ICP C9MPT075F14C1, CMPV050F12D1, C9MPT100J16C1, C9MPT125L20C1, C9MPV075F12D1 Technical Support Manual

...
Four Position Furnace
Models
Dual Certified *9MPT050F12C1 *9MPT075F14C1 *9MPT100J16C1 *9MPT125L20C1
*9MPV050F12D1 *9MPV075F12D1 *9MPV100J20D1 *9MPV125L20D1
Technical Support (*9MPT) 2................
Circulation Air Blower Data (*9MPT) 3.........
Wiring Diagram (*9MPT) 4...................
Parts (*9MPT) 5...........................
Technical Support (*9MPV) 8...............
Circulation Air Blower Data (*9MPV) 9.........
Wiring Diagram (*9MPV) 18..................
Parts (*9MPV) 19..........................
Save This Manual For Future Reference
®
International Comfort Products, LLC
Lewisburg, TN 37091 U.S.A.
®
440 04 2023 02 August 2007
1
TECHNICAL SUPPORT
Manufacturers Number (Mfr No --SeeRatingPlate) ALL Models
Specifications
*9MPT050F12 *9MPT075F14 *9MPT100J16 *9MPT125L20
General
Gas Type
Transformer Size (VA) T’stat Heat Anticipator
Input (Btuh) Std/Alt. HI Heat
LO Heat
Output (Btuh) Std/Alt. HI Heat
Tem p. Rise (
oF/o
LO Heat
C) HI Heat
LO Heat
Electrical (V olts/Hz) 115/60 115/60 115/60 115/60
Rating Plate Amps 11. 8 11. 8 11. 8 14.0
Gas & Ignition
Gas Type Std. Main Orifices (No/Size)
Gas Valve (Honeywell) Regulation Type Manifold Press. HI Heat (in wc)
LO Heat (in wc)
Ignition Type/Series Hot Surface
Combustion
Flue Outlet Size (Inches) Std. Outlet Temp (
oF/o
C)
@Blower/ @ Transition Box (HI Heat)
Std. Pressures (in wc) 5No Elbows 40+5--90° DWV Elbows
@Blower/ @ Transition Box (LO Heat)
Std. Pressures (in wc) 5No Elbows 40+5--90° DWV Elbows
Furnace Controls
Furnace Control (Type) Furnace Control On (Timed--secs) Off
Limits & Controls
Rollout Switch ( Limit Control Setting (
oF/o
C)
oF/o
C)
Std. Pressure Sw. (Part No)
Blower Switch Pressure (Close) Blower Switch Pressure (Open) Transition Switch Pressure (Close) Transition Switch Pressure (Open)
High Altitude Pressure Sw. (Part No)
Blower Switch Pressure (Close) Blower Switch Pressure (Open) Transition Switch Pressure (Close) Transition Switch Pressure (Open)
Blower Data
Blower Size (D x W inches) Motor Amps/RPM Motor Type/H.P. Cap. Mfd/Volts Filter Type & Size (qty.) Permanent -- supplied Cool Cap. (Tons) @ .5 in wc L, ML, MHi & HI
Gas Conversion Kits All Models
Nat to Propane NAHA002LP (1172959*) Propane to Nat NAHA002NG (1172961*)
*Order from Service Parts
Nat Propane Nat Propane Nat Propane Nat Propane
40
.50
35--65/19--46 25--55/14--30
Nat. 2/42
VR8205Q
SNAP
3.5
1.7
--1.80 / --2.60
--1.30 / --2.30
--1.20 / --1.90
--1.00 / --1.80
50,000 35,000 46,000 32,000
2
<140/60
Propane
2/54
VR8205Q
SNAP
10.0
4.9
VR8205Q
40--70/22--38 30--60/17--33
Nat. 3/42
SNAP
3.5
1.7
--1.80 / --2.60
--1.30 / --2.30
--1.20 / --1.90
--1.00 / --1.80
75,000 53,000 70,000 49,000
2
<140/60
Propane
3/54
VR8205Q
SNAP
10.0
4.9
40--70/22--38 30--60/17--33
Nat. 4/42
VR8205Q
SNAP
3.5
1.7
--1.80 / --2.60
--1.70 / --2.50
--1.20 / --1.90
--1.00 / --1.80
100,000
70,000 93,000 65,000
3
<140/60
Propane
4/54
VR8205Q
SNAP
10.0
4.9
125,000
87,500
117,000
82,000 40--70/22--38 30--60/17--33
Nat. 5/42
VR8205Q
SNAP
3.5
1.7
3
<140/60
--1.80 / --2.60
--1.70 / --2.50
--1.30 / --2.30
--1.20 / --2.20
Integrated
30 HI /45 LO
60,100,140,180
300/149 260/127
1013515
0.95
0.80
1.70
1.50
1013165
0.70
0.55
1.40
1.20
11 x 8
10/1050
1
PSC/
10/370
16x25x1
1.5 thru 3
/
2
300/149
210/99
1013515
0.95
0.80
1.70
1.50
1013165
0.70
0.55
1.40
1.20
11 x 10
10/1050
1
PSC/
/
10/370
16x25x1
1.5 thru 3.5
300/149 240/116
1013515
0.95
0.80
1.70
1.50
1013165
0.70
0.55
1.40
1.20
11 x 10
10/1050
1
PSC/
2
10/370
/
2
16x25x1
2.5 thru 4
300/149
180/82
1013166
1.30
1.10
1.80 1,60
1013157
0.85
0.70
1.70
1.50
11 x 10
13/900
PSC/
40/370
16x25x1 (2)
3.5 thru 5
Propane
5/54
VR8205Q
SNAP
10.0
4.9
3
/
4
2
Specifications are subject to change without notice
440 04 2023 02
Circulation Air Blower Data - *9MPT
