ICP C9MPX100L20A2, H9MPX060F12A2, T9MPX080J16A2 Installation Guide

These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and
throughout this manual and other manual that may
apply to the product. DANGER - Immediate hazards which will result in
severe personal injury or death.
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or property damage.
NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals The signal word WARNING is used throughout
this manual in the following manner:
The signal word CAUTION is used throughout this manual in the following manner:
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures or product labels.
z_ Safety-alert symbol
When you see this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury.
TABLE OF CONTENTS
Start-up Check Sheet ......................... 3
Safety considerations .......................... 4
Safe Installation Requirements .................. 4
Installation ................................... 6
Combustion & Ventilation Air .................... 10
Vent and Combustion Air Piping ................. 14
Concentric Termination ......................... 32
Gas Supply and Piping ......................... 32
Electrical Wiring ............................... 37
Ductwork and Filter ............................ 38
Checks and Adjustments ....................... 41
Furnace Maintenance .......................... 43
Sequence of Operation & Diagnostics ............ 44
Wiring Diagram (*9MPX) ....................... 46
Technical Support ............................. 47
Use of the AHRI Certified TM Mark indicates a
manufacturer's participation in the program. For verification of certification for individual
products, go to www.ahridirectory.org .
International Comfort Products, LLC
Lewisburg, TN 37091 U.S.A.
www.icpusa.com
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-2009©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington, DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
Printed in U.S.A. Specifications are subject to change without notice. 440 01 1051 03 Dec. 2010
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage,
3ersonal injury and/or death.
Installation or repairs made by unqualified persons could result in equipment malfunction, property damage,
3ersonal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
3rocedures and equipped with proper tools and test
instruments. Installation must conform with local building codes and
with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI Z223.1, and National standards of Canada CAN/CSA-B149.1 and .2 Natural Gas and Propane
Installation Codes.
INSTALLER: Affix these instructions on or adjacent to the furnace.
CONSUMER: Retain these instructions for future reference.
Required Notice for Massachusetts Installations
Important
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA-54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
(a)
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1,
INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed, in addition, the installing plumber or gasfitter shall observe that a battery operated or
hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified license
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period
of thirty (30) days to comply with the above requirement; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state of local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the
Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c)
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by
the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d)
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the
following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e)
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts
lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and Gas
Fitters, 239 Causeway Street, Boston, MA 02114. 617-727-9952
44001 1051 03
Specifications are subject to change without notice.
Printed in U.S.A.
START-UP CHECK SHEET
For 95% Furnace
(This sheet is optional. Keep this page for future reference.)
Date of Start-Up:
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Setup Checks
Check the box when task is complete
Calculated Firing Rate:(See Checks and Section)..
Heating Check
Measured Line Pressure when Firing Unit:
Measured Manifold Gas Pressure:
Temperature of Supply Air: (o)__
Temperature of Return Air: (o)__
Temperature Rise (supply-return temperature): (o)__
In Rise (see furnace rating plate)? (o)__
Static Pressure (Ducts): Supply Air Return __
Which blower speed tap is used? (Heating)
Optional Check: CO ? CO2 ?
Cooling Check
Temperature of Supply Air: (o)__
Adjustments
All Electrical Connections Tight?
Have hoses been relocated for furnace application (upflow/horizontal)?
Condensate Drain Connected?
Condensate Drain Trapped?
Manual Gas Shut-Off Upstream of Furnace/Drip-Leg?LU
Gas Valve turned ON?
Type of Gas: Natural: Lj
Filter Type and Size:
440 01 1051 03 Specifications are subject to change without notice. 3
Propane: Lj
Temperature of Return Air: (o)__
Temperature Difference: (o)__
Static Pressure (Ducts) cooling: Supply Air Return
Blower Speed Tap used for cooling:
Dealer Comments:
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock,
or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when
installing. Follow all safety codes. Wear safety glasses, protective
clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached
to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFCG) NFPA
54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the National standards of Canada CAN/CSA-B149.1 and .2 Natural Gas and Propane Installation Codes, and Canadian
Electrical Code CSA C22.1. Recognize safety information. This is the safety-alert
symbol z_. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are
used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could
result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is
used to highlight suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal
injury or death. Before performing service or maintenance operations
install lockout tag. Unit may have more than one power switch.
CARBON MONOXIDE POISONING AND FIRE HAZARD
Failure to follow safety warnings could result in personal injury, death, and/or property damage.
This furnace is not designed for use in mobile homes,
trailers or recreational vehicles.
CUT HAZARD
Failure to follow this caution may result in damage personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing,
safety glasses and gloves when handling parts and servicin 9 furnaces.
Safe Installation Requirements
FIRE, EXPLOSION, AND ASPHYXIATION HAZARD Improper adjustment, alteration, service,
maintenance or installation could cause personal injury, death and/or property damage.
Installation or repairs made by unqualified persons could result in hazards to you and others.
Installation MUST conform to local codes or, in the absence of local codes, with codes of all governmental authorities having jurisdiction.
The information contained in this manual is
intended for use by a qualified service agency that is experienced in such work, is familiar with all
precautions and safety procedures required in such work, and is equipped with the proper tools
and test instruments.
NOTE: This furnace is design-certified by the CSA International
(formerly AGA and CGA) for installation in the United States and Canada. Refer to the appropriate codes, along with this manual,
for proper installation.
Use only the type of gas approved for this furnace (see Rating Plate on unit). Overfiring will result in failure of heat exchanger and cause dangerous operation. (Furnaces can be converted to Propane gas with approved kit.)
Install this furnace only in a location and position as specified in "Installation" of these instructions.
Provide adequate combustion and ventilation air to the furnace as specified in "Combustion and Ventilation Air" of
these instructions. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as specified in "Vent and Combustion Air Piping" of these
instructions. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections, as
specified in "Gas Supply and Piping, Final Check" of these instructions.
Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which
has an external static pressure within the allowable range, as specified in "Technical Support Manual" of these instructions. See furnace rating plate.
4 Specifications are subject to change without notice. 440 01 1051 03
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
A gas-fired furnace for installation in a residential garage must be installed as specified in "Installation" of these
instructions.
This furnace is not to be used for temporary heating of buildings or structures under construction.
This furnace is NOT approved for installation in
mobile homes, trailers or recreation vehicles.
Seal around supply and return air ducts.
Install correct filter type and size.
Unit MUST be installed so electrical components are protected from direct contact with water.
SafetyRules
Your unit is built to provide many years of safe and dependable
service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and
create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission encourages
installation of carbon monoxide alarms. There can be various sources of carbon monoxide in a building or dwelling. The
sources could be gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas-fired fireplaces, wood
fireplaces.
Carbon monoxide can cause bodily injury and/or death. Carbon monoxide or "CO" is a colorless and odorless gas
produced when fuel is not burned completely or when the
flame does not receive sufficient oxygen. Therefore, to help alert people of potentially dangerous carbon
monoxide levels, you should have a commercially available carbon monoxide alarm that is listed by a nationally recognized testing agency in accordance with Underwriters Laboratories Inc. Standard for Single and Multiple Station
Carbon Monoxide Alarms, ANSl/UL 2034 or the CSA 6.19-01 Residential Carbon Alarming Devices installed and
maintained in the building or dwelling concurrently with the gas-fired furnace installation (see Note below). The alarm should be installed as recommended by the alarm
manufacturer's installation instructions.
B. There can be numerous sources of fire or smoke in a building
or dwelling. Fire or smoke can cause bodily injury, death, and/or property damage. Therefore, in order to alert people of potentially dangerous fire or smoke, you should have fire
extinguisher and smoke alarms listed by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below).
Note: The manufacturer of your furnace does not test any alarms
and makes no representations regarding any brand or type of alarms.
C. To ensure safe and efficient operation of your unit, you should
do the following:
1. Thoroughly read this manual and labels on the unit. This will help you understand how your unit operates and the hazards involved with gas and electricity.
2. Do not use this unit if any part has been under water. Immediately call a qualified service technician to inspect the
unit and to replace any part of the control system and any gas control which has been under water.
3. Never obstruct the vent grilles, or any ducts that provide
air to the unit. Air must be provided for proper combustion
and ventilation of flue gases.
FrozenWaterPipeHazard
WATER DAMAGE TO PROPERTY HAZARD Failure to follow this caution may result in property
damage. Do not leave your home unattended for long periods
during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and result in damage.
Your furnace is designed solely to provide a safe and comfortable living environment. The furnace is NOT designed to ensure that water pipes will not freeze. It is equipped with several safety devices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions.
If your furnace remains off for an extended time, the pipes in your home could freeze and burst, resulting in water damage.
If the structure will be unattended during cold weather you should take these precautions.
1. Turn off the water supply to the structure and drain the water lines if possible and add an antifreeze for potable water to
drain traps and toilet tanks. Open faucets in appropriate areas.
-or-
2. Have someone check the structure frequently during cold
weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required.
-or-
3. Install a reliable remote sensing device that wilt notify
somebody of freezing conditions within the home.
WinterShutdown
If you go away during the winter months and do not leave the heat on in your home, the plastic transition box and the condensate trap on the furnace must be protected from freeze damage.(See Figure 11 through Figure 20)
1. Disconnect the5/8"(15.9mm) OD rubber hose from the vent
drain fitting that is located downstream of the combustion blower. Insert a funnel into the hose and pour four(4) ounces of sanitary type (RV) antifreeze into the condensate trap.
Reconnect the 5/8" (15.9mm) OD rubber hose to the stub on
the vent drain fitting. Secure with the hose clamp.
2. Disconnect the 3/4" (19.1mm) OD rubber hose from the condensate trap. Insert a funnel into the hose and and pour four(4) ounces of sanitary type (RV) antifreeze into the plastic Transition box. Squeeze the hose together near the end and quickly reconnect the 3/4" (19.1mm) OD rubber
hose to the stub on the condensate trap. Secure with the hose clamp.
When you return home, your furnace will be ready to start, as it is not necessary to drain the antifreeze from the furnace.
440 01 1051 03 Specifications are subject to change without notice. 5
Installation
CARBON MONOXIDE POISONING HAZARD Failure to properly vent this furnace or other
appliances could result in personal injury or death. This furnace can NOT be common vented or
connected to any type B, BW or L vent or vent connector, nor to any portion of a factory-built or masonry chimney. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney
to prevent oversizing problems for the other
remaining appliance(s). See Venting and
Combustion Air Check in the Combustion &
Ventilation Air section. This furnace MUST be
vented to the outside.
InstallationPositions
This furnace can beinstalledin an upflow,horizontal (eitherleftor
right) or downflowairflow position. DONOT installthis furnace on its back. For the upflow position, the return air ductwork can be attachedto eitherthe left or rightside paneland/orthe bottom.For horizontal and downflowpositions,the returnair ductworkmust be
attached to the bottom. The return air ductwork must never be attachedto the back ofthefurnace.
Locationand Clearances
1. Refer to Figure 1 or Figure 2 for typical installation and basic connecting parts required. Refer to Figure 3 for
typical horizontal direct vent installation and basic
connecting parts required. Supply and return air plenums and duct are also required.
2. If furnace is a replacement, it is usually best to install the
furnace where the old one was. Choose the location or
evaluate the existing location based upon the minimum clearance and furnace dimensions (Figure 4).
Typical Upflow Installation
.... _H:_ (SeeVentTerminationShieldingfor dimensions)
8 (203 2...) iv,.
.... ,, ; _, ,, _ :__ Couplingon endsof
zU (b / m) tvlax '
in same ' _1 I_ _' exhaust pipe. Total
atmospheric _ (notusedon /' side structure = 8" zone _Ii SinglePipe / (203.2mm)
Vent PipesMUST
supported Horizontallyand
Vertically
* Increaseminimumfrom8" (203.2mm)to18" (457.2mm)forcoldclimates(sus- tainedtemperatures0°F (-17°C)and belowfor24 or moreconsecutivehours),
Aluminumornon-rusting shieldrecommended.
_ InletPipe pipe& couplingout-
"_ : - model)
Max.
zone
25-2,!-,!3
Typical Downflow Installation
See VentTermination Shieldingin VentSection.
_1 I_ '\_
InletPipe _ _ *8" (203.2mm) Min.
\
(notusedon_ _ 20' (6.1m) Max.in
Single Pipe _J_ sameatmosphericzone
model)
\
\
Coupling on inside andoutsideofwallto
restrainyen!pipe
\ 8" Min.
CARBON MONOXIDE POISONING HAZARD. Failure to follow this warning could result in
personal injury or death. Do NOT operate furnace in a corrosive atmosphere
VentPipesMUST
besupportedHorizon-
tally andVertically _.
(203.2mm) air
(6.1m)Max.
same osphericzone
containing chlorine, fluorine or any other damaging chemicals, which could shorten furnace life.
Refer to Combustion & Ventilation Air section,
/
Contaminated Combustion Air for combustion air
evaluation and remedy.
* Increaseminimumfrom8" (203.2mm)to18" (457.2mm)for coldclimates(sus- tainedtemperatures0°F (-17°C)andbelowfor 24 or moreconsecutivehours),
25-23-33a
FROZEN AND BURST WATER PIPE HAZARD Failure to protect against the risk of freezing may
result in property damage. Special precautions MUST be made if installing
furnace in an area which may drop below freezing. This can cause improper operation or damage to
equipment. If furnace environment has the potential of freezing, the drain trap and drainline must be protected. The use of electric heat tape or
RV antifreeze is recommended for these installations. (See "Condensate Trap Freeze
Protection Section"_
6 Specifications are subject to change without notice. 440 01 1051 03
InstallationRequirements
1. Install furnace level.
2. This furnace is NOT to be used for temporary heat of buildings or structures under construction.
3. Install furnace as centralized as practical with respect to the heat distribution system.
4. Install the vent pipes as short as practical, and in accordance to these instructions. (See Vent and
Combustion Air Piping section).
5. Maintain clearance for fire safety and servicing. A front clearance of 24" (609.6mm) required and 30" (762mm) recommended for access to the burner, controls and filter. See clearance requirements in Figure 4.
6. Use a raised base for upflow furnace if the floor is damp or wet at times.
7. For downflow installations, non combustible subbase must be used under the furnace unless installation is on a non
combustible floor surface. This requirement applies even when a coil box or cabinet is used.
8. For horizontal installations, line contact is permissible only between lines formed by intersection of back and two sides of furnace jacket, and building joists, studs or framing.
9. Residential garage installations require:
Burners and ignition sources installed at least 18" (457.2mm) above the floor.
Located or physically protected from possible damage by a vehicle.
10. Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in
attic application.
This furnace may be used for construction heat provided that all the following conditions are met:
The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products
into the structure.
The furnace is controlled by a thermostat. It may not be "hot
wired" to provide heat continuously to the structure without
thermostatic control.
Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is
maintained between 55° F (13° C)and 80° F (27° C), with no evening setback or shutdown. The use of the furnace while
the structure is under construction is deemed to be
intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the
rating plate value.
The filters used to clean the circulating air during the
construction process must be either changed orthoroughly cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise and venting according to these instructions.
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging chemicals, which could shorten furnace life.
Refer to Combustion & Ventilation Air section, Contaminated Combustion Air for combustion air
evaluation and remedy.
FurnaceInstallationConsiderations
The installation of the furnace for a given application will dictate the position of the furnace, the airflow, ductwork connections, vent and combustion air piping. Consideration must be given to the following:
CondensateTrap and Drain Lines
The supplied condensate trap must be attached to the furnace side panel on either the left or right side. For horizontal installations, the drain trap is vertically attached to the side panel below the furnace. A minimum clearance of 6" (152.4mm) below the furnace is required for the condensate trap. Downward slope of the
condensate drain line from the condensate trap to the drain location must be provided. Adequate freeze protection of the drain
trap and the drain line must be provided. See "Condensate Drain Trap" section for further details.
Leveling
Proper leveling of the furnace must be provided to insure proper drainage of the condensate from the furnace. The furnace must be
level to within 1/4" (6.4mm) from front to back and from side to side for upflow and downflow installations or top to bottom for horizontal
installations.
Vent and CombustionAir Connections
For venting information literature, call 931.270.4100 with the complete model and serial number of the furnace. Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC $636. The special vent fittings and accessory concentric vent termination kits and accessory external drain trap have been certified to ULC $636 for use with those Royal Pipe and IPEX PVC vent components which have been certified to this standard. In Canada, the primer and cement must be of the same manufacturer as the vent system - GVS-65
Primer (Purple) for Royal Pipe or IPEX System 636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and GVS-65 PVC
Solvent Cement for Royal Pipe or IPEX System 636(1),M,PVC Cement for Flue Gas Venting, rated Class IIA, 65 deg C. must be
used with this venting system - do not mix primers and cements from one manufacturer with a vent system from a different
manufacturer. Follow the manufacturer's instructions in the use of primer and cement and never use primer or cement beyond its
expiration date. The safe operation, as defined by ULC $636, of the vent system is
based on following these installation instructions, the vent system manufacturer's installation instructions, and proper use of primer
and cement. All fire stop and roof flashing used with this system must be UL listed material. Acceptability under Canadian standard CSA B149 is dependent upon full compliance with all
installation instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service
personnel. The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be consulted before installation to determine the need to obtain a
permit.
(1) System 636 is a trademark of IPEX Inc.
440 01 1051 03 Specifications are subject to change without notice. 7
Consignes sp6ciales pour rinstallation de ventillation au Canada
Uinstallation faite au Canada dolt se conformer aux exigences du
code CSA B149. Ce syst_me de ventillation dolt se composer de tuyaux, raccords, ciments et appr_ts conformes au ULC S636. La tuyauterie de ventillation des gaz, ses accessoires, le terminal
concentrique mural ainsi que I'ensemble du drain de condensat
exterieur ont et6 certifies ULCS 636 pour I'application des
composantes Royal Pipe, IPEX PVC qui sont certifiees & ce
standard. Au Canada, I'appr_t et le ciment doivent _tre du m_me fabricant que le systeme d'evacuation. Uappr_t GVS-65 (Purple)
et le ciment-solvant GVS-65 doivent _tre utilise avec les Royal
Pipe. Systeme IPEX 636, appr_t PVC/CPVC, Purple pour
evacuation des gaz de combustion et systeme IPEX 636(1)'=,
ciment PVC pour evacuation des gaz de combustion, cots classe
IIA, 65 deg C. doivent _tre utitises avec le systeme d'evacuation
IPEX 636 - Ne pas combiner I'appr_t et le ciment d'un
manufacturier avec un systeme d'evacuation d'un manufacturier
different.
Bien suivre les indications du manufacturier Iors de t'utilisation de
I'appr_t et du ciment et ne pas utiliser ceux-ci si ladate d'expiration
est atteinte.
Uoperation securitaire, tel que definit par ULC S636, du systeme
de ventilation est base sur les instructions d'installation suivantes,
ainsi que I'usage approprie de I'appr_t et ciment. Tout arret feu et
solin de toit utilises avec ce systeme doivent _tre des materiaux
listes UL. L'acceptation du standard Canadien CSA B419 est
directement relie & I'installation conforme aux instructions ci- haut
mentionnees. Le standard Canadien recommande I'inspection
par un personel qualifie et ce, une fois par annee.
Les autoritees ayant juridiction (inspecteurs de gas, inspecteurs
en b&timents, departement des incendies, etc) devraient _tre
consultees avant I'instatlation afin de determiner si un permis est
requis.
On the Dual Certified furnace, the vent and combustion air pipes
attach to the furnace through the top panel for the upflow and
horizontal installations. For the downflow installation, the vent and
combustion air pipes attach to the furnace through the alternate
locations on the furnace side panels.
Note: On the Direct Vent furnace, the vent pipe attaches to the furnace through the side panels. The combustion air pipe attaches to the top panel or to the alternate location on the side panel.
On the Single Pipe furnace, the vent pipe attaches to the furnace through the furnace side panels.
Note: Repositioning of the combustion blower is required for the vent pipe connection to the furnace through the "right side" panel.
See "Vent and Combustion Air Piping" section for further details.
HorizontalFurnaceInstallation
Typical Horizontal Installation
Inlet Pipe (notusedonSinglePipemodel)
Vent
Pipe
_'] Condensate
__ Trap
\h --4:
25-23-34
NOTE:5" (127mm) bottom clearance required for condensatetrap.
