ICP NOMF155E19A, NOMF105D12A Owner’s Manual

Save these instructions for future reference.
Printed in Canada
MULTI POSITION
WARM AIR
FURNACE
02/05/22 X40094 Rev. A
445 01 4094 00
1)
SAFETY LABELLING AND SIGNAL WORDS
PART 1
2) SAFE INSTALLATION REQUIREMENTS
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation
MUST conform with codes or, in the absence of local codes, with codes of the country having
jurisdiction.
The information contained in this manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions
in this manual can result in furnace malfunction, property damage, personal injury and/or death.
1.1) Danger, Warning and Caution:
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is
only used in product labels to signify an immediate hazard. The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the product.
1.2) Signal Words:
DANGER - Immediate hazards which WILL result in death or serious injury.
WARNING - Hazards or unsafe practices which COULD result in death or injury.
CAUTION - Hazards or unsafe practices which COULD result in personal injury or product or property damage.
1.3) Signal Words in Manuals:
The signal word WARNING is used throughout this manual in the following manner:
The signal word CAUTION is used throughout this manual in the following manner:
CAUTION
Fire hazard
The furnace must be installed in a level position, never where it will slope to the front.
If the furnace were installed in that position, oil could drain into the furnace vestibule and create a
fire hazard, instead of draining properly into the combustion chamber.
NOTE: It is the personal responsibility and obligation of the customer
to contact a qualified installer to ensure that the installation is adequate and conforms to governing codes and ordinances.
a. This furnace is NOT approved for installation in mobile homes,
trailers or recreation vehicles.
b. You must have a sufficient supply of fresh air for combustion and
ventilation to the area in which the furnace is located,
c, Do NOT use this furnace as a construction heater or to heat a
building that is under construction,
d. Use only the Type of fuel oil approved for this furnace (see
Rating Plate on unit). Overfiring wilt result in failure of heat exchanger and cause dangerous operation.
e, Visually check all oil line joints for signs of wetness, which would
indicate a leak, f, Connect furnace to the chimney, g. The points in Part 2 "Operation" are vital to the proper and safe
operation of the heating system, Take the time to be sure they
are all done. h. Follow the rules of the NFPA Pamphlet No.31 (for USA) and 13-
139 (for Canada) or local codes for locating and installing the oil
storage tank. i. Follow a regular service and maintenance schedule for efficient
and safe operation.
j. Beforeservicing,allowfurnacetocool.Alwaysshutoffelectricity
andfueltofurnacewhenservicing.ThiswilIpreventelectrical shockorburns.
k. Sealsupplyandreturnairducts. I. TheventsystemMUSTbecheckedtodeterminethatitisthe
correcttypeandsize. m. Installcorrectfiltertypeandsize. n. UnitMUST be installed so electrical components are protected
from direct contact with water.
2.1) Safety Rules:
Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
The U.S. Consumer Product Safety Commission recommends
that users of oil-burning appliances install carbon monoxide
detectors. There can be various sources of carbon monoxide in
a building or dwelling. The sources could be gas-fired clothes
dryers, gas cooking stoves, water heaters, furnaces, gas-fired
fireplaces, wood fireplaces, and several other items. Carbon
monoxide can cause serious bodily injury and/or death.
Therefore, to help alert people d potentially dangerous carbon
monoxide levels, you should have carbon monoxide detectors
listed by a nationally recognised agency (e.g. Underwriters
Laboratories or International Approval Services) installed and
maintained in the building or dwelling (see Note).
b.
There can be numerous sources of fire or smoke in a building or
dwelling. Fire or smoke can cause serious bodily injury, death,
and/or property damage. Therefore, in order to alert people of
potentially dangerous fire or smoke, you should have fire and
smoke detectors listed by Underwriters Laboratories installed
and maintained in the building or dwelling (see Note below).
Your unit is equipped with safety devices that may keep it from operating if sensors detect abnormal conditions such as clogged
exhaust flues.