*9MPT050F12 (1) * Denotes Brand
(in wc)
Exterrnal Static Pressure
Speed
Tap
0.1 826 1083 1301 1408
0.2 804 1050 1242 1347
0.3 770 1028 1195 1295
0.4 735 985 1153 1237
0.5 698 952 1093 1183
0.6 657 909 1040 1118
0.7 -- -- -- 863 935 1053
0.8 -- -- -- -- 812 865 976
0.9 -- -- -- -- -- -- 802 887
1.0 -- -- -- -- -- -- 720 787
Low Med L Med H Hi
*9MPT100J16 (1) * Denotes Brand
(in wc)
Exterrnal Static Pressure
Speed
Tap
0.1 823 1109 1527 1850
0.2 795 1087 1482 1791
0.3 747 1056 1426 1720
0.4 677 1016 1382 1648
0.5 617 970 1317 1575
0.6 544 854 1245 1485
0.7 -- -- -- 763 1154 1401
0.8 -- -- -- 652 1043 1284
0.9 -- -- -- -- -- -- 905 1161
1.0 -- -- -- -- -- -- 737 1028
Low Med L Med H Hi
*9MPT075F14 (1) * Denotes Brand *9MPT125L20 (2) * Denotes Brand
(in wc)
Exterrnal Static Pressure
Speed
Tap
0.1 695 1025 1455 1724
0.2 674 1001 1410 1662
0.3 653 951 1365 1601
0.4 631 921 1309 1530
0.5 609 891 1252 1460
0.6 569 845 1187 1380
0.7 529 799 1122 1300
0.8 490 730 1030 1190
0.9 -- -- -- 680 950 1080
1.0 -- -- -- -- -- -- 831 969
Low Med L Med H Hi
(in wc)
Exterrnal Static Pressure
Speed
Tap
0.1 1720 1910 2127 2315
0.2 1686 1881 2087 2268
0.3 1644 1833 2024 2201
0.4 1600 1777 1961 2131
0.5 1533 1720 1891 2029
0.6 1494 1647 1804 1948
0.7 1413 1571 1708 1820
0.8 1306 1470 1604 1730
0.9 -- -- -- 1349 1484 1614
1.0 -- -- -- -- -- -- 1328 1430
Low Med L Med H Hi
NOTE: (1) Data based on Bottom Only or One Side return.
(2) Data based on Both Sides or Bottom plus One Side
MAX CFM’s for Factory
Washable Filters
Filter Size CFM
14X25 1400
16X25 1600
20X25 2000
24X25 2500
Max CFM based on 600 FPM
NOTE: Disposable filtersare typically rated at 300 FPM.These filters only allow half the airflow when compared to 600 FPM filters. (EXAMPLE, 20 X 25 @ 600 FPM = 200 CFM, @ 300 FPM = 1000 CFM)
# CFM -- Cubic feet per minute airflow. Filter required for each return--air inlet. Airflow performance includes 1washable (600 FPM max) filter media.
440 04 2023 02
Specifications are subject to change without notice
3
Wiring Diagram *9MPT (Two Stage Heating with PSC Motor)
4
Specifications are subject to change without notice
440 04 2023 02
*9MPT Parts
25--24- -75a--4
M
TT
9
10
SSHRR
QQ
PP
KK
MM
3
4
5
F
A
B
1
Y
X
UU
VV
2
W
J
U
V
T
K
K
18
7
D
HH
NN
20
S
OO
EE
DD
17
FF
CC
R
8
6
P
16
13
Q
14
GG
16
FF
Representative drawing only, some models may vary in appearance.
15
WW
YY
440 04 2023 02
12
BB
N O
F
F
O
LL
N
Specifications are subject to change without notice
JJ
11
L
ZZ
5
Replacement Parts - *9MPT
Models -- *9MPT050F12C1, *9MPT075F14C1, *9MPT100J16C1 & *9MPT125L20C1 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key
No.
1 Heat Exchanger, Primary 1012850
2 Heat Exchanger, Secondary 1013762
3 Motor, Blower 1/1151/2CCW
4
5 Wheel, Blower 1013011
6 Transformer 1172810 1 1 1 1
7 Capacitor, 10Mfd., 370V
8 Control 1175594 1 1 1 1
9 Switch, Interlock 1171981 1 1 1 1
10 Switch, Pressure 1013166
11 Blower, Exhaust 1172825
12 Valve, Gas Nat. 2 Stage 1172822 1 1 1 1
13 Flame Sensor 1172827 1 1 1 1
14 Igniter 1172533 1 1 1 1
15 Orifice, Burner #42 Nat. 1011351 2 3 4 5
16 Switch, Limit (Rollout) 1013102 2 2 2 2
17 Burner Assembly 1172884
18 Switch, Limit (Main) 1320366
20 Filter,HH 16X25X1/2” 1010365 1 1 2 2
*See Table below for bellyband location on motor
Bellyband Location
Model *9MPT A(in.)
050F12 2.09
075F14 1.81
100J16 1.81
125L20 1.65
Description
Functional
Mount, Motor kit*
40Mfd., 370V
on Motor
1/115
3
/4CCW
Part
Number
1012854 1012858 1012862
1013763 1013765 1013767
1172488 11724891--
1014824 10148231--
10114201--
1171929 11719821--
1013515--1--1
11728261--
1172965 1172966 1172967
34335002
1008445
34335001
050 F12
*9MPT
075
100
F14
J16
1
--
--
--
--
1
--
--
--
1
--
--
--
1
--
--
--
A
--
1
--
--
1
--
--
--
--
1
--
--
1
--
--
1
1
--
--
--
--
1
1
--
--
1
1
1
1
--
--
-­1
1
1
--
--
--
--
1
--
-- --
1
-- --
--
--
--
--
1
--
--
1
--
125 L20
Key
No.
