TABLE OF CONTENTS
Part 1, installation .................... 3
Part 2, operation ..................... 19
Part 3, maintenance ................ 23
Part 4, information ................... 26
Technical specifications ............ 27
Wiring diagram ....................... 34
Parts list................................ 35
OLF
c us
OIL WARM AIR FURNACE
Save these instructions for future reference.
Printed in Canada
2000/11/23 X40030 Rev. i
445 01 4030 05
PART 1
INSTALLATION
I CAUTION I
ii_ii/ii
1) SAFETY LABELLING AND SIGNAL
WORDS
1.1) Danger, Warning and Caution:
The signal words DANGER, WARNING and CAUTION
are used to identify levels of hazard seriousness. The
signal word DANGER is only used in product labels to
signify an immediate hazard. The signal words
WARNING and CAUTION will be used on product
labels and throughout this manual and other manuals
that may apply to the product.
2)
SAFE INSTALLATION
REQUIREMENTS
Installation or repairs made by unqualified
persons can result in hazards to you and
others. Installation MUST conform with
codes or, in the absence of local codes,
with codes of the country having
jurisdiction.
The information contained in this manual
is intended for use by a qualified service
technician familiar with safety procedures
and equipped with the proper tools and
test instruments,
Failure to carefully read and follow all
instructions in this manual can result in
furnace malfunction, property damage,
personal injury and/or death.
1.2) Signal Words:
DANGER - Immediate hazards which WILL result in
death or serious injury.
WARNING - Hazards or unsafe practices which
COULD result in death or injury.
CAUTION - Hazards or unsafe practices which COULD
result in personal injury or product or property damage.
1.3) Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
NOTE: It is the personal responsibility and obligation of
the customer to contact a qualified installer to ensure
that the installation is adequate and conforms to
governing codes and ordinances.
Fire hazard
The furnace must be installed in a level
position, never where it will slope to the
front.
If the furnace were installed in that
position, oil could drain into the furnace
vestibule and create a fire hazard, instead
of draining properly into the combustion
chamber.
3
a. This furnace is NOT approved for installation in
mobile homes, trailers or recreation vehicles.
b. You must have a sufficient supply of fresh air for
combustion and ventilation to the area in which the
furnace is located.
c. Do NOT use this furnace as a construction heater
or to heat a building that is under construction.
d. Use only the Type of fuel oil approved for this
furnace (see Rating Plate on unit). Overfiring will
result in failure of heat exchanger and cause
dangerous operation.
e. Visually check all oil line joints for signs of wetness,
which would indicate a leak.
f. Connect furnace to a side-wall terminal or chimney.
g. The points in Part 2 "Operation" are vital to the
proper and safe operation of the heating system.
Take the time to be sure they are all done.
h. Follow the rules of the NFPA Pamphlet No.31 (for
USA) and B-139 (for Canada) or local codes for
locating and installing the oil storage tank.
i. Follow a regular service and maintenance schedule
for efficient and safe operation.
j. Before servicing, allow furnace to cool. Always shut
off electricity and fuel to furnace when servicing.
This will prevent electrical shock or burns.
k. Seal supply and return air ducts.
I. The vent system MUST be checked to determine
that it is the correct type and size.
m. Install correct filter type and size.
n. Unit MUST be installed so electrical components
are protected from direct contact with water.
2.1) Safety Rules:
potentially dangerous fire or smoke, you should
have fire and smoke detectors listed by
Underwriters Laboratories installed and maintained
in the building or dwelling (see Note below).
NOTE: The manufacturer of your furnace does not test
any detectors and makes no representations regarding
any brand or type of detector.
CAUTION
Insure that the area around the combustion air
intake terminal is free of snow, ice and debris.
CAUTION
The air pressure switch MUST be used when
the furnace is vented by the side-wall.
CAUTION
Do not use any commercially available soot
remover. This furnace has fiber type
refractory combustion chamber. Normal
servicing of this unit does not require
cleanings of the combustion chamber. Use
extreme care if for any reason you have to
work in the area of the combustion chamber.
