ICP N8MPN, N8MPL, H8MPN, T8MPN, C8MPL Installation Instructions Manual

...
N8MPN&N8MPL *8MPN&*8MPL
* Denotes Brands (C, H, T)
See section 5 for Category I definition.
SAFETY REQUIREMENTS
Recognizesafetyinformation. Thisisthesafety--alertsymbol!. Whenyouseethissymbolon thefurnaceand ininstructionmanualsbealert to the potential for personal injury.
Understand thesignalwordsDANGER,WARNING,orCAUTION. Thesewordsareusedwiththesafety--alert symbol. DANGERidentifiesthe mostserioushazards,thosethat will resultinsevere personalinjuryordeath. WARNING signifies ahazardthat couldresultin personalinjuryor death. CAUTION is used toidentify unsafepractices that couldresultinminorpersonalinjuryorproductandproperty damage. Note is usedto highlight suggestions that will result in enhanced installation, reliability, or operation.
Installingandservicingheatingequipment can behazardousdue to gasandelectrical components. Onlytrainedand qualifiedpersonnelshould install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels at­tached to or shipped with the furnace and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) ANSI Z223.1--2002/NFPA 54--2002. InCanada,refertotheNational StandardofCanada Natural GasandPropaneInstallationCode(NSCNGPIC) CSAB149.1--00. Wear safety glasses and work gloves. Have fire extinguisher available during start--up and adjustment procedures and service calls.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceedcertainlocalcodesandordinances,especiallythosethatmaynothavekeptupwithchangingresidential constructionpractic­es. We require these instructions as a minimum for a safe installation.
International Comfort Products, LLC
Lewisburg, TN 37091
INSTALLER: Affix these instructions on or adjacent to the furnace.
CONSUMER: Retain these instructions for future reference.
Ò
1. Safe Installation Requirements 3...............
2. Installation 4..............................
3. Side Venting 8.............................
4. Combustion & Ventilation Air 9................
5. Gas VentInstallation 12.......................
6. Horizontal Venting 14.........................
7. Masonry Chimney Venting 16...................
8. Gas Supply and Piping 19.....................
!
WARNING
exactly could result in serious injury, death, and/or property damage.
Turn Off All Power Before Servicing.
Portions of the textand tables are reprinted from NFPA54 / ANSI Z223.1--2002ã, withpermission of National Fire Protection Association, Quincy, MA 02269 andAmerican Gas Association, Washington, DC20001. This reprinted material isnot the complete and official position of the NFPA or ANSI,on the referenced subject, which is represented only by the standard in its entirety.
Printed in U.S.A. 10/19/2004 441 01 2611 (06)
Table of Contents
9. Electrical Wiring 22.........................
10.Ductwork and Filter (Upflow/Horizontal) 23.......
11.Ductwork and Filter (Downflow) 25.............
12. Checks and Adjustments 29...................
13. Furnace Maintenance 33.....................
14. Sequence of Operation & Diagnostics 34.........
TechSupport and Parts 37.......................
!
CARBON MONOXIDE POISONING AND FIRE HAZARD.
Failuretofollowsafetywarnings exactly could result in serious injury,death, and/or property damage.
This furnace is not designed for use in mobile homes, trailers or recreational vehicles.
WARNING
WARNING
Ò
START--UP CHECK SHEET
(Keep this page for future reference)
Recommended, but not required. Checklist DOES NOT apply in Canada
Dealer Name: Address: Business Card Here City, State(Province), Zip or Postal Code:
Phone: Owner Name:
Address: City, State(Province), Zip or Postal Code:
Model Number: Serial Number:
Type of Gas: Natural: LP:
Blower Motor H.P.: Supply Voltage: Limit Opens at...(°F) or(°C) Limit Closes at...(°F) or(°C) Which blower speed tap is used?
(Heating)
(Cooling)
Manual Gas Shut--Off Upstream of Furnace/Drip--Leg? YES
Drip--Leg Upstream of Gas Valve? YES NO
Blower Speed Checked? YES NO
All Electrical Connections Tight? YES NO
Gas Valve OK? YES NO
Measured Line Pressure When Firing Unit:
Calculated Firing Rate:(See Checks and Adjustments Section).
Measured Manifold Pressure:
Thermostat OK? YES NO
NO
Temperature of Supply Air: (°F) or(°C) Temperature of Return Air: (°F) or(°C) Rise (Supply Temp.--Return Temp.): (°F) or(°C) Filter Type and Size: Fan “Time ON” Setting: Fan “Time OFF” Setting:
Dealer Comments:
2
Subbase Level? YES NO
Anticipator Set? YES NO Set At?:
Breaker On? YES NO
Date of Installation:
Date of Start--Up:
441 01 2611 06
1. Safe Installation Requirements
!
WARNING
FIRE, EXPLOSION, AND ASPHIXIATION HAZARD Improper adjustment, alteration, service,
maintance or installation could cause serious injury, death and/or property damage.
