ICP PYPA60HA2, PYPA60HA1, PYPA48HA2, PYPA48HA1, PYPA48GA1 Owner’s Manual

...
Installation Instructions
I DIRECT DRIVE BLOWER
PH55/PYPA SERIES
THREE PHASE
SINGLE PACKAGE HEAT
_) PUMPS
ELECTRIC HEAT c
(OPTIONAL)
1, SAFETYLABELINGANDSIGNALWORDS .................... 2
2. UNITDIMENSIONS ...................................... 2
3, SAFEINSTALLATIONREQUIREMENTS....................... 2
4. LOCATINGTHE UNIT .................................... 2
5, UNITELECTRICALWIRING................................ 4
6. ELECTRICHEATINSTALLATIONGENERALINFORMATION....... 6
7.AIR DISTRIBUTIONSYSTEM .............................. 8
8. START-UPPROCEDURES................................ 8
9. SEQUENCEOFOPERATION ............................. 10
Printed in U.S.A. LP-1 10/15/01 427 01 1005 00
1. Safety Labeling and Signal Words
Danger, Warning and Caution
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING and CAUTION wil! be used on product labels
and throughout this manual and other manuals that may apply to the product.
2. Dimensions
NOTE: DUCTCOLLARSATTACHEDTOSUPPLYANDRETURNMUSTBEREVERSEDATINSTALLATION.SEEINSTRUCTIONSONPAGE3.
ALL DIMENSIONS IN INCHES
ROUND FLANGE
WILL 3/8 DIA HOLE** ACCOMMODATE
14" DIA. RETURN DUCT
m___
10
1/4 DIA.* 1/4 DIA.*
9
261/2
COIL
ACCESS
PANEL
PRESSURE
3 11/2
26 s/4
PORTS
* ELECTRICAL ACCESS FOR LINE VOLTAGE POWER SUPPLY-ONE FOR UNIT, ONE FOR HEATER ** FOR LOW VOLTAGE WIRING
51 \
CONDENSATE DRAIN
41
CONNECTION
3. Safe Installation Requirements 4. Locating The Unit
The unit is designed for outdoor installation only. Place the unit on a platform at ground level. The unit may be installed on a concrete
slab of 48" (1219mm) x 48" (1219mm) dimensions. Cement
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of
local codes, with the National Electrical Code NFPA70-1990 or current edition.
The information contained in this manual is intended for use by a qualified service technician familiar with
safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in unit malfunction, property damage, personal injury and/or death.
Seal supply and return air ducts.
Check to see that filters are installed correctly and are the proper type and size.
NOTE: It is the personal responsibility and obligation of the cus-
tomer to contact aqualified installer to ensure that the installation
is adequate and conforms to governing codes and ordinances.
CAUTION
Do NOT operate unit in a corrosive atmosphere containing
chlorine, fluorine, or any other corrosive chemicals.
blocks on a 3" sand footing will also work. The slab or blocks SHOULD NOT be in contact with any part of the structure. Check
local codes covering zoning, noise, platforms, etc..
If practical avoid locating next to fresh air intakes, vent or bed-
room windows. Noise may carry into the openings and disturb people inside.
Avoid installations under roof overhangs without guttering. Water draining from the roof onto the unit could produce excessive
noise, and may cause ice to build up on coil or fan.
Placement of the unit should be in a well drained area or the unit
MUST be supported high enough so runoff will not enter the unit.
Do not locate unit where heat, lint or exhaust fumes wil! be dis-
charged on unit (as from dryer vents.)
Clearances
Minimum clearances, as specified in FIGURE 1, MUST be main- tained from adjacent structures to provide adequate air circula-
tion and room for service personnel. While minimum clearances are acceptable for safety reasons,
they may not allow adequate air circulation around the unit for proper operation. Whenever possible, itis desirable to allow addi- tional clearance, especially around the condenser inlet and dis-
charge openings.
Do NOT install the unit in a recessed orconfined area that will per-
mit discharged air from the condenser to recirculate to the con- denser inlet.