Your unit is built to provide many years of safe and
dependable service providing it is properly installed and
maintained. However, abuse and/or improper use can
shorten the life of the unit and create hazards for you,
the owner.
a. The U.S. Consumer Product Safety Commission
recommends that users of oil-burning appliances
install carbon monoxide detectors. There can be
various sources of carbon monoxide in a building or
dwelling. The sources could be gas-fired clothes
dryers, gas cooking stoves, water heaters,
furnaces, gas-fired fireplaces, wood fireplaces, and
several other items. Carbon monoxide can cause
serious bodily injury and/or death. Therefore, to
help alert people of potentially dangerous carbon
monoxide levels, you should have carbon monoxide
detectors listed by a nationally recognised agency
(e.g. Underwriters Laboratories or International
Approval Services) installed and maintained in the
building or dwelling (see Note).
b. There can be numerous sources of fire or smoke in
a building or dwelling. Fire or smoke can cause
serious bodily injury, death, and/or property
damage. Therefore, in order to alert people of
2.2) Freezing Temperatures and Your
Structure:
Freeze warning.
Turn off water system.
If your unit remains shut off during cold
weather the water pipes could freeze and
burst, resulting in serious water damage.
Your unit is equipped with safety devices that may keep
it from operating if sensors detect abnormal conditions
such as clogged exhaust flues.
If the structure will be unattended during cold weather
you should take these precautions.
a. Turnoffmainwatersupplyintothestructureand
drainthewaterlinesifpossible.Openfaucetsin
appropriateareas.
b. Have someonecheckthe structurefrequently
duringcoldweathertomakesureitiswarmenough
topreventpipesfromfreezing.Suggesttheycalla
qualifiedserviceagency,ifrequired.
3.1) Location:
Locate the furnace as closely as possible to the
chimney or vent terminal, providing ample clearance to
permit easy accessibility for cleaning the inside of the
furnace, the removal of filters, blower, motors, controls
and flue connections. The furnace may be installed on
a combustible floor.
2.3) Installation regulation:
Installation MUST conform with local building codes or
in the absence of local codes, with the National
Electrical Code, ANSI/NFPA No.70-1990 or current
edition and Installation of Oil Equipment, NFPA No.31.
3) LOCATING THE FURNACE
Do not install furnace directly on carpeting, tile or other
combustible material.
The furnace must be installed level for safe quiet
operation.
Do NOT operate furnace in a corrosive
atmosphere containing chlorine, fluorine or
CAUTION
Check carefully your furnace upon delivery for
any other damaging chemicals. Refer to Part
1, section 5.2.
any evidence of damage that may have
occurred during shipping and handling. Any
claims for damages or lost parts must be
made with the Transport Company.
TABLE #1
Minimum Installation clearances from combustible materials (Chimney installation*)
" " NOUF160
Furnace 1"
Sides Supply plenum, warm air duct 1"
within 6 ft of furnace
Back Furnace 18"
Top Furnace casing or plenum 2"
Bottom Furnace - combustible floor 0"
Front Furnace 24"
* See Part 1 section 4.3 for Direct Vent application clearance.
CAUTION
OLR105 -OLF105. NOLF105
β’ OUF105 - NOUF105
1 "
1 "
1 "
1 "
0"
24"
4) VENTING
4.1) General:
The furnaces can be vented in several ways:
Chimney Vented:
Using the Beckett AFG or Riello 40-F burner, the
furnaces can be chimney vented with or without a
barometric damper. The unit will be operated at a
negative over fire draft and stack draft.
Poison carbon monoxide gas, fire and
explosion hazard.
Read and follow all instructions in this
section.
result in property damage, personal injury
I Failure to properly vent this furnace can I
and/or death,
Side-wall Vented:
Additionally, the liner must be insulated according to the
insulating procedure recommended by the
manufacturer of the liner.
I
Using the Beckett AFII or Riello 40-BF burner with the
integral pre and post purge controls, the system can be
side-wall vented with the new DV-2000 TM venting
system for maximum efficiency, and without the use of a
side-wall power ventor. The unit will be operated at a
positive overfire draft and stack draft.
Poison carbon monoxide gas hazard
Never co-vent the furnace with another
combustion appliance when side-wall
venting.