--
--
-­1
--
--
-­1
-­1
-­1
-­1
-­1
1
--
-­1
--
--
-­1
--
-­1
--
A Panel, Top 1012866
B Gasket, Top Panel 1012603
F Partition, Blower 1172008
H Housing, Blower 1172885
J Panel, Blower Cutoff 721020013
K Hanger, Blower 1012328 2 2 2 2
L Door, Blower (Comfortmaker only)
M Bracket Asy., Door Filler 1172232
N Door, Front (Comfortmaker only)
O Clamp, Capacitor 1170643
P Transition Assembly 1172228
Q Gasket, Blower 1014425 1 1 1 1 R Board, Insulating 1012418
S Box, Collector 1012244
T Gasket, Transition 1013263
U Gasket, Collector Box 1012594
V Partition, Front Heat Exchanger 1012650
Description
Non- Functional
(Comfortmaker only) (Comfortmaker only) (Heil only) (Heil only) (Heil only) (Tempstar only) (Tempstar only) (Tempstar only)
(Comfortmaker only) (Comfortmaker only) (Heil only) (Heil only) (Heil only) (Tempstar only) (Tempstar only) (Tempstar only)
Part
Number
1012867 1012868
1012604 1012605
1172005 1172006 1172007
11729691----1--1--1
7210200081----1--1--1
1173035 1173036 1173073 1173038 1173039 1173076 1173078 1173079 1173080
1172233 1172234
1013148 1013149 1013150 1013145 1013146 1013147 1173086 1173087 1173088
10143151--1--1----1
1172229 1172230
1012419 1012420
1012245 1012246
1013080 1013083 1013084
1012595 1012596
1012648 1012651 1012653
050 F12
*9MPT
075 F14
1
1
--
--
--
--
1
1
--
--
--
--
1
--
--
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
1
--
--
--
--
1
--
--
1
--
--
--
--
1
1
--
--
--
--
1
--
--
1
--
--
--
--
100 J16
125 L20
--
--
1
--
--
1
--
--
1
--
--
1
--
--
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
--
--
1
--
--
1
--
--
1
--
--
1
--
--
--
--
1
--
--
1
6
Specifications are subject to change without notice
440 04 2023 02
Replacement Parts - *9MPT
Models -- *9MPT050F12C1, *9MPT075F14C1, *9MPT100J16C1 & *9MPT125L20C1 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key No.
W Gasket, Attachment Plate 1012542
X Cover, Junction Box 1012350 1 1 1 1 Y Box, Junction 1172860 1 1 1 1
BB Manifold 1012970
CC Bottom, Burner Box 1172847
DD Baffle, Burner Box 1012338
EE Top, Burner Box 1013702
FF Bracket, Manifold Support 1012377 2 2 2 2 GG Bracket, Burner Box Side 1012532 2 2 2 2 HH Bracket, Control Mounting 1172845 1 1 1 1
JJ Tube, Sensor 1172238
KK Trap, Drain Assembly 1171917 1 1 1 1
LL Sightglass
MM Wrapper, Filter Rack 741010039 1 1 2 2
NN Front, Filter Rack 741020001 1 1 2 2 OO Cover, Filter 2791043 1 1 2 2 PP Clip, Filter 1008482 3 3 3 3 QQ Gasket, Trap 1013701 1 1 1 1 RR Bracket, Trap 1171986 1 1 1 1 SS Gasket, Trap Bracket 1171987 1 1 1 1
TT Tube, Drain Coll. Box5/8″ ID 1172245 1 1 1 1 UU Tube, Drain Tee1/2″ ID 1171989 1 1 1 1 VV Tube, Relief 1172012 1 1 1 1
WW Drain Vent 1014003 1 1 1 1
ZZ Sightglass 1 172768 1 1 1 1 YY Tee, Drain 1171915 1 1 1 1
)( PART NOT ILLUSTRATED
)( Door Screws 1014488 4 4 4 4 )( Door Screw Grommets 1171990 4 4 4 4 )( Coupling, Air Intake 1002284 1 1 1 1 )( Gasket, Air Intake 1012583 1 1 1 1 )( Clamp, Hose5/8” 1012975 4 4 4 4 )( Clamp, Hose3/4” 1012976 2 2 2 2 )( Coupling, Discharge 1002522 1 1 1 1 )( Clamp Hose 1013830 4 4 4 4 )( Grommet, Vent 1012697 1 1 1 1
)( Bushing, Strain Relief 1945287 1 1 1 1
)( Grommet, Vinyl (Gas Inlet) 1009535 1 1 1 1
)( Harness, Wire 1172818 1 1 1 1 )( Grommet,Casing 1171997 1 1 1 1
Description
Functional
(Tempstar only)
Part
Number
1012543 1012544 1012545
1012971 1012278 1012279
1172849 1172850
1012339 1012340
1013703 1013704
117224111111111
1013235 101323611111111
050
F12
*9MPT
075
100
F14
J16
2
--
--
--
--
1
--
--
-­1
--
--
1
--
--
1
--
--
--
2
--
--
2
--
--
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
125 L20
Key
No.
