L
2VENTMAX H
2VENTMIN L
2VENTMIN H
CFM COMM
smartphone or tablet with the mobile application installed on it is connected to the network provided by a Wi-Fi/WLAN stick plugged into the economizer controller. This can also be a manually defined setpoint. Dynamic item: Appears only if a CO
Damper minimum position when fan runs at a low speed. Dynamic item: Appears only if “6FAN” is configured as “2SPEED” under Parameter Settings — I/O Configurations on page 45.
Damper minimum position when fan runs at a high speed. Dynamic item: Appears only if “6FAN” is configured as “1SPEED” or “2SPEED”.
DCV maximum position when fan runs at a low speed. Dynamic item: Appears only if a CO configured as “2SPEED”.
DCV maximum position when fan runs at a high speed. Dynamic item: Appears only if a CO configured as “1SPEED” or “2SPEED”.
DCV minimum position when fan runs at a low speed. Dynamic item: Appears only if a CO configured as “2SPEED”.
DCV minimum position when fan runs at a high speed. Dynamic item: Appears only if a CO configured as “1SPEED” or “2SPEED”.
Air Flow Chart: CFM commissioning can only be initiated from the mobile application. When CFM commissioning is in progress, the local device
sensor is configured.
2
sensor is configured and “6FAN” is
2
sensor is configured and “6FAN” is
2
sensor is configured and “6FAN” is
2
sensor is configured and “6FAN” is
2
reads “CFM COMM”.
2DEGREES Temperature unit (°F or °C). °F
2FAN Fan cfm.
Exhaust Fan 1 low-speed parameter setting.
2EX1 L
Dynamic item: Appears only if:
• Exhaust Fan 1 is configured.
•“6FAN” is configured as “2SPEED”. Exhaust Fan 1 high-speed parameter setting.
2EX1 H
2EX2 L
Dynamic item: Appears only if:
• Exhaust Fan 1 is configured.
•“6FAN” is configured as “1SPEED” or “2SPEED”. Exhaust Fan 2 low-speed parameter setting.
Dynamic item: Appears only if:
• Exhaust Fan 2 is configured.
•“6FAN” is configured as “2SPEED”. Exhaust Fan 2 high-speed parameter setting.
2EX2 H
2THL
2EHL
Dynamic item: Appears only if:
• Exhaust Fan 2 is configured.
•“6FAN” is configured as “1SPEED” or “2SPEED”. Temperature high limitation.
Dynamic item: Appears only if an RAT sensor is configured. Enthalpy high limitation.
Dynamic item: Appears only if an RAH sensor is configured.
2FAN DLY Cooling delay via increasing fan speed. 0...30 min; increment by 1 5 min.
48...80°F; increment by 1 63°F
22...30 Btu/lbm; increment by 1 28 Btu/lbm
300...2000PPM;
increment by 100
1100PPM
2...10V; increment by 0.1 3.6V
2...10V; increment by 0.1 2.8V
2...10V; increment by 0.1 3.6V
2...10V; increment by 0.1 3.6V
2...10V; increment by 0.1 3.1V
2...10V; increment by 0.1 2.3V
——
100...50,000cfm;
increment by 100
5000cfm
0...100%; increment by 1 65%
0...100%; increment by 1 50%
0...100% 80%
0...100%; increment by 1 75%
0...100%; increment by 1 83%
30...50 Btu/lbm; increment by 1 33 Btu/lbm
44
Page 45
Table 21 — Parameter Settings — Advanced
PARAMETER DESCRIPTION VALUE/RANGE DEFAULT
3FREEZE POS Anti-freeze protection damper position (closed or minimum).
3SD ACT POS Damper position during shutdown (open or closed).
MAT sensor location:
3DIF T LOC
3LAT LOW
3LAT HIGH
3OAT CAL OAT sensor calibration. –2.5...2.5°F; increment by 0.5 0°F
3RAT CAL
3OAH CAL
3RAH CAL
3MAT CAL MAT or LAT sensor calibration. –2.5...2.5°F; increment by 0.5 0°F 3MAT SET Setpoint of MAT or LAT sensor. 38...70°F; increment by 1 53°F 3FRZ PROT Anti-freeze protection setpoint of MAT sensor. 35...55°F; increment by 1 45°F
3ACT TOLR
3OAT LOCK OAT lockout set point for anti-freeze protection. –45...80°F; increment by 1 32°F
3OAT LCKOVRD
3OAT LOCKODLY Indicates the overridden time if “YES” is selected for “3OAT LCKOVRD”. 0...300 min; increment by 1 45 min.
• Choose MAT if the sensor is installed before the DX (Direct Expansion) coil.
• Choose LAT if the sensor is installed after the DX coil.
• Choose AUTO to let the economizer controller automatically detect the location. Low limit of leaving air temperature.
Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC. High limit of leaving air temperature.
Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC.
RAT sensor calibration. Dynamic item: Appears only if an RAT sensor is configured.