To do so may result in asphyxiation and
death to the occupants
4.2) Chimney installations:
The oil furnaces, when set up for chimney venting, are
certified for use with L-vent, A-vent, tile-lined and metal-
liner-tile-lined chimneys, and can be vented both with
and without a barometric draft damper. However, the
furnace has not been certified without the barometric
damper when it is to be co-vented with another oil-fired
appliance, such as a water heater.
When a damper is used, the basement air entering the
damper reduces the possibility of vent condensation.
However, if the barometric damper is not used, a
chimney liner with insulation must be employed.
With a barometric damper:
Poison carbon monoxide gas hazard
Never install a hand operated damper in
the vent pipe. However, any Underwriters
Laboratories listed electrically operated
automatic type vent damper may be
installed if desired. Be sure to follow
instructions provided with vent damper.
Read and follow all instructions in this
section.
Failure to properly vent this furnace or
other appliances can result in property
damage, personal injury and/or death.
Vent connectors:
For installations without barometric damper, the vent
connector should be as short as possible and either be
of double wall construction, or be of single wall
construction insulated with 1" of insulation, tt should
rise a minimum of 1/4" per foot from the furnace to the
chimney. Field fabricated connectors should be a
minimum of 28 gauge. The joints must be mechanically
secure and there must be no flue product leakage at the
joints.
CAUTION
When the furnace (chimney installation) is co-
vented with other combustion appliances such
as a water heater, the allowable venting
materials (i.e. L-Vent etc.) for use with those
appliances should also be investigated.
The appliance may be installed in a chimney of the
proper size and adequate chimney base temperature as
specified in the Installation Code. The relevant excerpt
from the code is found in this section - Use it as a guide
when local or national codes do not exist.
Without a barometric damper:
Due to the lack of dilution air that would ordinarily be
drawn into the barometric damper, the dew point of the
flue gasses is raised. To offset the increased tendency
for vent condensation, the chimney must be lined.
Flue pipe sizing:
The following table is an except from the installation
code and indicates permitted flue sizes and minimum
base temperatures for circular flues in chimney with
thermal resistance less than R6 (6 ft2 ohr oΒ°F / Btu).
Where a new appliance, burner, or chimney is installed,
chimney vent sizes and maximum flue-gas
temperatures (measured at the chimney connector with
the barometric damper shut, after 5 minutes of
operation) shall comply with the table #2.
Applying the Table:
J Notes: Thermal resistance values for typical chimneysare as follows:
If a furnace with 0.60 USGPH nozzle is to be connected
to a 20 ft. tall clay-lined masonry chimney, the thermal
R2 (2 ft2 ohroΒ°F / Btu):
R3 (3 ft2 ohroΒ°F / Btu):
R6 (6 ft2 ohroΒ°F / Btu):
Total input rating of all Flue inside diameter Minimum base temperature (Β°F)
connected appliances (in) for chimney height (if) of :
kW kBtu/h USGPH Min. ' Max. 11 20 28 36
21 70 0.50 3 5 300 400 535 725
27 91 0.65 3 5 275 340 430 535
31 105 0.75 4 5 260 320 380 475
36 119 0.85 4 5 250 300 355 430
41 140 1.00 4 6 225 300 365 430
51 175 1.25 4 6 240 275 320 365
clay-lined masonry, A-vent
metal liner in clay-lined
Masonry
metal or clay-lined masonry
with R4.5 (4.5 ft2 ohroΒ°F / Btu)
insulation between liner and
masonry (e.g. 2 in. of
expanded mica or 1 3/8 in. of
high density glass fibreboard.)
TABLE # 2
resistance of this chimney type is R2, which is less than
R6. The actual firing rate at 156 psig is 1.25 x .60 = .75.
Therefore this table shall apply as:
The minimum size permitted shall be 4 in. inside
diameter.
The maximum size permitted shall be 5 in. inside
diameter.
The minimum base temperature shall be about 320Β°F.
4.3) Side-wall venting, DV-2000 TM Direct
Vent System:
The furnace can be side-wall vented without the use of
a side-wall power ventor using the new DV-2000 TM
venting system with the high static pressure Beckett
AFtt and Riello 40-BF oil burners. Outdoor
combustion air must be directly connected to the
burner of the DV-2000 TM venting system will not
function.