--
--
-­2
--
--
-­1
--
-­1
--
-­1
--
-­1
)( Trap, Drain Tee 1171916 1 1 1 1 )( Tube, Drain1/2”IDDrain 1171991 1 1 1 1 )( Tube,1/2” Elbow 1171992 2 2 2 2 )( Coupling,1/2” Barbed 1171993 1 1 1 1 )( Tubing,5/8”IDDrain 1171994 1 1 1 1 )( Connector,3/4”X1/2” 1171995 1 1 1 1 )( Elbow,1/2” CPVC street 1171996 1 1 1 1 )( Tube, Relief Ext. 1172239 1 1 1 1 )( Connector, Relief Tube 1171998 1 1 1 1 )( Plate, Cover 1171999 1 1 1 1 )( Gasket, Cover Plate 1172000 1 1 1 1 )( Cap, Drain Tee 1172255 1 1 1 1 )( Clamp, Tee Cap 1172256 1 1 1 1
)( Manual, Users 44102201103 1 1 1 1 )( Manual, Installation 44001202302 1 1 1 1 )( Manual, Technical 44004202302 1 1 1 1
Gas Conversion Kits -- All models
Nat to Propane NAHA002LP (1172959*) Propane to Nat NAHA002NG (1172961*)
* Must be ordered from Service Parts
Description
Functional
Number
Part
050 F12
*9MPT
075 F14
100 J16
125 L20
440 04 2023 02
Specifications are subject to change without notice
7
TECHNICAL SUPPORT
Manufacturers Number (Mfr No --SeeRatingPlate) ALL Models
Specifications
*9MPV050F12 *9MPV075F12 *9MPV100J20 *9MPV125L20
General
Gas Type
Transformer Size (VA) T’stat Heat Anticipator
Input (Btuh) Std/Alt. HI Heat
LO Heat
Output (Btuh) Std/Alt. HI Heat
Tem p. Rise (
oF/o
LO Heat
C) HI Heat
LO Heat
Electrical (V olts/Hz) 115/60 115/60 115/60 115/60
Rating Plate Amps 9.5 11. 4 14.6 15.4
Gas & Ignition
Gas Type Std. Main Orifices (No/Size)
Gas Valve Honeywell Regulation Type Manifold Press. HI Heat (in wc)
LO Heat (in wc)
Ignition Type
Combustion
Flue Outlet Size (Inches) Std. Outlet Temp (less than) Comb. Blower (MFD/Volts)
@Blower/ @ Transition Box (HI Heat)
Std. Pressures (in wc) 5No Elbows 40+5--90° DWV Elbows
@Blower/ @ Transition Box (LO Heat)
Std. Pressures (in wc) 5No Elbows 40+5--90° DWV Elbows
Limits & Controls
Rollout Switch ( Limit Control Setting (
oF/o
C)
oF/o
C)
Furnace Control (Type) Furnace Control On (Timed--secs) Off
Std. Pressure Sw. (Part No)
(HI Heat)Blwer Switch Press (Close) Blower Switch Pressure (Open) (LO Heat)Trans Switch Press (Close) Transition Switch Pressure (Open)
High Altitude Pressure Sw. (Part No)
(HI Heat)Blwer Switch Press (Close) Blower Switch Pressure (Open) (LO Heat)Trans Switch Press (Close) Transition Switch Pressure (Open)
Blower Data
Wheel Size (D x W inches) FLA Motor Amps/Max RPM Motor Type/H.P. Filter Type & Size (qty.) Permanent -- supplied Min. Cool Cap. (Tons) Max. Cool Cap. (Tons)
Gas Conversion Kits All Models
Nat to Propane NAHA002LP (1172959*) Propane to Nat NAHA002NG (1172961*)
*Order from Service Parts
Nat Propane Nat Propane Nat Propane Nat Propane
40
.50
35--65/19--46 35--65/19--46
Nat. 2/42
VR8205Q
SNAP
3.5
1.7
50,000 35,000 46,000 32,000
Propane
2/54
VR8205Q
SNAP
10.0
4.9
40--70/22--38 40--70/22--38
Nat. 3/42
VR8205Q
SNAP
3.5
1.7
75,000 52,500 70,000 48,000
Propane
3/54
VR8205Q
SNAP
10.0
4.9
40--70/22--38 40--70/22--38
Nat. 4/42
VR8205Q
SNAP
3.5
1.7
100,000
70,000 93,000 65,000
Propane
4/54
VR8205Q
SNAP
10.0
4.9
125,000
87,500
118,000
82,000 40--70/22--38 40--70/22--38
Nat. 5/42
VR8205Q
SNAP
3.5
1.7
Hot Surface
2
o
140
F/60oC
4/370
--1.80 / --2.60
--1.30 / --2.30
--1.20 / --1.90
--1.00 / --1.80
300/149 260/127
2
o
140
F/60oC
4/370
--1.80 / --2.60
--1.30 / --2.30
--1.20 / --1.90
--1.00 / --1.80
300/149
210/99
3
o
140
F/60oC
4/370
--1.80 / --2.60
--1.70 / --2.50
--1.20 / --1.90
--1.00 / --1.80
300/149 240/116
3
o
140
F/60oC
4/370
--1.80 / --2.60
--1.70 / --2.50
--1.30 / --2.30
--1.20 / --2.20
300/149
190/88
Integrated
30 HI /45 LO
60,100,140,180
1013515
0.95
0.80
1.70
1.50
1013165
0.70
0.55
1.40
1.20
11 x 8
7.7/1240
1
ECM/ 16x25x1
1.5 3
/
2
1013515
0.95
0.80
1.70
1.50
1013165
0.70
0.55
1.40
1.20
11 x 10
9.6/1240
3
ECM/
16x25x1
1.5 3
1013515
0.95
0.80
1.70
1.50
1013165
0.70
0.55
1.40
1.20
11 x 10
12.8/1240
/
4
ECM/1
16x25x1 (2)
2 5
1013166
1.30
1.10
1.80
1.60
1013157
0.85
0.70
1.70
1.50
11 x 10
12.8/1240 ECM/1
16x25x1 (2)
2 5
Propane
5/54
VR8205Q
SNAP
10.0
4.9
8
Specifications are subject to change without notice
440 04 2023 02
Circulation Air Blower Data - *9MPV050
Cooling CFM Adjustment Heating Rise Adjustment
Low Heat
Rise Change
at Resultant
Static
delay
DIP Switch
5&6
High Cool @
0.50 in wc
Low Cool
(80% of High
Cool)
** Adjust
Jumper
Setting
DIP Switch
3&4
High Heat
Rise Change
@0.20inwc
00 1246 997 + 00 -- 4 -- 3
*00 1211 969 *NOM *00 0 0
00 1122 898 -- 00 5 5 01 1105 884 + 01 3 4 01 1027 822 NOM 01 7 7 01 945 756 -- 01 13 14 10 892 714 + 10 -- 1 0 10 820 656 NOM 10 4 5 10 745 596 -- 10 9 9 11 688 550 + 11 -- 1 5 -- 1 5 11 609 487 NOM 11 -- 1 3 -- 1 2 11 541 433 -- 11 -- 9 -- 9
Airflow performance includes 1” washable filter media. *Factory Setting **Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable. Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls. Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise). Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings.