OAH sensor calibration. Dynamic item: Appears only if an OAH sensor is configured.
RAH sensor calibration. Dynamic item: Appears only if an RAH sensor is configured.
Actuator tolerance setpoint between output (in percent) and feedback (in percent).
When OAT LOCKOUT is enabled, choose to override the cooling lockout function or not.
35...65°F; increment by 1 45°F
70...180°F; increment by 1 80°F
–2.5...2.5°F; increment by 0.5
–10...10%; increment by 0.5 0%
0...15%; increment by 1 8%
CLO
MIN
CLO OPN
MAT
LAT
AUTO
YES
NO
CLO
CLO
LAT
NO
Table 22 — Parameter Settings — I/O Configurations
PARAMETER DESCRIPTION VALUE DEFAULT
6OCC
6AUX1-I
6AUX2-I
6OAT SIG Configures signal type of OAT sensor.
6RAT SIG Configures signal type of RAT sensor.
6OAH SIG Configures signal type of OAH sensor. 0-10V
6RAH SIG Configures signal type of RAH sensor.
6MAT SIG Configures signal type of MAT or LAT sensor.
6AUX-AI1
6X-AI1 SIG
6CO2 Rng L
6C02 Rng H
6AUX-AI2
Configures whether occupancy status receives signal from the connected thermostat or is displayed as ALWAYS in the economizer controller.
Auxiliary DI-1. Configurable as:
• None
• Heat Conventional (W1) from thermostat
• Heat pump (reversing valve O)
• Heat pump (reversing valve B)
• Pre-occupancy signal from thermostat
• Shutdown signal from unit Auxiliary DI-2. Configurable as:
• None
• Heat stage 1 (W1) from thermostat
• Heat pump (reversing valve O)
• Heat pump (reversing valve B)
• Pre-occupancy signal from thermostat
• Shutdown signal from unit NOTE: Whichever is chosen for 6AUX1-I does not appear in the list of 6AUX2-I.
Auxiliary AI-1. Configurable as:
•CO
sensor
2
• Static pressure (temporarily for cfm commissioning) sensor
• None
Configures CO2 sensor type. Dynamic item: Appears only if “CO2” is selected for “6AUX-AI1”.
Configures the low limit of CO2 measuring range. Dynamic item: Appears only if “CO2” is selected for “6AUX-AI1”.
Configures the high limit of CO2 measuring range. Dynamic item: Appears only if “CO2” is selected for “6AUX-AI1”.
Choose ACT FB if feedback signal is available from the connected damper actuator. Otherwise, choose NONE.
T-STAT
ALWAYS
NONE HP(O) HP(B)
PREOCC
SHUTDWN
NONE
W1 HP(O) HP(B)
PREOCC
SHUTDWN
0-10V
NTC10K
0-10V
NTC10K
NONE
4-20mA
NONE
0-10V
NTC10K
PRESSURE
CO2
NONE
0-10V 2-10V
0-5V
0...500; increment by 10 0
1000...3000;
increment by 50
ACT FB
NONE
T-STAT
NONE
NTC10K
NONE
NONE
NTC10K
NONE
0-10V
2000
ACT FB
W1
45
Page 46
NOTE(S):
Table 22 — Parameter Settings — I/O Configurations (cont)
PARAMETER DESCRIPTION VALUE DEFAULT
6Y2O
6AUX1-O
6AUX2-O
6RS485 Switch between MSTP and Modbus.
Choose “COOL 2” if Cooling Stage 2 is available (another compressor is connected to the Economizer). Otherwise, choose “NONE”.
Auxiliary DO-1. Configurable as:
• None.
• Exhaust fan (1 or 2).
• Alarm output to thermostat (Title 24). Auxiliary DO-2. Configurable as:
• None.
• Exhaust fan (1 or 2).
• Alarm output to thermostat (Title 24). NOTE: Except for Exhaust Fan, whichever is chosen for 6AUX1-O does not appear in the list of 6AUX2-O.
COOL 2
NONE
NONE
ALARM
EXHAUST
NONE
ALARM
EXHAUST
MSTP
MODBUSSLV
COOL 2
EXHAUST
ALARM
MSTP
Table 23 — Alarm Parameters
PARAMETER DESCRIPTION
NO ALARM No alarm is activated. 4MAT SEN ALARM MAT sensor has failed, gone out of range, or become disconnected. 4CO2 SEN ALARM CO 4OAT SEN ALARM OAT sensor has failed, gone out of range, or become disconnected. 4OAH SEN ALARM OAH sensor has failed, gone out of range, or become disconnected. 4RAT SEN ALARM RAT sensor has failed, gone out of range, or become disconnected. 4RAH SEN ALARM RAH sensor has failed, gone out of range, or become disconnected. 4FREEZE ALARM Anti-freeze notification when MAT sensor is below anti-freeze protection setpoint. 4RTU SHUTDOWN Notification of Shutdown Active when SHUTDWN is chosen for 6AUX1-I or 6AUX2-I. 4ACTUATOR ALARM Actuator gets disconnected or has failed. 4ACT UNDER V Voltage received by the actuator is below expected range. 4ACT OVER V Voltage received by the actuator is above expected range. 4ACT STALLED Damper actuator stopped before achieving commanded position. 4ACT SLIPPING Damper actuator slips after reaching commanded position. 4NOT ECON Not economizing when it should. 4ECON SHOULDNT Economizing when it should not. 4EXCESS OA Excess outdoor air. Outside air intake is significantly higher than it should be. 4LLA ALARM Leaving air temperature is lower than the low limit (3LAT LOW). 4HLA ALARM Leaving air temperature is higher than the high limit (3LAT HIGH).
