ICP CHP043AKA1, CHP430AKA1, CHP048AKA1, CHP060AKA1, HHP048GKA1 Installation Instructions Manual

...
Installation
Instructions
SPLIT SYSTEM
Premium Line
AC & HP CONDENSERS
Save This Manual for Future Reference
421 01 3201 07
_Installation Instructions Split System Condensers
Installation/Startup Information
These instructions must be read and understood completely before attempting installation.
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the
the National Electrical Code NFPA 70/ANSI C1-1999 or current edition and Canadian
Electrical Code Part 1 CSA C.22.1.
The information contained in this manual is
intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instruc-
tions in this manual can result in equipment
malfunction, property damage, personal injury
and/or death.
After uncrating unit, inspect thoroughly for hidden damage.
If damage is found, notify the transportation company im- mediately and file a concealed damage claim.
CAUTION
Improper installation, adjustment, alteration, service or
maintenance can void the warranty. The weight of the condensing unit requires caution and
proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
1. Always wear safety eye wear and work gloves when installing equipment.
2. Never assume electrical power is disconnected. Check with meter and disconnect.
3. Keep hands out of fan areas when power is connected to equipment.
4. R-22 causes frost-bite burns.
5. R-22 is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instruc-
tions and Warranty are to be given to the owner or promi- nently displayed near the indoor Furnace/Air Handler Unit.
Dimensions
Minimum Mounting Pad Sizes with pad starting at 9 from structure for minimum clearances
26-1/2
-- 24-3/4 --
Chassis #1
FRONT
35
33
Chassis #3
Chassis #2
32-3/4
Chassis #1 20" W X 20" D Chassis #2 24" W X 26" D Chassis #3 27" W X 28" D
/
"H" = Ranges from 26" to 44"
Refer to Specification Sheet
I I
IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_HH IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_]m IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_]m IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_]m IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_]m IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_]m IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_]m IIIIIIIIIIIIIIIIIIIIIIIIIIIII1_]m
11/2
38-11-17
I Split System Condensers Installation Instructions
Locating The Outdoor Unit:
Check local codes covering zoning, noise, platforms. Roof top installations are acceptable providing the roof will
support the unit and provisions are made for water drain- age and the noise or vibration through the structure.
If practical, avoid locating next to fresh air intakes, vent or bedroom windows. Noise may carry into the openings and
disturb people inside.
Placement of the unit should be in a well drained area or unit must be supported high enough so runoffwill not enter
the unit.
Do not locate where heat, lint or exhaust fumes will be dis-
charged on unit (as from dryer vents).
Clearances:
Do not install the unit in a recessed or confined area where
recirculation of discharge air may occur.
Heat Pumps Only: The top surface of platform must be
above average winter snow levels to prevent coil blockage.
Nominal operating clearances, where practical, are 48 inches (120 cm) above unit for discharge air and 18 inches
(40cm) around coil for intake air onthree sides. Clearance
on one side (normally between unit and structure) may be
reduced to 6 inches (15cm). Nominal clearances are based
from a solid parallel object, wall, roof overhang, etc.
Do Not install under roof overhangs without guttering. A minimum vertical clearance of 48" is required to overhang.
The clearance may be reduced from a single object with a small surface area, such as the end of a wall, outside cor-
ner of a wall, fence section or a post, etc. As a general rule the width ofthe object should equal the minimum clearance from the unit. For example, a 4 inch (lOcm) fence post could be 4 inches (lOcm) from the unit.
Unit Support:
Inside corner locations on single story structures require
evaluation. Large overhanging soffits may cause air recir- culation in a corner area even though recommended clear-
ances are maintained. As a guide locate the unit far enough out so that half of the discharge grille is out from under the
soffit.
Two or more units may be spaced with 18 inches (45cm) between units.
A service clearance of 24 inches (60cm) is desirable from control box end or side. Control box and corner panel be-
low it can be loosened and moved out to the side to facili- tate servicing. Internal components can be accessed
through control box corner or top only.