This furnace can be installed horizontally in an attic, basement, crawl space, alcove, or suspended from a ceiling in a basement or utility room (See Figure 3). Do not install furnace on its back or in the reverse airflow positions as safety control operation will be adversely affected.
If the furnace is to be suspended from the floor joists in a crawl space or the rafters in an attic, it is necessary to use steel pipe straps or an angle iron frame to rigidly attach the furnace to prevent movement. These straps should be attached to the furnace bottom side with sheet metal screws and to the rafters or joists with bolts.
The preferred method is to use an angle iron frame bolted to the rafters or joists.
If the furnace is to be installed in a crawl space, consult local codes. A suitable concrete pad or blocks are recommended for crawl space installation on the ground. NOTE: 6" (152.4mm) bottom clearance required for condensate trap. 24" (609.6mm) inches between the front of the furnace and adjacent construction or other appliances MUST be maintained for service clearance. [30" (762mm) inches is required to remove furnace].
Keep all insulating materials clear from Iouvered door. Insulating materials may be combustible. The horizontal furnaces may be installed directly on combustible wood flooring or supports as long as all required furnace clearances are met. See Figure 3. This furnace MUST NOT be installed directly on carpeting or tile or other combustible material other than wood flooring or supports.
For horizontal installation over a finished living space. A field fabricated auxiliary drain pan with drain pipe is required to prevent damage by overflow due to blocked condensate drain.
8 Specifications are subject to change without notice. 440 01 1051 03
iiiiii;_iiiiiiiii!iiiiiiiiii_i_Xi:iiiiii!i!_iiiii_ii;¸;iiiiiii/!ii_;_;iiiiii!iiiiiiiiiiii;;i;;i;;iiiiii;iiiii/iiiiiiiiiiiii111i/ilil
_!_i_:! I Dimensions & Clearances
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
---1 F -- _AIRINTAKE
J
J
FVENT
/
TOP
/
G T
r n
LEFTSIDE 611/1__
TRAP (KO) (COUNTERFLOW)- (177.5t
r
ELECTRICAL
11/4
(318)
11/16(27) t
AIRINTAKE(KO) F _
TRAP (KO) (122.2) .... ,_)
UPFLOW/HORIZONTAL....._ _
21/4 (57.2)
THERMOSTAT"j _.... 7....
(177.8)
i'
131/4
(336.6)
1 IKOl
17/6
(47.6
I
I
I BOTTOM
D I
I I I L
_ 231/8
VENT......... \_ ./
..... 4i3116"_'\__ )(ALTERNATE)
./ /
215/8 _ 47/8
(549.3) (123.8)
24
(609.6)
(587.4)
_(34.9) (804.9)_
o_ 13/8 297/8
175/16 1913/16
(439.7) (503.2)
111/16
(42.9)
/
I i ;
]
i
I
I I
I I
1311/16
/
(347.7)
3111/1J
283/a
(730.3
Drawing is representative, _-1T//4---_
but some models may vary // ,(31.7!: _, ............ ii191/ " (7239
ALLO,MENS,ONS=
' IN = 25.4MM - ( ) 1_:/68((6_ '3 )_= _ ,/'
Unit Cabinet Bottom Top
Capacity A B C D E F G H
*9MPX060F12 191/8 175/6 21/6 143/4 43/8 41/2 21/2 91/2
*9MPX080J12 223/4 211/4 115/16 183/4 43/8 41/2 25/8 113/8
*9MPX080J16 223/4 211/4 115/16 183/4 43/8 41/2 25/8 113/8
*RMPXl00L20 241/2 23 7/16 23 43/6 41/2 21/4 121/4
(485,8) (447,7) (54) (374,7) (111,1) (1143) (63,5) (2413)
(577.9) (539.8) (49.2) (476.3) (111.1) (114.3) (66.7) (266.9)
(577,9) (539,8) (49,2) (4763) (111,1) (1143) (6&7) (28&9)
(6223} (584,2) (11,1} (5842) (111,1} (1143} (57,2) (311,2)
MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS FOR ALL UNITS - in (mm)
REAR 0 FRONT (combustion air openings in 3" (76.2)
furnace and in structure)
Required For Service
A
ALL SIDES Of SUPPLY PLENUM
SIDES VENT TOP OF FURNACE
FRONT
*30" (762mm)clearancerecommendedforfurnaceremoval.
Horizontalposition:Linecontactis permissibleonly between linesformedbyintersectionsoftop and twosidesoffurnace
acket,and buildingjoists, studsor framing.
NOTE: Evaporator "A" coil drain pan dimensions may vary from furnace duct opening size. Always consult evaporator specifications for duct size requirements.
Furnace is designed for bottom return or side return.
Return air through back of furnace is NOT allowed.
/ _ _-_. --- 281/2
46/16 ,
GAS(KO)\
13/16
(30.2) (122,2)
297/.8
(758.6)
273/6
(690.61215/_ 913/16 (549.3 (249.2)
3311h. (439.7)
(855._1' 1111/_e
Y v v _
KO= KnockOut (123.8)
\
.... ' TRAP(KO)
,_/ (COUNTERFLOW)
b_ _ / /
__, _ ELECTRICAL(KO)
/ \ _AIRINTAKE(KO)
413/16
"\J iS_-_ (ALTERNATE) / _. _.----VENT(KO)
<_ TRAPIKOI
_/6 _-
..... 7 _,I \_ 21/4 _
(177.8) THEXRMOSTAT(57.2)_
175/16
/14291
_- 47/8
/ RIGHTSIDE
UPFLOW/HORIZONTAL
131/4
336.6
215/8
(549.3) 17/8
24 (47.6)
(609.6)
*24" (609.6)
1" (25.4)
0 0
1" (25.4)
3/4 (19.1 TYPE
L
4O
(lO16)
* Denotes Brand
25-23-36b
440 01 1051 03 Specifications are subject to change without notice. 9
Knockouts
.........................................................................................................................................................for Knockout
Hammer and Screwdriver used
CUTHAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate clothing, safety glasses and gloves when handling parts and
servicing furnaces.
Use a hammer and screwdriver to strike a sharp blow ( See Figure 5) directly to the knockout tie points or use a hammer in the upper left corner of the desired knockout. Remove any burrs and
sharp edges.
Combustion & Ventilation Air
ForSinglePipeInstallation
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Provide adequate combustion and ventilation air.
Use methods described here to provide combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or
openings for supplying combustion and ventilation air must comply with the gas codes, or in the absence of local codes, the applicable national codes.
Combustion and ventilation air must be supplied in accordance with one of the following:
Note: The Combustion & Ventilation Air Section in this document,
uses tables and information from the ANSI Z223.1/NFPA
54. For use in Canada, use CSA B149.1 for this information.
1. Section 9.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, (NFGC), ANSI Z223.1/NFPA 54-2009 inthe
U.S.,
2. Sections 8.2, 8.3, 8.5, 8.6, 8.7, and 8.8 of National Standard of Canada, Natural Gas and Propane Installation Code
(NSCNGPIC), CSA B149.1-05 in Canada,
3. Applicable provisions of the local building code.
I
i0 \ i / 'i
i f_ / ;;
/ /
\i
'\'9'!
i
25-40-06
NOTE: If a knockout does not come out after two sharp blows, pull and snip as needed to remove the knockout.
This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a factory-built or masonry chimney. Multistory venting is NOT permitted. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the other remaining appliance(s). See "Venting and Combustion Air Check" in this
section. This furnace MUST be vented to the outside. When the installation is complete, check that all appliances have
adequate combustion air and are venting properly. See Venting
And Combustion Air Check in "Gas Vent Installation" Section in
this manual.
OutdoorCombustionAirMethod
A space having less than 50 cubic feet per 1,000 BTUH (4.8 cubic meters per kW) input rating for all gas appliances installed in the
space requires outdoor air for combustion and ventilation.
AirOpeningsand ConnectingDucts
1. Total input rating for all gas appliances in the space MUST be considered when determining free area of openings.
2. Connect ducts or openings directly to the outdoors.
3. When screens are used to cover openings, the openings MUST be no smaller than 1/4" (6.4mm) mesh.
4. The minimum dimension of air ducts MUST NOT be less than 3" (76.2mm).
5. When sizing a grille, louver, or screen use the free area of opening. If free area is NOT stamped or marked on grill or louver, assume a 20% free area for wood and 60% for metal. Screens shall have a mesh size not smaller than 1/4" (6.4mm).
/'
/
10 Specifications are subject to change without notice. 440 01 1051 03
GasVent
Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
This installation NOT approved in Canada GasVent
Above Insulati,alternateInletAir (1) _ _1 _ 1_- _- _- _- _- _- _- _- _- _- _-=_
_ GasVent _ Outlet _ _ II II JILL[-- ou
OutletAir (1) SoffitVent I1_11 _ I II 3| II II (2)
_ n _Vventilated Attic_ Air (,) I II Airtlet
._../ GableVent _ ;::1i lr _-
/,IFI1 p bovelnsulation IrU-1 II II
I II I10utletAir(1) SoffitVentI."leL,_Fu'_cd Iw_;I ___-[_LL Inlet
I LL_ -,rt,, ]_._ I p,°rl L,_IFI._ Air (2)
I I I _ MinimumOneInlet and OneOutletAir Supply is Required I I I I I Inlet May be in anyCombinationShown
Inlet _ ...... IU _ InletAir OpeningMustbeWithin12"(304.8mm)°f fl°°r
alternatelnletAir (1) Air(l) _ I I_1 _1_ OutletAir OpeningMustbe Withinl2,, (304.8mm)of ceiling
ConfinedSpaceInstallation
NOTE: A confined space is defined as an area with less than 50
cubic feet per 1,000 BTUH (4.8 cubic meters per kW) input rating
for all gas appliances installed in the area.
Requirements
1.
Provide the space with sufficient air for proper combustion and
ventilation of flue gases using horizontal or vertical ducts or
openings.
2. Figure 6 illustrates how to provide combustion and ventilation air when two permanent openings, one inlet and one outlet, are
used.
a. One opening MUST commence within 12" (304.8mm) of
the floor and the second opening MUST commence
within 12" (304.8mm) of the ceiling. b. Size openings and ducts per Table 1. c. Horizontal duct openings require 1 square inch of free
area per 2,000 BTUH (11 cm2/kW) of combined input for
all gas appliances in the space (see Table 1). d. Vertical duct openings or openings directly
communicating with the outdoors require 1 square inch
of free area per 4,000 BTUH (5.5 cm2/kW) for combined
input of all gas appliances in the space (see Table 1).
3. When one permanent outdoor opening is used, the opening requires:
Air (2)
(1) 1SquareInch per4000 BTUH (2) 1SquareInch per2000 BTUH
a. 1 sq. in of free area per 3,000 BTUH (7 cm2/kW) for
combined input of all gas appliances in the space (see Table 1) and
b. not less than the sum of the areas of all vent connectors in
the space.
The opening shall commence within 12" (304.8mm) of the top of the enclosure. Appliances shall have clearances of at least 1"
(25.4mm) from the sides and back and 6" (152.4mm) from the
front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with
the outdoors.
4. Combination of Indoor and Outdoor Air shall have: a. Indoor openings that comply with the Indoor
Combustion Air Method below and
b. Outdoor openings located as required in the Outdoor
Combustion Air Method above and
c. Outdoor openings sized as follows.
1) Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method.
2) Outdoor opening size reduction Factor is I minus the Ratio in 1) above.
3) Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above
multiplied by reduction Factor.
Free Area
STUB(kW)
MinimumFreeAreaRequiredfor EachOpeningorDuctto Outdoors
Input TwoHorizontalDucts SingleOpening TwoVerticalDuctsorOpenings RoundDuct
Rating BTUH(kW) BTUH(kW) BTUH(kW) BTUH(kW)
sq.in./2,000(1cm2/,09) sq.in./3,000(1cm2/,135) sq.in./4,000(1cm2/,18) sq. in./4,000(6,5cm2/,18)
60,000(17.58) 30sq.in.(194cm2) 20sq.in.(129cm2) 15sq.in.(97cm2) 5" (127mm) 80,000(23.45) 40sq.in.(258cm2) 26.7sq.in.(172.3cm2) 20sq.in.(129cm2) 5" (127mm)
100,000(29.31) 50sq.in.(322cm2) 33.3sq.in.(214.8cm2) 25sq.in.(161cm2) 6" (152.4mm)
EXAMPLE: Determining Free Area
Furnace Water Heater Total Input 100,000 + 30,000 = (130,000 + 4,000) 32.5 Sq. In. Vertical
29.31 8.8 (38.11 + .18) 210 cm_ Vertical
Furnace Water Heater Total Input 100,000 + 30,000 = (130,000 + 2,000) 65 Sq. In. Horizontal
29.31 8.8 (38.11 + .09) 423 cm2 Horizontal
440 01 1051 03 Specifications are subject to change without notice. 11
IndoorCombustionAir(UnconfinedSpace)
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Most homes will require additional air from
outdoors for combustion and ventilation. A space
with at least 50 cubic feet per 1,000 BTUH (4.8 cubic
standard method permits indoor air to be used for combustion and
ventilation air. The Known Air Infiltration Rate Method shall be used if the
infiltration rate is known to be less than 0.40 air changes per hour
(ACH) and equal to or greater than 0.10 ACH. Infiltration rates
greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the
minimum required volume for each appliance in the space, and add the volumes together to get the total minimum required
volume for the space.
meters per kW) input rating or homes with tight construction may need outdoor air, supplied
through ducts, to supplement air infiltration for
CARBON MONOXIDE POISONING HAZARD
proper combustion and ventilation of flue gases.
Failure to supply additional air by means of
Standardand Known-Air-lnfiltrati0n Rate Methods
© NFPA &AGA
Indoor air is permitted for combustion and ventilation, if the Standard or Known-Air-Infiltration Rate Method is used.
The Standard Method may be used, if the space has no less volume than 50 cubic feet per 1,000 BTUH (4.8 cubic meters per
kW) input rating for alt gas appliances installed in the space. The
i .-,-,_ =. MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS
OtherThanFan-AssistedTotal Fan-assistedTotal
30,000BTU 40,000BTU 50,000BTU 50,000BTU 75,000 100,000BTU 125,000BTU
ACH (8,790kW) (11,720kW) (14,650kW) (14,650kW) (21,975kW) (29,300kW) (36,625kW)
0.60 1,050(29.7)
0.50 1,260(35.3)
0.40 1,575(44.1)
0.30 2,100(58.8)
0.20 3,150(88.2)
0.10 6,300 (176.4)
0.00 NP
ACH= Air Changes per Hour
NP = Not Permitted
Table 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI
Z223.1/NFPA 54-2009, 9.3.2.2:
1. For appliances other than fan-assisted appliances (such as a draft hood-equipped water heater), calculate using the
following equation:
Required Volume other _ 21ft3 ( .°ther )
-- ACH 1000 BTUH
1,400(39.2) 1,750(49) 1,250(35) 1,875(52.5) 2,500(70) 3,125(87.5)
1,680(47.04) 2,100(58.8) 1,500(42) 2,250(63) 3,000(84) 3,750(105)
2,100(58.8) 2,625(73.5) 1,875(52.5) 2,813(78.8) 3,750(105) 4,688(131.3) 2,800(78.4) 3,500(98) 2,500(70) 3,750(105) 5,000(140) 6,250(175)
4,200(117.6) 5,250(147) 3,750(105) 5,625(157.5) 7,500(210) 9,375(262.5)
8,400 (235.2) 10,500 (294) 7,500 (210) 11,250 (315) 15,000 (420) 18,750 (525)
NP NP NP NP NP NP
/ \
Required Volume other _ 59 m3 _k [ other )
2. For fan-assisted appliances (such as this furnace), calculate using the following equation:
RequiredVolume fan_ 15ft3 ( !fen )
-- ACH .293 kW
ACH 1000 BTUH
/ \
RequiredVolume fan _ .42 m3 _k ! fan )
ACH .293 kW
ventilation grilles or ducts could result in personal
injury or death.
An unconfined space or homes with tight
construction may not have adequate air infiltration for proper combustion and ventilation of flue gases.
Most homes will require additional air.
ft3(m3)
where:
! other= all appliances other than fan-assisted input in BTUH
! fan = fan-assisted appliance input in BTUH
ACH= air change per hour (percent of volume of space
exchanged per hour, expressed as a decimal)
3. For purposes of this calculation, an infiltration rate greater than 0.60 ACH shall not be used in the equations above.
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
. Adjoining rooms can be considered part of a space, if there
are no ctosable doors between rooms. Combining spaces on the same story. Each opening shall
have a minimum free area of at least 1 in.2/1,000 BTUH (22 cm2/kW) of the total input rating of all appliances in the space but not less than 100 in.2 (645 cm2). One opening shall commence within 12 in. (304.8 mm) of the top, and one opening shall commence within 12 in. (304.8 mm)of the
bottom, of the enclosure. The minimum dimension of air openings shall not be less than 3 in (76.2 mm).
Combining spaces in different stories. The volumes of spaces on different stories shall be considered as communicating
spaces where such spaces are connected by one or more
12 Specifications are subject to change without notice. 440 01 1051 03
openings in doors or floors having a total minimum free area of 2 in.2/1,000 BTUH (44 cm2/kW) of total input rating of all appliances.
An attic or crawl space may be considered a space that freely
communicates with the outdoors provided there are adequate
ventilation openings directly to outdoors. Openings MUST
remain open and NOT have any means of being closed off.
Ventilation openings to outdoors MUST be at least 1 square
inch of free area per 4,000 BTUH (5.5cm2/kW) of total input rating for all gas appliances in the space.
In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion,
ventilation and dilution of flue gases. However, in buildings
with unusually tight construction, additional air MUST be provided using the methods described in section titled
Outdoor Combustion Air Method:
Unusually tight construction is defined as Construction with:
1. Walls and ceilings exposed to the outdoors have a continuous, sealed vapor barrier. Openings are gasketed
or sealed and
2.
Doors and openable windows are weather stripped and
3.
Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between walt-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
VentilationAir
Some provincial codes and local municipalities require ventilation or make-up air be brought into the conditioned space as
replacement air. Whichever method is used, the mixed return air
temperature across the heat exchanger MUST not fall below 60°
so that flue gases wilt not condense excessively in the heat exchanger. Excessive condensation will shorten the life of the heat exchanger and possibly void your warranty.
VentingandCombustionAirCheck
NOTE: If this installation replaces an existing furnace from a
commonly vented system, the original venting system may no longer be sized to properly vent the attached appliances. An
improperly sized venting system may cause the formation of condensate in the vent and the leakage or spillage of vent gases.
To make sure there is adequate combustion air for all appliances,
MAKE THE FOLLOWING CHECK.
1111111111111111111111111111111111!]iili111iiiiililiiiliiliii!]Iiiliiliiii!iiiililliiiii
I I ontO.o°=
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation, could result in carbon monoxide poisoning or death:
The following steps shall be followed for each appliance connected to the venting system being
placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or CSA B149.1, Natural Gas and Propane Installation Code and these instructions. Deter-
mine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer
exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at
the draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle. (Figure 7)
8. If improper venting is observed, during any of the above
tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI
Z223. 1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when
tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
Vent Pipe "--'_1 I / Draft Hood
wTyPtieCra/eGatSr [ I I/ V,<.__" Match
If flame pulls towards draft hood, this indicates sufficient venting.
The following information is supplied to allow the installer to make
adjustments to the setup of existing appliances, IF REQUIRED, based on good trade practices, local codes, and good judgement of the installer. Manufacturer does NOT take responsibility for
modifications made to existing equipment.
440 01 1051 03 Specifications are subject to change without notice. 13
ForTwo PipeInstallation(DirectVent)
This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a factory-built or masonry chimney. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the other remaining appliance(s). See "Venting and Combustion
Air Check" in this section. This furnace MUST be vented to the
outside.
Vent and Combustion Air Piping
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Use methods described here to provide combustion
and ventilation air.
DualCertified(*9MPXModels)
This furnace is certified as a category iV appliance. This furnace
can be installed as a direct vent furnace using outside air for combustion or the furnace can use air from inside the structure for
combustion. The INLET air pipe is optional. If combustion air comes from inside the structure, adequate make up air MUST be provided to compensate for oxygen burned. See Confined Space
Installation in the Combustion and Ventilation Air chapter. If
combustion air is drawn from outside the structure, it MUST be
taken from the same atmospheric pressure zone as the vent pipe.