Table 2
Continuous Fan @
0.10 in wc ESP
DIP Switch 1 & 2 Airflow (CFM)
*00 592
01 1021
10 1346
Table 3 SW2 DIP Assignments
DIP Switch Blower Parameter
1&2 Cont Fan Adj 3&4 Heat Speed Adj 5&6 Cool Speed Adj 7&8 Cool On/Off Delay
11 1346
* Factory Setting
Table 4
ON DELAY OFF DELAY
DIP SW2 -- 7/8 Timed ON (sec)
Cooling Delay Options (SW2 -- 7, 8)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
*00 5 OFF 90 100%
01 5 OFF 0 OFF 10 30 50% 30 100%
11 30 50% 180 50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1 Airflow resumes to 100% after on delay time is completed Airflow stops (or switches to continuous fan speed) after off delay time is completed * Factory Setting
Note 1: Disposable filters are typically rated at 300 FPM. These filters only allow half the airflow when compared to 600 FPM filters. (example, 20 x 25 @ 600 FPM = 2000CFM, @ 300 FPM = 1000 CFM)
440 04 2023 02
MAX CFM’s for Factory Washable Filters
Dimensions Airflow (CFM)
14” x 25” 1400 16” x 25” 1600 20” x 25” 2000 24” x 25” 2500
MAX CFM based on 600 FPM
Specifications are subject to change without notice
9
1600
1400
1200
1000
CFM
Circulation Air Blower Data - *9MPV050
Cooling Airflow Settings
High Cooling Airflows
*9MPV050F12
800
600
400
Legend
Airflow
Selection is
from Highest to
Lowest
00 (+) 00 (NOM) 00 (-) 01 (+) 01 (NOM) 01 (-) 10 (+) 10 (NOM) 10 (-) 11 (+) 11 (NOM) 11 (-)
200
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
ESP (in. w.c.)
Low Cooling Airflows
*9MPV050F12
1200
1000
800
600
CFM
400
200
Legend
Airflow
Selection is
from Highest to
Lowest
00 (+) 00 (NOM) 00 (-) 01 (+) 01 (NOM) 01 (-) 10 (+) 10 (NOM) 10 (-) 11 (+) 11 (NOM) 11 (-)
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
10
ESP (in. w.c.)
Specifications are subject to change without notice
440 04 2023 02
Circulation Air Blower Data - *9MPV075
Cooling CFM Adjustment Heating Rise Adjustment
Low Heat
Rise Change
at Resultant
Static
delay
DIP Switch
5&6
High Cool @
0.50 in wc
Low Cool
(80% of High
Cool)
** Adjust
Jumper
Setting
DIP Switch
3&4
High Heat
Rise Change
@0.20inwc
00 1342 1074 + 00 -- 4 -- 4
*00 1210 968 *NOM *00 0 0
00 1053 842 -- 00 5 4 01 1135 908 + 01 1 1 01 1020 816 NOM 01 6 5
01 872 698 -- 01 12 10 10 965 772 + 10 -- 1 -- 1 10 840 672 NOM 10 3 3 10 680 544 -- 10 9 8 11 708 566 + 11 -- 6 -- 6 11 590 472 NOM 11 -- 2 -- 3 11 488 390 -- 11 3 2
Airflow performance includes 1” washable filter media. *Factory Setting **Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable. Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls. Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise). Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings.
Table 2
Continuous Fan @
0.10 in wc ESP
DIP Switch 1 & 2 Airflow (CFM)
*00 612
01 1096
10 1403
Table 3 SW2 DIP Assignments
DIP Switch Blower Parameter
1&2 Cont Fan Adj 3&4 Heat Speed Adj 5&6 Cool Speed Adj 7&8 Cool On/Off Delay
11 1403
* Factory Setting
Table 4
ON DELAY OFF DELAY
DIP SW2 -- 7/8 Timed ON (sec)
Cooling Delay Options (SW2 -- 7, 8)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
*00 5 OFF 90 100%
01 5 OFF 0 OFF 10 30 50% 30 100%
11 30 50% 180 50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1 Airflow resumes to 100% after on delay time is completed Airflow stops (or switches to continuous fan speed) after off delay time is completed * Factory Setting
Note 1: Disposable filters are typically rated at 300 FPM. These filters only allow half the airflow when compared to 600 FPM filters. (example, 20 x 25 @ 600 FPM = 2000CFM, @ 300 FPM = 1000 CFM)
440 04 2023 02
MAX CFM’s for Factory Washable Filters
Dimensions Airflow (CFM)
14” x 25” 1400 16” x 25” 1600 20” x 25” 2000 24” x 25” 2500
MAX CFM based on 600 FPM
Specifications are subject to change without notice
11
1800
1600
1400
1200
1000
CFM
Circulation Air Blower Data - *9MPV075
Cooling Airflow Settings
High Cooling Airflows
*9MPV075F12
800
600
400
Legend
Airflow
Selection is
from Highest to
Lowest
00 (+) 00 (NOM) 01 (+) 00 (-) 01 (NOM) 10 (+) 01 (-) 10 (NOM) 11 (+) 10 (-) 11 (NOM) 11 (-)
200
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
ESP (in. w.c.)
Low Cooling Airflows
*9MPV075F12
1400
1200
1000
800
CFM
600
400
200
Legend
Airflow
Selection is
from Highest to
Lowest
00 (+) 00 (NOM) 01 (+) 00 (-) 01 (NOM) 10 (+) 01 (-) 10 (NOM) 11 (+) 10 (-) 11 (NOM) 11 (-)
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
12
ESP (in. w.c.)
