ICP NHP260GKA1, NHP260AKA1, NHP248GKA1, NHP248AKA1, NHP242GKA1 Owner’s Manual

...
INSTALLATION INSTRUCTIONS
Split System
Premium Line
AC & HP Condensers
These instructions must be read and understood completely before attempting installation.
Installation / Startup Information & Warranty
CAUTION
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the
the National Electrical Code NFPA 70/ANSI C1-1999 or current edition and Canadian Electrical Code Part 1 CSA C.22.1.
The information contained in this manual is
intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instruc- tions in this manual can result in equipment
malfunction, property damage, personal injury
and/or death.
After uncrating unit, inspect thoroughly for hidden damage.
If damage is found, notify the transportation company im-
mediately and file a concealed damage claim.
Locating The Outdoor Unit:
Check local codes covering zoning, noise, platforms. If practical, avoid locating next to fresh air intakes, vent or
bedroom windows. Noise may carry into the openings and
disturb people inside.
Placement of the unit should be in a well drained area or unit must be supported high enough so runoffwill not enter
the unit.
Do not locate where heat, lint or exhaust fumes will be dis-
charged on unit (as from dryer vents).
Improper installation, adjustment, alteration, service or
maintenance can void the warranty. The weight of the condensing unit requires caution and
proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
1. Always wear safety eye wear and work gloves when installing equipment.
2. Never assume electrical power is disconnected. Check with meter and disconnect.
3. Keep hands out of fan areas when power is connected to equipment.
4. R-22 causes frost-bite burns.
5. R-22 is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instruc-
tions and Warranty are to be given to the owner or promi- nently displayed near the indoor Furnace/Air Handler Unit.
Roof top installations are acceptable providing the roof will support the unit and provisions are made for water drain- age and the noise or vibration through the structure.
Do not install the unit in a recessed or confined area where recirculation of discharge air may occur.
Heat Pumps Only: The top surface of platform must be above average winter snow levels to prevent coil blockage.
Clearances:
Nominal operating clearances, where practical, are 48 inches (120 cm) above unit for discharge air and 18 inches (40cm) around coil for intake air on three sides. Clearance
on one side (normally between unit and structure) may be
reduced to 6 inches (15cm). Nominal clearances are based
from a solid parallel object, wall, roof overhang, etc.
Do Not install under roof overhangs without guttering. A minimum vertical clearance of 48" is required to overhang.
The clearance may be reduced from a single object with a small surface area, such as the end of a wall, outside cor-
ner of a wall, fence section or a post, etc. As a general rule the width ofthe object should equal the minimum clearance from the unit. For example, a 4 inch (lOcm) fence post
could be 4 inches (lOcm) from the unit.
421 01 3202 02
Dec. 2004
_ Installation Instructions Split System Condensers I
Inside corner locations on single story structures require evaluation. Large overhanging soffits may cause air recir-
culation in a corner area even though recommended clear- ances are maintained. As a guide locate the unit far enough out so that half of the discharge grille is out from under the
soffit. Two or more units may be spaced with 18 inches (45cm)
between units.
Unit Support:
The unit must be level, and supported above grade by
beams, platform or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel or pressure treated timbers approved for ground contact. Refer to Unit Clear- ances to help determine size of supports etc. Soil condi- tions should be considered so the platform or pad does not shift or settle excessively and leave the unit only partially supported.
CAUTION
Inadequate support could cause excessive vibration and
noise or binding and stress on refrigerant lines resulting in equipment failure.
To minimize vibration or noise transmission, it is recom-
mended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
A, Ground Level Installation:
If beams or an open platform are used for support it is rec- ommended that the soil be treated or area be graveled to
retard the growth of grasses and weeds.
A service clearance of 24 inches (60cm) is desirable from control box end or side. Control box and corner panel be-
low it can be loosened and moved out to the side to facili- tate servicing. Internal components can be accessed
through control box corner or top only.
B. Roof Top Installation:
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof the unit should be 4 inches
(10cm.) above roof level. Four by four posts placed over a
load bearing wall make a suitable mounting platform.
If possible, place the unit over one or more load bearing
walls. If there are several units, mount them on platforms that are self-supporting and span load bearing walls.
These suggestions are to minimize noise and vibration transmission through the structure. If the structure is a
home or apartment, avoid (if practical) locating the unit over bedrooms or study.
NOTE: When condensing unit is to be installed on a bonded guaranteed roof, a release must be obtained from the building owner to free the installer from all liabilities.