2
_1 1/2
ROUND SHAPED FLANGE WILL ACCOMMODATE 12" DiA SUPPLY DUCT
427 01 1005 00
Minimum Clearances to Combustible Construction
SERVICE ACCESS CLEARANCES
Blower Access Panel Side ................... 30" (762mm)
Electrical Access Panel Side ................. 30" (762mm)
OPERATIONAL CLEARANCES Combustible Base
(Wood or Class A, B or C
roof covering material) .................... 0"
Supply and Return Air Ducts ........................... 0"
Duct Connection Side
....................................... 0 _
Clearance between Overhang
and Top of Unit ............... 48" (1219mm)
Clearance around Condenser Coil area to wall or shrubs . 10"
FIGURE Minimum Clearances and Access Panels
Overhang
Evaporator 48" Minimum Overhang Clearance
Access Panel
10"around
b( condenser
coil area
Installing Duct Collars
Duct collars are supplied with the unit and are attached to the sup-
ply and return openings with the flanges to the inside and must be reversed before unit's installation.
1. Remove the screws from the collars and reverse them so the flange is to the outside.
Blower/Electrical Access Panel
Cover Plate
Installation
CAUTION
The unit must be installed with a slope no greater than 1/8" per foot (lOmm per meter). For side to side leveling, the con- densate drain side side MUST always be lower.
The unit MUST be situated in such away as to provide safe access for servicing.
The platform may be made of either concrete or pressure treated wood and MUST be level and strong enough to support the unit's weight.
Position platform separate from the building's foundation. Install in a well-drained area, with the top surface of the
platform above grade level and above the average winter
snow levels to prevent coi! blockage.
Platform MUST be high enough to allow for proper conden-
sate drainage.
2. Make sure when pushing the collars into place that the "V" flange of the collars seats into the supply and return holes securely.
3. Re-install screw in each collar so it goes through both of the
holes in the collar end. It does not matter how the ends of
the collar overlap in order to accomplish this.
FIGURE 3 I Duct Collar Installation
427 01 1005 O0
3
Condensate Drain
Ground Connections
The condensate drain outlet is a 3/4" (19.1 mm) threaded female
PVC connection located at the bottom of the unit to the left of the
evaporator access panel. The circulating blower and the condenser fan create a negative
pressure on the condensate drain line that will prevent the con- densate from draining properly without a trap. To combat this neg-
ative pressure, a field supplied condensate trap that will allow a standing column of water of at least 2" (50.8mm) MUST be
installed. The outlet of the trap must be at least 1" below the unit
drain connection. Install the trap as near to the unit as possible
for proper drainage.
A 3/4" (19.1 mm) drain line MUST be installed if required by local codes or if location of unit requires it. Run the drain line to an open
drain or other suitable disposal point.
4 I Condensate Drain Information*
3/4" (19,1mm) Threaded Female
PVC Fitting
(25.4mm)
(82.! 2" (50.8rnm)
* Condensate trap MUST be installed.
3/4" (19,1mm)
Drain Line
A ground lug is installed on the control plate (or electric heat mounting plate) for the ground connection. Use a copper conduc-
tor of the appropriate size from the unit to a grounded connection in the electrical service panel orto a properly driven and electrical-
ly grounded ground rod. See warning on this page.
Line Voltage Wiring
Do NOT complete line voltage connections until unit is perma-
nently grounded. All line voltage connections and the ground con- nection MUST be made with copper wire.
Connections for line voltage are made on the unit electrical con- trol plate (see NO TAG). For access, remove the Blower/Electri- cal access panel.
Refer to applicable wiring diagram in this Manual. Complete the
line service connections to the contactor 'L1, L2, L3' terminals on the electrical control plate. Check all screw terminals to ensure
they are tight. NOTE: If an Electric Heat Accessory is installed, refer to the Elec-
tric Heat Accessory section of this manual to determine line volt- age connections. The Electric Heat Accessory mounts inside the unit in the heater box. Field supplied line voltage wires for the
Electric Heat Accessory (separate from the field supplied line
voltage wires to the unit) connect to the appropriate circuit break- er (if used) in the Electric Heat Accessory.