a All alarms are dynamic items. An alarm appears only if a related symptom mentioned above is detected. b An alarm activation triggers a general alarm and then the configured system alarm output (AUX1-O or AUX2-O) is activated. If there is no alarm, then NO ALARM is
displayed on the HMI.
sensor has failed, gone out of range, or become disconnected.
2
a,b
Table 24 — Test Commands
PARAMETER DESCRIPTION
7DAMPER MIN POS Press Enter to test whether the economizer controller can drive damper to minimum position. 7DAMPER CLOSE Press Enter to test whether the economizer controller can drive damper to 100% Closed. 7DAMPER OPEN Press Enter to test whether the economizer controller can drive damper to 100% Open. 7DAMPER ALL Press Enter to perform all the above tests. 7DAMPER Press Enter to test whether the economizer controller can drive damper to the selected voltage. 7Y1O Press Enter to test whether the economizer controller can turn on or off the first stage of cooling (close or open relay Y1O).
7Y2O
7AUX1-O Press Enter to test AUX1-O connection (close or open relay AUX1-O). 7AUX2-O Press Enter to test AUX2-O connection (close or open relay AUX2-O).
Press Enter to test whether the economizer controller can turn on or off the second stage of cooling (close or open relay Y2O).
46
Page 47
Table 25 — Enter Running State
PARAMETER DESCRIPTION
8RUN STATE Change to Running State. Press Enter to confirm the change. 8ENTER RUN? Confirm the change to Running State.
8FACTORY DEF
8DEF CONFIRM? Confirm the factory resetting. 8ACT CNT RESET Damper count reset. 8VER x.x.x Firmware version information such as 0.1.10.
Perform factory reset. Press Enter to confirm the reset. (This action resets the controller password to default: OneBT.)
Table 26 — Enter Configuration State and Restart
PARAMETER DESCRIPTION
5CONFIG STATE Change to Configuration State. Press Enter to confirm the change. 5ENTER CONFIG? Confirm the change to Configuration State. 5RESTART Restart the economizer controller. Press Enter to confirm the restart. 5CONF RESTART Confirm the restart.

INSTALLING OPTIONAL 1196582 SINGLE OUTSIDE AIR ENTHALPY SENSOR

When using the 1196582 enthalpy sensor (see Fig. 63) for outside air changeover, the existing 1193547 dry bulb sen­sor (see Fig. 64) must be removed. The enthalpy sensor will be mounted in the same location as the dry bulb sensor (see Fig. 65). When the enthalpy sensor’s OA (Outside Air) temperature, enthalpy, and dew point are below their re­spective setpoints, the outside air can be used for free cool­ing. When any of these are above the setpoint, free cooling will not be available. Enthalpy setpoints are configurable and create an enthalpy boundary according to the user’s in­put. For additional details, see Fig. 66-67 and Table 27.
Harness 1201876 is required to be connected between the EconomizerONE harness in the return air chamber. Har­ness 1201876 has a 5-pin plug that connects directly to the 1196582 enthalpy sensor.
Enthalpy Control Sensor Configuration
The optional enthalpy control sensor (P/N: 1196582) com­municates with the POL224 economizer controller using the 5-wire harness, 1201876. The 1196582 sensor can be used as a single outside air enthalpy, a differential return enthal­py, or a differential return temperature sensor. Refer to the base unit control wiring diagrams found earlier in this book to wire the 1196582 enthalpy sensor for each option. Use Fig. 63 and Table 29 on page 50 to locate the wiring termi­nals for each enthalpy control sensor.