The notable characteristics of the DV-2000 TM system
are as follows:
Certified to use the following materials for ducting the
intake air from the terminal to the burner; Schedule 40
PVC DWV, Schedule 40 ABS DWV, And ASTM 2729
Sewer Pipe.
One hole of minimal size (6") is required to be cut in the
side-wall, and the terminal is designed to fit through a
minimum 2 X 8-joist space.
The standard terminal is designed for a wall thickness
up to 14", and the deep wall terminal for wall thickness
up to 25".
Incorporates a vent blockage safety shutdown system.
If the vent or intake opening ever becomes partially or
fully blocked, the burner will shut down before a #_!
smoke occurs.
The intake and vent circuits within the terminal can be
accessed for cleaning.
There are 3 main components to the DV-2000 TM
system; the VTK vent terminal kit, the IFV insulated
flexible venting material and the field-supplied 3" PVC
or ABS intake piping.
Vent terminal kits - DV-2000TM:
The certified standard vent terminal kit is Model No.
VTK-1 or VTK-2, and is suitable for installation in walls
up to 14" thick. An alternate kit, Model VTK-1-DW or
VTK-2-DW is available to accommodate walls up to 25"
thick. Both kits contain the following items to complete
the hook-up to the venting and furnace:
1 Terminal
2 Sealing Clamps
1 Side-wall Venting Breech Plate
2 Sealing Strips
1 Inner Wall Plate
1 Pressure Control with Tubing
2 Insulated Quick-connect Terminals
3 StainlessSteelScrews
6 Selftappingstainlesssteelscrews
Insulated flexible venting - DV-2000TM:
The certified venting materials come in 3 lengths, Model
No. tFV3-15, IFV3-23 and IFV3-30 (or IFV4-15, IFV4-23
and IFV4-30 for 160 models) are corresponding to 15',
23' and 30' continuous lengths of vent. The vent
construction is coaxial and incorporates a stainless
steel corrugated flexible liner surrounded by a thick
insulation blanket and covered with an outer layer of
flexible corrugated aluminium sleeve to protect the
insulation. Splicing vent lengths together is prohibited.
The maximum and minimum continuous vent lengths
permitted for installation are:
5 feet minimum 30 feet maximum
Poison carbon monoxide gas hazard
c. within 6 feet of a window or door, or mechanical air
supply inlet to any building, including soffit
openings;
d. above a gas meter/regulator assembly within 3 feet
of a vertical centerline of the regulator;
e. within 6 feet of any gas service regulator vent
outlet, or within 3feet of an oil tank vent, or an oil fill
inlet;
f. within less than 1 foot above ground level;
g. 6 feet of any other combustion air inlet;
h. within 6 feet of a property line;
i. underneath a veranda, porch or deck;
j. so that the flue gases are directed at combustible
material or any openings of surrounding buildings
that are within 6 feet;
k. less than 3 feet from an inside corner of an L-
shaped structure;
I. so that the bottom of the vent termination opening is
less than 1 foot above any surface that may support
ice, snow, or debris;
m. so that the flue gases are directed toward
brickwork, siding or other construction, in such a
manner that may cause damage from heat or
condensation from flue gases.
Even though the flexible venting is insulated, it
cannot be run through an unheated space.
To do so could cause residual condensation
inside the stainless steel liner, which may
eventually perforate the liner and allow vent
gasses to enter the dwelling.
TABLE # 3
Side-wall venting clearances to combustibles
PORTION OF VENT ' CLEARANCES
Vent pipe, up to vent terminal* 3"
Vent terminal ZERO
*Do not enclose venting
Installation considerations - DV-2000TM:
Select a location for the vent terminal in accordance
with all local and national codes. The following
requirements shall be considered to be minimum
requirements that can be overridden by stricter local
and national codes.