ContaminatedCombustionAir
Installations in certain areas or types of structures will increase the exposure to chemicals or halogens that may harm the furnace.
The following areas or types of structures may contain or have
exposure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air
for combustion.
* Commercial buildings. * Buildings with indoor pools.
* Furnaces installed in laundry rooms. * Furnaces installed in hobby or craft rooms.
Furnaces installed near chemical storage areas.
Permanent wave solutions for hair.
Chlorinated waxes and cleaners.
Chlorine based swimming pool chemicals.
Water softening chemicals.
De-icing salts or chemicals.
Carbon tetrachloride.
Halogen type refrigerants.
Cleaning solvents (such as perchloroethylene).
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid.
Sulfuric Acid.
Solvent cements and glues.
Antistatic fabric softeners for clothes dryers.
Masonry acid washing materials.
Ventand CombustionAirPiping Guidelines
This furnace is approved for venting with Schedule 40 PVC,
CPVC, ABS fittings, and Cellular Core and SDR-26 PVC pipe.
Applicable ASTM Standards for Vent Materials
Sch.40 SDR Cell Solv,
Materials Pipe Pipe Core Fittings Primer Cement
ABS D1527 F628 & -- D2235
PVC D1785 D2241 F891 & F656 D2564
CPVC F44t F442 -- F438 -- F493
ABS to
PVC
NOTE: 1) In Canada, all pipe, fittings & cements must conform to
applicable CSA standards or to local codes having jurisdiction.
the specific venting material.
solvent cement that meets the requirements of ASTM D3138.
cementing plastic pipe and fittings. NOTE: In order to create a seal that allows future removal of pipe,
RTV sealant MUST be used on the inlet pipe where it joins to the furnace.
NOTE: All vent piping MUST be installed in compliance with local codes or ordinances, these instructions, good trade practices, and codes of country having jurisdiction.
1. Determine the best routing and termination for the vent pipe
2. Determine the size required for the vent pipe and air inlet
3. Loosely assemble all venting parts without adhesive (pipe
4. Furnace shall be installed so as to prevent the accumulation
5. Use of vertical piping is preferred because there will be
6. The vertical vent pipe MUST be supported so that no weight
7. Exhaust vent piping or air inlet piping diameter MUST NOT
8. All exhaust vent piping from the furnace to termination
9. Use DWV type long radius elbows whenever possible, as
10. All horizontal pipe runs MUST be supported at least every
11. All vertical pipe runs MUST be supported every six feet
.......... D3138
2) Only use solvent cements that are marked for use with
3) ABS to PVC transition joints REQUIRE a special
4) Refer to ASTM D2855 for general procedure to use for
and air inlet pipe by referring to all of the instructions and guidelines in this Section.
pipe.
joint cement) for correct fit before final assembly.
of condensate.
some moisture in the flue gases that may condense as it
leaves the vent pipe (See Instructions For Horizontal
Vents).
is allowed to rest on the combustion blower.
be reduced.
MUST slope upwards. A minimum of 1/4" per foot (6.4mm per 304.8 mm) of run is required to properly return condensate to the furnace drain system.
they provide for the minimum slope on horizontal runs and they provide less resistance in the vent system. If DWV
elbows cannot be used, use two, 45° elbows when possible. On horizontal runs the elbows can be slightly misatigned to
provide the correct slope.
five feet with galvanized strap or other rust resistant material. NO sags or dips are permitted.
(1.8m) where accessible.
Pipe
D2468
D2661
D2466 D2665
14 Specifications are subject to change without notice. 440 01 1051 03
12.
The minimum vent length is 5' (1.5m) of PVC.
13.
The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing. It
can also be run in the same chase with a vent from another 90+ furnace.
NOTE: In NO case can the piping be run in a chase where
temperatures can exceed 140° F(60°C). or where radiated
heat from adjacent surfaces would exceed 140 ° F(60°C).
14. The vent outlet MUST be installed to terminate in the same atmospheric pressure zone as the combustion air inlet.
15. The vent system can be installed in an existing unused chimney provided that:
Both the exhaust vent and air intake run the length of the chimney.
No other gas fired appliance or fireplace (solid fuel) is
vented into the chimney.
The top of the chimney MUST be sealed flush or crowned up to seal against rain or melting snow so ONLY the piping protrudes.
The termination clearances shown in Figure 8 & Figure 9
are maintained.
16.
Furnace applications with vertical vents requiring vent diameter increaser fittings must have increaser fittings installed in vertical portion of the vent. Condensate will be
trapped in the vent if the vent diameter is increased prior to
having an elbow turned upward. This could cause nuisance
tripping of the pressure switch.
CombustionAirandVentPiping Insulation Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent. If Fiberglass or equivalent insulation is used it must have a vapor barrier. Use R values of 7 up to 10' (3.1m), R-11 if exposure
exceeds 10' (3.1m). If Fiberglass insulation is used, exterior to the structure, the pipe MUST be boxed in and sealed against
moisture.
1. When the vent or combustion air pipe height above the roof exceeds 30" (76.2mm), or if an exterior vertical riser is used
on a horizontal vent to get above snow levels, the exterior portion MUST be insulated.
2. When combustion air inlet piping is installed above a suspended ceiling, the pipe MUST be insulated with
moisture resistant insulation such as Armaflex or other equivalent type of insulation.
3. Insulate combustion air inlet piping when run in warm, humid spaces.
SizingCombustionAirandVentPipe
Consult Table3 select the proper diameter exhaust and combustion air piping. Exhaust and combustion air piping is sized
for each furnace BTUH size based on total lineal vent length (on
inlet or outlet side), and number of 90 ° elbows required. Two 45 ° elbows can be substituted for one 90° elbow. The elbow or elbows
used for vent termination outside the structure ARE counted, including elbows needed to bring termination above expected
snow levels. The elbow inside the furnace on the *9MPX IS NOT included in the count.
Pipe Diameter Table
*9MPX Model
60,000 BTUH Furnaces
10' (3m)& (2) 90° elbows with 1.5" (38.1mm) PVC pipeor
40' (12.2m)& (5)90° elbowswith 2" (50.8mm) PVC pipe or
70' (21.3m)& (5) 90° elbows with 3" (76.2mm)PVCpipe
80,000 BTUH Furnace
40' (12.2m)& (5)90° elbowswith 2" (50.8mm) PVC pipe or
40' (12.2m)& (5) 90° elbows with 3" (76.2mm)PVCpipe
100,000 BTUH Furnace
10' (3m) & (2) 90° elbows with 2" (50.8mm) PVCpipe or 40' (12.2m)& (5) 90° elbows with 3" (76.2mm)PVCpipe
The minimum vent length is 5' (1.5m) of PVC. Elbows are DWV Long Radius Type for 2" (50.8ram) and 3" (76.2mm) vents,
If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5' (1.5m) for each additional elbow used, If less than five elbows are required, the length can be INCREASED by 5' (1.5m) for each additional elbow
NOT used, NOTE: It is allowable to use larger diameter pipe and fitting than
shown in the tables but not smaller diameters than shown. For concentric vent pipe diameter see Concentric
Termination tables in this manual,
VentTerminationClearances
CARBON MONOXIDE POISONING Failure to follow this warning could result in
personal injury or death. Inlet and outlet pipes may NOT be vented directly
above each other.
1. Determine termination locations based on clearances specified in following steps and as shown in Figure 8,
Figure 9, Figure 22 through Figure 24.
For concentric vent termination clearances, refer to
Concentric Termination Kit instructions.
2. For Single Pipe Installation refer to Figure 9 for vent termination clearances.
3. For Direct Vent Installation refer to Figure 8 for vent termination clearances.
440 01 1051 03 Specifications are subject to change without notice. 15
Direct Vent Termination Clearance
/'
/
/
I_1 VENTTERMINAL \\\\\
(y AIR SUPPLY INLET
E_ AREAWHERE TERMINAL IS NOT PERMITED
Item ClearanceDescription CanadianInstallation(1) U.S. Installation(2)
A Clearanceabovegrade, veranda,porch, deck,balcony,or 12" (30cm)# 12" (30 cm)
anticipatedsnowlevel
B Clearanceto awindowordoorthat maybe opened 12" (30cm) forappliances> 10,000Btuh (3kW) and < 9" (23cm) for appliances > 10,000Btuh(3 kW)and < 50,000
100,000Btuh (30kW), 36" (91cm)for appliances > 100,000 Btuh(14.7 kW), 12" (30cm) forappliances > 50,000Btuh (14.7 Btuh(30 kW) kW)
C Clearanceto apermanentlyclosed window * *
D Verticalclearanceto a ventilatedsoffit locatedabovethe * *
terminalwithin a horizontaldistanceof 2' (61cm)from the centedineofthe terminal
E Clearanceto an unventilatedsoffit * * F Clearanceto an outsidecorner * *
G Clearanceto an insidecorner * *
H Clearanceto each side of the centedineextendedabove 3' (91cm) within 15' (4.5 m)abovethe meter/regulator *
electricalmeteror gasserviceregulatorassembly assembly
I Clearanceto seMce regulatorvent outlet 3' (91cm) *
J Clearanceto non-mechanicalair supplyinlet to buildingor 12" (30cm) for appliances > 10,000Btuh(3kW) and< 9" (23 cm)forappliances> 10,000Btuh(3 kW)and <
thecombustionair inlet to any otherappliance 100,000Btuh (30kW), 36" (91cm)forappliances > 50,000Btuh(15 kW),12" (30cm) for appliances> 50,000
100,000Btuh (30kW) Btuh(14.7 kW) K Clearanceto a mechanicalair supplyinlet 6' (1.83 m) 3' (91 cm)aboveif within 10' (3m) horizontally L Clearanceunder averanda,porch, deck,or balcony 12" (30cm)+ *
M Clearanceto each side of the centedineextendedaboveor 12" (30 cm) 12" (30cm)
belowventterminal ofthefurnace to a dryer or water heater vent,orotherappliance'sdirectvent intake orexhaust.
N Clearanceto thevent terminalof a dryervent, water heater 3' (91cm) 3'(91 cm)
O Clearancefroma plumbing ventstack 3' (91cm) 3'(91 cm)
P Clearanceabovea pavedsidewalkor paveddrivewaylocated 7' (2.13m) ** *
onpublicproperty.
> greaterthan, _>greaterthan orequalto, < lessthan, _ lessthanor equalto
(1.) Inaccordancewith the currentCSAB149.1, NaturalGasandPropaneInstallationCode (2.) Inaccordancewith the currentANSI Z223.1/NFPA54,NationalFuelGasCode # 18" (46cm)aboveroof surface
+ Permittedonlyif veranda,porch,deck,or balconyis fully openon a minimumoftwo sides beneaththefloor.
Forclearancesnotspecifiedin ANSI Z223.1/NFPA54 or CSAB149.1,clearancesshall bein accordancewith local installationcodesand
the requirementsofthe gas supplierandthe manufacture'sinstallationinstructions.
** A ventshall notterminatedirectlyabovea sidewalkor paveddrivewaythat is locatedbetweentwo singlefamily dwellingsand servesboth dwellings.
Notes:
1. The ventfor this applianceshallnotterminate a. Overpublicwalkways;or
b. Nearsoffitvents orcrawlspaceventsor other areas wherecondensateorvaporcouldcreate a nuisanceor hazardor propertydamage;or c. Wherecondensatevapor could causedamage orcouldbe detrimentaltothe operationof regulators,relief valves, or other equipment.
2. When locatingventterminations,considerationmustbe givento prevailingwinds,location,and other conditionswhichmay causeredrcolation ofthe combustionproductsof adjacentvents. Recirculationcan cause poor combustion,inletcondensateproblems,andacceleratedcorrosionofthe heatexchangers.
3. Avoidventingundera deck orlargeoverhang.Recirculationcouldoccur and cause performanceor system problems.
16 Specifications are subject to change without notice. 440 01 1051 03
Other than Direct Vent Termination Clearance
H
I_l VENT TERMINAL /')'_
\\
\X!" AIR SUPPLY INLET _ AREAWHERE TERMINAL IS NOT PERMITED
Item ClearanceDescriptions CanadianInstallation(1) U.S.Installation (2)
A Clearanceabovegrade, veranda,porch, deck,balcony,or 12" (30cm)# 12" (30 cm)
anticipatedsnowlevel
B Clearanceto awindowordoorthat maybe opened 12" (30cm) forappliances> 10,000Btuh (3kW) and < 4'(1.2 m) belowor to the side ofthe opening.1'(30 cm)above
100,000Btuh (30kW), 36" (91cm)for appliances > 100,000 the opening. Btuh(30 kW)
C Clearanceto apermanentlyclosed window * *
D Verticalclearanceto a ventilatedsoffit locatedabovethe * *
terminalwithin a horizontaldistanceof 2' (61cm)from the centerlineofthe terminal
E Clearanceto an unventilatedsoffit * * F Clearanceto an outsidecorner * *
G Clearanceto an insidecorner *
H Clearanceto each side of the centerlineextendedabove 3' (91cm) within 15' (4.5 m)abovethe meter/regulator 3' (91cm)within15' (4.5 m)abovethemeter/regulator
electricalmeteror gasserviceregulatorassembly assembly assembly
I Clearanceto sewiceregulatorvent outlet 3' (91cm) *
J Clearanceto non=mechanicalairsupplyinlettobuildingor 12" (30cm)forappliances > 10,000Btuh (3kW) and < 4' (1.2 m) belowor to the side of opening: 1' (30 cm) above
thecombustionair inlet to any otherappliance 100,000Btuh (30kW), 36" (91cm)forappliances > opening.
100,000Btuh (30kW)
K Clearanceto a mechanicalair supplyinlet 6' (1.83 m) 3' (91 cm)aboveif within 10' (3m)horizontally L Clearanceunder averanda,porch, deck,or balcony 12" (30cm)+ *
M Clearanceto each side of the centerlineextendedaboveor * *
belowventterminal ofthefurnace to a dryer or water heater vent,orotherappliance'sdirectvent intake orexhaust.
N Clearanceto thevent terminalof a dryervent, water heater * *
O Clearancefroma plumbing ventstack * *
Clearanceabovea pavedsidewalkor paveddrivewaylocated
P 7' (2.13m)** 7' (2.13m)
on punic property.
> greaterthan, _>greaterthan orequalto, < lessthan, _ lessthanor equalto (1.) Inaccordancewith the currentCSAB149.1, NaturalGasandPropaneInstallationCode (2.) Inaccordancewith the currentANSI Z223.1/NFPA54,NationalFuelGasCode
# 18" (46cm)aboveroof surface + Permittedonlyif veranda,porch,deck,or balconyis fully openon a minimumoftwo sides beneaththefloor.
ForclearancesnotspecifiedinANSIZ223.1/NFPA54orCSAB149.1,dearancesshallbe inaccordancewith localinstallationcodesandthe requirementsofthegas supplierandthemanufacture'sinstallation instructions.
A ventshall notterminatedirectlyabovea sidewalkor paveddrivewaythatis locatedbetweentwo singlefamily dwellingsand servesboth dwellings.
Notes:
1. The ventforthis applianceshallnotterminate a. Overpublicwalkways;or b. Nearsoffitvents orcrawlspaceventsor other areas wherecondensateorvaporcouldcreate a nuisanceor hazardor propertydamage;or c. Wherecondensatevapor could causedamage orcouldbe detrimentaltothe operationof regulators,relief valves, or other equipment.
2. When locatingventterminations,considerationmustbe givento prevailingwinds,location,and other conditionswhichmay causerecircolationofthe combustionproductsofadjacentvents. Recirculationcan cause poor combustion,inletcondensateproblems,andacoeleratedcorrosionofthe heatexchangers.
3. Avoidventingundera deck orlargeoverhang.Recirculationcouldoccur and cause performanceor system problems.
440 O1 1051 03 Specifications are subject to change without notice. 17
CondensateDrainTrap
This furnace removes both sensible and latent heat from the
products of combustion. Removal of the latent heat results in
condensation of the water vapor. The condensate is removed from the furnace through the drains in the plastic transition and the vent fitting. The drains connect to the externally mounted condensate
drain trap on the left or right side of the furnace. The startup of a new furnace will involve a cycle or two of the
furnace to properly prime the condensate trap with water. Until the trap is fully primed, some condensate wilt be pulled into the
combustion blower. The furnace may cycle on the pressure switch
connected to the plastic transition box due to condensate buildup. After the trap is primed, the condensate will start draining from the furnace. The combustion blower will clear out any remaining
condensate in the blower housing through the vent fitting
downstream of the blower. Note that the condensate trap can also
be primed by pouring water into the 1/2" (12.7mm) drain hose.
Remove the1/2 " (12.7mm) ID drain hose from either the gutter or the white PVC tee trap. Using a funnel pour eight (8) ounces (257
ml) of water into 1/2" ID drain hose. Water will flow through the drain
hose and into the condensate drain trap. This will prime both the vent and the transition sides of the trap. Reconnect the 1/2"
(12.7mm) ID drain hose to the original component, either the gutter
or the PVC tee trap. The condensate drain trap supplied with the furnace MUST be
used. The drain connection on the condensate drain trap is sized for 3/4" PVC or CPVC pipe, however alternate 1/2" CPVC [nominal
5/8" (15.9mm) O.D.] or vinyl tubing with a minimum inner diameter
(I.D.) of 5/8" (15.9mm) may also be used, as allowed by local
codes. Alternate drain pipes and hoses may be used as allowed by
local codes. The drain line must maintain a 1/4" (19.1 mm) per foot downward
slope toward the drain. 1/4" (19.1mm) per foot (304.8mm) is
recommended. Installation of an overflow line is recommended
when the 1/4" (19.1mm) per foot (304.8mm) slope to the
condensate drain cannot be maintained. A drain tube clip is
included in the furnace to prevent kinking/buckling of the drain tube. The clip should remain in the furnace (between the door
switch plate and the blower shelf, Figure 10) during operation. See
Figure 20 for proper routing and installation of the overflow.
Fi_} _0 !,i,iI ] Drain Tube Clip Location
FROZEN AND BURST WATER PIPE HAZARD Failure to follow this caution may result in property
damage. If a condensate pump is installed, a plugged
condensate drain or a failed pump may cause the
furnace to shut down. Do not leave the home
unattended during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes.
If possible, DO NOT route the drain line where itmay freeze. The drain line must terminate at an inside drain to prevent freezing of the condensate and possible property damage.
1. A condensate sump pump MUST be used if required by local codes, or if no indoor floor drain is available. The
condensate pump must be approved for use with acidic condensate.
2.
A plugged condensate drain line or a failed condensate pump will atlowcondensate to spill. If the furnace is installed where a condensate spill could cause damage, it is
recommended that an auxiliary safety switch be installed to
prevent operation of the equipment in the event of pump failure or plugged drain line. If used, an auxiliary safety switch should be installed in the R circuit (low voltage)
ONLY.
3.
If the auxiliary switch in the condensate pump is used, the
furnace may shut down due to a blocked condensate line or failed pump. To prevent frozen water pipes see the "Frozen
Water Pipe Hazard" Installation Section of this manual.
CondensateDrainTrap FreezeProtection
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to the equipment. If the the furnace environment has the potential of freezing, the drain trap and drain line must be protected. Use 3 to 6 watt per foot at 115 volt, 40° F self-regulating shielded and waterproof heat tape. Wrap the drain trap and drain line with the heat tape and secure with the ties. Follow the heat tape manufacturer's recommendations.
Drain Tube
Blower
Shelf
Representativedrawing only,some models may vary in appearance.
Door Switch
DO NOT trap the drain line in any other location than at the condensate drain trap supplied with the furnace.
18 Specifications are subject to change without notice. 440 01 1051 03
Upflow Installations Top Vent
-_ s ¸
VentDrain & Clamps
Dual Pressure Switch Detail
DrainConnectorBlack PVC
3/4" (18,1mm)PVCX 1/2"
(12,7mm)CPVC (Loose partsbag)
CasingGrommet // BlackRubber /
5/8"(15,9mm)ID - i" (Loosepartsbag)
Coupling&Clamps (Optional)
DrainTee....
DrainTube BlackRubber
1/2" (12,7mm)ID &
Clamps
DrainTube
Corrugated5/8"ID....