47
Page 48
Fig. 63 — 1196582 Dimensional, Connection and Switching Information
Actuator
HH79NZ039 Outside Air Temperature Sensor
Outside Air Damper
Wiring Harness
16
16
16
15
15
14
14
10
7
8
9
6
5
4
3
13
12
11
2
1
Fig. 64 — 1193547 Dry Bulb and Mixed Air Sensor Wiring
Fig. 65 — EconomizerONE Component Locations
(CRECOMZR108A00 Shown)
Fig. 66 — California Title 24 Zones
48
Page 49
NOTE(S):
U.S. and Canada I-Codes / ASHRAE Zones
Climate Zone 1 Climate Zone 2 Climate Zone 3 Climate Zone 4 (Except Marine)
Climate Zone 5 and Marine Climate Zone 6 Climate Zone 7 and 8
Fig. 67 — U.S. and Canada Climate Zones
Table 27 — Enthalpy Manual Entry Setpoints for EconomizerONE Per Climate Zone
CLIMATE ZONES
a
2 TEMP OFF
1 65°F 22 Btu/lbm 43% 28 Btu/lbm 86% 83°F 33 Btu/lbm 48% 2 65°F 22 Btu/lbm 43% 28 Btu/lbm 86% 83°F 33 Btu/lbm 48% 3 65°F 22 Btu/lbm 43% 28 Btu/lbm 86% 83°F 33 Btu/lbm 48% 4 65°F 22 Btu/lbm 43% 28 Btu/lbm 86% 83°F 33 Btu/lbm 48% 5 70°F 22 Btu/lbm 28% 28 Btu/lbm 65% 83°F 33 Btu/lbm 48% 6 70°F 22 Btu/lbm 28% 28 Btu/lbm 65% 83°F 33 Btu/lbm 48%
7 and 8 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48%
CALIFORNIA
TITLE 24 ZONES
2 TEMP OFF
b
1 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48% 2 73°F 22 Btu/lbm 22% 28 Btu/lbm 55% 83°F 33 Btu/lbm 48% 3 75°F 22 Btu/lbm 19% 28 Btu/lbm 55% 83°F 33 Btu/lbm 48% 4 73°F 22 Btu/lbm 22% 28 Btu/lbm 55% 83°F 33 Btu/lbm 48% 5 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48% 6 71°F 22 Btu/lbm 28% 28 Btu/lbm 62% 83°F 33 Btu/lbm 48% 7 69°F 22 Btu/lbm 32% 28 Btu/lbm 68% 83°F 33 Btu/lbm 48% 8 71°F 22 Btu/lbm 28% 28 Btu/lbm 62% 83°F 33 Btu/lbm 48%
9 71°F 22 Btu/lbm 28% 28 Btu/lbm 62% 83°F 33 Btu/lbm 48% 10 73°F 22 Btu/lbm 22% 28 Btu/lbm 55% 83°F 33 Btu/lbm 48% 11 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48% 12 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48% 13 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48% 14 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48% 15 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48% 16 75°F 22 Btu/lbm 19% 28 Btu/lbm 50% 83°F 33 Btu/lbm 48%
CONTROLLER
DEFAULT SETTINGS
DEFAULT
SET POINTS
2 TEMP OFF 2 ENTH OFF 2THL 2EHL RH%
63°F 28 Btu/lbm 94% 83°F 33 Btu/lbm 48%
LOWEST
SETTING
LOWEST
SETTING
RH% 2 ENTH OFF RH% 2THL 2EHL RH%
RH% 2 ENTH OFF RH% 2THL 2EHL RH%
a See Fig. 67 for map of U.S. and Canada climate zones. b See Fig. 66 for map of California Title 24 zones.
49
Page 50
Economizers are shipped standard with an 1193547 outside
NOTE(S):
air dry bulb sensor (see Fig. 64). System default setting (high temp limit) is 63°F (17°C) and has a range of 48°F to 80°F (9°C to 27°C). Sensor is factory installed on economizer.
NOTE: A second 1193547 sensor is provided for mixed air temperature.
NOTE: California high temperature setting requirements by region are shown in Table 28.
Enthalpy Settings (Enthalpy Option) If installing the optional 1196582 enthalpy sensor, the
1193547 dry bulb outside air sensor must first be removed. Wire sensor to harness 1201876 and the (5) wires from the harness to the EconomizerONE harness in the return air chamber. Harness 1201876 has a 5-pin plug that connects directly to the 1196582 enthalpy sensor. Refer to the base unit control wiring diagrams earlier in this book for wiring connections. Refer to Fig. 63 and Table 29.
California’s Title 24 High Temperature Limit Settings
California’s Title 24 code requires a high temperature lim­it setting for all dry bulb outside air economizer change­over. The temperatures vary by the region within Califor­nia. See Table 28 for high limit settings.
Table 28 — California Title 24 Regional High Limit
Dry Bulb Temperature Settings
CLIMATE
DEVICE TYPE
FIXED DRY
BULB
DIFFERENTIAL
DRY BULB
FIXED
ENTHALPY
+ FIXED DRY
BULB
a This table sourced from 2019 California Energy Code, Title 24, Part 6, Table
140.4-E Air Economizer High Limit Shut Off Control Requirements.
b Only the high limit control devices listed are allowed to be used and at the set
points listed. Others such as Dew Point, Fixed Enthalpy, Electronic Enthalpy, and Differential Enthalpy Controls, may not be used in any climate zone for compliance with Section 140.4(e)1 unless approval for use is provided by the Energy Commission Executive Director.