The vent shall not terminate:
a. directly above a paved sidewalk or paved driveway
that is located between two buildings, and that
serves both buildings;
b. less than 7 feet above any paved driveway;
CAUTION
Most codes have a notwithstanding clause
that states that products of combustion shall
not enter the dwelling under any
circumstances, even if all other code
requirements as to construction and location
have been complied with. The installer is
ultimately responsible to do whatever is
necessary to ensure that flue gasses do not
enter the dwelling.
Installation of side-wall venting - DV-2000TM:
Cuts and abrasion hazard.
Always wear protective gloves and eye
protection when handling the vent material
The process of cutting and fitting the flexible
venting material exposes the installer to sharp
edges that could cause severe cuts to the
skin.
FIGURE # 1.1
FIGURE # 1.2
SL
EAD SPIN SLEEVE
NTO OUTER SLEEV
FIGURE # 1.3 FIGURE # 1.4
FIGURE # 1.5 FIGURE # 1.6
Connection to the furnace breech - DV-2000TM:
1. Remove the standard breech plate by removing the
brass nuts.
.
Determine which direction the venting will be routed
from the furnace and then install the special side-
wall venting breech plate provided in the VTK
Series vent kit so that the breech plate test port will
be accessible after vent installation. However, do
not install the breech plate with the test port
pointing downward. Tighten the brass nuts.
.
The flexible venting has 4 pieces of corrugated spin
sleeving that has been temporarily screwed on over
top of it. Remove the spin sleeving completely by
unscrewing it in a counter-clockwise direction.
.
Using tin snips, cut the aluminium outer sleeve back
by 5" for the IFV Series vent (see figure #1.1).
Ensure the snips are well adjusted and sharp or the
cut end of the venting will be too jagged to start the
threads of the spin sleeve (see figure #1.1 ).
.
Prepare the furnace breech end of the insulated flex
vent by first screwing the spin sleeve onto the
corrugated aluminium jacket (see figure #1.2) until
the trailing edge of the spin sleeve is about 12" from
the end of the vent (see figure #1.3).
6. Pull the insulation back to expose the corrugated
stainless steel core.
the seal strip around once, allow 1/2" overlap and
tear off the residual length (see figure #1.7).
10.
Break the residual length of seal strip in to 3 equal
parts and stuff them onto the screw heads of the
stainless steel self-drilling screws so that the screw
heads are completely covered.
11.
Two stainless steel band clamps are provided in the
VTK Series kits. Position one stainless steel band
clamp over the gum seal joint so that the edge of
the clamp closest to the breech lines up with the
edge of the gum seal that is closest to the breech.
Ensure that the band will close with an action of one
strip sliding over the other - not under the gearhead
of the draw clamp (see figure #1.8). Tighten the
band clamp with considerable torque to cause the
gum seal be squeezed into all crevices and to ooze
out of the end of the clamp closest to the breech
(see figure #1.9). The gum will eventually become
rubbery.
12. The seal is permanent and should never need to be
disconnected as the breech plate can be removed
for cleaning and inspection using the 4-bolt joint.
13. Tuck the vent insulation into the breech collar.
14.
Screw the spin sleeve tightly into the breech collar
for a finished appearance. Wrap the other end of
the spin sleeve with aluminium tape to cover any
metal burrs that may be present (see figure #1.10).
.
Cut the corrugated stainless steel core back by 3"
for the IFV Series vent. You should now have about
3" of insulation hanging out past the stainless steel
core (see figure #1.4).
.
Push the stainless steel core onto the breech pipe
as far as it will go (see figure #1.5) and
mechanically attach the vent to the breech using
three of the #8 X 1/2" self-drilling screws provided
with the VTK Series kit. The screws should be
equally spaced around the circumference of the
stainless steel core, starting with the first screw at
top dead center. Start the drill point of the screws in
the valleys of the corrugations at 3/8"-5/8" back
from the end of the stainless steel core, so the
screw heads can be properly sealed in the
forthcoming operations (see figure #1.6).
.
With the stainless steel core now firmly attached to
the breech, tear off one green gum-sealing strip
from the backing strip. Wrap the seal strip around
the joint, always keeping the centerline of the seal
strip over the line where the corrugated stainless
steel core makes the transition to the smooth outer
surface of the breech pipe. In other words, the seal
strip must be centered over the joint. After wrapping
15. Bend the venting into the desired radius coming off
the breech.