&Clamps
...............ONLY
......On
_ ==,,,,D % i
..... _r_ --, l_--_ _
\ <_, ,,7
. j-----
', i o o
SomeModels
ReliefTube
..............Black Rubber3/16"
(4.8mm)ID
Single Pressure Switch
Street Elbow
......... 1/2" (12.7mm) CPVC
.j-
(Loose parts bag)
DrainLineVentTee3/4" " ",, (18.1mm)PVCor1/2"(12.7mm) DrainTubeBlackRubber/8 (15.9mm)ID &
CPVC(Fieldsupplied) Clamps,Cutlengthtofit (Loosepartsbag)
25-24-80
Representativedrawingonly_somemodelsmayvaryinappearance.
Upflow Installations Top Vent (SeeFigure11)
Remove knockout from the side of the furnace casing where drain
tube will exit.
Install casing grommet [black rubber 518" (15.9mm) ID grommet- in loose parts bag]
Install the 1/2" CPVC street elbow on discharge of trap Install the black PVC tube connector [3/4" (18.1mm PVC x 1/2"
(12.7mm) CPVC from loose parts bag] as shown in the illustration above.
Cut the black drain tube [5/8" (15.9mm) ID -in loose parts bag] to length to fit between trap and tube connector through grommet.
Clamp both ends of the drain tube using clamps provided.
NOTE: "PVC" is used as a generic term. Pipe and fitting materials used must be acceptable to the local code officials having
jurisdiction.
Glue the CPVC street elbow to the trap using appropriate cleaner and solvent cement.
The field supplied 3/4" (18.1mm) PVC or 1/2" (12.7mm) CPVC drain line vent tee must vent outside the furnace cabinet (see
exploded view above). Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Trap must be primed before operation. Verify all condensate drain
connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of
the vent system.
440 01 1051 03 Specifications are subject to change without notice. 19
Upflow Installations Vent through Left Side
Plastic Cap
Yelloworblack
J
Coupling&Clamps (Optional).
Either:ThePVC
VentDrain & Clamps
essure Switch Detail
DrainConnectorBlackPVC
3/4"(19,1mm)PVCX1/2"
(12,7mm)CPVC
(Loosepartsbag),,\.....
CasingGrommet / \,
DrainTeeorafield supplied2"
(50.8mm)PVCTee
\
TeeTrapWhite PVC (loosepartsbag)
DrainTube BlackRubber
1/2"(12,7mm)ID
& Clamps DrainTube Corrugated
5/8"(15,9mm)ID &Clamps
,_\\ _\\
BlackRubber --. // \,\ .__- ', 5/8"(15,9mm)ID _ / '_ _ _-"
(Loosepartsbag) _ _ "_\_"_',,,,,
.... ,,
2" (50,8mm)PVC Coupling
/
q r
\
..... ---
.....OnSomeModels
i i
/;\
. ]_J.' -.
0 o j
ONLY
ReliefTube
.....Black Rubber3/16"
(4.8mm)ID
Single Pressure Switch
SIDE VIEW
Rotatedownward 5° to 100
]uilt-in channelwill
be angled5° to 10° also.
DrainLineVentTee3/4" (18,1mm)PVCor1/2"" (12.7mm)CPVC(Fieldsupplied)
Representativedrawingonly_somemodelsmayvaryinappearance.
25-24-81
Upflow Installations Vent through Left Side (SeeFigure12)
Remove drain tee from inducer discharge and remove black drain Cut the black drain tube [5/8" (15.9mm) ID - in loose parts bag] to
tube 1/2" (12.7mm) ID from bottom of drain tee. length to fit between trap and tube connector through grommet.
Install Vent Pipe grommet in side of casing. Clamp both ends of the drain tube using clamps provided. Cut an appropriate length of 2" (50.8mm) PVC pipe long enough
to exit the cabinet and connect the vent drain to either:
A standard field supplied 2" (50.8mm) PVC tee, or
A 2" (50.8mm) PVC coupling fastened onto the drain tee. Install tee trap into bottom of tee. Remove knockout from the side of the furnace casing where drain
tube will exit.
Install the 1/2" (12.7mm) CPVC street elbow on discharge of trap Install the black PVC drain connector [3/4" (19.1mm) PVC x 1/2"
CPVC from loose parts bag] as shown in the illustration above.
20 Specifications are subject to change without notice. 440 01 1051 03
Glue the CPVC street elbow to the trap using appropriate cleaner and solvent cement.
Connect the tee trap and the main drain line exiting the casing as shown in Figure 20.
Note: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both
the internal trap and the external tee trap must be primed before operation, Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
Downflow Left-Side Vent and Trap
j Plastic Cap
J Yellow or black
Coupling&Clamps (Optional)\
VentDrain
&Clamps Either:The PVC
Single Pressure Switch Detail \\
DrainTeeora field supplied2"
(50.8mm)PV_Tee
PartsBag)
WARNING MoveCapsto
topoftrap
2" (50.8mm)PVC
Coupling
/ DrainTube
/ / BlackRubber1/2"
// (12.7mm)ID&Clamps
/
/
Dual PressureSwitch
SIDE VIEW
__[ Rotatedownward
.L 5°to10°
,//% .....
NOT_B. uilt-in channel will be angled 5°to 10° also.
ReliefTubeBlackRub-
...._ber 3/16" (4.8mm)ID
\
.....OnSomeModels
,,Ljjj ONLY
INLET _,.
Flexible TubingConnector,3/16" (4.8mm)OD (loosepartsbag)
ReliefTube,ExtensionBlack
.......Rubber,3/16" (4.8mm)ID Cutto
fit (loosepartsbag)
TrapConnection
"Clampears"
PointedOUT
DrainTubeBlack,5/8"(15.9mm)ID CorrugatedCutatstraightsection {_i _ _-_ /_-_/._ _
I
i.......
...............A_,_,_,,_ _,............ BarbedCoupling1/2"(12.7mm)
Leaveroomforclamp _CutHere
Representativedrawing only_some modelsmay vary in appearance.
Downflow Left-Side Vent and Trap (SeeFigure13)
Remove the inducer mounting screws, rotate the inducer 180 ° and retighten the inducer screws to 20" pounds (2.26 newton
meter) torque. Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and
secure with screws. Move the caps to the top of the trap and mount the trap externally
to the left side of the unit using the two(2) screws provided.
Cut the 5/8" (15.9mm) ID corrugated hose as shown above and
fasten the 90° bend end to the trap and fasten the straight end to the transition drain. Secure both connections with clamps.
Reconnect the 1/2" (12.7mm) ID drain hose from the vent drain to
the trap and secure with a clamp. Insome cases, additional length
will be required for this hose. Use the Black plastic 1/2" (12.7mm) OD barbed coupling and a suitable section of 1/2" (12.7mm) ID
hose to make the connection. Secure all connections with clamps Connect the 3/16" (4.8mm) ID relief tube from the small port on the
trap to the top port of the transition as shown inthe picture. In some
OD(loosepartsbag)
\ J
Preassemble& insertinto furnace
cases, additional hose length will be needed. Use the clear plastic
3/16" (4.8mm) OD flexible tubing connector and a suitable length
of extra 3/16" (4.8mm) ID hose to make this connection. Install the vent pipe grommet into the casing Cut an appropriate length of 2" (50.8mm) PVC pipe long, enough
to exit the cabinet and connect the vent drain to either:
A 2" (50.8mm) PVC coupling fastened onto the drain tee Install tee trap into bottom section of tee and glue pipe. Remove knockout from the side of the furnace casing where drain
tube will exit. Connect the tee trap and the main drain line exiting the casing as
shown in Figure 20. Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation, Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
25-24-69
440 01 1051 03 Specifications are subject to change without notice. 21
Downflow Right-Side Vent and Trap
f- ".... _ J Yellowor black
VentDrain & Clamps
j Plastic Cap
SIDE VIEW
"-I-_ Rotatedownward
_J_ 5° to10°
i, :¢_ _ /,
NOT_J n_e_
be angled5°to 10" also.
Single Pressure Switch Detail
ElbowTube BlackRubber 1/2"(12.7mm)ID&Clamps
(LoosePartsBag)
Dual Pressure'Switch
Dr
]ir
TubeCorrugatedBlack,
5/8
' i
15.9mm)ID & Clamps
TrapConnection
ReliefTube BlackRubber
BarbedCoupling 1/2"(12.7mm)OD
(LoosePartsBag)
,\
/16"(4.8mm)ID
/
DrainHose /- _ BlackRubber| |
1/2" (12.7mm)I_
Preassemble &
insert intofurnace
"Clampears" PointedOUT
Coupling&Clamps
.(Optional)
,/
Cutto Fit&
Clamps
OnSome
Models
//////
ONLYJ
/ 2"(50.8mm)PVC
Coupling
Either:ThePVC DrainTeeorafield
supplied2"
(50.8mm)PVCTee
TeeTrapWhitePVC
.c
(loosepartsbag)
DrainConnectorBla( PVC3/4"(19.1mm)
WARNING
PVCX 1/?. (12.7mm)
CPVC(Looseparts
bag)
Representativedrawing only_some models may vary in appearance.
Downflow Right-Side Vent and Trap (SeeFigure14)
Remove the drain tee if installed. Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the
hole from the burner compartment to the blower compartment and secure with screws.
Move the caps to the top of the trap and mount the trap externally
to the right side of the unit using the two(2) screws provided.
Connect the corrugated drain tube from the transition box to the
trap as shown. If an extension isrequired, use the black PVC tube
connector and the black 5/8" (15.9mm) ID drain tube inthe loose parts bag. Cut tube to length. Secure all connections with clamps.
Connect the drain hose from the Vent Drain to the trap. If an extension is required, use the black 1/2" (12.7mm) OD barbed coupling, connect a black 1/2" (12.7mm) ID elbow tube and a
suitable section of a 1/2" (12.7mm) ID drain tube to make connection from the vent drain to the trap. Secure all connections
with clamps.
\\
\
_ DrainTube)BlackRubber,5/8"
(15.9mm)IDCuttofit &Clamps
(loosepartsbag)
25-24-69b
Install the vent pipe grommet into the casing Cut an appropriate length of 2" (50.8mm) PVC pipe long, enough
to exit the cabinet and connect the vent drain to either:
A 2" (50.8mm) PVC coupling fastened onto the drain tee Install tee trap into bottom section of tee. Remove knockout from the side of the furnace casing where drain
tube will exit. Connect the tee trap and the main drain line exiting the casing as
shown in Figure 20. Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation, Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
22 Specifications are subject to change without notice. 440 01 1051 03
Plastic Cap Yelloworblack
J
All Models Vent through Right Side
OnSomeModels ONLY
\
VentDrain & Clamps
Dual Pressure Switch
DrainTube Corrugated 1.
5/8"(15,9mm)ID & Clamps _
/'-_ _ Rotate downward _12_o_'_r_L_0i_ "-"_
/_ __ 5°to10° :; U/;
SIDEVIEW _ i_,;_;D6_i,_771:_, - /
be angled 5° to 10° also.
Representativedrawingonly,somemodelsmayvaryinappearance.
K_J _-!o; @g f
ReliefTube BlackRubber
3/16" <4,8mm)ID
Teeorafieldsupplied 2"(50.8mm)PVCTee
/
/
i'
/iSingle Pressure Switch Detail
Either:ThePVCDrain
/
F
H
k'X
I
TeeTrapWhitePVC (loosepartsbag)
ElbowTubes(2)BlackRubber 1/2"(12.7mm)ID&Clamps
(loosepartsbag)
BarbedCoupling,1/2"(12.7mm)OD (loosepartsbag)
...... . (18,1mm)PVCor 112"
DrainLineVentTee3/4"
/_ .... _\.. (12.7mm)CPVC(Fieldsup-
/ "y plied)
: DrainConnectorBlackPVC
3/4"(19.1mm)PVCX 1/2"
t (12.Vmm)CPVC
(Loosepartsbag)
/
_._ CasingGrommet
........ BlackRubber5/8"(15.9mm)CPVC
(Loosepartsbag)
25-24-82
All Models Vent through Right Side (SeeFigure15)
Disconnect the black drain tube between the drain vent and the
trap.
Rotate the inducer 180° for a right side vent after loosening the 4 inducer attachment screws. Reinstall and retighten the inducer
screws to 20" pounds (2.26 newton meter) torque. Using the 1/2" (12.7mm) OD barbed coupling in the loose parts bag
connect together with the 2 short 1/2" (12.7mm) ID elbow tubes and connect the lower discharge port of the vent drain to the trap.
Secure all connections with clamps. Install the vent pipe grommet into the casing
Cut an appropriate length of 2" (50.8mm) PVC pipe long enough
to exit the cabinet and connect the vent drain to either:
A standard field supplied 2" (50.8mm) PVC tee, or
A 2" (50.8mm) PVC coupling fastened onto the drain tee. Install tee trap into bottom section of tee. Remove knockout from the side of the furnace casing where drain
tube will exit.
Install casing grommet [black rubber [5/8" (15.9mm) ID grommet
- in loose parts bag]
440 01 1051 03 Specifications are subject to change without notice. 23
Install the 1/2" (12.7mm) CPVC street elbow on discharge of trap Install the black PVC tube connector [3/4" (19.1mm) PVC x 1/2"
(12.7mm) CPVC from loose parts bag] as shown in the illustration
above Cut the black drain tube [5/8" (15.9mm) ID - in loose parts bag] to
length to fit between trap and tube connector through grommet. Clamp both ends of the drain tube using clamps provided.
Glue the CPVC street elbow to the trap using appropriate cleaner and solvent cement.
Connect the tee trap and the main drain line exiting the casing as shown in Figure 20.
Note: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both
the internal trap and the external tee trap must be primed before operation. Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
Horizontal Left through Top
VentDrain & Clamps
t_
Plastic Caps Yellowor black
Alternate Orientation
Dual PressureSwitch
Single Pressure Switch Detail
_ ReliefTubeBlackRubber
3/16"(4.8mm)ID
oj JoJ
Flexibletubingconnector
3/16"(4,8mm)OD (Loose
PartsBag)
TrapConnection
[ / i _D ;_ ZZ" PontedOUT
...... _-_.,.._ ..
"_ _,-_3J ,¢7\?,'/
/' i' "z "Clampears"
--_ .
Preassemble& insertinto furnace
Field
SuppliedTee
TeeTrapWhitePVC
Coupling &Clamps /' DrainTube
(Optional) 1/2"(12,7mm)ID
Cap andClamp &Clamps OpenEnd [_
BlackRubber
(loosepartsbag)
Representativedrawingonly,somemodelsmayvaryinappearance.
Horizontal Left through Top (SeeFigure16)
Disconnect the hoses from the trap assembly, and remove trap and trap mounting bracket from the blower compartment. Using
cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and
secure with screws. Remove knockout from the side of the furnace casing where drain
tube will exit.
Mount the trap externally to the bottom side of the unit using the
two screws provided in the location shown.
Cut the corrugated tube as shown in the illustration above. Connect the corrugated hose from the transition to the trap.
Secure connections with clamps. Remove the black 1/2" (12.7mm) ID drain tube from the drain tee.
Install a yellow cap and clamp over the open drain port of the drain
tee.
Connect the black 1/2" (12.7mm) ID drain tube from the Vent Drain
to the trap. Secure connections with clamps.
ReliefTubeExtension
.......... Black Rubber3116" (4.8ram)ID
.... Cutto Fit(LoosePartsBag)
RemoveKObefore mountingTrap
DrainTubeCorrugatedDrainTubeCorrugated 5/8"(15,9mm)ID& Clamps Cutat straightsection
Leaveroomforclamp
I
25-24-84
Connect the 3/16" (4.8mm) ID relief tube to the middle port on the trap. Ifan extension is required, use the 3/16" (4.8mm) OD flexible
tubing connector and the black 3/16" (4.8mm) ID relief tube in the loose parts bag. Cut tube to length. Secure all connections with
clamps. Cut an appropriate length of 2" (50.8mm) PVC pipe, long enough
to exit the cabinet and connect the vent drain to either:
A standard field supplied 2" (50.8mm) PVC tee, or
A 2" (50.8mm) PVC coupling fastened onto the drain tee.
Install tee trap into bottom section of tee. Connect the tee trap and the main drain line exiting the casing as
shown in Figure 20. Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed
before operation, Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may
be installed as shown for future servicing of the vent system.
24 Specifications are subject to change without notice. 440 01 1051 03
_i_i{{_;iii]i_i{!_iii1_i_ii}{{{{i_;i_;7_i_i_Hi{7_i_{{{iij;{{_iii_!iii;t_i!iii_ii_i{i_}!_jiii1_{ii_i¸
......L iii"°r'z°nt°l,o vont
Alternate Orientation
Field Supplied Tee._\
TeeTrapWhitePVCj (loosepartsbag)
OnSome / - ModelsONLY
Single Pressure Switch Detail
TrapConnection
...... _,_
Yelloworblack
Plastic Cap
i
l-
-i-
x ILl
Level or Sloped towards Tee
i'
/
/'
/
/
\
/ \
Ii
_R ji
Z
]
/
-. _'_._'_._d_ ii
Dual Pressure Switch
ReliefTubeBlack Rub-
\
F _
...... ElbowTubeBlackRubber1/2"(12,7r
...... BarbedCouplingt/2"(12,7mm)OD
,/
/
& Clamps
Preassemble& insertinto furnace
ID&Clamps(LoosePartsBag)
(LoosePartsBag)
DrainTubeBlackRubber
t/2"(12,7mm)ID&Clamps
Im)
FlexibleTubeConnector3/16" (4.8mm)OD(LoosePartsBag/)/X
ReliefTubingExtension/ BlackRubber3/16" (4,8mm)ID Cutto Fit(LoosePartsBag)
Representativedrawingonly,somemodelsmayvaryinappearance.
Horizontal Left-Side Vent (SeeFigure17)
Remove the drain tee from the Vent Drain if installed. Rotate the inducer 180° for a side vent after loosening the 4
inducer attachment screws. Reinstall and retighten the inducer screws to 20" pounds (2.26 newton meter) torque.
Disconnect the hoses from the trap assembly, and remove trap and trap mounting bracket from the blower compartment. Using
cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and
secure with screws. Remove knockout from the side of the furnace casing where drain
tube will exit.
Mount the trap externally to the bottom side of the unit using the
two screws provided in the location shown.
Cut the corrugated tube as shown in the illustration above. Connect the corrugated hose from the transition to the trap.
Secure connections with clamps. Connect the black 1/2" (12.7mm) ID drain tube from the Vent Drain
to the trap. Ifan extension is required, use the black 1/2" (12.7mm)
OD flexible tubing connector and the black 1/2" (12.7mm) ID drain
tube in the loose parts bag. Cut tube to length. Secure
connections with clamps.
\.
/ /
/
/
\
\ ..... DrainTubeCorrugated/8 (15.9mm)
ID&Clamps
Cutatlstraightsection
C
Leaveroomforclamp _CutHere
Connect the 3/16" (4.8mm) ID relief tube to the middle port on the trap. Ifan extension is required, use the 3/16" (4.8mm) OD flexible tubing connector and the black 3/16" (4.8mm) ID relief tube in the
loose parts bag. Cut tube to length. Cut an appropriate length of 2" (50.8mm) PVC pipe, fittings and
extension pipe long enough to exit the cabinet and connect the vent drain to either:
A standard field supplied 2" (50.8mm) PVC tee, or
A 2" (50.8mm) PVC coupling fastened onto the drain tee.
Install tee trap into bottom section of tee. Important: The pipe to the tee trap must be level or sloping towards
the tee trap Connect the tee trap and the main drain line exiting the casing as
shown in Figure 20. Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation, Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
25-24-88
440 01 1051 03 Specifications are subject to change without notice. 25
Horizontal Right through Top
TrapConnection
Preassemble& insertinto furnace
"Clampears"
PointedOUT
Single Pressure Switch Detail
WARNING \,
AddCapand \,
Clamp "
\
3/16"(4,8mm)ID RubberTube
Coupling&Clamps (Optional)_
\\\\\\
,\
,\
'\ L
Plastic Cap Yelloworblack
II
/
/
VentDrain & Clamps
Alternate Orientation
Field
_</ SiuppliedTee
_u-I,"/TeeTrap
\ _" WhitePVC
oosepartsbag)
Elbow Tube Black Rubber 1/2" ID& Clamps (Loose Parts Bag)
iNLET
OnSomeModels ONLY
Dual PressureSwitch/_X
DrainTubeCorrugated5/8"(15,9mm)ID &ClampsCutatstraightsection
I
Leaveroomforclamp "CutHere
Representativedrawingonly_somemodelsmayvaryinappearance.
