ICP CCA724GKA100, CCA736GKA100, CCA748GKA100, CCA760GKA100, HCA724GKA100 Installation Guide

...
INSTALLATION INSTRUCTIONS
R- 410A Two- Stage Split System Air Conditioner
CCA7, HCA7, TCA7
These instructions must be read and understood completely before attempting installation.
IMPORTANT: Effective January 1, 2015, all split system and packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
SAFETY CONSIDERATIONS
70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety- alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety- alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury and/or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warn­ing label.
!
CUT HAZARD
Failure to follow this caution may result in personal injury
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
!
!
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some s lack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon- based caulk. (See Fig. 1.)
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing.(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4 mm) wide and conform to shape of tubing insulation. (See Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
CAUTION
421 01 1702 05 10/18/16
INSTALLA TION INSTRUCTIONS R- 410A Split System Air Conditioner
Figure 1 Connecting Tube Installation
Avoid contact between tubing and structureNOTE:
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
1 (25.4 mm)MIN.
SUSPENSION
LIQUID TUBE
VAPOR TUBE
JOIST
INSULATION
VAPOR TUBE
LIQUID TUBE
Outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field- supplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover and/or in the Check Charge section of this instruction.
IMPORTANT: Maximum liquid- line size is 3/8- in. OD for all residential applications including long line.
IMPORTANT: Always install the factory- supplied liquid- line filter drier. Obtain replacement filter driers from your distributor or branch.
For hurricane tie downs - contact your local distributor for details and PE (Professional Certification), if required by local authorities.
On rooftop applications, mount on level platform or frame. Place unit above a load- bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles. Consult the Low- Ambient pressure switch installation instructions for wind baffle construction.
NOTE: Unit must be level to within 2_ (3/8 in./ft..) per compressor manufacturer s pecifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6 in. (152.4 mm) clearance on one side of unit and 12 in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
Figure 2
3/8- in. (9.53 mm) Dia. Tiedown Knockouts in Basepan(2) Places
Tie Down Knockouts
INSTALLATION
View From Top
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
R- 410A refrigerant systems operate at higher pressures than standard R- 22 systems. Do not use R- 22 service equipment or components on R- 410A refrigerant equipment.
Specifications for this unit in residential new construction market require the outdoor unit, indoor unit, refrigerant tubing sets, metering device, and filter drier listed in presale literature. There can be no deviation.
Check Equipment and Job Site
Unpack
Move to final location. Remove carton. Do not to damage unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.
2 421 01 1702 05
Unit
WARNING
UNIT BASE PAN
Dimension
31–1/2 X 31–1/2
(800 X 800)
35 X 35
(889 X 889)
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.
Operating Ambient
The minimum outdoor operating ambient in cooling mode is 55°F (12.78 _C), and the maximum outdoor operating ambient in cooling mode is 125°F (51.67_C).
*CA7 product is approved for low ambient cooling operation down to an ambient as low as 0 _F (- 17.78 _ C) with low ambient accessory kits.
Make Piping Connections
!
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Use all service ports and open all flow- control devices, including solenoid valves.
Specifications subject to change without notice.
TIEDOWN KNOCKOUT LOCATIONS in. (mm )
A B C
9–1/8 (231.8) 6–9/16 (166.7) 24–11/16 (627.1)
9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)
WARNING
INSTALLA TION INSTRUCTIONS R- 410A Split System Air Conditioner
beyond 80 ft/24.38 m, substantial capacity and performance
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further special consideration. Do not bury lines more than 36 in. (914.4 mm).
losses can occur. Following the recommendations in the Long Line Applications Guideline for Split- System Air Conditioners and Heat Pumps will reduce these losses. Refer to Table 1 for accessory requirements. Refer to Table 2 for field tubing diameters.
There are no buried- line applications greater than 36 in. (914.4 mm).
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
Outdoor Unit Connected to Factory Approved Indoor Unit
Outdoor unit contains correct system refrigerant charge for
operation with factory approved AHRI rated indoor unit when Outdoor units may be connected to indoor section using accessory tubing package or field- supplied refrigerant grade tubing of correct size and condition. For tubing requirements
connected by 15 ft. (4.57 m) of field- supplied or
factory- accessory tubing, and factory supplied filter drier. Check
refrigerant charge for maximum efficiency.
Table 1 - Accessory Usage
REQUIRED FOR LOW AMBIENT
COOLING APPLICATIONS
Accessory Crankcase Heater Yes Standard on some units Yes, standard on some units No Compressor Start Assist Ca­pacitor and Relay Liquid Line Solenoid Valve No See Long Line Applications Guideline No Support Feet Recommended No Recommended
Hard Shutoff TXV
Evaporator Freeze Thermostat Yes No No Low-Ambient Pressure Switch Yes No No Winter Start Control Yes No No
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Long Line Applications Guideline.