Connection to the vent terminal - DV-2000TM:
Prepare the terminal end of the insulated flex vent
by first screwing the spin sleeve onto the
corrugated aluminium jacket until the trailing edge
of the spin sleeve is about 10" from the end of the
vent.
2. Using sharp tin snips, cut the aluminium outer
sleeve back by 5"for the IFV Series vent
3. Pull the insulation back to expose the corrugated
stainless steel core.
.
Cut the corrugated stainless steel core back by 3"
for the IFV Series vent. You should now have
about 3" of insulation hanging out past the stainless
steel core.
Push the stainless steel core onto the pipe on the
back of the terminal as far as it will go and
mechanically attach the vent to the terminal using
three of the #8 X 1/2" self-drilling screws provided
with the VTK Series kit. The screws should be
10
FIGURE# 1.7 FIGURE # 1.8
FIGURE # 1.9 FIGURE # 1.10
FIGURE # 1.11
11
equallyspacedaroundthe circumferenceof the
stainlesssteelcore,startingwiththefirstscrewat
topdeadcenter.Startthedrillpointofthescrewsin
thevalleysof thecorrugationsat 3/8"-5/8"back
fromtheendofthestainlesssteelcore.
downward slope of the terminal, in the direction
from the inside to the outside.
Remove the 2 screws fastening the end cone in
place and remove the cone.
.
With the stainless steel core now firmly attached to
the terminal, tear off the other green gum-sealing
strip from the backing strip. Wrap the seal strip
around the joint, always keeping the centerline of
the seal strip over the line where the corrugated
stainless steel core makes the transition to the
smooth outer surface of the terminal pipe. After
wrapping the seal strip around once, allow 1/2"
overlap and tear off the residual length.
.
Break the residual length of seal strip in to 3 equal
parts and stuff them onto the screw heads of the
stainless steel self-drilling screws so that the screw
heads are completely covered.
.
Position the other stainless steel band clamp over
the gum seal joint so that the edge of the clamp
closest to the terminal lines up with the edge of the
gum seal that is closest to the terminal. Tighten the
band clamp with considerable torque to cause the
gum seal be squeezed into all crevices and to ooze
out of the end of the clamp closest to the terminal
(see figure #1.11 ).
.
The seal is permanent and should never need to be
disconnected as the end of the terminal can be
opened for cleaning and inspection by removing the
screened end-cone assembly. Tuck the vent
insulation into the recess in the terminal body.
10. Screw the spin sleeve tightly into the recess for a
finished appearance. Wrap the other end of the
spin sleeve with aluminium tape to cover any metal
burrs that may be present (see figure #1.12).
11. Bend the venting into the desired radius coming off
the terminal.
Installing terminal in the wall - DV-2000TM:
1. Cut a 6" hole in the side-wall in accordance with the
location considerations outlined in the previous
section.
.
Fasten the wall plate to the inside-wall using 4 field-
provided fasteners appropriate for the material
behind the wall plate. Depending on the angle of
access, the pressure control bracket may need to
be removed to access the top right wall plate screw
hole. For concrete and block, Tapcon TM screws or
equivalent are recommended. Install the wall plate
so that the top of the hole in the wall plate is
positioned 1/8" lower than the top of the 6" hole in
the wall. This will accommodate the proper
.
Remove the 2 screws fastening the stabiliser
shroud in place and remove the stabiliser shroud.
Insert the main body of the terminal through the wall
plate so that the end of the terminal extends about
2" past the outside wall.
.
Install the stabiliser shroud and replace the two
mounting screws. (see figure #1.13).
For concrete and block wall installations in
particular, If it appears that the flange on the back
of the stabiliser shroud is not large enough to cover
the irregularities in the hole, a field fabricated wall
plate can be constructed out of 304, 316, or 316L
stainless steel.
Silicone seal the circumference of the joint where
the stabiliser shroud connects to the main body of
the terminal.
.
Apply caulking to the back plate of the stabiliser
shroud and push the terminal back firmly against
the wall.
10.