Horizontal Right through Top (SeeFigure18)
Disconnect the hoses from the trap assembly, and remove trap and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the
hole from the burner compartment to the blower compartment and secure with screws.
Remove knockout from the side of the furnace casing where drain
tube will exit.
Mount the trap externally to the bottom side of the unit using the
two screws provided in the location shown.
Cut the corrugated tube as shown in the illustration above. Connect the corrugated hose from the transition to the trap.
Secure connections with clamps. Connect the black 1/2" (12.7mm) ID drain tube from the Vent Drain
to the trap. Ifan extension is required, use the black 1/2" (12.7mm)
OD barbed coupling and the black 1/2" (12.7mm) ID drain tube in
the loose parts bag. Cut tube to length. Secure connections with
clamps.
/
DrainTubeBlackRubber 1/2"(12,7mm)ID &Clamps
BarbedCoupling 1/2" (12,7mm) OD (LoosePartsBag)
25-24-89
Connect the 3/16" (4.8mm) ID relief tube to the middle port on the trap. If an extension is required, use the clear 3/16" (4.8mm) OD flexible tubing connector and the black 3/16" (4.8mm) ID relief tube
in the loose parts bag. Cut tube to length. Cut an appropriate length of 2" (50.8mm) PVC pipe, fittings and
extension pipe long enough to exit the cabinet and connect the vent drain to a standard field supplied 2" (50.8mm) PVC tee
Install tee trap into bottom section of tee. Connect the tee trap and the main drain line exiting the casing as
shown in Figure 20. Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation, Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
26 Specifications are subject to change without notice. 440 01 1051 03
Horizontal Right-Side Vent
Plastic Cap
Yelloworblack
Coupling&Clamps
Optional)
//
Single Pressure Switch Detail
ReliefTubeBlackRub- ber3/16"(4.8mm)lD _-_
FlexibleTubingConnector
3/16(4.8mm)OD(Loose...............
PartsBag)
J-- o ; " /
ReliefTubeExtension ......-....
BlackRubber3/16" (4.8mm)ID CuttoFit(LoosePartsBag)
Dual PressureSwitch/1_',!,_
DrainTubeCorrugated,5/8" ID & Clamps
Cutat straightsection
Leaveroomfor clamp Cut Here Clamps
Representative drawing only_some models may vary in appearance.
i DrainTubeBlack
Horizontal Right Side Vent (SeeFigure19)
Disconnect drain tee if installed Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the
hole from the burner compartment to the blower compartment and secure with screws.
Remove knockout from the side of the furnace casing where drain
tube will exit.
Mount the trap externally to the bottom side of the unit using the
two screws provided in the location shown.
Cut the corrugated tube as shown in the illustration above. Connect the corrugated hose from the transition to the trap.
Secure connections with clamps. Connect the black 1/2" (12.7mm) ID drain tube from the Vent Drain
to the trap. If an extension is required, use the 1/2" (12.7mm) OD
barbed coupling and the black 1/2" (12.7mm) ID drain tube in the loose parts bag. Cut tube to length. Secure connections with
clamps. Connect the 3/16" (4.8mm) ID relief tube to the middle port on the
trap. If an extension is required, use the clear 3/16" (4.8mm) OD
VentDrain & Clamps
Field
_ SuppliedTee
/
TeeTrap
]q WhitePVC
_ ___-(loosepartsbag)
,4
/' /
Level or Sloped
f
/
towards Tee
-ElbowTube
BlackRubber
1/2"(12,7mm)ID &Clamps (LoosePartsBag)
OnSomeModels
ONLY
INLET _/"
?
Alternate Orientation
J
BarbedCoupling1/2" (12,7mm)
Rubber 1/2"(12,7mm)ID &
OD (LooseParts Bag)
25-24-84c
splice connector and the black 3/16" (4.8mm) ID relief tube in the loose parts bag. Cut tube to length.
Cut an appropriate length of 2" (50.8mm) PVC pipe, fittings and extension pipe long enough to exit the cabinet and connect the
vent drain to either:
A standard field supplied 2" (50.8mm) PVC tee, or
A 2" (50.8mm) PVC coupling fastened onto the drain tee.
Install tee trap into bottom section of tee. Important: The pipe to the tee trap must be level or sloping towards
the tee trap. Connect the tee trap and the main drain line exiting the casing as
shown in Figure 20. Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed
before operation, Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may
be installed as shown for future servicing of the vent system.
440 01 1051 03 Specifications are subject to change without notice. 27
iiiiiMMii;iiii_iiiiiiiiii_;_;_;iiiiii@i¸iii_iiiii_?i£iix_iiiii/iiii;iiii/iiiiiii};iiii;ii!iMiiiiiiiiiiiiii¸I¸
.........................................................................................................................................................Trap and Main Drain Line
Connecting Tee Trap to Condensate
s
LU -4
t
I__ ........... _i
© /
OpenTee f
Evaporator _--_
Coil
DrainLine
(Optional)
/
/
,/
Condensate
Trap 25-24-85
Representativedrawin.qonly,somemodelsmayvaryinappearance.
The tee trap must be connected to the main condensate drain
line as conceptually shown above. Different installations may require slightly different orientations. The following steps apply
to all installations.
1. The tee trap should be installed as close to the side or top of
the furnace as practical. Minimize the distance between the
inducer and the tee trap as much as possible.
2. An open tee is to be used at the tee trap discharge. The top
end of the tee should be open to the atmosphere to eliminate potential air lock problems.
3. The drain line from the tee trap is to be connected to the
furnace condensate trap drain line as shown above.
4. Condensate drain lines from a cooling coil may be
connected downstream of the connection point of the tee
trap and furnace condensate trap.
Important: Prime both traps with water before operation.
Failure to prime the traps may result in discharge of flue gases
from the condensate drain line and open tee for a period of time, and may result in temporary lockout of the furnace upon
start up. Main drain line construction is left to the discretion of
the installer. It may be made of either rigid pipe or flexible tube. Tube ID should NOT be less than 1/2, (12.7mm).
Connecting Vent and CombustionAir Piping
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Cement or mechanically seal all joints, fittings, etc.
to prevent leakage of flue gases.
Refer to Figure 11 through Figure 19 that corresponds to the installation position of the furnace for the application.
Preassemble the vent and combustion air piping from the furnace to the vent termination. Do not cement the pipe joints until the pipe preassembly process is complete.
CombustionAir PipeConnection (Dual Certified or
Direct Vent)
Install the air intake coupling and gasket to the furnace with the four(4) screws. Note: The air intake coupling and gasket can be installed to the top panel, or to the alternate air intake locations on either the left or right side panels of the furnace.
For downflow installation, the air intake coupling and gasket must be installed to the alternate air intake location on either the left or
right side panels. Remove the 3" (76.2mm) hole plug from the furnace accessory bag and relocate to the open hole in the furnace panel. Use four screws to seal the four mounting holes in the top panel next to the hole plug. Drill four 7/64" (2.8mm) diameter holes in the casing using the air intake coupling as the template.
The air intake coupling is sized for 2" (50.8mm) PVC pipe. Install the combustion air pipe to the air intake coupling using RTV
sealant to provide for future serviceability.
Vent Pipe Connection
Install the vent pipe grommet to the furnace panel. Locate the grommet in the furnace panel at a location directly away from the vent fitting on the combustion blower. The grommet snaps into the 3" (76.2mm) hole on the furnace panel. NOTE: Depending on the installation position, the vent pipe grommet will be installed to the top panel or to the alternate location on the side panels. If needed, remove the 3" (76.2mm) hole plug from the loose parts bag and relocate to the open hole in the furnace panel. (See Figure 11 or Figure 20)
Install the vent pipe to the rubber coupling, the vent fitting or the PVC vent extension pipe. Securely attach using the clamp or PVC cement as required.
Note: The vent fitting MUST be installed with the air flow marking arrow pointed toward the vent pipe, (See Figure 21)
Some installations require the vent fitting to be installed with a 5° to 10° downward slope, (See Figure 11 through Figure 20)
28 Specifications are subject to change without notice. 440 01 1051 03
_i_i_i!iiiiiii_;_i1i_iii;_i_i_i;ii_i;;;i_i_i_i_i_i_;_i_
Proper Sealing Procedure for Combustion Blower
RubberCoupling J . VentPipe
&Clamps- =_,_ _ .... (TopPanelExit)
/_, ..... _% NOTE: The 90 ° elbow is approved
- vent _'lpe _'"_ , ,
/
z for use Inslde the furnace ONLY.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer
to inside surface of socket and outside of pipe. Do NOT allow primer to dry before applying cement.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe
into fittings with a slight twisting movement until it bottoms
out.
NOTE: Cement MUST be fluid while inserting pipe. If NOT, recoat pipe.
4. Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit,
temperature and humidity.
ConnectingVentPipesandTermination (DirectVent)
NOTE: For direct vent applications, combustion air intake and vent MUST terminate in the same atmospheric pressure zone. If
installation is in a cold climate (sustained temperatures 0°F and belowfor 24ormoreconsecutivehours), increase the minimum distance between vent pipe and air intake from 8" to 18".
NOTE:Built-in channelwill beangled5°to 10° also.
25-24-14a
Joining Pipe and Fittings
SEE VENT AND COMBUSTION AIR PIPING, vent and Combustion Air Piping Guidelines inthis manual for applicable
ASTM Standards for vent materials.
FIRE HAZARD Failure to follow this warning could result in
personal injury, death, and/or property damage. Observe all cautions and warnings printed on
material containers Provide adequate ventilation and do NOT assemble
near heat source or open flame. Do NOT smoke
while using solvent cements and avoid contact with skin or eyes.
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Do NOT use solvent cement that has become
curdled, lumpy or thickened and do NOT thin.
Observe precautions printed on containers. For applications below 32°F(0°C), use only low tempera- ture type solvent cement. Poor joints may lead to
disconnected or leaking vent pipe joints allowing
carbon monoxide to enter the living space.
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Maintain a minimum of 36" (914.4mm) between
combustion air inlet and clothes dryer vent.
Terminate the combustion air intake as far as
possible from any air conditioner, heat pump, swimming pool, swimming pool pumping, chlori-
nator or filtration unit.
1.
Install all couplings, nipples and elbows using proper
procedures for Joining Pipe and Fittings and maintain spacing between vent and combustion air piping as
indicated in Figure 22 through Figure 24.
...................................................................................................................................More Above Snow Level or Grade Leve
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
8" 203=2mm*MIN. _ "18"(457.2mm)Minimumfor
20'(6.1 m) MAX / _.._ cold climates (sustained tem-
// / '% EXHAUS'r "_>_,---------_S_
f:::f INLET _k. / 12"
Sidewall Termination 12" (304.8mm)or
_ _ peratures0°F(-17°0) and below
_ _ for 24 or moreconsecutive
_ _F_F hours)
(304.8mm)
._J" MIN.
//'_\ W
._ "GRADE LEVEL
OR
SNOW LEVEL 25-00-05F
1. Cut pipe end square, remove ragged edges and burrs.
HorizontalTermination
Chamfer end of pipe, then clean fitting, socket and pipe joint
1.
of all dirt, grease, or moisture.
NOTE: Stir the solvent cement frequently while using. Use a natural bristle brush or the dauber supplied with the cement. The proper brush size is one inch.
440 01 1051 03 Specifications are subject to change without notice. 29
Cut two holes. 21/2" (63.5mm) for 2" (50.mm) pipe, 3"
(76.2mm) for 21/2" (63.5mm) pipe, or 31/2 ,, (88.9mm) for 3" (76.2mm) pipe. Do NOT make the holes oversized, or it will
be necessary to add a sheet metal or plywood plate on the outside with the correct size hole in it.
2. Check hole sizes by making sure it is smaller than the couplings or elbows that wilt be installed on the outside. The
couplings or elbows MUST prevent the pipe from being pushed back through the wall.
3. Extend vent pipe and combustion air pipe through the wall 3/4" (19.1 mm) to 1" (25.4mm) and seat area between pipe
and wall.
4. Install the couplings, nipple and termination elbows as shown and maintain spacing between vent and combustion air piping as indicated in Figure 22 and Figure 23.
A metal shield is recommended 18" x 18" (457.2mm x 457.2mm)
min. or 18" (457.2mm) min. diameter around the vent termination at the exterior walt to protect the house exterior materials from flue product or condensation (freezing) damage.
Using ExteriorRisers
1. Install elbows and pipe to form riser as shown in Figure 23.
2. Secure vent pipe to wall with galvanized strap or other rust resistant material to restrain pipe from moving.
3. Insulate pipe with Armaflex or equivalent moisture resistant closed cell foam insulation or fiberglass insulation if boxed in and sealed against moisture.
Recommended Alternate Installation
i!_i _i forSustainedColdWeather[0°F(-17°C)&belowfor24
hoursormoreconsecutivehours]
EXHAUST
.. ................................... "--. _evel OR Snow Level
FRONT Vl EW
/
_,1_/ J2" (304.8mm)MIN.
OVERHANG
INLET
/
JL
..........12" (304.8mm) MIN. Ground
SIDE VIEW
¢.,. "S,°ewa,,toTerm,n°.,onw,t.Ex.er,Oror
Risers Get Above Snow Level
Grade Level
8" (203.2mm)* MIN. _ "18" (457.2mm) Minimum for
20' (6.1m) MAX z jz,-_ _ coldclimates[sustained0°F
._ _ z_y. (-17°C) and belowfor24 or
j_z _ - moreconsecutivehours]
iii/iiiiii__iiiili!ii;iiiiiJi Rooftop_rmination
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
/ ..... i
/!:::::::_ _ -" i 12 " (304.8mm)
/(:::_ _ MIN.
," j INLET3J /
EXHAUST J/_
.-J ',, GRADE LEVEL
/;;} .J ' OR
-q'_-/ SNOW LEVEL 25-00-04F
VerticalTermination
1. Figure 25 shows the proper installation and clearances for
vertical vent termination. The vertical roof termination
should be sealed with a plumbing roof boot or equivalent
flashing. The inlet of the intake pipe and end of the exhaust vent must be terminated no less than 12" (307.8mm) above the roof or snow accumulation level, and 12" (307.8mm)
away from a vertical wall or other protrusion.
2. If the vent system is installed in an existing chimney make sure clearances shown in Figure25 are maintained.
Horizontal section before the termination elbow can be extended on the inlet air to provide necessary clearance.
A = 12" (304.8mm) Above roof or snow accumulation level
B = 8" (203.2mm) Min., 20' (6.1m) Maximum, except in areas
with extreme cold temperatures [sustained 0°F(-17°C) and be-
low for 24 or more consecutive hours], the 18" (457.2mm) Min.
VentTerminationShielding
Under certain wind conditions some building materials may be affected by flue products expelled in close proximity to unprotected surfaces. Sealing or shielding of the exposed surfaces with a corrosion resistant material (such as aluminum sheeting) may be required to prevent staining or deterioration. The protective material should be attached and sealed (if necessary) to the building before attaching the vent terminal.
SameJoist
J
Space
12"
_./ 104"8mm)
25-23-73
30 Specifications are subject to change without notice. 440 01 1051 03
MultiVentTerminationClearances
When two (2) or more furnaces are vented near each other, each furnace must be individually vented.
Two (2) vent terminations may be installed as shown in Figure 26,
Figure 27, Figure 28, Figure 29, Figure 30 and Figure 24, but the next vent termination must be at least 36" (914.4mm) away from first two terminations. It is important that vent terminations be
made as shown to avoid recirculation of flue gases.
;:;ii _(
Concentric Vent and Combustion-
Air Roof Termination
_i_i;:iii_i_ii_i1_!!_i_i¢_i_ii_ii1_i_!i_i!_i_i_i;i_iiii_:
Sidewall Inlet Vent and Exhaust-Air Termination with Exterior Risers
- 7_L_ 8" (203.2mm)Min. D- /j _1_ 4ii7-- _--_---_- >_ 20' (6lm) Max [_ _ __----_8" (203,2mm)Mm.
:>_ ::_M-_-- .t, I ..... __-_ / / _-_
:_%_W-< 7k-_;;;----i Z ' { ( _L :\ '__---i
:---.:_:-m:::W---_-_-_- F---4 _ '., L f "
1:::__-Exhaust_-,_ i/ +/-- ]_--_ _:-_ -T"_I_ /_ 12" (457.2mm1
/" / /-" _ _ _ _---J -i Jk. j_ Inlet Min.Gradeor
, i_ _:_ _, _,_ / SnowLeve
_---__ UI -- 7"_ ,' ' -
_2" (50.8mm) Max 36" Min
'in. Grade or t _-- /_ - _ --J36"Min-_
i[i}[ J Ji] }
Concentric Vent and Combustion-
Air Sidewall Termination
_ - .... J- ...... jj .....
JJJ "_ll "---J ....
................ _-... 1" (25.4mm) .......
/J J- .....
CombustionAir ....... Maximum _.__----.............
.................... ..................................
........... \r ,_ '__._.xj_.<,-r L ........
.......... ----_--r-\_F?:;:_-_--.i........'
), L [ .......i .... I_-m!:A......
1/ f_'_ _ .-J ....................18"(457.2mm)lin. for Cold Climates
\- _--_' / ,,A,;........ [Sustained 0°F(-17°C) and below for
. J _J- 24 hours ormore consecutivehours]
Dimension "A" is touching or 2" (503.8mm) maximum separation.
iiiiiiiiliiiiiilJiiiiiil;;iiiillIliiiiiiiiiiii!ii!iiiii{iiiii:iliiI!!Iii11iliiiii!ii¢illi!i
iliiiii I III!IilI!Rooftop inlet Vent and Exhaust-
Air Termination
_1_',, 8" (203.2mm)Min. ".... ,,____,_ts_
_",,",, 20' (6.1m1 Max. _1 ' ' ..... "
,,,, ...... ,, !-4/_. _ ..........,, _ , .:__
", ",, ]__"-_, "*,:-t-- ._,--'<,," ",__Exhaust
12" (304.8mm1 ", 'L --_"7-- -. '_--- _,.-;'----}'-, ............;'--"7 .................
Min.Gradeor ',,,, _;.- -'_ X .......... _.......
SnowLeve ',,',,, ....;_...... .--- 18" (457.2mm)Min.for ColdClimates
,,]..... ............ [Sustained0°F(-17°0) andbelowfor
/"4........... 24 hoursor moreconsecutivehours]
...............j /_l ...._, .....
Vent 25-22-02d
Dimension "A" is touching or 2" (503.8mm) maximum separation.
Sidewall Inlet Vent and Exhaust-
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii Air Termination
i-::t-_::-_zt_LJ--Lt--iC]_-:_>_::<-tiJ----l::<-XL_--Lt_-C_-;....
z .j--j_%.<-S_zl_.._--- j Jj..j_ Exnaust.... W/" -.__
S:_--?:b--_-vW->iJ---L_.- ..........._/" _.___ /2+_......
......:>-[;<.-_j>---.,,^,,- ........ ,, : l-_7:-_-_,t/ _\\
...... Inlet _<..-- //_ ......... J {._._ .-
........ Dimension "A" is touching or 2" (50.8mm) maximum separatior
440 01 1051 03 Specifications are subject to change without notice. 31
"ili_' i':_- _ \' ........... J8" (203.2mm] Min. -.........
1\ f ' I-jjZ _....... 20' (6.1m)Max.
_ ,, __ __ ,i.- --j j-
12"(304.8mm)Min. - [Sustained 0°F(-17°C) and below for
Grade orSnowLevel 24 hours ormoreconsecutivehours]
j.jJJ_
..... .---/ 18" (457.2mm)lin. for Cold Climates
Concentric Termination
ConcentricVentTermination- Kit#
NAHAO01CV& NAHAO02CV
For Concentric Vent Termination information call 931.270.4100
with the complete model and serial number of the furnace.