Specifications are subject to change without notice
440 04 2023 02
Circulation Air Blower Data - *9MPV100
Cooling CFM Adjustment Heating Rise Adjustment
Low Heat
Rise Change
at Resultant
Static
delay
DIP Switch
5&6
High Cool @
0.50 in wc
Low Cool
(80% of High
Cool)
** Adjust
Jumper
Setting
DIP Switch
3&4
High Heat
Rise Change
@0.20inwc
00 2144 1715 + 00 -- 4 -- 4
*00 2013 1610 *NOM *00 0 0
00 1842 1474 -- 00 5 5 01 1772 1418 + 01 2 1 01 1624 1299 NOM 01 8 7 01 1471 1177 -- 01 14 14 10 1367 1094 + 10 0 -- 1 10 1227 982 NOM 10 6 5 10 1077 862 -- 10 13 11 11 930 744 + 11 -- 6 -- 7 11 808 646 NOM 11 -- 2 -- 2 11 634 507 -- 11 3 3
Airflow performance includes 1” washable filter media. *Factory Setting **Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable. Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls. Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise). Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings.
Table 2
Continuous Fan @
0.10 in wc ESP
DIP Switch 1 & 2 Airflow (CFM)
*00 1007
01 1742
10 2204
Table 3 SW2 DIP Assignments
DIP Switch Blower Parameter
1&2 Cont Fan Adj 3&4 Heat Speed Adj 5&6 Cool Speed Adj 7&8 Cool On/Off Delay
11 2204
* Factory Setting
Table 4
ON DELAY OFF DELAY
DIP SW2 -- 7/8 Timed ON (sec)
Cooling Delay Options (SW2 -- 7, 8)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
*00 5 OFF 90 100%
01 5 OFF 0 OFF 10 30 50% 30 100%
11 30 50% 180 50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1 Airflow resumes to 100% after on delay time is completed Airflow stops (or switches to continuous fan speed) after off delay time is completed * Factory Setting
Note 1: Disposable filters are typically rated at 300 FPM. These filters only allow half the airflow when compared to 600 FPM filters. (example, 20 x 25 @ 600 FPM = 2000CFM, @ 300 FPM = 1000 CFM)
440 04 2023 02
MAX CFM’s for Factory Washable Filters
Dimensions Airflow (CFM)
14” x 25” 1400 16” x 25” 1600 20” x 25” 2000 24” x 25” 2500
MAX CFM based on 600 FPM
Specifications are subject to change without notice
13
2700
A
2200
1700
CFM
1200
Circulation Air Blower Data - *9MPV100
Cooling Airflow Settings
High Cooling Airflows
*9MPV100J20
Legend
Airflow
Selection is
from Highest to
Lowest
00 (+) 00 (NOM) 00 (-) 01 (+) 01 (NOM) 01 (-) 10 (+) 10 (NOM) 10 (-) 11 (+) 11 (NOM) 11 (-)
700
200
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
ESP (in. w.c.)
Low Cooling Airflows
*9MPV100J20
2000
1800
1600
1400
1200
1000
CFM
800
600
400
Legend
irflow Selection
is from Highest
to Lowest
00 (+) 00 (NOM) 00 (-) 01 (+) 01 (NOM) 01 (-) 10 (+) 10 (NOM) 10 (-) 11 (+) 11 (NOM) 11 (-)
200
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
14
ESP (in. w.c.)
Specifications are subject to change without notice
440 04 2023 02
Circulation Air Blower Data - *9MPV125
Cooling CFM Adjustment Heating Rise Adjustment
Low Heat
Rise Change
at Resultant
Static
delay
DIP Switch
5&6
High Cool @
0.50 in wc
Low Cool
(80% of High
Cool)
** Adjust
Jumper
Setting
DIP Switch
3&4
High Heat
Rise Change
@0.20inwc
00 2150 1720 + 00 -- 4 -- 4
*00 2025 1620 *NOM *00 0 0
00 1856 1485 -- 00 4 5 01 1755 1404 + 01 1 2 01 1615 1292 NOM 01 6 7 01 1452 1162 -- 01 12 13 10 1338 1070 + 10 -- 1 0 10 1201 961 NOM 10 3 4 10 1069 855 -- 10 9 10 11 909 727 + 11 -- 6 -- 6 11 800 640 NOM 11 -- 3 -- 3 11 627 502 -- 11 3 3
Airflow performance includes 1” washable filter media. *Factory Setting **Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable. Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls. Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise). Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings.
Table 2
Continuous Fan @
0.10 in wc ESP
DIP Switch 1 & 2 Airflow (CFM)
*00 1032
01 1778
10 2178
Table 3 SW2 DIP Assignments
DIP Switch Blower Parameter
1&2 Cont Fan Adj 3&4 Heat Speed Adj 5&6 Cool Speed Adj 7&8 Cool On/Off Delay
11 2178
* Factory Setting
Table 4
ON DELAY OFF DELAY
DIP SW2 -- 7/8 Timed ON (sec)
Cooling Delay Options (SW2 -- 7, 8)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
*00 5 OFF 90 100%
01 5 OFF 0 OFF 10 30 50% 30 100%
11 30 50% 180 50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1 Airflow resumes to 100% after on delay time is completed Airflow stops (or switches to continuous fan speed) after off delay time is completed * Factory Setting
Note 1: Disposable filters are typically rated at 300 FPM. These filters only allow half the airflow when compared to 600 FPM filters. (example, 20 x 25 @ 600 FPM = 2000CFM, @ 300 FPM = 1000 CFM)
440 04 2023 02
MAX CFM’s for Factory Washable Filters
Dimensions Airflow (CFM)
14” x 25” 1400 16” x 25” 1600 20” x 25” 2000 24” x 25” 2500
MAX CFM based on 600 FPM
Specifications are subject to change without notice
15
2700
2200
1700
CFM
1200
Circulation Air Blower Data - *9MPV125
Cooling Airflow Settings
High Cooling Airflows
*9MPV125L20
Legend
Airflow
Selection is
from Highest to
Lowest
00 (+) 00 (NOM) 00 (-) 01 (+) 01 (NOM) 01 (-) 10 (+) 10 (NOM) 10 (-) 11 (+) 11 (NOM) 11 (-)
700
CFM
200
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
ESP (in. w.c.)
