ICP HC4H3 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
R410A Ducted Horizontal Heat Pump
Product Family: HC4H3
Figure 1 - HC4H3
NOTE: Read the entire instruction manual before starting
the installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1........................
INSTALLATION 26..................................
Step 1 − Complete Pre−Installation Checks 2........
Step 2 Rig and Mount Unit 6.....................
Step 3 Complete Refrigerant Piping Connections 6..
Step 4 Make Electrical Connections 7.............
STARTUP 10.......................................
SERVICE 10........................................
MAINTENANCE 15...................................
TROUBLESHOOTING 1617..........................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety−alert
symbol instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
!
When you see this symbol on the unit and in
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
428 01 9700 03 Sep 2010
INSTALLATION
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
R410A refrigerant systems operate at higher pressures than standard R22 systems. Do not use R22 service equipment or components on R410A refrigerant equipment.
PERSONAL INJURY AND EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and / or equipment damage.
DO NOT operate the unit without a filter or with grille removed.
Step 1 —Complete PreInstallation Checks Unpack Unit
Move the unit to final location. Remove unit from carton, being careful not to damage service valves and grilles.
Inspect Shipment
File a claim with the shipping company if shipment is damaged or incomplete. Check the unit nameplates to ensure units match job requirements.
WARNING
!
CAUTION
Consider System Requirements
Consult local building codes and NEC for special installation requirements.
Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit. See Figure 3.
Locate unit so that condenser airflow is unrestricted on both sides. Refer to Figure 3.
Unit may be mounted on a level pad directly on base legs or mounted on raised pads at support points. See Figure 3 for center of gravity.
Matching the Heat Pump to an Indoor Unit
The HC4H3 ducted heat pump units can be matched to corresponding indoor units. The HC4H3 unit can be matched with underceiling and residential fan coils and evaporator coils. Refer to separate indoor unit literature for more information.
Expansion Device − Cooling Mode
A hard shutoff, thermostatic expansion valve (TXV) is required at the indoor section of the system for proper operation of these products. If the indoor section of the system is not equipped with a hard shutoff TXV, refer to Spec Sheet for the correct TXV kit to be installed. Follow the instructions in the kit for proper installation.
Check AccuRater Metering Device − Heating Mode
The correct AccuRater (bypass type) refrigerant control is required for system capacity optimization. An AccuRater device with fieldreplaceable piston is supplied with the outdoor unit (see Figure 2).
Do not interchange components between the AccuRater device types. Matching of outdoor unit with indoor unit may require field replacement of piston. Replace piston, if required, before connecting refrigerant lines. See Figure 2. Piston replacement instructions are included in the indoor unit installation instructions. After system installation is complete, see the Refrigerant Charging section in this document to check and/or adjust refrigerant charge.
2 428 01 9700 03
A07407b
Figure 2 - AccuRater (bypass type)
Metering Device Components
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 6 MIN CLEARANCE ON COIL SIDE AND COIL END AND 36 MIN CLEARANCE ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 8 MIN CLEARANCE ON FAN SIDE AND COIL END AND 36 MIN CLEARANCE ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION; ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
3. SERIES DESIGNATION IS THE 10TH POSITION OF THE
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING UNIT MODEL NUMBER.
MODE IS 55 $
5. ALL DIMENSIONS ARE IN INCHES UNLESS NOTED.
FIELD POWER SUPPLY CONN. HOLE SIZES PROVIDED: 7/81/2TRADE 1 3/16−3/4TRADE 1 3/8−1TRADE
F, MAX. 125 $F.
OPERATING
WEIGHT(lbs)
4. CENTER OF GRAVITY
14 1/2 8 1/2 18 7/8 7/8 3 7/16 6 1/2 278 303 50 1/2 X 20 1/2 X 46 2/10
14 1/2 8 1/2 18 7/8 7/8 3 7/16 6 1/2 306 331 50 1/2 X 20 1/2 X 46 2/10
11/168 1/8 15 7/8 3/4 3 7/16 6 1/2 187 210 50 1/2 X 20 1/2 X 40 2/10
3 11/168 1/8 15 7/8 3/4 3 7/16 6 1/2 232 255 50 1/2 X 20 1/2 X 40 2/10
6 5/8 11 1/4 5/8 2 15/16 6 167 183 42 9/10 X 18 X 28 1/10
14 6 3/4 11 5/8 5/8 2 15/16 6 176 194 42 9/10 X 18 X 34 1/10
4 3/16
2 1/2
1 7/16
JUNCTION BOX FOR POWER SUPLLY AND CONTROL CONNECTIONS
FIELD CONTROL SUPPLY WIRE ENTRY 7/8 HOLE W/GROMMET
1 1/2
8
L
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
MEASUREMENT ENGLISH
4 1/2
1
K
P
X = YES O = NO
N
7 1/2
AIR
E
J
AIR
B
460360
208/230360
230160
208230160
11/16
A
DIMENSIONS
FDC
UNIT SERIES ABC DE FG H J K L MNP
HC4H318 A XOOO25
HC4H324 A XOOO31
HC4H330 A XOOO37
HC4H336 A XOXX37
HC4H348 A XOXX43
HC4H360 A XOXX43
UNIT SIZE
Figure 3 - HC4A3 Unit Dimensions
428 01 9700 03 3
FIELD POWER SUPPLY CONN.