Refer to Special Venting Requirements for Installations in Canada
in the Vent and Combustion Air Connections Section. These kits are for vertical or horizontal termination of the
combustion air inlet and the exhaust vent pipes on Category iV
gas-fired condensing furnaces. The NAHA001CV kit can be used for 3" (76.2mm) diameter pipe systems. The NAHA002CV kit can
be used for 2"(50.8mm) diameter pipe system. Refer to Table 4 for the correct pipe size for the furnace. Both the combustion air
inlet and the exhaust vent pipes must attach to the termination kit. The termination kit must terminate outside the structure and must
be installed per the instructions outlined below for vertical or
horizontal termination. Vertical termination is preferred. Field
supplied pipe and fittings are required to complete the installation.
t;;' : Concentric Termination Kit
_ NAHA001CV & NAHA002CV Venting
Table for *9MPX Models
60,000 Btuh Furnaces
NAHAOO2CV- 35' (10.7m) & (4) 90°elbows
with 2" (50.8mm)PVC pipe or
NAHAOOICV- 65' (20m)& (4) 90° elbows
with 3" (76.2mm) PVC pipe
80,000 Btuh Furnace
NAHAOO2CV- 35' (10.7m) &(4) 90° elbows
with 2" (50.8mm)PVC pipe or
NAHAOOICV- 35' (10.7m) & (4) 90°elbows
NAHAOOICV- 35' (10.7m) & (4) 90°elbows
1. Do not include the field supplied 45° elbow in the total elbow count.
2, If more elbows are required, reduce the length of both the inlet
and the exhaust pipes five feet (1,5m) for each additional elbow used.
3, Elbows are DWV long radius type for 2" and 3" (50,8mm and
76,2mm) vents,
NOTE: The minimum vent length is 5' (1.5m) of PVC. Feet (mm) of pipe is whichever pipe length is the longest, either inlet or outlet
side.
with 3" (76.2mm) PVC pipe
100,000Btuh Furnace
NAHAOO2CV- 5' (7.6m) & (2)90° elbows
with 2" (50.8mm)PVC pipe or
with 3" (76.2mm) PVC pipe
Do not use field supplied couplings to extend the pipes. Airflow restriction will occur and the furnace pressure switch may cause intermittent operation.
Gas Supply and Piping
Do not allow minimum supply pressure to vary downward. Doing so wilt decrease input to furnace. Refer to Table 5for
FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in
personal injury, death, and/or property damage. Models designated for Natural Gas are to be used
with Natural Gas ONLY, unless properly converted to use with Propane gas.
NOTE: The rating plate is stamped with the model number, gas
type and gas input rating.
GasSupply Requirements
Gas supply pressure should be within minimum and maximum
values listed on rating plate. Pressures are usually set by gas
suppliers. (See Propane Gas Conversion Kit instruction manual for furnaces
converted to Propane gas)
Use only the Type of gas approved for this furnace. See rating plate for approved gas type.
A 1/8" NPT plugged tapping, accessible for a test gauge connection,must be installed immediately upstream of the gas supply connection to furnace.
Gas supply pressure should be within minimum and maximum values listed on rating plate. Pressures are usually set by gas suppliers.
Gas input must not exceed the rated input shown on the rating plate. Overfiring will result in failure of heat exchanger and cause dangerous operation.
32 Specifications are subject to change without notice. 440 01 1051 03
Gas supply. Refer to Table 6 or Table 7 for manifold pressures.
GasPressures
Gas Type Supply Pressure
Recommended Min.
Natural 7 in wc 4.5 in wc
(1.8 kPa) (1.1 kPa)
Propane 11 in wc 11 in wc
(2.8 kPa) (2.8 kPa)
GasPiping Requirements
NOTE: The gas supply line must be installed by a qualified service technician in accordance with all building codes. NOTE: In the state of Massachusetts.
a. Gas supply connections MUST be performed by a
licensed plumber or gas fitter.
b. When flexible connectors are used, the maximum length
shall not exceed 36" (915 mm).
c. When lever handle type manual equipment shutoff
valves are used, they shall be T-handle valves.
d. The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
1. Install gas piping in accordance with local codes, or in the absence of local codes, the applicable national codes. Refer to NFPA 54/ANSI Z223.1 for proper gas pipe size.
2. It is recommended that a manual equipment shutoff valve be installed in the gas supply line outside the furnace. Locate valve as close to the furnace as possible where it is readily accessible. Refer to Figure 31.
Max.
14 in wc
(3.5 kPa)
14 in wc
(3.5 kPa)
3. Use black iron or steel pipe and fittings or other pipe approved by local code.
4. Use pipe thread compound which is resistant to natural and Propane gases.
5. Use ground joint unions and install a drip leg no less than 3" (76.2mm) long to trap dirt and moisture before it can enter gas
control valve inside furnace.
NOTE: Refer to Figure 31 and Figure 32 for the general layout at
the furnace. The rules listed apply to natural and Propane gas pipe
installations.
NOTE: Install the gas pipe grommet to the furnace side panel with the gas pipe entry. If needed, remove the 2" (50.8mm) hole plug from the plastic accessory bag and relocate to the open hole in the furnace side panel.
6. Use two pipe wrenches when making connections to prevent gas valve from turning.
7. Install a manual shut-off valve external to furnace casing and tighten all joints securely.
8. If local codes allow the use of flexible gas appliance connectors, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance.
iiiiii_iiiiii_ii!iiiIi_iiiiii}_iiii_i_.i_!_iiiii!_iii_i.`.iiii!iiiii_i?_.i_i_i_iiiiiiijii!i!!!iiii_ii1!!jii_iiii_ji!iii
Typical Gas Piping for Upflow
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
A flexible corrugated metal gas connector must be properly installed, shall not extend through the side
of the furnace,and shall not be used inside the
furnace.
Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2" (50.8mm) outside furnace casing.
9. Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace
or ductwork.
10. Properly size gas pipe to handle combined appliance load or run gas pipe directly from gas meter or Propane gas
regulator.
11. Install correct pipe size for run length and furnace rating.
12. Measure pipe length from gas meter or Propane second stage regulator to determine gas pipe size.
DripLegandUnion,Union*shouldbeoutsidethe
VentPipeGrommet(SinglePipe)
cabinet.Manualshut-offvalveMUSTbeupstreamof Manualshut-off
dripleg,union,andfurnace. -......... valve
Useelbowsand3"(76.2rnrn)pipenippletoconnectvalveto ................
pipingwhenusing..............rightsidegaspipeentry. __'_._" _- i_X_:_
, , _ _._ ] Q _ -- \ /
PropaneLowpres-_ _>> 3" (762mm) _ ._
sureswitch _. J/ pipe " _" ............
REQUIRED. nipple
_" "-. press_
* Union may be installed inside the cabinet when necessary
because of clearances. _\ _
Representativedrawingonly,somemodelsmayvaryinappearance. _/_
have 1
switch
Alternative
installation
may
or 2 re
8S
25-24-86
440 01 1051 03 Specifications are subject to change without notice• 33
iiii/_iiiii!ii__J__//ii;liMiii!iiiiiiiiiii/ii/!!Iii:i:i:ii/iiiiiiiiiM7iiii/iiiiiii//ii!!!iiiiii{iiiii///!liiiiiiii!{i
_ _iU _i_ _, Typical Gas Piping forDownflow
Use elbows and 3" (76.2mm) pipe nipple to connect ........
valve to piping when using left side gas pipe entry. _"- "--_
_W _ _s_#7 ! 7 Propane Low pressure _" "_.; " /
\_ '(('_ _2,/ switch. Optional \_
_ _ Propane conversion. _" .................
" ............. Manualshut-off
Drip Leg and Union, Union* should be outside the cabinet. Manual shut-off valve MUST be upstream of dripleg, unio ,r_i_
and furnace. /
*Union may be installed inside the cabinet when necessary (Single Pipe)
because of clearances.
Representative drawing only_some models may vary in appearance,
valve _
Vent Pipe Grommet
AdditionalPropaneConnectionRequirements
1. Have a licensed Propane gas dealer make all connections at storage tank and check all connections from tank to
furnace.
2. If copper tubing is used, it MUST comply with limitation set in National Fuel Gas Code or CGA codes.
3. Two-stage regulation of Propane gas is recommended.
PropaneConversion
An accessory kit shall be used to convert to propane gas use, see the furnace rating plate for the Propane conversion accessory kit
part number.
FIRE, EXPLOSION, UNIT DAMAGE HAZARD Failure to follow this warning could result in death,
property damage and/or personal injury.
A Propane conversion accessory kit is required when operating the furnace with Propane gas.
SupplyPressure
FIRE HAZARD Failure to follow this warning could result in
personal injury, death, and/or property damage. Do NOT set input rating above that shown on rating
plate.
1. A 118" NPT plugged tapping, accessible for a test gauge connection, must be installed immediately upstream of the gas supply connection to the furnace.
2. Gas input to burners MUST NOT exceed the rated input shown on rating plate.
3. Do NOT allow minimum gas supply pressure to vary downward. Doing so will decrease inputto furnace. Refer to Table 6 and Table 7 for normal gas supply and manifold
pressures.
ManifoldGasPressureAdjustment
SEE CHECKS AND ADJUSTMENTS, Manifold Gas Pressure Adjustment inthis manual.
34 Specifications are subject to change without notice. 440 01 1051 03
NATURAL GAS MANIFOLD PRESSURE (in wc) 20,000 BTU per burner*
i!j
MEANELEVATIONFEETABOVESEALEVELft (m)
HEATING
VALUE
BTU/CU.
FT.
700 725
750 775
800 825
850 875
900 925
950 975
1000 1050
1100
* When installing the 100,000 BTU furnace in downflow or horizontal positions, firing rate is reduced to 19,500 BTU/celI. Subtract
0.2" w.c from the manifold pressures listed in table above for the correct manifold pressure.
Conversion:1inwc=.25kPa Bold- indicates factory orificesize.
NOTE: Natural gas data is based on 0.60 specific gravity. Forfuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1/N FPA 54-2009 or National Standard of Canada, Natural Gas And Propane Installation Code CSA B149.1-05.
In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design-certified by CSA.
1- In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to
1371.6m) above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 6 and Table 7.
0to 2000 2001to 30001 3001to 4000 4001to5000 5001to 6000 6001to7000 (0to 610) (610.1to 914)1" (914.1to 1219) (1219.1to 1524) (1524.1to 1829) (1829.1to 2134)
Orifice Orifice Orifice Orifice Orifice Orifice
Mnfld Mnfld Mnfld Mnfld Mnfld Mnfld Press Press Press Press Press Press
, , . 44 3.7 44 3.4 . . , 44 3.5 44 3.2
44 3.5 44 3.2 44 3.0
44 3.6 44 3.3 44 3.0 44 2.8
44 3.7 44 3.4 44 3.1 44 2.9 44 2.6 44 3.5 44 3.2 44 2.9 44 2.7 44 2.5
44 3.5 44 3.3 44 3.0 44 2.8 44 2.5 47 3.4
44 3.7 44 3.2 44 2.9 44 2.7 44 2.5 48 3.7 48 3.4 44 3.5 44 3.0 44 2.8 44 2.6 47 3.4 48 3.5 48 3.3
44 3.3 44 2.8 44 2.6 47 3.5 48 3.7 48 3.4 49 3.6 44 3.2 44 2.7 44 2.5 47 3.3 48 3.5 48 3.2 49 3.4
44 2.9 44 2.5 48 3.7 48 3.4 49 3.7 ........
46 3.3 48 3.7 48 3.4 49 3.7 ............
44 3.3 44 3.1 44 2.8 44 2.6 47 3.5 48 3.6
7001to 8000
(2134.1to 2438) Orifice
Mnfld
Press
44 3.7
LPG or PROPANE GAS MANIFOLD PRESSURE (in wc)
HEATING FURNACE MEANELEVATIONFEETABOVESEALEVELft (m)
VALUE
BTU/CU.
FT. BURNER (0 to610) (610.1to914)1" (914.1to1219) (1219.1to 1524) (1524.1to 1829) (1829.1to2134) (2134.1to 2438)
2500 10.0 8.9 8.4 10.0 10.0 10.0 10.0
OrificeSize 20000 #55 #55 # 55
2500 9.9 8.4 8.0 10.0 10.0 10.0 9.6
OrificeSize 19500:1: #55 #55 # 55
Applies to 100,000 BTU models when installed in the downflow or horizontal applications
Conversion:1inwc=.25kPa NOTE: Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI
Z223.1/N FPA 54-2009 or National Standard of Canada, Natural Gas and Propane Installation Code CSA B149.1-05.
In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design-certified by CSA.
1- In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to
1371.6m) above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 6 and Table 7.
The burner orifice part nos. are as follows: General Berating Rules
Orifice Part # Orifice Part #
INPUTBTU/ 0to 2000 2001to 30001" 3001to 4000 4001to5000 5001to6000 6001to 7000 7001to 8000
1. These furnaces may be used at full input rating when
41 1096942 42 1011351 43 1011377 44 1011352
45 1011353 46 1011744 47 1011378 48 1113201 49 1113202 54 1011376
55 1011354 56 1011355
installed at altitudes up to 2,000' (609.6m). When installed
above 2,000' (609.6m), the input must be decreased 2%
(Natural) or 4% (Propane) for each 1000' above sea level in
the USA. In Canada, the input rating must be derated 5%
(natural) or 10% (Propane) for each 1000' (304.8m) above
sea level. See Table 6 orTable 7 for required high altitude
input rate.
2. For operation with natural gas at altitudes above 2,000'
(609.6m), orifice change and/or manifold pressure adjustments may be required for the gas supplied. First consult your local gas supplier, then refer to Table 6 for
required pressure change and/or orifice change for high altitudes.
440 01 1051 03 Specifications are subject to change without notice. 35
3.
For operation with Propane gas, gas orifices MUST be changed and manifold pressure MUST be maintained as
per Table 7. Orifices can be ordered through our distributor. (See Figure 33)
Nameplate Sea Level Input Rate x (Multiplier) "1"
Elevation
2001' - 3000'1"
(609.9 - 914.4)1" 0.95 0.90
3001' - 4000'
(914.7 - 1219.2) 0.93 0.86
4001' - 5000'
(1219.5 - 1524) 0.91 0.82
5001' - 6000'
(1524.3 - 1828.8) 0.89 0.78
6001' - 7000'
(1829.1 - 2133.6) 0.87 0.74
7001' - 8000'
(2133.9 - 2438.4) 0.85 0.70
* Based on mid-range of elevation.
High Altitude Input Rate =
High Altitude Multiplier
Natural Gas Propane Gas
NaturalGas InputRatingCheck
SEE CHECKS AND ADJUSTMENTS, Natural Gas Input Rating Check in this manual.
Changing Orifices
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Measure from face of orifice
FinalGasPipingCheck
HighAltitudeAir PressureSwitch
Altitudes over 4,000' (1219.2m) may require a different air
pressure switch than the one installed at the factory. Check parts list for pressure switch and consult your distributor for part number and availability. In Canada, provincial codes may govern installation of switch. Check with governing authorities.
* In the USA, derating of these furnaces at 2% (Natural Gas)
and 4% (Propane Gas) has been tested and design-certified by CSA.
1- In Canada, the input rating must be derated 5% (Natural Gas)
and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6
to1371.6m) above sea level. Use the 2001 to 3000 (609.9 to
914.4m) column in Table 6 and Table 7.
Changing Orifices for HighAltitude
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Turn OFF electric power at fuse box or service
panel and gas supply at manual valve in gas valve, lockout and tag switch with a suitable warning label, when installing orifices. Installation of
orifices requires a qualified service technician.
NOTE: Main burner orifices can be changed for high altitudes.
1. Disconnect gas line from gas valve.
2. Remove manifold from furnace.
3. Remove the orifices from the manifold and replace them with properly sized orifices.
4. Tighten orifices so it is seated and gas tight. (See Figure 33)
5. Reinstall manifold. Ensure burners do NOT bind on new orifices.
36 Specifications are subject to change without notice. 440 01 1051 03
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion could result causing property damage, personal injury and/or
loss of life.
1.
The furnace and the equipment shut off valve must be
disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2z" PSIG. Close the manual shut-off valve before testing at such pressures.
RISQUE D'INDENDIE OU D'EXPLOSION
Le non-respect des avertissements de securite pourrait d'entrainer des blessures graves, la mort ou des dommages materiels.
Ne jamais utiliser une flamme nue por verifier la presence des fuites de gaz. Pour la verification de
tous les joints, utiliser plut6t une solution savonneuse commerciale fabriquee specifiquement pur la detection des fuites de gaz.
Un incendie ou une explosion peut entrainer des dommages materiels, des blessures ou la mort.
2. When installation is complete, test all pipe connections for leaks with the gas pressure less than /2" PSIG to the gas
valve.
3. The furnace must be isolated from the gas supply system by
closing the equipment shut off valve during any pressure testing of the gas supply system at test pressure equal to or
less than /2" PSI.
4. Apply a commercial soap solution to all joints to test for leaks. Correct any leaks indicated by bubbles.
5. Correct even the smallest leak at once.
6. Check for leaks at gas valve and orifice connections to the
burner manifold while the furnace is operating.
1
1
Electrical Wiring
with manufacturer's instructions. The wiring MUST have a minimum temperature rating of 105 ° C.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in
personal injury or death.
Turn OFF electrical power at fuse box or service
panel, lockout and tag switch with a suitable
warning label, before making any electrical connections and ensure a proper ground connec-
tion is made before connectin£1 line volta£1e.
PowerSupply Wiring
The furnace MUST be electrically wired and grounded in
accordance with local codes, or in the absence of local codes with
the latest edition of The National Electric Code, ANSI NFPA 70
and/or The Canadian Electric Code CSA C22.1.
The power supply to the furnace connections must be between
104 VAC and 127 VAC during furnace operation for acceptable performance.
Field wiring connections must be made inside the furnace connection box. A suitable strain relief should be used at the point
the wires exit the furnace casing.
Copper conductors shall be used, Line voltage wires should conform to temperature limitation of 63° F (35° C) rise and be sized
for the unit maximum amps stated on the rating plate. Add the full
load amps for potential field-installed accessories such as electronic air cleaners and humidifiers that would receive power
from the furnace control. The furnace control is rated for a
maximum of 1.0 amp combined for EAC and HUM. Consult NEC or local codes for proper wire and circuit sizing.
NOTE: Furnace will not have normal operation if line polarity is reversed. Check ALL field and control connections prior to
operation.
JunctionBox(J-Box) Relocation
The J-box is installed on left side of casing. An alternate j-box
location on right side can be used.
1. Remove bag containing two hole plugs and two self tapping screws from loose parts bag in blower compartment.
2. Remove two screws holding J-Box to casing.
3. Move large hole plug from right to left J-Box location.
4. Clip wire tie holding J-Box wires.
5. Move J-Box to alternate location and attach using two self
tapping screws from bag.
6. Apply two hole plugs from bag at left J-Box location.
Thermostat
Thermostat location has an importanteffect on the operation of the
unit. Follow instructions included with thermostat for correct mounting and wiring.
Low voltage connections to furnace must be made on terminal board of furnace control.
When using a nonelectronic thermostat, the thermostat heat
anticipator must be set to match the amp draw of the electrical components in R-W circuit. Accurate amp draw readings can be
obtained at thermostat subbase terminals R and W. For an electronic thermostat, set cycle rate for 3 cycles per hour. Measure heat anticipator current in series from R to W at the
thermostat. If 24VAC humidifier is wired up to control, humidifier
must be energized. Allow furnace to operate for two minutes before recording the AC amperage reading. Set anticipator on
thermostat to recorded value.
OptionalEquipment
All wiring from furnace to optional equipment MUST conform to
local codes or, inthe absence of local codes with the latest edition of The National Electric Code, ANSI NFPA 70 and/or The
Canadian Electric Code CSA C22.1. Install wiring in accordance
440 01 1051 03 Specifications are subject to change without notice. 37
Humidifier/ElectronicAir Cleaner
The furnace is wired for humidifier and/or electronic air cleaner connection.
REDUCED FURNACE LIFE HAZARD Failure to follow caution may result in reduced
furnace life.
Do NOT exceed 115V/1.0 amp. maximum current load for both the EAC terminal and the HUM
terminal combined.
HUMIDIFIER - The 24V HUM is energized when the pressure switch closes on a call for heat. The 115V HUM (called HUM on
control) is energized when the inducer is energized. ELECTRONIC AIR CLEANER - EAC is energized when there
is a blower speed call, except is NOT energized when blower operates inthe hard-wired continuous fan mode.
FurnaceControl
The furnace control is preset at the factory with a fixed blower ON delay of 30 seconds inthe heating mode. The blower OFF timing is preset at 140 seconds. Ifdesired, the fan OFF delay can be reset to obtain the longest delay times while still maintaining comfort levels. See "Furnace Wiring Diagram".