Low Cooling Airflows
*9MPV125L20
2000
1800
1600
1400
1200
1000
800
600
400
Legend
Airflow
Selection is
from Highest to
Lowest
00 (+) 00 (NOM) 00 (-) 01 (+) 01 (NOM) 01 (-) 10 (+) 10 (NOM) 10 (-) 11 (+) 11 (NOM) 11 (-)
200
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
16
ESP (in. w.c.)
Specifications are subject to change without notice
440 04 2023 02
Variable Speed (MPV) Tap Select Interface Board (TSIB)
TO FURNACE BOARD
P3
BLU WHT
GRN BLK
BRN YEL
TO FURNACE CONTROL24VAC
RED
FROM 24V
TRANS RED
J1
+NOM--
BLOWER ADJUST
HP MODE
SW2
1234 6578
ON
OFF
CONT
FAN
COOL
COOL
HEAT
DLY
SW2
1234 6578
CONT
FAN
HEAT
COOL
COOL
DLY
J2
AC/HP EFFICIENCY
HP COMFORT
SELECT
SELECTION
O
Y1
J1
+NOM --
P7
BLOWER ADJUST
INCREASE/NO CHANGE/DECREASE
J2
AC/HP EFFICIENCY
HP COMFORT
HP MODE
SELECT
HEAT PUMP EFFICIENCY OR HP COMFORT SELECTION
CONTINUOUS
CFM SELECT
HEATING RISE
SELECT
COOLING CFM
SELECT
COOLING ON/OFF DELAY PROFILES
25--25--54
440 04 2023 02
Specifications are subject to change without notice
17
Wiring Diagram *9MPV (Variable Speed Blower Motor)
18
Specifications are subject to change without notice
440 04 2023 02
*9MPV Parts
25--25--32b
MM
PP
M
F
B
A
1
V
EE
DD
17
Y
X
UU
VV
W
18
FF
CC
10
9
KK
5
QQ
SSHRR
TT
2
J
U
T
K
K
S
22
R
21
3
4
NN
HH
20
OO
23
8
6
P
16
Representative drawing only, some models may vary in appearance.
FF
YY
GG
16
15
WW
440 04 2023 02
13
14
12
BB
LL
N
Specifications are subject to change without notice
Q
JJ
11
L
ZZ
19
Replacement Parts - *9MPV
Models -- *9MPV050F12D1, *9MPV075F12D1, *9MPV100J20D1 & *9MPV125L20D1 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
A
075 F12
-­1
--
--
-­1
--
--
-­1
-­1
-­1
1
--
-­1
--
--
-­1
--
--
-­1
--
--
*9MPV
100 J20
--
-­1
--
--
-­1
--
-­1
-­1
-­1
1
--
--
-­1
--
--
-­1
--
--
-­1
--
Key No.
1 Heat Exchanger, Primary 1012850
2 Ht Exchanger, Secondary 1013762
3 Motor, Blower 1172828
4
5 Wheel, Blower 1013011
6 Transformer 1172810 1 1 1 1
8 Control 1175594 1 1 1 1
9 Switch, Interlock 1171981 1 1 1 1
10 Switch, Pressure 1013166
11 Blower, Exhaust 1172825
12 Valve, Gas Nat. 2 Stg 1172822 1 1 1 1
13 Flame Sensor 1172827 1 1 1 1
14 Igniter 1172533 1 1 1 1
15 Orifice, Burner #42 Nat. 1011351 2 3 4 5
16 Switch, Limit (Rollout) 1013102 2 2 2 2
17 Burner Assembly 1172884
18 Switch, Limit (Main) 1320366
20 Filter,HH 16X25X1/2” 1010365 1 1 2 2
22 Board, Tap Select Interface 1174894 1 1 1 1
21 Control, Motor Variable Spd 1174887
23 Choke, Power 1172838 -- -- 1 1
*See Table below for bellyband location on motor
Model *9MPV A(in.)
050F12 13/8″
075F12 27/8″
100J20 27/8″
125L20 27/8″
Description
Functional
Mount, Motor kit*
Bellyband Location
on Motor
Part
Number
1012854 1012858 1012862
1013763 1013765 1013767
11728291--
1014822 1 1 1 1
11721291--
1013515--1
11728261--
1172965 1172966 1172967
34335001
1320367 1008445
1174888 1174889 1174895
050
F12
1
--
--
--
1
--
--
--
1
--
--
--
1
--
--
--
1
--
--
--
125 L20
Key No.