The unit must be level, and supported above grade by
beams, platform or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel or pressure treated timbers approved for ground contact. Refer to Unit Clear- ances to help determine size of supports etc. Soil condi- tions should be considered so the platform or pad does not shift or settle excessively and leave the unit only partially supported.
CAUTION
Inadequate support could cause excessive vibration and
noise or binding and stress on refrigerant lines resulting in
equipment failure. To minimize vibration or noise transmission, it is recom-
mended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
A. Ground Level Installation:
If beams or an open platform are used for support it is rec- ommended that the soil be treated or area be graveled to
retard the growth of grasses and weeds.
B. Roof Top Installation:
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof the unit should be 4 inches
(10cm.) above roof level. Four by four posts placed over a
load bearing wall make a suitable mounting platform.
If possible, place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are self-supporting and span load bearing walls. These suggestions are to minimize noise and vibration transmission through the structure. If the structure is a home or apartment, avoid (if practical) locating the unit over bedrooms or study.
NOTE: When condensing unit is to be installed on a bonded guaranteed roof, a release must be obtained from the building owner to free the installer from all liabilities.
_Installation Instructions
Figure 2 I Clearances
Recommended Clearances
Split System Condensers I
Minimum Clearances
24"
24"
24"
24"
24"
24"
Minimum Clearances
Minimum Clearances
24"
18"
6_ , !
F J
J
18"
24"
18"
Minimum Clearances
24"
24"
24"
24"
I Split System Condensers Installation InstructionsI
Installing Refrigerant Lines
Component Matches
Check to see that you have the proper system compo- nents. APPROVED MATCHED SYSTEM COMPONENTS
MUST BE USED. Refer to the Sales Specification Sheet
or Split System Summary for match data and orifice
sizes.
The outdoor units are shipped with a refrigerant charge to
match the indoor unit and 25 ft. (7.5m) of refrigerant line. If
shorter or longer lines are used, the charge will have to be adjusted.
OUR STANDARD RECOMMENDED REFRIGERANT
LINE LENGTH IS 75 ft. WITH A MAXIMUM VERTICAL SEPARATION OF 50ft. BETWEEN THE OUTDOOR AND INDOOR UNITS WITH 3TRAPS, 2 TRAPS FOR 40 FOOT
RISE. LONGER REFRIGERANT LINES CAN BE INSTALLED BY USING THE EXTENDED LENGTH RE-
FRIGERANT PIPING MANUAL #42106111400 WITH PRIOR APPROVAL FROM ICP TECHNICAL SERVICE DEPARTMENT.
Restrictor Orifice
Some indoor matches use a restrictor orifice in the fitting at
the indoor coil. Some matches may require a different ori- fice for proper system performance and it must be changed
before the refrigerant lines are connected.
Changing the Restrictor Orifice
The restrictor orifice is located in a fitting in the liquid line. The fitting is actually the distributor end of the cap tube as-
sembly.
1. Remove the liquid line fitting and replace restrictor ori- fice. (STANDARD RIGHT HAND THREAD)
2. Make sure the restrictor is installed with the rounded end toward the feeder tubes. See Figure 3.
Figure 3 J Restrictor Orifice
Nut and Liquid Line
with Strainer
! ''°e
_ Feeder Tubes
Refrigeration Line Sets
If itis necessary to add tubing in the field, use dehydrated or dry sealed deoxidized copper refrigeration tube. DO NOT use copper water pipe.
It is important that no tubing is cut or seals broken until
you are ready to actually make connections to the evaporator and to the condenser section.
Do not remove rubber plugs or copper caps from the tube ends until ready to make connections at evapora-
tor and condenser.
PLEASE! UNDER NO CIRCUMSTANCES LEAVE THE
LINES OPEN TO THE ATMOSPHERE FOR ANY
PERIOD OF TIME.
Be extra careful with sharp bends. This tubing can "kink" very easily, and if this occurs, the entire tube length will have to be replaced. Extra care at this time will eliminate future service problems.
Suspension And Installation Of
Refrigeration Lines
DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist. Use an insulated or suspension type of hanger. Keep both lines separate, and insulate the suction line. Both lines should be insulated in extremely long runs in an attic or underground in a raceway, 50' or
more.