Electrical Connections
NOTE:Junction Boxcan be mountedto eithertheleftorright
side.
115V.60Hz
Models may have 1 or 2
Box
Gr=_nd
LowVoltage
TerminaIBoard
NOTE: 115VAC/60Hz/single-phase Operating voltage range*: 127 VAC max, 104VAC min.
* Permissible limits of voltage at which unit will operate satisfactorily
somemodelsma
pressure
/
_25-24-90-2
./
FurnaceControlFuse
The 24V circuit contains a 5-amp, automotive-type fuse located
on furnace control. (See Figure 35) Any electrical shorts of 24V wiring during installation, service, or maintenance may cause fuse
to blow. If fuse replacement is required, use only a fuse of identical
size (5 amp.)
Ductwork and Filter
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Control Board
BlowerOff _ DelayJumper_ _,
24VAC _d._
HUM........._-_
FU
Connections
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Do NOT draw return air from inside a closet or utility
room where furnace is located. Return air duct MUST be sealed to furnace casing.
Installation
NOTE: Design and install the air distribution system to comply with
Air Conditioning Contractors of America manuals and/or NFPA
pamphlets 90A and 90B or other approved methods that conform
to local codes and good trade practices.
1. When furnace supply ducts carry air outside furnace area, seal return air duct to furnace casing and terminate duct outside furnace space.
2. Install air conditioning cooling coil (evaporator) on outlet side of furnace.
3. For furnaces installed without a cooling coil it is recommended that the outlet duct be provided with a removable access panel. This panel should be accessible
when the furnace is installed so the exterior of the heat exchanger can be viewed for inspections. The access panel
MUST be sealed to prevent leaks.
4. If separate evaporator and blower units are used, install good sealing dampers for air flow control. Chilled air going
through the furnace could cause condensation and shorten the furnace life.
NOTE: Dampers (field supplied) can be either automatic or manual. Manually operated dampers MUST be equipped with a means to prevent furnace or air conditioning operation unless damper is in the full heat or cool position.
NOTE: On upflow installations, return air can enter through either side, both sides, or the bottom. On horizontal installations the
return air must enter through the knockout opening in the lower panel of the furnace. Return air can not enter through rear of the furnace. When the furnace is located inan area near or adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return grille. Any blower moving a high volume of air will produce audible noise which could be objectionable to when the unit is located very close to living areas. It is advisable to route the return air ducts under the floor or through the attic.
1. For side connections using a 16"x 25" (406.4 x 635mm) filter, cut out the embossed area shown in Figure 36. This wilt provide a 141/2" x 221/2" (368.3 x 571.5mm) approximate opening.
2. Bottom returns can be made by removing the knockout panel in the furnace base. Do NOT remove knock-out except for a bottom return.
3. Installation of locking-type dampers are recommended in all branches, or in individual ducts to balance system's air flow.
4. Non-combustible, flexible duct connectors are
recommended for return and supply connections to
furnace.
iiiiiii_iiiiii_iiiiiiiii_i;;iiiiiIII_ii;i;_iiii11ii_iii_i!!iiiii!_iiiiiiiii!ii:i_iiiiiiiii!iiii!!iiiiii_Iiiiiiii;iiiiiiii!iiiiiii;i
SideReturnAirCutout
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
1
A= 14/2" (368,3mm)HeightofCutoutfor16"x25"(406,4x635mm)Filter
1
B=22/2" (571.5mm)Widthof Cutoutfor16"x25"(406.4x635mmFilter
CARBON MONOXIDE POISONING HAZARD
EmbossedArea J on Side of Furnace _
Failure to follow this warning could result in personal injury or death.
Cool air passing over heat exchanger can cause condensate to form resulting in heat exchanger
failure.
38 Specifications are subject to change without notice. 440 01 1051 03
Furttace
NOTE: Furnaces with 5 ton cooling rating may require both (left and right) side return or one side and bottom return. Side return air duct(s) is not permitted with horizontal furnace
installation.
5. If air return grille is located close to the fan inlet, install at least one, 90° air turn between fan and inlet grille to reduce
noise.
NOTE: To further reduce noise, install acoustical air turning vanes and/or line the inside of duct with acoustical material.
Sizing
Existing or new ductwork MUST be sized to handle the correct amount of airflow for either heating only or heating and air conditioning.
Insulation
1. Insulate ductwork installed in attics or other areas exposed
to outside temperatures with a minimum of 2" (50.8mm)
insulation and vapor barrier.
2. Insulate ductwork in indoor unconditioned areas with a minimum of 1" (25.4mm) insulation with indoor type vapor
barrier.
Filters
A Filter must be used:
Filters are not supplied with these furnaces, but can be purchased
from the distributor.
Use either filter type:
* Washable, high velocity filters are based on a maximum
air flow rating of 600 FPM.
* Disposable, low velocity filters are based on a maximum
air flow of 300 FPM when used with filter grille.
* See Circulating Air Blower Data for additional data.
NOTE: Disposable, low velocity filters may be replaced with washable, high velocity filter providing they meet the minimum size areas. Washable, high velocity filters can be replaced ONLY with same type and size.
Side Mounted Filter Rack
Bottom Mounted Filter Rack
9" (152.4mm) _._J 25-24-18-1
Slide filter clips towards back before removing
Filter Clip Construction
11_,, \\ _-,\
/2 j-_.. _-_.
-4_(381) _/ \\ \\-
26 Ga. Galvanized Steel -\ ). FASTpart number 1008482 "_'_ 11/16"(27)
Refer to Figure 40 and for guidelines to install filters. Furnaces which require larger filter media and have limited clearances on
one side of furnace, require a standoff filter rack, see Figure 40, available from your distributor.
Standoff Filter Rack
UsingOptional StandoffFilter Rack
25-20-90
FilterInstallationusing OptionalFilterRack
When installing or removing a bottom mounted filter, slide the two
side filter clips to the back of the furnace BEFORE installing or removing. This will allow the filter to clear the front raised edge of
the furnace. Insert filter into side clips first and push filter back until
it is fully engaged into back clip. When filter is in place, slide clips back into place midway on filter as shown in Figure 38 and Figure 39,
440 01 1051 03 Specifications are subject to change without notice. 39
AdditionOfAir Conditioning
When a refrigeration coil is used in conjunction with this unit, it must be installed parallel with or on the discharge side of the unit to avoid condensation on the heat exchanger. All furnaces are designed with a break-away duct flange on the supply air side of the furnace. This allows for installation in the horizontal right or downflow applications. The coil installation instructions must be consulted for proper coil location and installation procedures. With a parallel flow arrangement, dampers must be installed to prevent chilled air from entering the furnace. If manually operated dampers are used,
t_25-21-45a
they must be equipped with a means to prevent operation of either
unit unless the damper is in full heat or full cool position.
A 3" clearance is required on the right side of the furnace in order to
run the condensate drain line. Copper or plastic tubing may be used for the condensate drain line.
DownflowFurnaceInstallation Non-CombustibleFloorInstallation
Fabricate a plenum to the dimensions given in Figure 4, for the
furnace outlet. Plenum should be flanged, approximately 3/4"
(19.1 mm)for support. Note: The three(3) screws in the top panel of the furnace next to the duct flange MUST be removed to provide serviceability of the primary heat exchangers in the downflow installation
1. Position plenum through the floor and set the furnace over
the opening in the floor. If necessary, grout around the base to seal air leaks between the base and the floor.
CombustibleFloorInstallation
FIRE HAZARD Failure to follow this warning could result in
personal injury, death, and/or property damage. Place furnace on noncombustible subbase on
downflow applications, unless installing on non-combustible flooring.
The noncombustible subbase also must be used
on downflow application sin addition to a coil box installation.
Subbase for Combustible Floor
NOTE: The three(3) screws in the top panel of the furnace next to
the duct flange MUST be removed to provide serviceability of the primary heat exchangers in the downflow installation
Note: When using the subbase for combustible floors, the discharge air duct flanges on the furnace MUST be broken down to provide proper fit up to the subbase. Use duct pliers to bend the duct flanges flat onto the furnace casing. DO NOT bend the duct flanges inward (toward the heat exchangers) as air flow restrictions
may occur. The Subbase for Combustible Floors MUST be used when a
downflow furnace is set on a combustible floor, even when the furnace is installed on a coil box.
1. Cut the opening in the floor according to Table 8. The hole in the floor must be cut to the dimensions listed in Table 8
since the base is equipped with locating tabs that center the base over the opening.
The opening in the base is 11/4" (31.8mm) shorter and 11/8"
(28.6mm) narrower than the recommended size of the opening in
the floor. This is done to maintain clearance between the floor and the plenum.
2. Fabricate the plenum to the dimensions given in Table 8. Note that the dimensions given are outside dimensions.
3. Set the base over the opening inthe floor, centering it over
the opening. Fasten the base to the floor with screws or
nails. See Figure 41, Figure 42 and Figure 43.
4. Drop the plenum through the opening in the base. The
flange of the plenum should rest on top of the subbase.
Sub-base for
Combustible Floors
Part Number
FurnaceOnly
NAHH001SB (398.5) (730.3) (369.9)
NAHH002SB (490.5) (730.3) (462)
NAHH003SB (582.6) (730.3) (554)
NAHH010SB (627.1) (730.3) (598.5) 16(406.4)
Subbasefor CoilBox
NAHH004SB (25.4) (522.3) (369.9) (408) NAHH005SB 19_/8 20_/16 18_/16 161/16
NAHH006SB 23 (284.2) (522.3) (554) (408)
NAHH009SB (628.7) (522.3) (598.5) (408)
OutsideDimension
** BaseSpacerSideToSide Conversion:1 in=25.4 mm
Subbases for Combustible Floors Dimensions - in(mm)
Sub-base for Combustible
Floor Dimensions OpeningIn Floor
H* J* K** L M N
1511/16 28_/4 14u/16 16(406.4)
19_/16 28_/4 18_/16 16(406,4)
221=/16 28_/4 211_/16 16(406,4)
241t/16 28_/4 23u/16
15_/4 20u/16 14u/16 16_/16
(181.1) (522.3) (462) (408)
20u/16 211"_/16 161/16
24_/4 20_/16 23_/16 161/16
16_/4 14=/8 13_/2
(412.8) (371.5) 15 (381) (342.9)
16_!4 18_!4 15 (381) 17'!8
(412.8) (463.6) (435.6)
16_/4 21t/8 19_/4
(412.8) (555.6) 15 (381) (501.7)
16 _/4 23=/8 22 _/2
(412.8) (600.1) 15 (381) (571.5)
16_/4 14=/8 13_/2
(412.8) (371.5) 15 (381) (342.9)
16_!4 18_!4 17V8
(412.8) (463.6) (435.6)
16_/4 21_/8 19"_/4
(412.8) (555.6) 15 (381) (501.7)
16_/4 23=/8 22 '/2
(412.8) (600.1) 15 (381) (571.5)
Opening In
Base For Plenum
P R
15(381)
Typical Plenum
Dimensions
S
15(381) 13V2
15(381) (435.6)
15(381) (501.7)
15(381) (571.5)
15(381) (342.9) 15(381)
15(381) (501.7)
15(381) (571.5)
(342.9)
17'/8
19_/4
221/2
131!2
17V8
(435.6)
19_/4
22'/2
40 Specifications are subject to change without notice. 440 01 1051 03
///il///i!!iiii/i;iiiiii!_iiii/ii!li}i¸i_iiiiii¸ii_i/iiiii/iiiiiiii///iii_ii_!ii_lii!ilii/i
iiiii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii Furnace ON LY
jl_r_ s
_;_ Plenum _#_
.1, H_ I_ 2" (50.Smm)
A = 4 1/4" (108mm) Minimum clearance from back of hole to wall or other obstruction.
i i:: t: iii
Exploded View of Base for Downflow Cased Coil
%..
_.. _
21/2" (63.5mm)
(50.8mm) L _
5. Position furnace or coil cabinet and furnace on subbase so it aligns between the locating tabs.
Fig_43': Setting the Subbase
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
J
Furnac_' \/_\
Installation of _ _IL Combustible
Floor Base
_-_._:@::/::::: i I \._._._ Wood Floor
Plenum
25-20-46a
This subbase for combustible floors has been designed so that the
height of the subbase raises the downflow coil off the floor to allow easy installation of the condensate drain. See Figure 44.
11/2" (38.1mm)
iliiiiiI! i iiCondensate Line Raised by Base
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
I I
I I
25-20-5;
A 3" (76.2mm) clearance is required on the right side of the furnace in order to run the copper or plastic tubing for the condensate drain
line.
Checks and Adjustments
NOTE: Verify the input rate of the furnace.
FIRE OR EXPLOSION HAZARD
FIRE OR EXPLOSION HAZARD Failure to follow this warning could
result in
personal injury, death, and/or property damage. Turn OFF gas at shut off before connecting
manometer.
Failure to follow this warning personal injury, death, and/or property damage.
If any sparks, odors or unusual noises occur, immediately shut OFF power to furnace. Check for wiring errors or obstruction to blower.
GasSupply Pressure
Startup
NOTE: Refer to the start-up procedures in the "User's Information
Manual" or to the "Operating Instructions Label" on the furnace.
Gas supply pressure should be within minimum and maximum values listed on rating plate (minimum and maximum pressures, refer to Table 5). Pressures are usually set by gas suppliers.
ManifoldGasPressureAdjustment
NOTE: Make adjustment to manifold pressure with burners
operating.
440 01 1051 03 Specifications are subject to change without notice. 4t
could result in
1. Remove the burner compartment door.
2. Remove the blower compartment door. Place a jumper across furnace controls R to W. Replace blower compartment door.
3. With gas OFF, connect manometer to tapped opening on gas valve. Use manometer with a 0 to 15 inches of water column range.
4. Turn gas ON and remove adjustment screw cap on gas
valve. Turn adjusting screw using 3/32 hex wrench,
counterclockwise to decrease manifold pressure and clockwise to increase pressure.
NOTE: Adjustment screw cover MUST be replaced on gas control
valve before reading manifold pressure and operating furnace.
5. Set manifold pressure to value as shown in Table 6 or
Table 7 under GAS SUPPLY AND PIPING section in this
manual.
6. When the manifold pressure is properly set, replace the adjustment screw cover on the gas control valve.
7. Remove blower compartment door. Remove jumper wire
from thermostat connection on furnace control board.
Remove manometer connection from manifold pressure
tap, and replace plug in manifold.
8. Check for leaks at plug.
9. Replace the burner and blower compartment doors.
Fi_ _ _ii,ii_1Typical Gas Control Valve
RegulatorAdjustment UnderCap
INLET
Inlet Pressure
Tap 1/8 NPT z
Outlet Pressure
Tap
1/8NPT
j_---
OUTLET
Example (kW)
Number of
seconds per seconds per Size of test dial
hour complete (.05m3) kW m3/h
3,600 80 .05 2.25
3. Remove jumper wire from R to W.
4. Relight all appliances and ensure all pilots are operating.
Number of
rotation
3,600+ 80 x .05= 7.2 m3/h
2.25m3/hx 10.35kWh/m 3= 23.28 kW
23.28 x 3.412 =79,431 BTU
MainBurnerFlameCheck
Allow the furnace to run approximately 10 minutes then inspect the main burner. See Figure 46.
Check for the following (Figure 46):
Stable and blue flames. Dust may cause orange tips or wisps of yellow, but flames MUST NOT have solid, yellow
tips.
Flames extending directly from burner into heat exchanger.
Flames do NOT touch sides of heat exchanger.
If any problems with main burner flames are noted, it may be necessary to adjust gas pressures, or check for drafts.
o,n..rner
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
r Face
NaturalGasInput RatingCheck
NOTE: The gas meter can be used to measure input to furnace. Rating is based on a natural gas BTU content of 1,000 BTU's per cubic foot. Check with gas supplier for actual BTU content.
1. Turn OFF gas supply to all appliances and start furnace. Use jumper wire on R to W for Heat.
2. Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution. Refer to Example.
NOTE: If meter uses a 2 cubic foot dial, divide results (seconds) by two.
Example (BTUH)
Natural Gas BTU Per BTU Content Hour
1,000 3,600 48 75,000
TO Determine the appliance kW input rate from a .05m3 test dial that has been clocked at 80 seconds for one complete revolution.
No. of Time Per
Seconds Cubic Foot in Per Hour Seconds
1,000 x 3,600+ 48 = 75,000 BTUH
10-10-78
NOTE: For Ignitor location see Figure 47.
, n,,or,oco,,on
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
21/16(52.4)
5/16(8)_ F
NOTE: Flame sensor has a different orientation in all 050 models.
TemperatureRiseCheck
The blower speed MUST be set to give the correct air temperature rise through the furnace as marked on the rating plate. Temperature rise is the difference between supply and return air temperatures.
To check temperature rise,use the following procedure:
1. Place thermometers in supply and return air registers as close to furnace as possible, avoiding direct radiant heat
from heat exchangers.
42 Specifications are subject to change without notice. 440 01 1051 03
2. Operate furnace continuously for 15 minutes with all registers and duct dampers open.
3. Take reading and compare with range specified on rating plate.
4. If the correct amount of temperature rise is NOT obtained, it may be necessary to change blower speed. A higher blower
speed will lower the temperature rise. A lower blower speed will increase the temperature rise.
ChangingBlowerSpeed
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in
personal injury or death.
Turn OFF power, lockout and tag with a suitable warning label, to furnace before changing speed taps.
NOTE: The speed taps that the manufacturer sets from the factory
for this product are based on a nominal 400 CFM per ton cooling
and the basic mid range on the temperature rise for heating. Since the manufacturer cannot establish the static pressure
that will be applied to the unit, it is the responsibility of the installer dealer/contractor to select the proper speed taps for
the application when the unit is installed.
If it is necessary to change speeds, refer to steps below.
REDUCEDFURNACELIFEHAZARD Failure to follow this caution may result in reduced
furnace life.
Use ONLY the blower motor speed taps insert indicated in the Circulation Air Blower Data for
setting air temperature rise.
Blower Speed Chart
Wire Color
Black
Orange*
Blue
Red
* Med-High speed may not be provided on all models.
1. Refer to Furnace Wiring Diagram for location of the heating and cooling speed taps located on the furnace control as well as location of unused blower motor speed leads. Use
the chart (Table 9) to determine the blower motor speed
settings.
Motor Speed
High
Med-High
Medium
Low
Furnace Maintenance
2. Change the heat or cool blower motor speed by removing the motor lead from the "Heat" or "Cool" terminal and
replace it with the desired motor speed lead from the "Unused Motor Lead" location. Connect the wire
previously removed from the "Heat" or "Cool" terminal to the vacated "Unused Motor Lead" terminal.
3. If the same speed must be used for both heating and cooling, remove the undesired motor speed lead from the
"Heat" or "Cool" terminal and connect that lead to the open terminal at "Unused Motor Lead" location. Attach a jumper between the "Heat" and "Cool" terminals and the remaining
motor speed lead.
Note: For motors with (4) speed leads, it will be necessary to tape off the terminal of the motor speed lead removed from the "Heat" or "coor' terminal with electrical tape since an open terminal will not be available at the "Unused Motor
Lead" location.
Continuous-Fan Operation using "G"
Energizing the "G" terminal on the furnace control provides continuous fan operation. This is done by connecting the G
terminal of the thermostat to the G terminal on the furnace control. When the FAN switch is turned from auto to ON the fan will operate
continuously at "HEAT" speed. EAC will be energized in this mode.
NOTE: In heating, the fan will turn off during furnace ignition and warm up then restart at heating speed.
Hard Wired Continuous Fan Operation
A terminal is provided on the furnace control board located in the circulating blower compartment for operation of the continuous fan option. This connection is intended for the low speed motor tap, and has a lower contact rating (8 amps) than the heat and cool taps. When the low speed blower lead is connected to this terminal, this will provide low speed blower operation whenever the other two speeds (Heat or Cool) are not energized.
Thoroughly check the system after modification to ensure the proper operation of the circulating air blower in all modes of operation.
Separatespeedselectionsfor Heat,Cool,and ContinuousFan
Connect low speed lead from circulating motor to the "Cont." terminal at the furnace control. The appropriate motor leads should already be connected to the "Heat" and "coor' terminals.