Installationorrepairsmadeby unqualified persons could result in hazards to you and others. Installation MUST conform with local codes or, in the absence of local codes, with codes of all governmental authorities having jurisdiction.
The information contained in t his manual is intended for use by a qualified service agency that is experienced in such work, is familiar with all precautions and safety procedures required in such work, and is equipped with the proper tools and test instruments.
NOTE: This furnace is design--certified by the CSA International
(formerly AGA and CGA) for installation in the United States and Canada. Refer to the appropriate codes, along with this manual, for proper installation.
· Use only the Type of gas approved for this furnace (see
RatingPlateon unit).Overfiringwill resultinfailure ofheat exchanger and cause dangerous operation. (Furnaces can be converted to LP gas with approved kit.)
· Installthisfurnaceonly in a location andpositionasspeci-
fied in “2. Installation” of these instructions.
· Provideadequatecombustionandventilationairtothefur-
naceasspecifiedin “4.CombustionandVentilationAir” of these instructions.
· Combustionproductsmustbedischargedoutdoors.Con-
nectthisfurnacetoan approved vent systemonly,as spe­cifiedin “5.GasVentInstallation,6.Horizontal Ventingand
7. Masonry Chimney Venting” of these instructions.
· Never test for gas leaks with an open flame. Use a com-
merciallyavailablesoapsolution made specifically for the detectionofleakstocheckallconnections,asspecifiedin “8. Gas Supply and Piping, Final Check” of these instruc­tions.
· Always install furnace to operate within the furnace’s in-
tended temperature--rise range with a duct system which hasanexternalstatic pressurewithintheallowablerange, as specified in “Technical Support Manual” of these in- structions.
· When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con­tainingthe furnace,thereturnairshallalsobe handledbya duct(s) sealed to the furnace casing and terminating out­side the space containing the furnace.
· Agas--fired furnace for installation in a residential garage
must be installed as specified in “2. Installation” of these instructions.
· This furnace is not to be used for temporary heating of
buildings or structures under construction. See “2. Installation, Item 10”.
· This furnace is NOT approved for installation in mo-
bile homes, trailers or recreation vehicles.
· Seal around supply and return air ducts.
· Install correct filter type and size.
· Unit MUST be installed so electrical components are pro-
tected from direct contact with water.
Safety Rules
Your unit is built to provide many years of s afe and dependable serviceprovidingit is properly installedandmaintained.However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
A. The U.S. ConsumerProduct Safety Commission encourages
installation of carbon monoxide alarms. There can be various sources of carbon monoxide in a building or dwelling. The sources could be gas--fired c lothes dryers, gas cooking stoves, water heaters, furnaces, gas--fired fireplaces, wood fireplaces, and several other items.
Carbon monoxide can cause serious bodily injury and/or death. Carbon monoxide or “CO” is a colorless and odorless gas produced when fuel is not burned completely or whenthe flame does not receive sufficient oxygen.
Therefore,tohelpalertpeopleofpotentiallydangerouscarbon monoxide levels, you should have a commercially available carbon monoxide alarm that is listed by a nationally recog­nizedtestingagencyinaccordancewithUnderwritersLabora­tories Inc. Standard for Single and Multiple Station Carbon Monoxide Alarms, ANSI/UL 2034 or the CSA 6.19--01 Resi­dential Carbon Alarming Devices installed and maintained in thebuildingordwellingconcurrentlywiththegas--firedfurnace installation(seeNote below).Thealarm shouldbeinstalledas recommended by the alarm manufacturer’s installation in­structions.
B. There can be numerous sources of fire or smokein a building
or dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert peopleofpotentiallydangerousfireorsmoke,youshouldhave fireextinguisherandsmokealarmslistedbyUnderwritersLab­oratories installed and maintained in the building or dwelling (see Note below).
Note: The manufacturer of your furnace does not test any alarms
and makes no representations regarding any brand or type of alarms.
C. To ensure safeandefficientoperationofyourunit,youshould
do the following:
1. Thoroughly read this manual and labels on the unit. This will help you understand how your unit operates and the haz­ards involved with gas and electricity.
2. Do not use this unit if any part has been under water. Im­mediatelycallaqualifiedserviceagencytoinspecttheunitand to replace any part of the control system and any gas control which has been under water.
3. Never obstruct the vent grilles, or any ducts that provide airto theunit.Airmustbeprovidedforpropercombustionand ventilation of flue gases.
441 01 2611 06
3
Frozen Water Pipe Hazard
Ifyour furnace remains off for an extended time, the pipes in your home could freeze and burst, resulting in serious water damage.
!
WARNING
FROZEN AND BURST WATER PIPE HAZARD FaiIure to protect against the risk of freezing could
result in property damage and/or personal injury. Donotleaveyourhomeunattendedforlongperiods
during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and resultant damage.
Yourfurnaceisdesignedsolelytoprovidea safe and comfortable living environment. The furnace is NOT designed to ensure that water pipes will not freeze. It is equipped with several safety de­vices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions.
2. Installation
!
CARBON MONOXIDE POISONING HAZARD. Failure to properly vent this furnace or other
appliances could result in death, personal injury and/or property damage.