c At altitudes substantially different than sea level, the Fixed Enthalpy limit value
shall be set to the enthalpy value at 75°F and 50% relative humidity. As an ex­ample, at approximately 6,000 foot elevation, the fixed enthalpy limit is approx­imately 30.7 Btu/lb.
b
ZONES
1, 3, 5, 11-16 OAT exceeds 75°F (23.8°C)
2, 4, 10 OAT exceeds 73°F (22.7°C)
6, 8, 9 OAT exceeds 71°F (21.6°C)
7 OAT exceeds 69°F (20.5°C)
1, 3, 5, 11-16
2, 4, 10
6, 8, 9
7
c
All
REQUIRED HIGH LIMIT
(ECONOMIZER OFF WHEN):
DESCRIPTION
OAT exceeds
RA temperature
OAT exceeds return air temperature
OAT exceeds return air temperature
OAT exceeds return air temperature
OAT exceeds 28 Btu/lb of dry airb or
–2°F (–18.8°C)
–4°F (–20°C)
–6°F (–21.1°C)
OAT exceeds 75°F (23.8°C)
a
LEGEND
OAT Outdoor-air Thermostat RA Return Air
Table 29 — 1196582 Sensor Wiring Terminations
TERMINAL
NUMBER LABEL
1 TCOM NTC 10k Outside Air Temperature Sensor Output 2 TSIG NTC 10k Outside Air Temperature Sensor Output 3 HSIG 0-10 vdc Outside Air Relative Humidity Sensor Output 4 HCOM COMMON Sensor 24-v Common Input 5 H24V 24 vac Sensor 24-v Operating Voltage Input
TYPE DESCRIPTION
50
Page 51
CHECKOUT Inspect all wiring connections at the economizer module’s
terminals, and verify compliance with the installation wiring diagrams. For checkout, review the Status of each config­ured parameter and perform the Test Commands tests (re­fer to Table 24).
For information about menu navigation and use of the key­pad see Interface Overview on page 32.
WARNING
ELECTRIC SHOCK HAZARD Failure to follow this warning could result in personal
injury, property damage, or death. Before performing service or maintenance operations on
unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
If any wiring changes are required, first be sure to remove power from the economizer module before starting work. Pay particular attention to verifying the power connection (24 vac).
Power Up
After the POL224 module is mounted and wired, apply power.
Initial Menu Display On initial start up, “Welcome” displays on the economizer
HMI screen. After a brief pause, the Parameter Settings — I/O Configuration (refer to Table 22) of the software ap­pears, allowing the user to check that presets and default values are configured correctly.
Power Loss (Outage or Brownout)
All set points and advanced settings are restored after any power loss or interruption.
NOTE: All settings are stored in non-volatile flash memory.
Status
Use the Status menu (refer to Table 19) to check the param­eter values for the various devices and sensors configured.
NOTE: For information about menu navigation and use of the keypad, see Interface Overview on page 32.
Checkout Tests
Use the Test Commands menu (refer to Table 24) to test the damper operation and any configured outputs. Only items that are configured are shown in the Test Commands menu.
NOTE: For information about menu navigation and use of the keypad, see Interface Overview on page 32.
To perform a Test Command test:
1. Scroll to the desired test in Test Command menu 7 using the Up and Down buttons.
2. Press the Enter button to select the item. RUN? appears.
3. Press the Enter button to start the test. The unit pauses and then displays IN PROGRESS. When the test is complete, DONE appears.
4. When all desired parameters have been tested, press Enter + Up to end the test.
The Checkout tests can all be performed at the time of in­stallation or at any time during the operation of the system as a test that the system is operable.
CAUTION
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage. Be sure to allow enough time for compressor start-up
and shutdown between checkout tests so that you do not short-cycle the compressors.
51
Page 52

TROUBLESHOOTING

NOTE(S):
For EconomizerONE troubleshooting issues see Table 30.
Table 30 — Operating Issues and Concerns
SYMPTOM REASON SOLUTION
An alarm is displayed on the LCD
DAC LED is blinking RED Damper slippage Check whether the damper works properly. DAC LED is blinking
RED quickly
DAC LED is OFF
Economizer controller has no alarm, but the Free Cooling LED will not turn on when the OA seems to be suitable for Free Cooling
Economizer controller/mechanical cooling is not operating
Firmware update failure
Free Cooling LED is solid RED
Free Cooling LED is blinking RED
Incorrect controller password error on mobile application
RS485 communication failure
Sensor LED is blinking RED Excess outdoor air Check the whole economizer working system, such as the sensor, damper, and thermostat.
Sensor LED is solid RED
Sensor LED is OFF CO
Sensor LED is YELLOW Humidity sensor error
Wi-Fi connection failure
Sensor, damper, or the whole working system may not work properly
Damper unplugged Check whether the damper is connected.