_ Installation Instructions
Do not let refrigerant lines come in direct contact with
foundation. When running refrigerant lines through the foundation or wall, the openings should be made large
enough to allow for a sound absorbing material to be placed or installed between the tubing and the foundation.
This will prevent noise transmission between the tubing and the wall section (foundation) or the building.
Installation Instructions For Condensing Units That Are Higher Than Evaporator
It is recommended that vertical suction risers not be up-
sized. Proper oil return to the compressor should be main- tained with suction gas velocity. If velocities drop below
1500 fpm (feet per minute), oil return will be decreased. An
oil trap should be installed every 20' of vertical suction line
riser (condenser above evaporator,) Refer to line sizing
charts,
Figure4[ OilTraps
10" Max
Min,
0 ft.
Line Valves
The outdoor condensing unit is supplied with straight sweat
brass service valves with copper stubs,
All line valves are positioned to seal the refrigerant in the condensing unit with gauge ports open to connecting lines when the Schraeder valve is depressed. Gauge ports have
Schraeder installed and require use of charging hoses with
depressors.
Split System Condensers I
Brazing Connections
Fire Hazard
Refrigerant and oil mixture under pressure could ignite as it escapes and contacts brazing torch resulting in Fire. Make sure the refrigerant charge is properly removed from both the high and low sides of the system before brazing any compo-
nent or lines. FAILURE TO DO SO COULD RESULT IN BODILY
INJURY OR DEATH.
Before making braze connections, be sure all joints are clean. Before heat is applied for brazing, nitrogen should be flowing through the tubing to prevent oxidation and scale formation on the inside of the tubing.
Liquid & Suction Lines
Fully annealed refrigeration lines should be used when installing the system.
The following is the recommended method for making braze connections at the refrigerant line connections:
1. Clean refrigerant tube end with emery cloth or steel
brush.
2. Use a suitable brazing alloy for copper to copper joints, 3, Insert tubing into swage fitting connection,
4. Apply heat absorbing paste or heat sink product to pre- vent damage to the service valve,
CAUTION
Do not heat valve body above 250 degrees F.
5, Braze joint.
6. Quench the joint and tubing with water using a wet rag.
Leave rag on fitting body and re-wet with water to help cool area.
Evacuating, And Charging Instructions
NOTE
Intentional release of CFC or HCFC Refrigerant to the Atmosphere violates Federal Law. It may also violate State and Local Codes. Check all Federal, State and
Local Codes before proceeding.
These instructions are intended for use with condensing units that are precharged at the factory with adequate re- frigerant to handle 25 feet.
NOTE: Do not use any portion of the charge for purging or leak testing. Itis mandatory that a thorough evacuation of the refrigerant in the piping and evaporator be performed.
The liquid line and suction line service valves have been closed after final testing at the factory. Do not disturb
these valves until the lines have been leak checked and evacuated or the charge in the unit may be lost.
LIJ
I Split System Condensers Installation Instructions
Recommended Method Of Evacuating A System
1. Connect the vacuum pump to the suction and liquid line
gauge ports.
The service valve cap is a primary seal for the valve and must be properly tightened to prevent leaks. Make sure cap
is clean and apply refrigerant oil to threads and sealing sur- face of cap.
2. If the evacuation is being performed on a new system installation, the valves should be kept in the "front seated" (closed) position. This will allow the mechanic to evacuate
the refrigeration lines and the indoor coil, without disturbing the factory charge in the outdoor unit.
For valves with retaining rings: Replace service valve
cap and torque to; 8-11 ft. Ibs. on 1/4" and 3/8" valves,
12-16 ft. Ibs. on 5/8" and 3/4", 15-21 ft. Ibs on 7/8" valves. If
torque wrench is not available, tighten cap finger tight and then tighten one (1) additional wrench flat or 1/6 of a turn.
3. Follow the vacuum pump manufacturer's instructions.
Allow the pump to operate until the system has been eva- cuated down to 300 microns. Allow the pump to continue
running for an additional 15 minutes. Turn offthe pump and leave the connections secured to the two service valves.