If the structure will be unattended during cold weather you should take these precautions.
a. Turn off main water supply into the structure and drain the water
lines if possible. Open faucets in appropriate areas.
b.
Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Suggest they call a qualified service agency, if required.
2.3) Installation regulation:
All local and national code requirements governing the installation of oil burning equipment, wiring and flue connections MUST be followed. Some of the codes that may be applicable are:
CSA B139 INSTALLATION CODE FOR OIL
BURNING EQUIPMENT
NFPA31 INSTALLATION OF OIL BURNING
ANSI/NFPA90B WARM AIR HEATING AND AIR
ANSI/NFPA 70 NATIONAL ELECTRICAL CODE
CSA C22.2 No3 CANADIAN ELECTRICAL CODE
ANSI/NFPA 211 CHIMNEYS, FIREPLACES, VENTS
EQUIPMENT
CONDITIONING SYSTEMS
AND SOLID FUEL BURNING APPLIANCES
and makes no representations regarding any brand or type of
I NOTE: The manufacturer of your furnace does not test any detectors
detector.
Insure that the area around the combustion air intake
I CAUTION
terminal is free of snow, ice and debris.
2.2) Freezing Temperature and Your
Structure:
Freeze warning.
Turn off water system.
If your unit remains shut offduring cold weather the water pipes could freeze and burst, resulting in
serious water damage.
Only the latest issues of the above codes should be used.
3) LOCATING THE FURNACE
CAUTION
Check carefully your furnace upon delivery for any evidence of damage that may have occurred during
shipping and handling. Any claims for damages or lost parts must be made with the Transport Company.
As this unit may be installed as an upflow, counterflow or horizontal furnace (right or left), it may be located in a basement, on the same level as the area to be heated, suspended, or in a crawlspace. In any case, the unit should always be installed level.
4) VENTING
In a basement, or when installed on the floor (as in a crawlspace), it is recommended that the unit be installed on a concrete pad that is
1" to 2" thick.
When installed in the counterflow position, this furnace must not be installed on combustible flooring, unless the approved sub-base is used (Model # DFB-101). The flue pipe must exit the cabinet through one of the panel opening, then extended up the side of the
furnace. Care must be taken to insure that the clearances from the flue pipe to combustible construction are maintained.
Also, it is recommend to use the flue pipe guard kit (Model # FPG-101 or # FPG102) to insure that a fire hazard
condition does not exist.
When installed in a horizontal position, the furnace may be suspended by using an angle iron frame, as long as the total weight of both the furnace and the frame are allowed for in the support calculations. (Other methods of suspending are acceptable.) When installed in the Horizontal Position, this furnace must not be installed
on combustible flooring, unless the approved sub-base is used (Model # HFB-101).
This furnace is approved for reduced clearances to combustible construction. Therefore, it may be installed in a closet or similar
enclosure.
The required minimum clearances for this furnace in all positions are specified in tables # 3.2 and 3.3.
The furnace should be located as close as possible to the chimney or vent in order to keep vent connections shorts and direct. The furnace should also be located as near as possible to the center of the air distribution system.
Do NOT operate furnace in a corrosive atmosphere containing chlorine, fluorine or any other damaging
I CAUTION
chemicals. Refer to Part 1, section 5.2.
Poison carbon monoxide gas, fire and explosion
hazard.
Read and follow all instructions in this section.
Failure to properly vent this furnace can result in
property damage, personal injury and/or death.
CAUTION
When the furnace (chimney installation) is co-vented with other combustion appliances such as a water
heater, the allowable venting materials (i.e. L-Vent etc.) for use with those appliances should also be
investigated.
Poison carbon monoxide gas hazard
Never install a hand operated damper in the vent
pipe. However, any Underwriters Laboratories listed electrically operated automatic type vent damper may be installed if desired. Be sure to
follow instructions provided with vent damper.
Read and follow all instructions in this section.
Failure to properly vent this furnace or other appliances can result in property damage, personal injury and/or death.
Venting of the furnace should be to the outside and in accordance with local codes or requirements d the local utility.