Terminal ACT-FB is configured but there is no available feedback signal
Shutoff SP setting error
OA temp is too low
OA temp is too high or too humid
No input power
Brownout
Y1/Y2 signal is missing from the thermostat
24 vac~ and 24 vac are incorrectly wired
Application file is damaged, operation is incorrect, and/or USB flash disk does not work properly
Sensor, damper, or whole working system may not work properly
Not economizing when it should Check the whole economizer working system, such as the sensor, damper, and thermostat.
and single enthalpy (control
For CO
2
mode 3) configurations from the factory, the password has changed
RS485 signal or configuration error
Mixed Air (MA) sensor error Check the MA sensor. It must be either a Type II NTC 10K or 0-10 vdc sensor.
Outside Air (OA)/Return Air (RA) sensor error
Air temperature failure/fault
sensor error
2
Wi-Fi/WLAN stick error or wrong user name and password
Check sensor, damper, or the whole working system following the detailed alarm information.
Check whether the feedback signal is connected; check if ACT-FB is faulty.
Shutoff temperature and/or enthalpy set point is incorrectly set up. Consult an HVAC professional to set up the shutoff set point correctly.
The OA temperature is too low; therefore, there is no cooling demand. This could possibly enable anti-freeze protection.
In DIFF mode, even though OA temperature is lower than RA temperature, if both OA and RA temperatures exceed the high limit, then Free Cooling turns off. In Differential Enthalpy control mode, even though OA enthalpy is lower than RA enthalpy, if both OA and RA enthalpy exceed the high limit, then Free Cooling turns off.
Use a multi-meter to check whether there is 24 vac ± 25% (18-30 vac) at the POWER terminals. If there is no voltage or if the voltage is significantly low, then check the transformer output voltage at the RTU. If 24-v is not present at the transformer secondary side, then check the primary line voltage to the transformer. If the line voltage is not present at the transformer primary side, then check the primary power to the RTU, fuses, circuit breaker, and so on.
If voltage is below 17-v, then the economizer controller may be in Brownout Protection mode. This mode disables all of the relay outputs. When the power is 19 vac or higher, the economizer controller and RTU operate normally.
Mechanical cooling does not run until there is cooling demand (Y1/Y2 Active). Check the wiring from Y1I and Y2I terminals to the commercial thermostat. 24-v should be present between Y1I/Y2I and Y1O/Y2O respectively.
24 vac power supply has polarity when all devices are powered by the same 24 vac transformer; reversing polarity may cause a short circuit that can damage the system. Follow the transformer polarity mark, check the wiring of 24-v~ (or G or 24-v+), and ensure that they are tied to the same polar of 24 vac power supply; while checking the wiring of ⊥ (or G0 or 24-v- or COM), ensure that they are all tied to another polar of 24 vac power supply.
a
Reload a BIN file, restart the controller, update firmware service provider if failure still exists.
Check sensor, damper, or the whole working system following the detailed alarm information.
For units coming from the factory with CO use the controller password OneBT2.1. For all other units, use the controller password OneBT. Performing a factory reset on the controller will also reset the password to OneBT.
Check wiring, configuration, Baud Rate (using mobile application), and other network communication parameters.
Check the wiring and signal of the OA sensor. If in Differential (DIFF) mode, also check the RA sensor. The following sensor signals are valid: Type II NTC 10K or 0-10 vdc temperature. 0-10 vdc or 4-20 mA humidity.
Check the air temperature sensor signal. The valid signal must be Type II NTC 10K or 0-10 vdc.
Check CO type.
Check humidity sensor connection, sensor signal (under range or over range), and sensor signal type.
Unplug and re-plug in the Wi-Fi/WLAN stick, enter a correct user name and password, restart the controller, or replace the Wi-Fi/WLAN stick. If the Wi-Fi/WLAN stick is POL903.00/100, then the default user name and password are Siemens-WLAN-Stick and SIBPAdmin. DNS name is siemens.wlanstick. Contact Application Engineering for information on this accessory.
sensor connection, sensor signal (under range or over range), and sensor signal
2
configuration or single enthalpy (control mode 3),
2
, or change a USB flash disk. Contact
a Back up configurations before firmware update. All the previous configuration data is erased after firmware update. Contact Application Engineering for more information
on support for firmware. IMPORTANT: If the controller enters the configuration state for the convenience of I/O configurations, then users can manually switch to the running state after finishing configurations. To do so, press Enter + Up at the same time, then press Enter to confirm the switch after 8RUN STATE appears on the LCD.
52
Page 53

Controller Options

Return Air Smoke Detector (As Shipped)
Step 1 Step 2 Step 3
LOW AMBIENT If the unit comes with electromechanical (EM) controls, then
no adjustment is necessary.

Smoke Detectors

Smoke detectors are available as factory-installed options on RGV models. Smoke detectors may be specified for supply air only, for return air without or with economizer, or in combination of supply air and return air. Return-air smoke detectors are arranged for vertical return configurations on­ly. All components necessary for operation are factory­provided and mounted. The unit is factory-configured for im­mediate smoke detector shutdown operation; additional wir­ing or modifications to unit terminal board may be necessary to complete the unit and smoke detector configu­ration to meet project requirements.