After 5 minutes, if the system fails to hold 500 microns or
less, check all connections for tight fit and repeat the evac- uation procedure.
4. Isolate the vacuum pump from the system by closing the
shutoff valves on the gauge bar. Disconnect the vacuum
pump.
Valve Actuation: Service Valves
For valves with rolled tops: Replace service valve cap
tighten cap finger tight and then tighten one (1) additional wrench flat or 1/6 of a turn to properly seat the sealing sur- faces. Subsequent installations will seat with 1/2 to 1 wrench flat of turning.
Gauge Ports: All Valves
Check for leaks at the schrader port and tighten valve core if necessary. Install plastic caps finger tight.
Remove the service valve cap, if there is a male valve stem
see instructions for Ball Valves. For the standard service valve there are two variations, but both have internal stems. The first style uses an internal snap ring to retain the
valve stem and the second has a rolled top and also has finer threads on the valve cap. NOTE: You may encounter
more than one type of valve on a unit. For service valves fully insert a hex wrench into the stem. A
back-up wrench is required on the valve body to open the
valve stem. Backout counterclockwise until the valve stem stops or just touches the retaining ring. NOTE: THIS IS
NOT A BACKSEATING VALVE, For valves with retainer rings care must be taken to prevent dislodging them when
opening valve.
Electrical Wiring
Ball Valves
On models with ball type valves use a 6" crescent wrench to rotate the valve stem 90° counter clockwise. Retighten valve cap to 6-8 ft. Ibs. If torque wrench is not available, tighten cap finger tight and then tighten one (1/2) additional
wrench flat.
REFRIGERATION PIPING & CHARGING
For extended piping over the recommended 75 feet please
refer to Extended Length Refrigerant Piping Manual (Part #
42106111400).
Permanently ground unit in accordance with the National
Electrical Shock Hazard.
Shut off electric power at fuse box or service pan-
el before making any electrical connections.
Failure to shut off electric power can result in, property damage, personal injury and/or death.
The supply voltage should be 208-230 volts (196 volt mini-
mum to 253 volts maximum) 60Hz single phase.
APPROVED FOR USE WITH COPPER CONDUCTORS
ONLY. DO NOT USE ALUMINUM WIRE, REFER TO UNIT RATING PLATE FOR CIRCUIT
PROTECTION.
Grounding
Electrical Code and local codes or ordinances. Use a cop-
per conductor of the correct size from the grounding termi- nal in control box to a grounded connection in the service panel or a properly driven and electrically grounded ground
rod.
Wiring Connections
Make all outdoor electrical supply (Line Voltage) connec- tions with raintight conduit and fittings. Most codes require a disconnect switch outdoors within sight of the unit.
Route Line Voltage wiring through entrance and through hole in the bottom of the Control Box to connect to Contac-
tor and Ground Lug.
Route Low Voltage wiring through entrance ONLY and make ALL low voltage connections to the low voltage pig- tails in the area below the Control Box. (Two Yellow wires, AC or W,Y,O,BL, & R for HP). The pigtail wires have 600V insulation meeting approval for use in high voltage areas.
_ Installation Instructions Split System Condensers I
See Figures 5 thru 8 and Wiring Diagram on unit.
Use of Rigid Metal Conduit
It is recommended that wires be tied together or twisted to- gether inside the conduit. This will minimize any buzzing type sounds that could be produced with high current
loads, such as during starting. Under some conditions it
may be necessary to use a hard start kit to eliminate prob-
lem noises.
Figure5
A/C Control Box
Contactor
Ground Lug
Wires
(Low Voltag e)
Line Voltage Entrance
Low Voltage Entrance
Control Box Access
Remove the four screws. Cover is notched so it will slide out from under top edge of unit.
Figure 6 Heat Pump Control Box
Figure 7|'" " A/C Condenser Typical Low
I Voltage Connections
Indoor Thermostat
R G BL
! I I
(Compressor
W
!