R
HOLE SIZES PROVIDED:
22.22 12.70 TRADE
30.16 19.05 TRADE
34.92 25.40 TRADE
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 152.4 MIN CLEARANCE ON COIL SIDE AND COIL END AND 914.4 MIN CLEARANCE ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 203.2 MIN CLEARANCE ON FAN SIDE AND COIL END AND 914.4 MIN CLEARANCE ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION; ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
85.0 95.4 1282.7 X 520.7 X 1020.7
105.4 115.9 1282.7 X 520.7 X 1020.7
126.4 137.7 1282.7 X 520.7 X 1173.1
WEIGHT(KG)
OPERATING
165.1
165.1
87.3 165.1
215.9 479.4 22.2 87.3
330.2 168.3 285.8 15.9 74.6 152.4 75.9 83.2 1090.2 X 457.7 X 714.3
355.6 171.5 295.3 15.9 74.6 152.4 80.0 88.2 1090.2 X 457.7 X 866.7
347.7 206.4 403.2 19.0
347.7 206.4 403.2 19.0 87.3
711.2
558.8
741.4 865.2
741.4 865.2
893.8 1017.6 368.3
3. SERIES DESIGNATION IS THE 10TH POSITION OF THE
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING UNIT MODEL NUMBER.
MODE IS 12.8 $
C, MAX. 51.7 $C.
139.0 150.4 1282.7 X 520.7 X 1173.1
165.1
215.9 479.4 22.2 87.3
893.8 1017.6 368.3
4. CENTER OF GRAVITY
5. ALL DIMENSIONS ARE IN MM UNLESS NOTED.
36.5
JUNCTION BOX FOR POWER SUPLLY AND CONTROL CONNECTIONS
FIELD CONTROL SUPPLY WIRE ENTRY
22.22 HOLE W/GROMMET
38.1
MEASUREMENT MET
203.2
114.3
25.4
L
UNIT SERIES ABC DE FG H J K L MNP
XOOO 638.2 938.2 369.9 406.4 595.3 436.6 435.0
XOOO 790.6 938.2 369.9 406.4 595.3 436.6 587.4
HC4H318 A
HC4H324 A
XOOO 944.6 1131.9 433.4 468.3 774.7 498.5
HC4H330 A
XOXX 944.6 1131.9 433.4 468.3 774.7 498.5
HC4H336 A
XOXX 1097.0 1131.9 433.4 468.3 774.7 498.5
HC4H348 A
XOXX 1097.0 1131.9 433.4 468.3 774.7 498.5
HC4H360 A
X = YES O = NO
VAPOR LINE CONN.M
63.5
106.4
FEMALE SWEAT CONN.
K
N
AIR
N
190.5
J
AIR
B
460360
208/230360
230160
208230160
17.5
A
DIMENSIONS
FDC
UNIT SIZE
4 428 01 9700 03
Figure 4 - HC4A3 Unit Dimensions
Table 1—HC4H31860 Physical Data
UNIT HC4H3 18 24 30 36 48 60 NOMINAL CAPACITY Tons 1.5 2.0 2.5 3.0 4.0 5.0 OPERATING WEIGHT lb (kg) 167 (75.75) 176 (79.83) 187 (84.82) 232 (105.23) 278 (126.10) 306 (138.80) REFRIGERANT TYPE R-410A METERING DEVICE TXV (Indoor Unit) CHARGE* (lb) (kg) 6.8 (3.89) 7.0 (3.18) 12.0 (5.45) 12.5 (5.68) 12.2 (5.55) 12.8 (5.82) COMPRESSOR
Type Scroll Oil Charge (POE -oz) 25.0 25.0 25.0 25.0 42.0 42.0 Crankcase Heater (watts) 40 40 40 40
OUTDOOR FAN
Rpm/Cfm 840/1720 840/1720 850/3900 850/3900 850/3900 850/3900 Diameter in. (mm) 18 (457) 18 (457) 24 (610) 24 (610) 24 (610) 24 (610) No. Blades 3 3 3 3 3 3 Motor (hp)
OUTDOOR COIL
Face Area sq. ft. (sq. m.) 5.8 (.54) 7.3 (.68) 12.1 (1.12) 12.1 (1.12) 14.1 (1.31) 14.1 (1.31) No. Rows 3 3 2 3 3 3 FPI 20 20 20 20 20 20
HIGH PRESSURE SWITCH
Cut-In (psig) Cutout (psig)
LOW PRESSURE SWITCH
Low Cutout (psig) Low Cut-in (psig)
REFRIGERANT LINES
Connection Type Sweat Liquid Line (in.) OD Vapor Line (in.) OD Max Length ft (m) 200 (60.96) Max Lift ft (m) 65 (19.81) Max Drop ft (m) 150 (45.72)
CONTROLS
Fusible Plug F (C) 210 (98.89) Control Voltage 24 vac System Voltage 208/230 v 208/230 v 208/230 v 208/230 v, Single and 3 Phase, 460 v, 3 Phase
FINISH Gray
* Unit shipped with full factory charge. See ARI (Air Conditioning and Refrigeration Institute) capacity table for proper charge and piston for each fan coil type.