Electrical shock hazard.
This furnace is not watertight and is not designed for outdoor installation. This furnace shall be
installed in such a manner as to protect the
electrical components from water. Outdoor installation would lead to a hazardous
electrical condition and to premature furnace failure, property damage, bodily injury or death.
OIL FIRED APPLIANCES SHALL BE CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIANCE.
For additional venting information refer to ANSl/NFPA 211 Chimney, Fireplaces, Vents and Solid Fuel Burning Appliances and/or CSA
B139 Installation Code.
This furnace is certified for use with Type '%" vent (maximum flue gas temperature 575°F). The flue pipe clearance knockout in the
front top or side panel should be removed. Install the flue elbow so that it exits the furnace cabinet through that opening.
Pre-instatlation vent system inspection:
Before this furnace is installed, it is highly recommended that any existing vent system be completely inspected.
For any chimney or vent, this should include the following:
a. Inspection for any deterioration in the chimney or vent. If
deterioration is discovered, the chimney must be repaired or the vent must be replaced.
b. Inspection to ascertain that the vent system is clears and free
of obstructions. Any blockage must be cleared before installing this furnace.
¢. Clearing the chimney or vent if previously used for venting a
solid fuel burning appliance or fireplace.
d. Confirming that all unused chimney or vent connections are
properly sealed.
e. Verification that the chimney is properly lined and sized per the
applicable codes, (Refer to list of codes on page 3.)
Masonry Chimney:
This furnace can be vented into an existing masonry chimney. This furnace must not be vented into a chimney servicing a solid fuel- burning appliance. Before venting this furnace into a chimney, the chimney must be checked for deterioration and repaired if necessary. The chimney must be properly lined and sized per local
or national codes.
Poison carbon monoxide gas hazard.
Comply with ANSI/NFPA (in U.S.) or CSA (in Canada) standard for the installation of Oil Burning
Equipment and applicable provision of local building codes to provide combustion and
ventilation air.
Failure to provide adequate combustion and ventilation air can result in personal injury and/or
death.
If the furnace is vented into a common chimney, the chimney must be of sufficient area to accommodate the total flue products of all appliances vented into the chimney.
The following requirements are provided for a safe venting system: a. Ensure that the chimney flue is clear of any dirt or debris.
b. Ensure that the chimney is not servicing an open fireplace. C. Never reduce the pipe size below the outlet size of the furnace.
d. All pipes should be supported using the proper clamps and/or
straps. These supports should be at least every four (4) feet.
e. All horizontal runs of pipe should have at least a 1/4" per foot of
upward slope.
f. All runs d pipe be as short as possible with as few turns as
possible.
g. Seams should be tightly joined and checked for leaks. h. The flue pipe must not extend into the chimney but be flush
with the inside wall.
i. The chimney must extend three (3) feet above the highest point
where it passes through a roof of a building and at least two (2) feet higher than any portion of a building within a horizontal
distance of ten (10) feet. It shall also be extended at lest five (5) feet above the highest connected equipment flue collar.
j. Check local codes for any variance.
Factory Built Chimneys:
May use listed factory built chimneys. Refer to chimney manufacturer's instructions for proper installation.
5.1) General:
Oil furnaces must have an adequate supply of combustion air. It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the
furnace. However, home improvements such as new windows, doors, and weather stripping have dramatically reduced the volume of air leakage into the home.
When this furnace is installed in a closet or enclosure, two (2) ventilation openings are required for combustion air. The openings
should be located about 6" from the top and the bottom of the enclosure at the front of the furnace. Table # ! indicates the
minimum ventilation openings dimensions required.
TABLE # 1
Input Length Height
(MBTUH) (in,) (in,)
75- 105 16 8
120-155 20 10
Home air exhausters are common. Bathroom and kitchen fans, power vented clothes dryers, and water heaters all tend to create a negative pressure in the home. Should this occur, the chimney become less
and Iess effective and can easily downdraft.