(Co
Outdoor
Unit
:ontactor)
_. Y--
INDOOR
BLOWER COIL
GAS
OR FURNACE
Defrost
Control
Contactor
Ground Lug
Line Voltage Entrance
Low Voltage Entrance
Pigtail Wires (Low Voltage)
I Split System Condensers Installation Instructions I
Figure 8
Heat Pump Typical Low Voltage Control Connections
ELECTRIC HEAT
NO OUTDOOR THERMOSTAT
Indoor
Thermostat
C
--©
White Rogers 1F92 only, field jumper required
Y1-Wl.
NOTE: White Rogers 1F92
thermostat cannot be used for direct staging of electric
heat. Outdoor thermostat
must be used for staging.
\
\__
I
INDOOR ACCESSORY BLOWER ELECTRIC
COIL HEAT PKG.
t
Outdoor Unit
-0-- O -- (Heat/Cool Relay)
-0-- Y D (Compressor)
-O-- W-- (Electric Heat)
-O-- BLD (Common 24V)
-O-- R_ (24V-Hot)
SPLICE (WIRE NUT OR SOLDER AND TAPE) (1) FIRST STAGE ELECTRIC HEAT ALL HEATERS
(2) ADDITIONAL STAGES, ELECTRIC HEAT STAGE 2 = BK, STAGE 3 = V, STAGE 4 = BR
If electric heat is not used, discard connection shown from electric heat package.
Start-Up Procedure
Start-up Procedure
1. Close electrical disconnects to energize system,
2. Energize crankcase heater on units so equipped, 3, Set Thermostat selector switch to OFF,
4. Set room thermostat at desired temperature. Be sure setpoint is below indoor ambient temperature for cooling and above indoor ambient for heating.
5. Set the system switch of the thermostat on COOL and fan switch for continuous operation or AUTO, as desired.
Operate unit for 15-20 minutes, then check the system re-
frigerant charge if it was necessary to adjust.
6. After the refrigerant charge has been adjusted, the sys- tem is now ready for continuous operation.
Final Refrigeration Charge Adjustment
Before any adjustment is made to the refrigerant charge, it is imperative that the air flow characteristics of the indoor
blower be established.
When checking indoor air flow, it is important to remember that the blower will deliver a higher quantity of air across a dry coil versus awet coil. Blower charts are calculated with
a dry coil.
Recommended air flow for installations of cooling units and heat pumps is 350-450 CFM per ton (12,000 BTUH) through a wet coil. Refer to indoor unit installation instruc- tions for proper methods of determining air flow and blower performance.
To Check System Refrigerant Charge
(Superheat Method), Cooling Only
NOTE: On units with two speed fan control the fan will be
on low speed if the temperature is below 83 ° F. Pull one of the yellow low voltage wires off the fan control and the unit will default to high speed fan for servicing. Reconnect wire after checking.
1. Attach an accurate temperature sensing device to the suction line approximately 4" - 6" away from the suction line service valve. The temperature sensing device should be clamped securely to the suction line, on a horizontal plane (between 9 & 3 O'clock) and insulated. Record the suction line temperature.
_ Installation Instructions Split System Condensers I
2. Measure and record the suction line refrigeration pres- sure. (Measure at the suction line service valve gauge
port.) Using Temperature / Pressure Chart convert this
pressure to the saturation refrigerant temperature. The dif- ference between actual and saturated temperatures is the amount of superheat.
Figure 9
Temper ature °F.
-6
-4
-2 0 1
2 3 4 5 6
7 8 9
10 11
12 13
14 15 16 17 18
- Temperature / Pressure Chart
PSIG Temper PSIG Temper R-22 ature °F. R-22 ature °F.