Valve connection size is 7/8 inch. Recommended line size is 1-1/8 inches. 24 v and a minimum of 40 va is provided in the fan coil unit.
FPI - Fins Per Inch POE - Polyol Ester
1/8 1/8 1/4 1/4 1/4 1/4
420 ± 25 650 ± 10
20 ± 5
45 ± 25
420 ± 25 650 ± 10
20 ± 5
45 ± 25
5/8 3/4 7/8 7/8
420 ± 25
650 ± 10
20 ± 5
45 ± 25
3/8
420 ± 25 650 ± 10
20 ± 5
45 ± 25
420 ± 25 650 ± 10
20 ± 5
45 ± 25
420 ± 25 650 ± 10
20 ± 5
45 ± 25
428 01 9700 03 5
Step 2 —RIG AND MOUNT UNIT Mounting on Ground
Mount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly onto unit. Use fieldprovided snow stand or ice rack where prolonged subfreezing temperatures or heavy snow occurs.
If conditions or local codes require unit be fastened to a pad, 6 field−supplied tiedown bolts should be used and fastened through slots provided in unit mounting feet.
Mounting on Roof
Mount unit on a level platform or frame at least 6 in. (152.4 mm) above roof surface. Isolate unit and tubing from structure.
Rigging
!
PERSONAL INJURY AND/OR EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and/or equipment damage. Be sure unit panels are securely in place prior to rigging.
Keep the unit upright and lift unit using a sling. Use cardboard or padding under the sling, and spreader bars to prevent sling damage to the unit. See Figure 5. See Figure 3 for center of gravity reference. Install the unit so that the coil does not face into prevailing winds. If this is not possible and constant winds above 25 mph are expected, use accessory wind baffle. See installation instructions provided with the accessory kit.
NOTE: Accessory wind baffles should be used on all units with accessory low ambient temperature control.
Fieldfabricated snow or ice stands may be used to raise unit when operation will be required during winter months. Units may also be wall mounted using the accessory wall mounting kit.
CAUTION
Step 3 —COMPLETE REFRIGERANT PIPING CONNECTIONS
Outdoor units may be connected to indoor units using fieldsupplied tubing of refrigerant grade and condition. See Table 1 for correct line sizes. Do not use less than 10 ft (3.05 m) of interconnecting tubing.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4 mm) vertical rise to the valve connections on the outdoor unit. If more than the recommended length is buried, refrigerant may migrate to cooler, buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start−up.
When more than 80 ft (24.38 m) of interconnecting tubing and more than 20 ft (6.10 m) of vertical lift is used, consult the residential Long Line Application Guide for required accessories. If either refrigerant tubing or indoor coil is exposed to the atmosphere, the system must be evacuated following good refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding unnecessary turns and bends. Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to structure. Also, when passing refrigerant tubes through a wall, seal the opening so that vibration is not transmitted to structure. Leave some slack in refrigerant tubes between structure and outdoor unit to absorb vibration. Refer to separate indoor unit installation instructions for additional information.
Filter Drier
Refer to Figure 6 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from step 1.
4. Connect and braze liquid refrigerant tube to the filter drier.
CAUTION
Figure 5 - Lifting Unit with Sling
6 428 01 9700 03
A07396
A05227
Figure 6 - Filter Drier Components
The filter drier must be replaced whenever the refrigeration system is exposed to the atmosphere.
Only use factory specified liquid−line filter driers with rated working pressures less than 600 psig.
NOTE: Do not install a suctionline filter drier in liquid line.
Loading...
+ 11 hidden pages