--
--
--
1
--
--
-­1
-­1
-­1
1
--
-­1
--
--
-­1
--
--
-­1
--
--
-­1
A Panel, Top 1012866
B Gasket, Top Panel 1012603
F Partition, Blower 1172008
H Housing, Blower 1172885
J Panel, Blower Cutoff 721020013
K Hanger, Blower 1012328 2 2 2 2
L Door, Blwer (Cmaker only)
M Bracket Asy., Door Filler 1172232
N Door, Front (Cmaker only)
P Transition Assembly 1012228
Q Gasket, Exhaust Blower 1014425 1 1 1 1
R Board, Insulating 1012418
S Box, Collector 1012244
T Gasket, Transition 1013263
U Gasket, Collector Box 1012594
Description
(Cmaker only) (Cmaker only) (Heil only) (Heil only) (Heil only) (Tstar only) (Tstar only) (Tstar only)
(Cmaker only) Cmaker only) (Heil only) (Heil only) (Heil only) (Tstar only) (Tstar only) (Tstar only)
Part
Number
1012867 1012868
1012604 1012605
1172005 1172006 1172007
11729691--
7210200081--
1175025 1175026 1175042 1175028 1175029 1175043 1175031 1175032 1175044
1172233 1172234
1013148 1013149 1013150 1013145 1013146 1013147 1173086 1173087 1173088
1012229 1012230
1012419 1012420
1012245 1012246
1013080 1013083 1013084
1012595 1012596
050 F12
1
--
--
1
--
--
1
--
--
--
1
--
-­1
--
-­1
--
--
1
--
--
1
--
-­1
--
-­1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
--
1
--
--
*9MPV
075 F12
1
--
--
1
--
--
-­1
--
--
-­1
-­1
1
--
-­1
--
-­1
--
--
1
--
--
1
--
-­1
--
-­1
--
--
1
--
--
1
--
--
1
--
--
-­1
--
--
1
--
--
100 J20
125 L20
--
--
1
--
--
1
--
--
1
--
--
1
--
--
--
--
1
--
--
1
--
--
1
1
--
--
1
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
1
--
--
--
--
1
--
--
1
--
--
1
--
--
1
20
Specifications are subject to change without notice
440 04 2023 02
Replacement Parts - *9MPV
Models -- *9MPV050F12D1, *9MPV075F12D1, *9MPV100J20D1 & *9MPV125L20D1 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
*9MPV
075
F12
Key
No.
V Partition, Front Ht Exchger 1012650
W Gasket, Attachment Plate 1012542
X Cover, Junction Box 1012350 1 1 1 1
Y Box, Junction 1172860 1 1 1 1
BB Manifold 1012970
CC Bottom, Burner Box 1172847
DD Baffle, Burner Box 1012338
EE Top, Burner Box 1013702
FF Bracket, Manifold Support 1012377 2 2 2 2
GG Bracket, Burner Box Side 1012532 2 2 2 2
HH Bracket, Control Mounting 1172845 1 1 1 1
JJ Tube, Sensor 1172238
KK Trap, Drain Assembly 1171917 1 1 1 1
LL Sightglass
MM Wrapper, Filter Rack 741010039 1 1 2 2
NN Front, Filter Rack 741020001 1 1 2 2
OO Cover, Filter 2791043 1 1 2 2
PP Clip, Filter 1008482 3 3 3 3
QQ Gasket, Trap 1013701 1 1 1 1
RR Bracket, Trap 1171986 1 1 1 1
SS Gasket, Trap Bracket 1171987 1 1 1 1
TT Tube, Drain Coll. Box5/8″ ID 1172245 1 1 1 1
UU Tube, Drain Tee1/2″ ID 1171989 1 1 1 1
VV Tube, Relief 1172012 1 1 1 1
WW Drain Vent 1014003 1 1 1 1
YY Tee, Drain 1171915 1 1 1 1
ZZ Sightglass 1172768 1 1 1 1
Description
(Tstar only)
Part
Number
1012648 1012651 1012653
1012543 1012544 1012545
1012971 1012278 1012279
1172848 1172849 1172850
1012339 1012340
1013703 1013704
117224111
1013235 101323611
050 F12
1
--
--
--
2
--
--
--
1
--
--
--
1
--
--
--
1
--
--
1
--
--
075 F12
-­1
--
--
-­2
--
--
-­1
--
--
-­1
--
--
1
--
--
1
--
--
1 1
1 1
*9MPV
100 J20
--
-­1
--
--
-­2
--
--
-­1
--
--
-­1
--
-­1
--
-­1
--
1 1
1 1
Key
125
No.
L20
)( PART NOT ILLUSTRATED
-­)( Door Screws 1014488 4 4 4 4
--
--
)( Door Screw Grommets 1171990 4 4 4 4
1
)( Coupling, Air Intake 1002284 1 1 1 1
--
)( Gasket, Air Intake 1012583 1 1 1 1
-­)( Clamp, Hose5/8” 1012975 4 4 4 4
-­)( Clamp, Hose3/4” 1012976 2 2 2 2
2
)( Coupling, Discharge 1002522 1 1 1 1 )( Clamp Hose 1013830 2 2 2 2 )( Grommet, Vent 1012697 1 1 1 1
-­)( Bushing, Strain Relief 1945287 1 1 1 1
--
--
)( Grommet, Vinyl (Gas Inlet) 1009535 1 1 1 1
1
)( Harness, Wire 1172818 1 1 1 1
--
)( Harness, Wire Blower V.S. 1174758 1 1 1 1
-­)( Trap, Drain Tee 1171916 1 1 1 1
-­)( Tube, Drain1/2”IDDrain 1171991 1 1 1 1
1
)( Tube,1/2” Elbow 1171992 2 2 2 2
-­)( Coupling,1/2” Barbed 1171993 1 1 1 1
--
1
)( Tubing,5/8”IDDrain 1171994 1 1 1 1
--
)( Connector,3/4”X1/2” 1171995 1 1 1 1
-­)( Elbow,1/2” CPVC street 1171996 1 1 1 1
1
)( Grommet, Casing 1171997 1 1 1 1 )( Tube, Relief Ext. 1172239 1 1 1 1 )( Connector, Relief Tube 1171998 1 1 1 1 )( Plate, Cover 1171999 1 1 1 1 )( Gasket, Cover Plate 1172000 1 1 1 1
1 1
)( Cap, Drain Tee 1 172255 1 1 1 1 )( Clamp, Tee Cap 1172256 1 1 1 1 )( Manual, Users 44102201103 1 1 1 1
1 1
)( Manual, Installation 44001202301 1 1 1 1 )( Manual, Technical 44004202301 1 1 1 1
Gas Conversion Kits -- All models
Nat to Propane NAHA002LP (1172959*) Propane to Nat NAHA002NG (1172961*)
* Must be ordered from Service Parts
Description
Part
Number
050
F12
100 J20
125 L20
440 04 2023 02
Specifications are subject to change without notice
21