(Below 55F / 12.8C)
No No No
Yes (Standard with factory approved
indoor unit)
REQUIRED FOR LONG LINE
APPLICATIONS* (Over 80 ft. / 24.38 m)
Yes (Standard with factory approved in-
door unit)
Required for Sea Coast Applica-
tion (within 2 miles/3.22 km)
Yes (Standard with factory ap-
proved indoor unit)
Table 2 - Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
RATED VAPOR
LIQUID
Connection and Tube
UNIT SIZE
*CA724 3/8 3/4 3/4 *CA736 3/8 7/8 7/8 *CA748 3/8 7/8 1- 1/8 *CA760 3/8 7/8 1- 1/8
* Units are rated with 25 ft. (7.6 m) of lineset. See Specification sheet for performance data when using different size and length linesets.
Notes:
1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Long Line Applications Guideline.
Diameter
Install Liquid Line Filter Drier Indoor
Connection
Diameter
4. Connect and braze liquid refrigerant tube to the filter drier.
up to 80 ft. (24.38 m)*
Rated Tube
Diameter
!
CAUTION
Figure 3
Liquid Line Filter Drier
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Installation of filter drier in liquid line is required. Filter drier must be wrapped in a heat- sinking material such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5 in. (127 mm) liquid tube. Flow arrow must point towards indoor coil.
421 01 1702 05 3
Specifications subject to change without notice.
Refrigerant Tubing Connection Outdoor
Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 2.) Use refrigerant grade tubing.
INSTALLA TION INSTRUCTIONS R- 410A Split System Air Conditioner
Sweat Connection
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Service v alves must be wrapped in a heat- sinking material such as a wet cloth.
Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
CAUTION
Evacuate Refrigerant Tubing and Indoor Coil
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
CAUTION
2. Close manifold valves or valve at vacuum pump and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and fill with nitrogen until system pressure is 2 psig.
4. Close nitrogen valve and allow system to stand for 1 hour. During this time, dry nitrogen will diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Figure 5.
6. After the final evacuate sequence, confirm there are no leaks in the system. If a leak is found, repeat the entire process after repair is made.
Figure 5
BREAK VACUUM WITH DRY NITROGEN
BREAK VACUUM WITH DRY NITROGEN
Triple Evacuation Sequence
EVACUATE
WAIT
EVACUATE
WAIT
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. If deep vacuum equipment is not available, the alternate triple evacuation method may be used by following the specified procedure. If vacuum must be interrupted during the evacuation procedure, always break vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 4)
Figure 4
Deep Vacuum Graph
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
EVACUATE
CHARGE SYSTEM
Make Electrical Connections
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
MINUTES
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A95424
Triple Evacuation Method
The triple evacuation method should only be used when system does not contain any water in liquid form and vacuum pump is only capable of pulling down to 28 inches of mercury (711mm Hg). Refer to Fig.5 and proceed is as follows:
1. Pull system down to 28 inches of mercury (711mm Hg) and allow pump to continue operating for an additional 15 minutes.
4 421 01 1702 05
Specifications subject to change without notice.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not supply power to unit with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440- 14 of NEC.
WARNING
INSTALLA TION INSTRUCTIONS R- 410A Split System Air Conditioner
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
WARNING
Connect Ground and Power Wires
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig.6.
Figure 6
DISCONNECT PER N. E. C. AND/OR LOCAL CODES
FIELD POWER
WIRING
Line Power Connections
CONTACTO R
65F(18C). To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the Long Line Applications Guidelines.
Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when installing.
Check OAT Thermistor and OCT Thermistor Attachments
Outdoor Air Temperature (OAT) Thermistor is factory installed by inserting the nibs on either sides of the thermistor body through a keyhole in the bottom shelf of the control box and locking it in place by turning it 90 degrees, such that the spherical end of a nib faces the front of the control box.
Check to make sure the OAT is locked in place. See Fig. 7.
Figure 7
OAT Thermistor must be locked in place with spherical nib end facing towards the front of the control box.
Outdoor Air Thermistor (OAT) Attachment
DX+ DX- C
FIELD GROUND
WIRING
Connect Control Wiring
This unit is capable of communication with an Observer Wall Control, or will operate using standard 24v 2 - stage thermostat. Route 24v control wires through control wiring grommet and connect leads to control board. When an Observer Wall Control is available, connect DX+ and DX- connections only. If additional grounding is needed connect to C terminal. If a 2 - stage thermostat is used, connect to the C, Y1, and Y2 connections. Refer to the wiring label for further clarification.
Use No. 18 AWG color- coded, insulated (35_C minimum) wire. If thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use No. 16 AWG color- coded, insulated wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24- v/40- va minimum.
NOTE: Use of available 24- v accessories may exceed the minimum 40 - va power requirement. Determine total transformer load and increase the transformer capacity or split the load with an accessory transformer as required.
GROUND LUG
The Outdoor Coil Temperature (OCT) Thermistor is factory installed on the liquid tube between the coil assembly and the liquid service valve. See Fig. 8.
Check to make sure the thermistor is securely attached on the liquidtubewiththeclipasshowninFig.8.
Figure 8
Outdoor Coil Thermistor (OCT) Attachment
OCT Thermistor must be
secured tight on the liquid tube.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire c onnections for
secure and tight terminations. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit if ambient is less than
421 01 1702 05 5
Specifications subject to change without notice.
Airflow Setup with Observer Communicating Furnace or Fan Coil
When using an Observer Communicating Wall Control and communicating indoor equipment, airflow is automatically selected based on equipment size. See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments.
Loading...
+ 9 hidden pages