ICP FEA4X1805A1, FEA4X1807A1, FEA4X2405A1, FEA4X2407A1, FEA4X2411A1 Installation Guide

...
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate
throughout this manual and other manuals that may apply to the product.
DANGER - Immediate hazards which will result in severe personal injury or death.
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or property damage.
NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Introduction .................................... 2
Check Equipment .............................. 2
Location ....................................... 2
Installation .................................. 2 - 6
Electrical Connections ....................... 6 - 7
Controls - FSA ................................ 7
Motor Speed Selection .......................... 8
Start-up Procedures ............................ 8
Care and Maintenance .......................... 8
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per- sons could result in equipment malfunction, prop- erty damage, personal injury and/or death.
The information contained in this manual is in- tended for use by a qualified service technician fa- miliar with safety procedures and equipped with
the proper tools and test instruments. Installation must conform with local building
codes and with the National Electrical Code NFPA70 current edition.
66401500200 Feb2009
INTRODUCTION
FSA Fan Coils may be used for cooling or heat pump operation, with or without electric heat. Models are available with factory installed electric heaters (5 kW, 7.5
kW, or 11 kw) and with no heat. Installations without electric heat require a Cooling Control Kit (accessory part
number AMWK001CK).
FEA and WAHA Fan Coils may be used for cooling or heat pump operation, with or without electric heat. Models have
factory installed electric heaters (5 kW, 7.5 kW, or 11 kw).
FSA, FEA, and WAHA Fan Coils are designed to be installed in an upflow position, free air return ONLY,
suitable for closet or flush-mount installations. NOTE: Local codes may limit application of systems
without a ducted return to single story dwellings.
CHECK EQUIPMENT
Unpack Fan Coil and move to final location. Remove carton, taking care not to damage Fan Coil. Inspect
equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete.
LOCATION
Select the best position which suits the installation site conditions. The location should provide adequate
structural support, space in the front of the unit for service access, clearance for return air and supply duct connections, space for refrigerant piping connections and
condensate drain line connections. If heaters are being installed, make sure adequate clearance is maintained
from supply duct work. See "Clearances" in Figure 1.
All models have a factory installed and appropriately
sized hard shut-off TXV metering device for use with R-22 (FSA2X) or R410A (FSA4X, FEA4X, WAHA)
refrigerant.
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product
damage. This Fan Coil has a hard shut-off TXV metering de-
vice. A compressor Hard Start Kit is REQUIRED in all applications where the matching outdoor unit
has a single-phase reciprocating compressor.
Locate rating plate on Fan Coil. It contains information needed to properly install Fan Coil. Check rating plate to
be sure Fan Coil matches job specifications.
If the Fan Coil is located in an area of high humidity, nuisance sweating of casing may occur. On these
installations, a wrap of 2" (51mm) fiberglass insulation
with a vapor barrier is recommended. An access panel is provided on the front of the cabinet for
simple access to blower assembly and electrical controls. Minimum clearance of 21" (533mm) in front of access
panel is required for service.
INSTALLATION
Fan coil is designed for free-air return, such as enclosed in a closet with Iouvered door or flush mounted in a wall.
Factory-authorized Iouvered grille kits are available for flush mount applications (accessory part numbers AMWK001WG and AMWK002WG).
In Closet When Fan Coil is installed in a closet with a Iouvered door
in return-air path, the free area of Iouvered opening in the door must be a minimum of 2.25ft 2 (0.2m2) Either align
door opening with Fan Coil inlet or provide a 10" (254mm) clearance between door and Fan Coil.
Flush Mount
If Fan Coil is to be flush mounted in a wall, provide adequate support underneath base of unit. Make sure
Fan Coil is level or top tilting slightly forward to assure proper condensate drainage.
Hanging Cabinet Cabinet may by hung from the wall using accessory
brackets (accessory part number AMWK001MK).
Use 1"x4" or 2"x4" (25x102mm or 51x102mm) wood piece across studs for support at top of cabinet and same
size wood for spacer at bottom of cabinet. Position bottom spacer between cabinet and wall so that it holds
the Fan Coil out from the wall in a vertical position. Refer to Figure 2.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in proper-
ty damage
When hanging cabinet, both wall support and
spacer must be the same thickness or the unit will
not hang correctly and Condensate Water will not drain correctly. Fan Coil must be vertical or top tilted slightly forward (accessory bracket creates slight tilt).
2 66401500200
Figure1 [ ClearancesandDimensions(inches)
// _7/8" HOLE
REFRIGERANT LINES ENTRY LOW VOLTAGE EN _ 8" OLE ' _.. .
TOP VIEW
C" B" _4-3/16" 7/8"_ _11-3/16° _t0-t/t6 °_
2"314" _ ff
D"
rPOWER ENTRY
_t 318" KNOCKOUT
LOWER, CONTROL AND LECTRICAL HEATER
ACCESS PANEL
_1.I2"
KNOCKOUT \.
DRAINS _
3/4" l ......................
5-11/t6"
SIDEVIEW
DIMENSIONAL DATA (in.)
Model Size A B C D
18 153/16 81/4 23/4 381/16
FSA2X 24 153/16 81/4 23/4 381/16 FSA4X 30 153/16 81/4 23/4 381/16
36 183/8 91/4 5 433/16
Model Size A B C D
18 153/16 81/4 23/4 381/16
FEA4X 24 153/16 81/4 23/4 381/16
WAHA 30 183/8 91/4 5 433/16
36 183/8 91/4 5 433/16
.........FILTER MEDIA
_ SECONDARY DRAIN
13116"
PRmARY i 9-7/16......
............ ti-1/16 ....
FRONTV_
11_1/16_ .
BOTTOMVIEW
CLEARANCES (in.)
No Heaters
All Sides 0
From Supply Duct 0
From Front (for Service) 21
CLEARANCES (in.)
With Heaters
All Sides
From First 3 Feet of Supply Duct to Combustibles
From Supply Duct After 3 Feet From Front (for Service)
SD4786-4-1-A SD4350-4-1-3
0
1 0
21
66401500200 3
Loading...
+ 5 hidden pages