Units equipped with factory-optional return-air smoke detec­tors require a relocation of the sensor module at unit installation. See Fig. 68 for the as-shipped location.
Completing Return Air Smoke Sensor Installation
1. Unscrew the 2 screws holding the return air smoke detector assembly. See Fig. 69, Step 1. Save the screws.
2. Turn the assembly 90 degrees and then rotate end to end. Make sure that the elbow fitting is pointing down. See Fig. 69, Step 2.
3. Screw the sensor and detector plate into its operating position using screws from Step 1. See Fig. 69, Step 3.
4. Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.
Additional Application Data
Refer to the application data document “Factory Installed Smoke Detectors for Small and Medium Rooftop Units 2 to 25 Tons” for discussions on additional control features of these smoke detectors including multiple unit coordination.
Fig. 68 — Return Air Smoke Detector,
Shipping Position
Fig. 69 — Completing Installation of Return Air Smoke Sensor
53
Page 54

Step 14 — Adjust Factory-Installed Options

SMOKE DETECTORS Smoke detector(s) will be connected at the Unit Control
Board (UCB), at terminals marked “Smoke Shutdown.” De­tach the jumper covering the Smoke Shutdown terminals on the UCB and then attach the wiring harness from the smoke detector.
ECONOMIZERONE OCCUPANCY SWITCH External occupancy control is managed through a connec-
tion on the Unit Control Board. If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OC­CUPANCY. Detach the jumper covering the “Occupancy” terminals on the UCB and then attach the required connections.

Step 15 — Install Accessories

Available accessories include:
•Roof curb
Thru-base connection kit (must be installed before unit is set on roof curb)
LP conversion kit
Flue discharge deflector
Manual outside air damper
Two-position motorized outside air damper
EconomizerONE (with POL224 controller)
Power Exhaust
Differential dry-bulb sensor (EconomizerONE)
Outdoor enthalpy sensor
Differential enthalpy sensor
•CO
Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information on installing these accessories.
sensor
2
54
Page 55

Step 16 — Fan Speed Set Up

Fan Speed Set Up Controls
Fan Speed Set Up Controls
Switch 1
5-Pin DIP
UNITS WITH ELECTROMECHANICAL CONTROLS The fan speed set up controls are located on the lower sec-
tion of the Unit Control Board (UCB). See Fig. 70 for the lo­cation on 3-phase voltage units or Fig. 71 for the location on single phase voltage units.
1. Check the job specifications for the cfm (cubic feet per minute) and ESP (external static pressure) required.
2. Using the chart on the Fan Speed Set Up labels (see Fig. 73), calculate the vdc from the cfm and ESP for the base unit. Then add vdc for any accessories installed per the “Field Accessories” section of the label.
NOTE: The Fan Speed Set Up labels are located on the High Voltage cover in the Control Box.
3. Connect a multimeter to the vdc terminals on the UCB.
4. Set the Range Switch to either A, B, or C per the Switch Range table.
5. Using a straight blade screwdriver, turn the vdc con­trol dial to fine tune the vdc reading.
6. Record the reading in the Field Setting field.
NOTE: Fan set-up vdc is not affected by the operating stage of the unit.
Fig. 71 — UCB Fan Speed Controls —
Single Phase Units
NOTE: On single phase units, the approximate static pressure of the ductwork must be set for optimal unit effi­ciency. The unit is factory set for greater than 1.0 in. wg. If the external static pressure is less than 1.0 in. wg, slide switch 1 on the 5-pin DIP to the “ON” position. See Fig. 72.
Fig. 72 — Detail — 5-Pin DIP Switch
Fig. 70 — UCB Fan Speed Controls — 3-Phase Units
55
Page 56
VDC Calculator
NOTE: Values in the Field Accessories section are vdc adders.
1500 1625 1750 1875 2000
CFM
2125 2250 2375
UNIT MODEL NUMBER
2500
Field Accessories:
Fig. 73 — Example of Fan Speed Set Up Labels for Electromechanical Controls
0.2
6.0
6.3
6.7
7.1
7.5
7.9
8.3
8.7
9.1
0.1
0.4
6.7
7.1
7.4
7.7
8.1
8.4
8.8
9.2
9.5
0.1
0.6
7.4
7.7
8.0
8.3
8.7
9.0
9.4
9.7
0.1
ESP in. wg
0.8
8.0
8.3
8.6
8.9
9.2
9.5
9.9
0.1
1.0
8.5
8.8
9.1
9.4
9.7
0.1
1.2
9.0
9.3
9.5
9.8
0.1
1.4
9.5
9.7
10.0
0.1
1.6 1.8 2.0
9.9
0.1Economizer
Factory Setting:
9.0 V
DC
Field Setting:
Record field setting here
V
Switch Range:
B
A
A
4.1 - 7.5
6.9 - 8.7
B
7.7 - 10.0
C
* Overlap in A, B, C switch range designed for maximum field adjustment potential. For example
7.2 can be set at either A or B.