Dimensions
-- 24-3/4 -- Chassis #1
33
Chassis #3
6-1/2
Minimum Mounting Pad Sizes with pad starting at 9" from structure for minimum clearances
Chassis #1 20" W X 20" D
2-3/4
Chassis #2
Chassis #2 24" W X 26" D Chassis #3 27" W X 28" D
"H" = Ranges from 26" to 44"
Refer to Specification Sheet
[][]
_ H
35
_ 11/2
38-11-17
I Split System Condensers
Figure 2 Clearances
Installation Instructions
Recommended Clearances Minimum Clearances
24"
24'_
24"
Minimum Clearances
24"
24" 24" 24"
18"
Minimum Clearances
18
Pipe
Minimum Clearances
24"
24"
18"
24"
Installing Refrigerant Lines
Component Matches
Check to see that you have the proper system compo- nents. APPROVED MATCHED SYSTEM COMPONENTS
MUST BE USED. Refer to the Sales Specification Sheet
or Split System Summary for match data and orifice
sizes,
The outdoor units are shipped with a refrigerant charge to
match the indoor unit and 25 ft. (7.5m) of refrigerant line. If
shorter or longer lines are used, the charge will have to be adjusted.
TOTAL LENGTH OF REFRIGERANT LINES MUST NOT
EXCEED 75 ft. WITH A MAXIMUM VERTICAL SEPARA-
TION OF 50 ft. BETWEEN THE OUTDOOR AND IN-
DOOR UNITS WITH 3 TRAPS, 2 TRAPS FOR 40 ft.
Restrictor Orifice
Some indoor matches use a restrictor orifice in the fitting at the indoor coil. Some matches may require a different ori- fice for proper system performance and it must be changed
before the refrigerant lines are connected.
Changing the Restrictor Orifice
The restrictor orifice is located in a fitting in the liquid line. The fitting is actually the distributor end of the cap tube as- sembly.
1. Remove the liquid line fitting and replace restrictor ori- fice. (STANDARD RIGHT HAND THREAD)
2. Make sure the restrictor is installed with the rounded
end toward the feeder tubes. See Figure 3.
Figure 3 I Restrictor Orifice
Nut and Liquid Line
with Strainer
!
_Feeder Tubes
I Installation Instructions Split System Condensers I
Refrigeration Line Sets
Ifit is necessary to add tubing in the field, use dehydrated or
dry sealed deoxidized copper refrigeration tube. DO NOT
use copper water pipe.
It is important that no tubing is cut or seals broken until you are ready to actually make connections to the evaporator and to the condenser section,
Do not remove rubber plugs or copper caps from the tube ends until ready to make connections at evapora-
tor and condenser,
PLEASE! UNDER NO CIRCUMSTANCES LEAVE THE
LINES OPEN TO THE ATMOSPHERE FOR ANY
PERIOD OF TIME,
Be extra careful with sharp bends. This tubing can "kink" very easily, and if this occurs, the entire tube length will
have to be replaced. Extra care at this time will eliminate future service problems.
Suspension And Installation Of
Refrigeration Lines
DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist. Use an insulated or suspension type of hanger. Keep both lines separate, and insulate the suction line. Both lines should be insulated in extremely
long runs in an attic or underground in a raceway, 50' or
more.
Do not let refrigerant lines come in direct contact with foundation. When running refrigerant lines through the foundation or wall, the openings should be made large enough to allow for a sound absorbing material to be
placed or installed between the tubing and the foundation. This will prevent noise transmission between the tubing and the wall section (foundation) or the building.
Installation Instructions For Condensing
Units That Are Higher Than Evaporator
It is recommended that vertical suction risers not be up- sized. Proper oil return to the compressor should be main- tained with suction gas velocity. If velocities drop below
1500 fpm (feet per minute), oil return will be decreased. An oil trap should be installed every 20' of vertical suction line
riser (condenser above evaporator.) Refer to line sizing charts.
Line Valves
The outdoor condensing unit is supplied with straight sweat brass service valves with copper stubs.
All line valves are positioned to seal the refrigerant in the condensing unit with gauge ports open to connecting lines
when the Schraeder valve is depressed. Gauge ports have Schraeder installed and require use of charging hoses with depressors,
Brazing Connections
Fire Hazard
Refrigerant and oil mixture under pressure could ignite as it escapes and contacts brazing torch resulting in Fire, Make sure the refrigerant charge is properly removed from both the high and low sides of the system before brazing any compo-
nent or lines. FAILURE TO DO SO COULD RESULT IN BODILY
INJURY OR DEATH.
Before making braze connections, be sure all joints are clean. Before heat is applied for brazing, nitrogen should be flowing through the tubing to prevent oxidation and scale formation on the inside of the tubing.
Liquid & Suction Lines
Fully annealed refrigeration lines should be used when installing the system.
The following is the recommended method for making braze connections at the refrigerant line connections:
Figure 4 [ Oil Traps
12J
0 ft.
10" Max
Min.
1. Clean refrigerant tube end with emery cloth or steel
brush.
2. Use a suitable brazing alloy for copper to copper joints. 3, Insert tubing into swage fitting connection.
4. Apply heat absorbing paste or heat sink product to pre- vent damage to the service valve.
CAUTION
Do not heat valve body above 250 degrees F. 5, Braze joint. 6, Quench the joint and tubing with water using a wet rag.
Leave rag on fitting body and re-wet with water to help cool
area.
Loading...
+ 8 hidden pages