While pushing down gently on the top of the
stabiliser shroud, install the 3 stainless steel 2"
screws provided with the kit to secure the back of
the shroud to the wall. Do not overtighten the
screws or it will distort the stabiliser shroud. The
screws will not be necessary in a concrete or block
wall as the mortar can provide positive positioning.
11.
Tighten the clamp on the wall plate to secure the
terminal in position.
12.
Apply more caulking all around the seam where the
stabiliser shroud meets the wall. It is important to
have a good seal to prevent water from entering the
dwelling (see figure #1.14). A considerable amount
of caulking may be necessary for irregular wall
surfaces such as lapped siding.
13.
Install the end cone and replace the two mounting
screws.
14.
Support the vent and intake air piping so that a 1/4"
to 1/2" downward slope (toward the outside) results
for proper drainage out the terminal body.
12
FIGURE# 1.12
FIGURE # 1.13 FIGURE # 1.14
13
Connectionofcombustionairpipingto theterminal
. DV.2000TM:
Refer to Part 1, section 5.3, Outdoor Combustion Air -
Side-wall Venting, DV-2000 TM for a complete
description.
5) AIR FOR COMBUSTION
Poison carbon monoxide gas hazard.
Comply with NFPA standard for the
installation of Oil Burning Equipment and
applicable provision of local building
codes to provide combustion and
ventilation air.
Failure to provide adequate combustion
and ventilation air can result in personal
injury and/or death.
The following areas or types of structures may contain
or have exposure to the substances listed below. The
installation must be evaluated carefully as it may be
necessary to provide outside air for combustion.
a. Commercial building.
b. Building with indoor pools.
c. Furnaces installed near chemical storage areas.
Exposure to these substances:
a. Permanent wave solutions for hair.
b. Chlorinated waxes and cleaners.
c. Chlorine based swimming pool chemicals.
d. Water softening chemicals.
e. De-icing salts or chemicals.
f. Carbon tetrachloride.
g. Halogen type refrigerants.
h. Cleaning solvent (such as perchloroethylene).
i. Printing inks, paint removers, varnishes, etc..
j. Hydrochloric acid.
k. Solvent cements and glues.
I. Antistatic fabric softeners for clothes dryers.
m. Masonery acid washing materials.
5.3) Ducted outdoor combustion air:
5.1) General:
Oil furnaces must have an adequate supply of
combustion air. It is common practice to assume that
older homes have sufficient infiltration to accommodate
the combustion air requirement for the furnace.
However, home improvements such as new windows,
doors, and weather stripping have dramatically reduced
the volume of air leakage into the home.
Home air exhausters are common. Bath and kitchen
fans, power vented clothes dryers, and water heaters all
tend to create a negative pressure in the home. Should
this occur, the chimney becomes less and less effective
and can easily downdraft.
Heat recovery ventilation (HRV) systems are gaining in
popularity. The HRVs are not designed to supply
combustion air. tf not properly balanced, a serious
negative pressure condition could develop in the
dwelling.
5.2) Contaminated Combustion Air :
Installation in certain areas or types of structures will
increase the exposure to chemicals or Halogens which
may harm the furnace. These instances will require that
only outside air for combustion.
Three burners are set up to duct outside combustion air
directly to the burner; the Beckett AFII and Riello 40-BF
for side-wall venting using the new DV-2000 TM venting
system, and the Beckett AFG for use with conventional
chimney venting. The Riello 40-F is not suitable for
direct-connected outdoor air.
CAUTION
The use of ducted outside combustion air is
mandatory for the DV-2000 TM venting system.
This system operates on a balanced flue
principle and will not function properly if the
combustion air piping is not attached and
sealed at all connections between the vent
terminal and burner inlet.
Outdoor combustion air kit - chimney venting:
The following kit has been certified for use on the
appliance. The component kits contain an important
safety feature, namely a vacuum relief valve, or VRV.
During normal operation the burner aspirates outdoor
air. If the intake terminal ever becomes partially blocked
or fully blocked from ice or snow etc., the VRV will open
to allow a proportion of air from the dwelling to enter the
burner thus maintaining proper combustion. Once the
blockage is removed, the VRV will close and the burner
will draw all air from the outdoors again:
14