4.1) BAROMETRIC DRART CONTROL
The barometric draft control shipped with furnace MUST be used with furnace to ensure proper operation. Instructions for installing control are packed with control.
5) AIR FOR COMBUSTION
Heat recovery ventilation (HRV) systems are gaining in popularity. The HRVs are not designed to supply combustion air. If not properly balanced, a serious negative pressure condition could develop in the
dwelling.
5.2) Contaminated Combustion Air :
Installation in certain areas or types of structures will increase the exposure to chemicals or Halogens which may harm the furnace.
These instances will require that only outside air for combustion.
The following areas or types of structures may contain or have exposure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for
combustion.
a. Commercial building. b. Building with indoor pools. c. Furnaces installed near chemical storage areas.
Exposuretothesesubstances: a. Permanentwavesolutionsforhair.
b. Chlorinatedwaxesandcleaners. c. Chlorinebasedswimmingpoolchemicals. d. Watersofteningchemicals.
e. De-icingsaltsorchemicals. f. Carbontetrachloride.
g. Halogentyperefrigerants. h. Cleaningsolvent(suchasperchloroethylene).
i. Printinginks,paintremovers,varnishes,etc..
j. Hydrochloricacid.
k. Solventcementsandglues. I. Antistaticfabricsoftenersforclothesdryers. m. Masoneryacidwashingmaterials.
6) OIL TANKS AND LINES
Check your local codes for the installation of the tank and accessories.
A manual shut-off valve and an oil filter shall follow sequence from tank to burner. Be sure that the oil line is clean before connecting to the burner. The oil Iine should be protected to eliminate any possible
damage. Installations having the fuel oil tank below the burner level must employ a two pipe fuel supply system with an appropriate fuel pump (more than 8' lift use 2 stage pump and more than 16' an auxiliary pump).
a. Set your voltmeter to line voltage. b. Place one prong on your grounded electric entry box and one
prong on the black wire. c. Read the voltage. d. If the voltage is zero, check the white wire. If Iine voltage shows.
Reverse the 115-volt leads entering the furnace junction box.
FIGURE # 1
BLACK
V C A
o o
\
BLACK
RED
Nozzles:
Follow the pump instructions to determine the size of tubing you need in relation of the lift, or the horizontal distance. At the beginning of each heating season or each year, verify the complete oil distribution system for oil leak.
At the beginning of each heating season or each year, verify the complete oil distribution system for oil leak.
7) BURNER INSTALLATION
I IMPORTANT: Burner must always be installed in the
upright position with the ignition control on top.
Mounting the burner:
a.
The warm air furnace burner mounting plate has a four bolts configuration.
b.
Position the mounting gasket between the mounting flange and the appliance burner mounting plate. Line up the holes in the mounting flange with the studs on the appliance mounting plate
and securely bolt in place.
After the burner is mounted:
a. Remove drawer assembly or air tube combination b. Install nozzle (see specifications)
c. Confirm electrode settings d. Make the electrical connections
e. Complete oil line connections
The burners are provided with the highest capacity USGPH nozzle installed. If another size nozzle, or replacement nozzle is required, use the nozzle spray angle, type and manufacturer recommended in Table #3. Note that all nozzle-marked sizes are based on a pump pressure of 100 psi.
Always select nozzle sizes by working back from the actual desired flow rate at operating pressure, and not by the nozzle marking.
Air and turbulator settings:
Before starting the burner for the first time, adjust the air and turbulator settings to those listed in the Table #3. Once the burner becomes operational, final adjustment will be necessary.
Fuel supply system:
Fuel Specifications
I NOTE: Use No.1 or No.2 Heating Oil (ASTM D396) or in Canada, useNo.! or No.2 Furnace Oil.
Before starting the burner be sure the fuel tank is adequately filled with clean oil.
Do not turn on the burner until you have checked the
I CAUTION
polarity
Checking the polarity:
The oil burners used on the furnaces have solid state control systems which makes them sensitive to the proper connections of the hot and neutral power lines. The controls will be damaged if the two lines are
reversed.
Loading...
+ 14 hidden pages