19,3 19 41,9 41 20,8 20 43,0 42 22,4 21 44,1 43 24,0 22 45.3 44 24,8 23 46,4 45
25.6 24 47,6 46 26,4 25 48,8 47 27,3 26 49,9 48 28,2 27 51,2 49 29,1 28 52,4 50
30,0 29 53,6 55 30,9 30 54.9 60 31,8 31 56,2 65 32,8 32 57,5 70
33,7 33 58,8 75 34,7 34 60,1 80
35.7 35 61,5 85 36,7 36 62,8 90
37,7 37 64,2 95 38,7 38 65,6 100 39,8 39 67,1 105
40.8 40 68.5 110
115
PSIG R-22
70.0
71.4
73.0
74.5
76.0
77.6
79.2
80.8 82,4 84,0
92,6
101.6
111.2 121,4
132,2 143,6 155,7
168,4 181,8 195,9
210.8 226,4
242.7
3. Measure and record the outside ambient air tempera- ture.
4. Optimum performance will be achieved when the oper- ating charge produces 15°-20 ° F suction superheat at compressor with 82° F outdoor ambient and 80° Fdry bulb
(67° F wet bulb) indoor temperature (ARI "B" test condi- tions) at rated airflow. If these conditions cannot be ob- tained, compare the calculated superheat value with the
recommended valves given in Figure 13,
Figure 10 - Recommended Superheat Values
Outside Air Superheat °F
Temp ° F Variator or Piston
65 75 85
95
1O5
38 -45 27 - 33 20 - 25
10 - 15
2-6
Ifthe actual superheat readings are higher than shown, the
system is most likely under-charged, and charge should
be added. Add charge in 4 ounce increments, and recalcu- late superheat values. Continue adjusting charge until the
actual superheat approximately matches the recom-
mended values.
'IZ2J
If the actual superheat readings are lower than shown, the
system is most likely over-charged, and charge should be removed. Remove charge in 4 to 6 ounce increments, and
recalculate superheat values. Continue adjusting charge until the actual superheat approximately matches the rec-
ommended values.
NOTE: Each time that charge is added or removed from the system, allow the system to run approximately 15 min- utes before pressure and temperature readings are taken and superheat calculations made.
NOTE: Indoor Wet Bulb Temperature ( and Relative Hu- midity) will alter superheat values. All readings should be at 50% humidity inside and 350 to 450 CFM per ton across
the indoor coil.
Heating Checkout (Heat Pump Only)
1. Turn thermostat heat-cool switch to OFF. Turn ther- mostat fan switch to AUTO.
2. Turn on all power except 230 volt line to outdoor sec- tion.
3. Turn fan switch on thermostat to ON. Blower should
run. Reset to AUTO; blower should turn off.
4. Set thermostat below room temperature. Turn selec- tor switch to heat. Move thermostat above room tem-
perature. Blower should run on heating speed and a
click should be heard in the condensing unit outside
(contactor closing). The sequencer coils for auxiliary heat should be energized. After approximately 30
seconds the contacts in the sequencers should close and the electric heat elements start heating. Allow 3
minutes for all heaters to come on.
5. Set system switch to OFF. Turn the thermostat above
room temperature. Turn on the 230 volt power to the
outdoor unit. Nothing apparent will be happening, but the crankcase heater is now energized. If the outdoor
temperature is below 75 °F allow the unit to stay in this mode at least 6 hours. This is needed to vaporize
any refrigerant that may be in the compressor oil.
6. Set the thermostat above room temperature. Move system switch to heat. Count to 5 (about 5 seconds).
Turn the electric power off at the condensing unit dis- connect switch. Check that there is no clattering or
unusual noises. The outdoor fan blade should have
started turning and a humming noise should have
been heard from the compressor. The indoor fan
should continue to run at its normal speed and elec- tric elements continue to heat.
7. Wait 2 minutes, then repeat the procedure and re- check the same things in case you missed something
during the first power application.
8. With the unit operating, close all doors, windows, storm windows, and openings to the house. Set the
thermostat to the desired setting. Set outdoor ther-
mostat (if installed) to balance point of house. If tem-
perature of house is at least two degrees below thermostat setting, heat pump and auxiliary heat not controlled by outdoor thermostats will continue to run
until room temperature is approximately 2° below thermostat set point. Auxiliary heat light should go out and auxiliary heat cycle off. Heat pump should
continue to run until thermostat reaches set point.
I Split System Condensers Installation Instructions
To Check System Refrigerant Charge
(Heating Mode)
The recommended method of addition or removal of charge in the heating mode is by weight. The system op-
eration may be checked against the performance charts.
Remember, indoor airflow must be approximately 400 CFM per ton to compare operation to performance charts.