Heating and Continuous Blower Speedthe
Same
If it is necessary to operate the heating speed and continuous blower speed using the same blower speed, connect a jumper
between the "Heat" and "Cont." terminals on the furnace control. Note: There should be only ONE motor lead going to the "Heat"
and "Cont." terminals.
FIRE, EXPLOSION, OR CARBON MONOXIDE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
It is recommended that the furnace be inspected and serviced on an annual basis (before the heating season) by a qualified service technician.
See "User's Information Manual':
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Before servicing, disconnect all electrical
power to furnace.
When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
440 01 1051 03 Specifications are subject to change without notice. 43
Sequence of Operation & Diagnostics
The following is the normal operating sequence.
Cooling(Y) Request:
24VAC signals applied to Y & G terminals of FCB (furnace control board)
Cool motor speed is energized after 5 second Cool Fan On Delay time.
Y & G signals removed from FCB
Cool motor speed is de-energized after 90 second Cool Fan Off Delay time.
ContinuousCirculatingFan(G) Request:
24 VAC signal is applied to G terminal of the FCB.
Heat motor speed is energized without delay. G signal removed from FCB.
Heat motor speed is de-energized after 5 second delay. NOTE 1)Furnace de-energizes the fan during the heat exchanger warm-up period on a call for Heating that occurs during a G request
unless a blower motor lead is connected to the Cont terminal on the FOB, in which case see NOTE 2). NOTE 2) Heating or Cooling requests received during a Fan request cause the fan speed to change to the appropriate heat or cool
speed after the Fan on Delay time expires. The fan returns to continuous circulating speed after the selected Fan Off Delay time expires
following loss of the Heating or Cooling request.
ContinuousCirculatingFanHard-Wired (Cont) Request:
Field selected low speed motor tap installed on "CONT" terminal.
Low speed is energized when power applied to furnace. Operates at this speed continuously while there are no other blower demands from furnace control. Fan demands from furnace control for heat, cool or "G" will override hard-wired speed tap.
NOTE 3) EAC is NOT active for hard-wired mode but IS active for fan demands from furnace control for heat, cool and "G".
Heating(W) Request:
Heating (W) Request:
24 VAC signal applied to W terminal of FOB.
Inducer motor turns on and the pressure switch(es) close(s).
Following a 15 second prepurge delay, after the pressure switches closes, the igniter begins a 17 second warm-up.
The gas valve is energized, the main burners light and flame is sensed.
The igniter is de-energized after the main burners ignite.
FOB will delay blower operation for the 30 seconds timed from the opening of the gas valve.
W signal removed from FCB.
The gas valve de-energizes and the main burners go out.
The inducer runs for a 15 second postpurge period.
The fan stays at Heat speed.
The fan de-energizes after the selected Heat Fan Off Delay time expires, timed from the gas valve de-energizing. HUMIDIFIER - The 24V HUM is energized when the pressure switch closes on a call for heat. The 115V HUM (called HUM on Control)
is energized when the inducer is energized. ELECTRONIC AIR CLEANER - EAC is energized when there isa blower speed call. It is NOT energized when blower operates in the
hard-wired continuous fan mode. NOTE 4) Ifa new Heating request arrives while the control is waiting in the Heat Fan Off Delay time, the FCB will wait for the selected
Heat Fan Off Delay then start a new heating cycle as long as the heat call remains.
44 Specifications are subject to change without notice. 440 01 1051 03
HeatingRequestwith GasShutOff:
24 VAC signal applied to W terminal of FCB.
The FOB will attempt 4 cycles for ignition then go to soft lockout for 3 hours then try for ignition again as long as the heat call remains.
Power reset will clear lockout.
Inducer motor turns on
Following a 15 second prepurge delay, the igniter begins warm up.
The igniter glows red-hot for 22 seconds, then turns off. The FOB flashes error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FOB continues flashing error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FOB continues flashing error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FOB proceeds to soft lockout and stops flashing error code 6 and begins flashing error code 6 + 1.
The inducer motor de-energizes after a 15 second post purge.
ControlBoardDiagnosticCodes (SeeFigure48)
OFF = 24VAC or 115VAC is off, fuse is open Heartbeat = Normal operation or no previous Diagnostic Code ON SOLID = Soft Lockout - Furnace Control Error (1 hr delay)
If code repeats immediately following power reset then replace control
1 Flash = Not used 2 Flashes = Pressure switch(es) closed when should be open
3 Flashes = Pressure switch open when should be closed 4 Flashes = Limit or roll-out switch open (less than 2 minutes)
5 Flashes = Flame sensed out of sequence 6 Flashes = Failure to ignite or flame sense lost while running 6 + 1 Flashes = Soft Lockout - Max trials for ignition reached (3hr delay) 7 Flashes = Soft Lockout - Limit or roll-out switch open longer than 2 minutes (1 hr delay)
(roll-out switch requires manual reset) 8 Flashes = Permanent Lockout - Gas valve relay contact stuck closed or miswired gas valve (power reset only) 10 Flashes = Line voltage (115VAC) polarity reversed. Iftwinned, refer to twinning kit instructions
* If status code recall is needed, briefly (2-3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored
status code. Do not remove power or blower door before initiating status code recall or code will be lost. Code is automatically cleared after 72 hours or upon power reset.
* Proper flame sense microamps: 0.7 microamps D.C. minimum
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
DiagnosticLight
115VAC
L< 25-24 -98
2.0 - 4.0 microamps nominal
440 01 1051 03 Specifications are subject to change without notice. 45
CONNECTION DIAGRAM 1 WARNING:ELECTRICAL SHOCK HAZARD l LADDER DIAGRAM zoo
ROLLOUT SWITCH 1 TO 2 TO 115VAC FIELD DISCONNECT
IN SERIES DEPENDING ON MODEL COPPER CONDUCTORS
R m 0 + Z_Iz
_0 m m c0c_ F-mr-
DEPENDINGONMODEL \ MOIOR J _ rlUUI BK | --z mOO
DISCONNECT BEFORE SERVICING m o o
( O o-nu /
GND _. i m C] m /
:::,L. ±
GRNHI NOTE,,2
--_F------W_SENSORE3:_P4 / _ M"
mml 100 180 60SEC
-H 60 140
ROLLOUT SWITCH ] TO 3
HEAT COOL
- :': _,
_W
1. If any of the original equipment wire is replaced use wire rated 1050 C. SPEED TAP CODE
fanyoftheo _
Jse only cop_ 140SEC
2. Use only copper wire between the disconnect switch and the furnace BK
3. This wire must be connected to furnace sheet metal for control to
4. Symbols are electrical representation only. GREEN!YELLOW
5. Solid lines inside circuit board are printed circuit board traces and are not depicted as shown in the legend.
Thisjunctionprovewireflame,box.mu: ORANGEREDBLUEBLACK_ MLO _MHILOHI,...,..,..j._LOW_1_1E_uA_KWHITEGREENG!_GREEN!YREDBROWN YW0RGRN/YBRBK _"__ 1ooJl 180
6. Replace only with a 5 amp fuse.
7. Blower motor speed selections are for average conditions, see installation instructions for details on optimum speed selection.
8. Factory connected when LP Pressure Switch and BVSS (Chimney LOW VOLTAGE FACTORY
Adapter Accessory Kit) are not installed.
9. Blower off-delay, gas heating selections are (60, 100, 140, and 160) seconds, cooling or heat pump 90 seconds. _ LINE VOLTAGE FACTORY
lO. Ignition lockeut will occur after four consecutive unsuccessful trials for _ _ . LINEVOLTAGEFELD
ignition. Control will auto-reset after three hours.
11. Blower motor and inducer motor contain internal auto-reset thermal CONDUCTOR ON CONTROL
overload switches.
12. Flame sensor: 0.7 pA D.C. minimum, 2.0 -4.0 pA nominal. UNMARKEDTERMINAL
13. Depending on model, P4 inducer motor leads and P5 gas valve leads may CONTROLTERMINAL
be in asingle connector or two quick connectors.
-- LOW VOLT/ 80
..... LOW VOLTAGE FIELD
.... LOW VOLTP
LINEVOLTA
_ LINEVOLT,_
JUNCTION
0
CONDUCT( _D
[ CONTROLBOA
I P1-10 LPPRESSSWITCH
TRANSFORMER
333309-10I REV. B
Q
_>oo
x
100SEC. _l_
95% Furnace
Up flo w/Ho rizo ntal/D own flo w
Models
Dual Certified
*9M PX060F 12A2
*9M PX080J 12A2 *9M PX080J 16A2
*9M PX100L20A2
* Denotes Brand
\
\
International Comfort Products, LLC Lewisburg, TN 37091 U.S.A.
Save This Manual For Future Reference
44001 105103 Specifications are subject to change without notice 47
Model Specifications (*9MPX)
TECHNICAL SUPPORT
Manufacturers Number (Mfr No-See Rating Plate)
ALL Models
General
GasType Input(Btuh)
Output(Btuh)
TransformerSize (VA) Tstat Heat Anticipator
Temp.Rise(F/C)
Electrical(Volts/Hz) RatingPlateAmps
Gas&Ignition
GasType GasValve(Honeywell)
RegulationType IgnitionType/Series
ManifoldPress,(inwc/Pa) Std,MainOrifices(No/Size)
FurnaceControls
FurnaceControl On (Timed-secs) Off
Combustion Flue Outlet Size (Inches) Std. Outlet Temp (less than) °5' No Elbows (°FPC)
BlowerPressure5' No Elbows (in wc/Pa) BlowerPressure40' +5-90 ° DWV Elbows (in wc/Pa)
Transition Bx Pressure 5' No Elbows (in wc/Pa)
TransitionBxPressure40' +5-90 ° DWV Elbows (in wc/Pa)
Limits &Controls RolloutSwitch (°F/°C)
LimitControlSetting (°FPC)
AuxilliarySwitchSetting (°F/°C)
Standard Pressure Sw. (Part No)
Blower Switch Pressure (Close) (in wc/Pa)
Blower Switch Pressure (Open) (in wc/Pa) Transition Switch Pressure (Close) (in wc/Pa) Transition Switch Pressure (Open) (in wc/Pa)
High Altitude Pressure Sw. (Part No)
Blower Switch Press (Close) (in wc/Pa)
Blower Switch Pressure (Open) (in wc/Pa) Transition Switch Press (Close) (in wc/Pa)
Transition Switch Pressure (Open) (in wc/Pa)
Blower Data BlowerSizeInchesDx W - in(mm)
MotorAmps/RPM MotorType/H,E
Cap,Mfd/Volts FilterType&Size (mm)(qty.)Permanent- notsupplied
CoolCap. (Tons)@ .5 inwc (125Pa)- L,ML,MHi & Hi
GasConversionKits
Natto Propane PropanetoNat
**Order from Service Parts
Upflow Downflow/Horizontal
Upflow Downflow/Horizontal
NAHA00701LP(1178473'_) NAHA00701NG (1178474**)
Specifications (*9MPX)
*9MPX060F12A *9MPX080J12A *9MPX080J16A *9MPX100L20A
Nat./Propane
60,000 60,000
58,000 58,000
40
.50
30-60/17-33
115!60
10
Nat, Propane
3.5/872 10.0!2490 3/44 3/55
140/60
-1.8/-448
-1.7/-423
-3.2/-797
-2.9/-722
300/148 250/121
1177767 0,58/144 0,43/107
1,73/431
1.70/423 1177767
0,58/144 0,43/107 1,73/431
1.70/423
11x10(279x254)
7.2/1020 PSC!I_
7,5/370
16x25xl
(406x635x25)
11/2through3
Nat./Propane
80,000 80,000
77,000 77,000
4O
.50
35-65/19-36
115!60
10.5
Nat. Propane Nat.
VR8205S
SNAP
HotSurface
3.5/872 10.0/2490 4/44 4/55
30
60,100,140,180
140/60
-1.9/-473
-2.0/-498
-3.2/-797
-2.9/-722
300/148 250/121
160/71
1177764
0.95/237
0.80/199
1.89/471
1.55/386 1177768
0.95/237
0.80/199
1.61/401
1.43/356
11x10(279x254)
5.7/1075 PSC/1/3
10/370
16x25xl
(406x635x25)
11/2through3
Nat./Propane
80,000 80,000
77,000 77,000
4O
.50
30-60/17-33
115!60
13.6
Propane
3.5/872 10.0/2490 3.5/872 10.0/2490 4/44 4/55 5/44 5/55
140/60
-1.9/-473
-2.0/-498
-3.2/-797
-2.9/-722
300/148 220/104
1177764
0.95/237
0.80/199
1.89/471
1.55/386
1177768
0,95/237
0.80/199 1,61/401
1.43/356
11x10(279x254)
10/1050 PSC!I_
10/370
16x25xl
(406x635x25)
21/2through4
Nat./Propane
100,000
97,500 96,000 94,000
40
.50
30-60/17-33
115!60
14.8
Nat,
Propane
140/60
-2.3/-573
-2.4/-598
-3.2/-797
-2.9/-722
350/177
190/88
1174465
1.56/396 1,38/344
2,32/578
1.66/413 1177769
1.30/324
1.14/384
1.97/491
1.78/443
11x10(279x254)
11,5/935
PSCf3/4
40/370
16x25xl
(406x635x25) (2)
31/2through 5
48 Specifications are subject to change without notice. 440 01 1051 03
CIRCULATION AIR BLOWER DATA (CFM & L/s)
*9MPXO60F12 (1)(2) * Denotes Brand *9MPXO80J16 (1)(2) * Denote Brand
Rnrl_,_ee_ HI MED H MED L LO
Tap
in wc Pa CFM L/s CFM L/s CFM L/s CFM L/s
"_ 0.1 25 1478 697 1204 568 901 425 mm 0.2 50 1418 669 1154 545
_. _" 0.3 75 1350 637 1103 521
O n
'_ 0.4 100 1280 604 1053 497
,- 0.5 125 1201 567 993 469
"_" 0.6 149 1116 527 924 436
-_ 0.7 174 1023 483
LLI
0.8 199 931 439
0.9 224 1 249
*9MPXO80J12 (1)(2) * Denotes Brand
Speed HI MED H MED L LO
Tap
in wc Pa CFM L/s CFM L/s CFM L/s CFM L/s
•_ 0.1 25 1456 687 1326 626
0.2 50 1440 680 1312 619
_. _" 0.3 75 1420 670 1280 604
08.
_ 0.4 100 1379 651 1241 586
,- 0.5 125 1325 625 1209 571
_ 0.6 149 1261 595
0.7 174 1208 570
LLI
0.8 199
0.9 224 1 249
NOTE:
# CFM - Cubic Feet Per Minute airflow. Filter required for each return-air inlet.
Airflow performance includes 1" (25.4mm) washable [600 FPM (3.0 m/s) max] filter media.
(1) Data Based on Bottom Only or One Side return. (2) Gray area is above maximum temperature rise range.
Speed HI MED H MED L LO
Tap
in wc Pa CFM Us CFM L/s CFM Us CFM L/s
0.1 25 2032 959 1690 798 1246 588
0.2 50 1952 921 1650 779 1250 590
_. _" 0.3 75 1874 884 1601 756 1226 579
o8-
_ 0.4 100 1785 842 1533 723 1187 560
c 0.5 125 1688 797 1462 690
_ 0.6 149 1593 752 1381 652
LLI
0.7 174 1482 699 1287 607
0.8 199 1360 642 1182 558
0.9 224 1231 581 1 249 iiiiiiiiiiiiii!ii_i_iiiiiiiiiiiiiili!iiiiiiiiiii_ii!_i!_i_i;i;i;iiiiiiiiiiiiiiiii;!_ii_iiiiiiiiiiiiiiiii iiiiiiiiiiiii_i_i_!ii!ii!ii!iiii!iliiiiiiiiiii_!iiiiiiiiiiiii
*9MPXIOOL20 (1)(2) * Denotes Brand
Rnd__ee_ HI MED H MED L LO
Tap
in wc Pa CFM L/s CFM Us CFM L/s CFM L/s
0.1 25 2240 1057 2137 1008 1993 941 1820 859
0.2 50 2163 1021 2062 973 1934 913 1768 834
_" 0.3 75 2083 983 1992 940 1872 883 1722 813
o8-
_ 0.4 100 2002 945 1916 904 1801 850 1656 782
_ 0.5 125 1912 902 1833 865 1723 813 1590 750
_ 0.6 149 1821 859 1745 824 1636 772 1513 714
0.7 174 1727 815 1654 781 1547 730
w
0.8 199 1618 764 1551 732
0.9 224 1502 709 1 249 iiiiiiii;_i!ii;ii_!_i!i_ii!i:!i!i!iiiiiiiiiiii_ii;ii;ii;ii;ii;ii;ii;ii;iiiliiiiiiiiii;_i!iiiiii_i!_ilililil;!iiiiiiiii_iiiiii_!i_ii!ii!ii!ii!iiiiiiiii_!_i!ii!ii!ii!ii!iiiiiiiiii;ii!ii!i_!_i!ii!ii:ii!iiiiiiiiiii_i_:!i:!i:!i:!i:!i:!i!!i
MAX CFM'sfor Factory Washable Filters
Filter Size (in/mm) CFM Ws
14"X 25"/356 x 635 1400 661
16"X 25"/406 x 635 1600 755 20"X 25"/508 x 635 2000 944 24" X 25"/610 x 635 2500 1180
Max CFM based on 600 FPM (3.0 m/s)
NOTE: Dis _osable filters are typically rated at 300 FPM (1.5 m/s). These filters
only allow half the airflow when compared to 600 FPM (3.0 m/s) filters.
Bellyband Location on Motor - A Dimension
E
....
44001 105103 Specifications are subject to change without notice. 49
Model
*9M PX
inches mm
060 F 12 13/8 35.1
080J 12 17/8 46
080J20 17/8 46
100L20 15/8 41.9
INDUCED-COMBUSTION GAS FURNACE
PARTS REPLACEMENT INFORMATION GUIDE
CASING GROUP
Blower door Front door
Door filler plate Top panel gasket Blower partition
INDUCER GROUP
Gasket inducer motor Pressure switch(es)
Inducer assembly
BLOWER GROUP
Blower assembly Blower hanger Blower housing Blower cutoff panel
Blower motor Blower wheel
Capacitor Capacitor strap
FILTER GROUP
Filter(s)
HEAT EXCHANGER GROUP
Primary heat exchanger cell Primary heat exchanger partition Secondary heat exchanger assembly
Transition assembly
Plate gasket
ELECTRICAL GROUP
Control box Junction box
Limit switch (es) Control board
Door switch
Transformer Wiring harness
5-amp fuse
GAS CONTROL GROUP
Manifold Burner
Orifice
Flame sensor Hot surface ignitor
Gas valve
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause
carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which
may cause personal injury or property damage. Consult a qualified installer,
service agency, local gas supplier, or your distributor or branch for information or
assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product.
PRODUCT NOMENCLATURE
* 9
Brand Identifier
* = Brand (C, H, T)
Model Efficiency
8 = Non-Condensing, 80+% Gas Furnace 9 = Condensing, 90+% Gas Furnace
Installation Configuration
DN = Downflow UH = Upflow/Horizontal
MP = Multiposition, Up/Down/Horizontal MV = Multiposition, Variable Speed, Up/Down/Horizontal
Major Design Feature
1 = One (Single) Pipe 2 = Two Pipe
D=lor2Pipe L = Low NOx
X = High Efficiency
N = Single Stage P = PVC Vent
T = Two Stage V = Variable Speed
Have available the product!model number and the serial number located on the unit rating plate to ensure correct replacement parts. TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or the classified section of your local telephone
directory under the "Heating Equipment" or "Air Conditioning Contractors and Systems" headings for dealer listing by brand name, or contact:
MP X o 40 12 A #
Engineering Rev.
Denotes minor changes
Marketing Digit
Denotes major change
Cooling Airflow
08 = 800 CFM
12 = 1200 CFM 14 = 1400 CFM
16=1600CFM
20 = 2000 CFM
Cabinet Width B = 15.5"Wide
F = 19.1"Wide
J = 22.8" Wide L = 24.5" Wide
Input (Nominal MBTUH)
International Comfort Products, LLC
Consumer Relations Department
P.O. Box 128
Lewisburg, TN 37091, USA
931-270-4100
50 Specifications are subject to change without notice. 44001 105103
Loading...