Converting 230V Units to 208V
To convert 230V units to 208V:
1. Turn electric power OFF
5. Unit Electrical Wiring
Electrical shock hazard.
Disconnect power at fuse box or service panel before
making any electrical connections.
Unit MUST be grounded to electrical service panel.
Failure to follow this warning can result in property
damage, personal injury, and/or death.
NOTE: All electrical work MUST conform with the requirements of
local codes and ordinances and inthe United States with National Electrical Code ANSI/NFPA 70-1990 (or current edition). Provide line voltage power supply from a separate fused circuit with a dis-
connect switch (when required) located within sight of the unit. Supply voltage, amperage, fuse and disconnect switch sizes
MUST conform with local codes and ordinances.
Wiring MUST be protected from possible mechanical damage and MUST NOT interfere with removal of access panels, filters,
etc.
All exposed line voltage connections MUST be made through liq- uid tight conduit to prevent water from entering the unit through
the electrical access..
2. Remove the blower/electrical access panel.
3. Locate the 24V control transformer.
4. Remove wire from the terminal labeled "240V" on the 24V control transformer and reconnect it to the 208V terminal of
the 24V control transformer.
5. Replace the blower / electrical access panel.
Low Voltage Wiring
For access, remove the electrical blower / electrical access panel. Refer to the connection wiring diagram for the applicable model
and to the instructions included with the thermostat.
Route low voltage wires through the port located on the rear panel
and up to the control box. NOTE: If an Electric Heat Accessory is installed, see the Electric
Heat Accessory Installation Section of this manual for low voltage
connections.
Thermostat Connections
The location of the thermostat has an important effect on the op- eration of the unit. See the thermostat instructions for proper con-
nection. See NO TAG for Low Voltage Wire Harness Connections
4
427 01 1005 00
Field Installed Equipment
Wiring to be done in the field between the unit and other devices, or between separate devices which are field installed and located,
MUST NOT exceed the temperature limitations for type T wire
and MUST be installed according to the manufacturer's instruc- tions for the devices.
Final Electrical Check
Make a final wiring check to be sure system is correctly wired. In- spect field installed wiring and the routing to ensure that rubbing
or chafing due to vibration will not occur. NOTE: Wiring MUST be installed so it is protected from possible
mechanical damage.
FIGURE 5 J HarnessElectr°niCConnectionTherm°statDiagramL°WVoltage Wi ri ng
ES: * Common maybe "B" or "X" on some T-stats.
-NQT Typical Thermostat Subbase
* "W" may be "W2" on some T-stats.
[,c]*
I I I I
I
I I I I
i I I I I I I I I /
A A A A A
I I I I I
[Blue] [Green] [F_ed][Y_llow] [White]
Com Fan 24V Com- Elect. When outdc)or \ (when Hot pressor Heat thermostat is \
used) Acces. used, route this. I
Unit Low Voltage Wiring Harness.
, (where,used)
W2
I
', [Orange] "_,XX
Reversing
valve
(energized in cooling)
FIGURE 6 J TypicalConnections at Unit
.............................. R ................................................................................. 2_98/23eV 6f_HZ 3PH
,'I BL _ =y--_
............ ;. .................... _ ', LJpR_
,,'L---R ............................ _-, _ _d_bN
I"1 RCOYW
" PACK_OZ iiii ',i i ',_W--(W)_.OSTHE_T
+ (WHEN USED) ; L+:............. _' ', ,, Ly-++-e.{y) EOMPRESSOR
.................... _ _.................... R ........... o=,{R) 24 VAC
BR Cr
! ---+ ............... ' LD ...... .='(D) HEAT/COOL
:................. _ ........ _=,(c)COHNON
FIGURE 7 I Control Box Configuration
Transformer
Defrost Board
Low Volt Wire Entrance
Blower
Sequencer
Condensor Fan
Capacitor
Ground lug_
Opening
Contactor
Control Box
Line Volt Wire Entrance
5
427 01 1005 O0
Loading...
+ 9 hidden pages