*
C
56
Page 57
Page 58
© 2024 Carrier
Form No. RGV-036-072-02SI Rev. B Pg 58 3-24 Replaces: RGV-036-072-01SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 59
START-UP CHECKLIST FOR RGV036-072 SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNIT
(Remove and use for job file)
NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this document.
I. PRELIMINARY INFORMATION
MODEL NO. _____________________________________________ JOB NAME ______________________________________________ SERIAL NO. _____________________________________________ ADDRESS _______________________________________________ START-UP DATE ________________________________________ TECHNICIAN NAME _____________________________________ ADDITIONAL ACCESSORIES _____________________________________________________________________________________________________
II. PRE-START-UP
Verify that all packaging materials have been removed from unit. (Y/N) _____ Verify installation of outdoor air hood. (Y/N) _____ Verify installation of flue exhaust and inlet hood. (Y/N) _____ Verify that condensate connection is installed per instructions. (Y/N) _____ Verify that all electrical connections and terminals are tight. (Y/N) _____ Verify ground integrity with a continuity test. (Y/N) _____ Verify gas pressure to unit gas valve is within specified range. (Y/N) _____ Check gas piping for leaks. (Y/N) _____ Check that indoor-air filters are clean and in place. (Y/N) _____ Check that outdoor air inlet screens are in place. (Y/N) _____ Verify that unit is level. (Y/N) _____ Verify that fan assembly is free of obstructions and rotor spins freely. (Y/N) _____ Verify that scroll compressors are rotating in the correct direction. (Y/N) _____ Verify installation of thermostat. (Y/N) _____ Verify that crankcase heaters have been energized for at least 24 hours. (Y/N) _____
III. START-UP
ELECTRICAL
Supply Voltage L1-L2_____________ L2-L3_____________ L3-L1_____________ Compressor Amps 1 L1 _____________ L2 _____________ L3 _____________ Compressor Amps 2 L1 _____________ L2 _____________ L3 _____________ Supply Fan Amps L1 _____________ L2 _____________ L3 _____________
TEMPERATURES
Outdoor-Air Temperature _____________ °F DB (Dry Bulb) Return-Air Temperature _____________ °F DB _____________ °F WB (Wet Bulb) Cooling Supply Air Temperature _____________ °F Gas Heat Supply Air _____________ °F
Form No. RGV-036-072-02SI Rev. B Pg CL-1 3-24 Replaces: RGV-036-072-01SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 60
PRESSURES
Gas Inlet Pressure in. wg _____________ in. wg Gas Manifold Pressure STAGE 1 _____________ in. wg
STAGE 2 _____________ in. wg Refrigerant Suction _____________ PSIG Refrigerant Discharge _____________ PSIG Verify Refrigerant Charge using Charging Charts. (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped). (Y/N) _____ Verify smoke detector unit shutdown by utilizing magnet test. (Y/N) _____ Verify outdoor fan operation. On units with head pressure controls, verify outdoor fan ramps up. (Y/N) _____
IV. HOT GAS RE-HEAT SYSTEM START-UP
STEPS
1. Check UCB (Unit Control Board) for jumper 1, 2, 3 (Jumper 1, 2, 3 must be cut and open). (Y/N) _____
2. Open humidistat contacts. (Y/N) _____
3. Start unit In cooling (Close Y1). (Y/N) _____
OBSERVE AND RECORD
a. Suction pressure ______________ PSIG b. Discharge pressure ______________ PSIG c. Entering air temperature ______________ °F d. Liquid line temperature at outlet or reheat coil ______________ °F e. Confirm correct rotation for compressor. (Y/N) _____ f. Check for correct ramp-up of outdoor fan motor as condenser coil warms. (Y/N) _____
4. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed. (Y/N) _____
5. Check unit charge per charging chart. (Y/N) _____
OBSERVE
a. Reduction in suction pressure (5 to 7 psi expected). (Y/N) _____ b. Discharge pressure unchanged. (Y/N) _____ c. Liquid temperature drops to 50 to 55°F range. (Y/N) _____ d. LSV solenoid energized (valve closes). (Y/N) _____
6. Switch unit to dehumid (reheat) by opening Y1. (Y/N) _____
OBSERVE
a. Suction pressure increases to normal cooling level. (Y/N) _____ b. Discharge pressure decreases (35 to 50 psi). (Limited by head pressure control.) (Y/N) _____ c. Liquid temperature returns to normal cooling level. (Y/N) _____ d. LSV solenoid energized (valve closes). (Y/N) _____ e. DSV solenoid energized, valve opens. (Y/N) _____
7. With unit in dehumid mode, close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized. (Y/N) _____
8. Open W1 restore unit to dehumid mode. (Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized. (Y/N) _____
10. Restore set points for thermostat and humidistat. (Y/N) _____
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
© 2024 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Form No. RGV-036-072-02SI Rev. B Pg CL-2 3-24 Replaces: RGV-036-072-01SI
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...