Defrost System (Heat Pump Only)
Time / Temperature Type: The defrost system is electronic with an adjustable time in- terval of 90, 60, or 30 minutes, It is factory set at 60 or 90
minutes. At the selected time interval with the outdoor coil
temperature at approximately 28°F, the system will defrost. When the sensor sees the correct rise in the outdoor coil
temperature or after approximately 10 minutes, the defrost will be terminated.
In some areas, with high humidity, the time interval or tem-
perature termination may require adjustment for complete removal of ice from the coil. For best economy, always set
to the longest interval or lowest temperature that will keep the coil clear of ice.
NOTE: The term ice means hard but not frost. During nor- mal operation, the coils may become coated with frost until they are solid white. The time interval for the defrost should be set so the frost and ice melt off completely without hard
ice building up on the coil.
Defrost Control
Time Interval Adjustment
(Except Demand Defrost)
Demand Type:
The defrost frequency is demand based on the coil reach-
ing atemperature of 35 °F for a minimum of 34 minutes and
a maximum of 6 hours of run time. The actual time interval will vary depending on the outdoor temperature which the
control is also sensing. This can not be adjusted, but the defrost termination temperature can be. Factory setting is 50°F for termination or after approximately 14 minutes, the defrost will beterminated. Temperature can be set higher if
all the ice is not melting off the coil.
To adjust defrost frequency, turn off all power to the Heat
Pump. Remove control box cover and locate the electronic defrost control board.
The defrost control board has a jumper clip that fits over two pins. To change the time interval, remove the jumper clip and place it on pins for the desired time interval, 30, 60
or 90 minutes.
U JJ
_ Installation Instructions Split System Condensers I
Temperature Adjustment
(Demand Defrost)
Turn off all power to the Heat Pump. Remove control box cover and locate the electronic defrost control board.
3, Never use a weather cover over the outdoor unit un-
less it is aventilated type or made of breathable fabric
that will allow moisture to evaporate rapidly. A cover that holds moisture in the unit will cause more rust
build-up and damage than normal exposure to
weather.
The defrost control board has a jumper clip that fits over two pins. To change the temperature termination, remove the jumper clip and place it on pins for the desired interval of 50, 60, 70 or 90 degrees.
Functional Check (Demand Defrost)
Toforce a defrost cycle place the jumper on the TEST pins. This will cause an accelerated test defrost cycle at 240 times the normal speed (14 min. = 3.5 secs). Reversing valve will energize, condenser fan stop and electric heat
should come on. This will verify the switching functions of the board.
Maintenance
Electrical Shock Hazard.
Shut off electric power at fuse box or service pan-
el before making any electrical connections.
Failure to shut off electric power can result in, property damage, personal injury and/or death.
Figure 1i [
Jum
Adjusting Defrost Time - Time Temperature Type
Condensate Drain
During the cooling season check at least monthly for free
flow of drainage and clean if necessary.
Cleanliness
These tips will help you keep your air conditioner looking
better and working more efficiently:
1.
2,
Free air flow is essential. Keep the outdoor coil clean
and free of restrictions. Keep fences, shrubs, snow drifts and any other obstructions at least two feet from
all coil air inlets.
Keep the coil free of grass clippings, weeds and other
debris. BE SURE TO TURN OFF ELECTRICITY BE-
FORE CLEANING!
Coils may require cleaning. The coil should al-
ways be cold when cleaning. Use an alkaline
based cleaner only. Cleaning a hot coil or using
an acid based cleaner will remove the paint from the fins and may clog the coil.
Figuie!2 [ Adjusting Defrost-Demand Type
Jumper
I Split System Condensers Installation Instructions
SHIPPING BRACKET
A shipping bracket has been added to some chassis to increase the stacking height for im-
proved warehousing.
If present the bracket may be left in place or removed by the installer. NOTE: The bracket is installed using the same screw(s) that secure the service valve. If only
one screw is used there is a clearance hole that fits over one screw securing the suction valve. If bracket is removed. MAKE SURE SCREW(S) IS REINSTALLED.
Loading...