INSTALLATION INSTRUCTIONS
For Natural Gas to Propane Conversion Kit Model No:
NAHA00701LP or Part No. (1178473)
This kit is designed to convert *9UHX and *9MPX Natural Gas furnace to Propane Gas furnace.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock,
or other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency, or
your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes,
the current editions of the National Fuel Gas Code (NFCG) NFPA
54/ANSI Z223.1, National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the National standards
of Canada CAN/CSA-B149.1 and .2 Natural Gas and Propane
Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol /_ .
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety-alert symbol. DANGER identifies
the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
General Information
This kit is for conversion of furnaces equipped with Honeywell VR8205S
Series single stage gas valves certified for use with Natural Gas (and so
marked) to units functionally the same as the certified furnace for use
with Propane Gas, Before the furnace can be operated with Propane
Gas, the low pressure switch must be installed. A gas valve conversion
kit must be installed and main burner orifices must be replaced with ori-
fices in this kit or with properly sized orifices for high altitude (or-
dered separately),
* Denotes Brand (T, H or C)
FIRE, EXPLOSION, ELECTRIC SHOCK, AND CAR-
BON MONOXIDE HAZARD.
This conversion kit shall be installed by a qualified
service technician in accordance with the Manufac-
turer's instructions and all applicable codes and re-
quirements of the authority having jurisdiction. If
the information in these instructions is not followed
exactly, a fire, an explosion or production of carbon
monoxide could result causing property damage,
personal injury or loss of life. The qualified service
agency is responsible for the proper installation of
this kit. The installation is not proper and complete
until the operation of the converted appliance is
checked as specified in the manufacturer's instruc-
tions supplied with the kit.
Cette trousse de conversion dolt 6tre install6e par
un service d'entretien qualifie, selon les instruc-
tions du fabricant et selon toutes les exigences et
tous les codes pertinents de rautorite competente.
Assurezvous de bien suivre les instructions dans
cette notice pour r6duire au minimum le risque d'in-
cendie, d'explosion ou la production de monoxyde
de carbone pouvant causer des dommages mate-
riels, des blessures ou la mort. Le service d'entreien
qualifi6 est responsable de rinstallation de cette
trousse. L'installation n'est pas ad6quate ni com-
pl6te tant que le bon fonctionnement de rappareil
convertin'a pas 6te verifi6 selon les instructions du
fabricant fournies avec la trousse.
This conversion kit shall be installed by a qualified service agency.
Please read these instructionscompletely before attempting instal-
lation. Consult gas supplier and tables in National Fuel Gas Code
NFPA 54/ANSI Z223.1, 2006 or latest edition. In Canada, the Na-
tional Standard CAN/CGA B149-1 and B149-2.
Parts List
Description Part# Qty,
Burner Orifice #55 1011354 6
Honeywell Conv. Kit (396221) 330733-401 1
Switch, Low Pressure(LGPS) 1008801 1
Fitting Asy. 1009775 1
Wire Asy. 1173071 1
Label, Field Conversion 1009678 1
Label, Propane Conversion 332874-101 1
Label, Derate 334836-101 1
Label, Conversion 336084-101 1
Label, Conversion 336085-101 1
Instructions 441 06 1082 00 1
Orifices for High Altitude Conversion (Not included in kit)
(Referto Table 1- for required orifice)
Burner Orifice #56 1011355 as required
Specifications subject to change without notice.
441 06 1082 00 June 2009
The orifices provided in this kit are stamped to indicate the size (twist
drill number) and are sized for commercially pure propane gas
ONLY. DO NOT use them with butane or a mixture of butane and
propane gas. The parts list specifies the size orifices supplied in the
kit. Compare the size marking on the orifices with the sizes as listed
in the parts list. Make sure you have the correct main burner orifices.
Extreme care is used to assure that this kit contains the proper
orifices. Oversized orifices could result in hazardous
conditions, especially if the venting is inadequate. For that
reason, we recommend that the installer check the size of the orifice
with a new twist drill of the correct size. This procedure assures that
the orifices provided are the correct size.
Installation
2.
Tighten the orifices so they are seated and gas fight about 11/8"
(28.6mm) from the face ofthe orifice to the back ofthe manifold
pipe (Figure 2). Make sure orifice is installed straight so that it
forms a right angle (90°) to the manifold.
Figure 2 JRemove Orifices
ELECTRIC SHOCK, FIRE AND EXPLOSION
HAZARD.
Failure to follow this warning could result in
personal injury, death, equipment damage, and/or
property damage.
Turn OFF gas supply at manual gas valve before
turning OFF electric power supply and starting
conversion.
Turn OFF electric power supply at disconnect
switch or service panel before starting
conversion. Tag and lockout shutoff(s) with appro-
priate device warning labels. There may be more
than one disconnect.
Disassembly
Refer to Figure 1 and the following steps.
1. After disconnecting power and gas supply to the furnace,
remove the access door, exposing gas valve and burner
compartment.
2. Disconnect gas line from gas valve so manifold assembly can
be removed.
3. Disconnect wiring at gas valve. Be sure to note the proper
location of any and all electrical wiring disconnected.
4. Remove the four (4) screws holding the manifold and gas
valve to the manifold supports. Do not discard any screws.
5. Carefully remove the manifold assembly.
Figure 1
Disassembly
25-21-00
Figure 3
I .t1" (28.2mm)_
1.2t" (30.8ram)
J Changing Orifices
Measure from face of orifice
to the back side of the mani-
fold.
High Altitude Installation
Gas input rate on the furnace rating plate is for installation at up to
2000' (609.6m). The #55 burner orifices supplied in this kit are sized
for Propane Gas at full rate ONLY, for use between 0-2000' (0 -
609.6m) elevation. Do not use them above 2000' (609.6m) except
when noted by Table 1. Orifices for conversion at high altitude must
be ordered from Service Parts.
In the USA, derating of these furnaces at 2% (Natural Gas)
and 4% (Propane Gas) has been tested and design-certified
by CSA.
1- In Canada, the input rating must be derated 5% (Natural Gas)
and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6
to1371.6m) above sea level. Use the 2001 to 3000 (609.9 to
914.4m) column in Table 1.
Figure 4 J lgnitor Location in(mm)
21/16( 52. 39)
5/1o/8)_
i..............................;_ _,- ::o
t
\-- .....................................................................................................................................i
NOTE: Flame sensor has a different orientation in all 050
Main Burner Orifices
Remove the Natural gas (typically black) burner orifices from
the manifold assembly and replace them with the appropriate
Propane (silver) orifices furnished in the conversion kit unless
converting a high altitude unit, then see Table 1 for
appropriate orifices. (Figure 2)
44106 1082 00 Specifications subject to change without notice. 2
and alternate 040 input model&