If this furnace is replacing a previously common­vented furnace, it may be necessary to resize the existing vent system to prevent oversizing problems for the other remaining appliances(s). SeeVentingand CombustionAirCheckinthe5.Gas Vent Installation section of this instruction.
Location and Clearances
If furnace is a replacement, it is usually best to install the furnace wheretheoldone was. Choose the location or evaluate the exist­ing location based upon the minimum clearance and furnace di­mensions (Figure 1 or Figure 2).
!
CARBON MONOXIDE POISONING HAZARD. Failure to follow safety warnings could result in
serious injury, death, or property damage. Do NOT operate furnace in a corrosive
atmosphere containing chlorine, fluorine or any other damaging chemicals which could harm the furnace and vent system, and permit spillage of combustion products into an occupied space.
Refer to 4. Combustion & Ventilation Air section, Contaminated Combustion Air for combustion air evaluation and remedy.
Installation Requirements
1. Install furnace level.
2. ThisfurnaceisNOT to be usedfortemporaryheat of buildings or structures under construction.
3. Install furnace as centralized as practical with respect to the heat distribution system.
4
WARNING
WARNING
If the structure will be unattendedduring cold weather you should take these precautions.
1. Turnoffthewater supplytothe structureanddrain thewater lines if possible and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets in appropriate areas.
-- o r --
2. Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required.
-- o r --
3. Installareliableremotesensingdevicethatwillnotifysome­body of freezing conditions within the home.
4. Install the vent pipes as short as practical. (See 5. Gas Vent Installation section).
5. DoNOTinstallfurnacedirectlyoncarpeting, tileorothercom­bustible material other than wood flooring.
6. Maintain clearance for fire safety and servicing. A front clear­anceof30² is minimum for access to the burner, controls and filter. See clearance requirements in Figure 1 or Figure 2.
7. Use a raised base if the floor is damp or wet at times.
8. Residential garage installations require:
· Burners and ignition sources installed at least 18² (457
mm) above the floor.
· Furnace must be located or physically protected from
possible damage by a vehicle.
9. Ifthefurnace is tobesuspendedfromthefloorjoistsin abase­mentoracrawlspaceortheraftersinanattic,it isnecessaryto use steel pipe straps or an angle iron frame to attach the fur­nace. These straps should be attached to the furnace bottom side with sheet metal screws and to the rafters or joists with bolts. The preferred method is to use an angle iron frame bolted to the rafters or joists.
10. This furnace maybeusedforconstruction heat provided that:
· The furnace is permanently installed with all electrical
wiring,piping,ventingandductinginstalledaccordingto these installation instructions. A return air duct is pro­vided,sealed to the furnace casing, and terminated out­side the space c ontaining the furnace. This prevents a negativepressurecondition ascreatedbythe circulating air blower, causing a flame rollout and/or drawing com­bustion products into the structure.
· The furnace is controlled by a thermostat. Itmay not be
“hot wired” to provide heat continuously to the structure without thermostatic control.
· Clean outside air is provided for combustion. This is to
minimizethecorrosiveeffectsofadhesives, s ealers and otherconstruction materials. Italsopreventstheentrain­mentofdrywalldustintocombustionair,whichcancause fouling and plugging of furnace components.
· The temperature of the return air to the furnace is main-
tained between 55° F(13° C) and 80° F(27° C) , with no evening setback or shutdown. The use of the furnace whilethestructureisunderconstruction is deemed to be intermittent operation per our installation instructions.
441 01 2611 06
· The air temperature rise is within the rated rise range on
Furnace
ReturnAir
thefurnace ratingplate,andthefiringratehasbeensetto the rating plate value.
· The filters used to c lean the circulating air during the
construction process must be either changed or thor­oughly cleaned prior to occupancy.
· The furnace, ductwork and filters are cleaned as neces-
sarytoremovedrywalldustandconstructiondebris from all HVACsystemcomponentsafter construction is com­pleted.
· Verifyproperfurnaceoperatingconditionsincluding igni-
tion,gas input rate, air temperature rise, and venting ac­cording to these installation instructions.
Figure 1
Dimensions and Clearances (N8MPN/L)
TOP
51/
3
61/
2
5
LEFT SIDE
7
21/
131/
4
4
17/
D
C
8
Plugged starting hole tocutside duct opening
213/
BOTTOM
231/
8
4
265/
1
47/
8
8
DIMENSIONAL INFORMATION
Furnace
Model
N8MPN/L050B12 N8MPN/L075B12
N8MPN/L075F16
N8MPN100F14
N8MPN/L100F20
N8MPN/L100J22 N8MPN/L125J20 N8MPN/L125J22
Cabinet Bottom
A B C D
151/
2 14
191/8175/
8
223/4211/4115/
MINIMUM CLEARANCES TO COMBUSTIBLE
REAR 0 FRONT (combustion air openings
in furnace and structure)
31/
4
30² Min.
33/
171/
131/
3
4
33
271/
2
241/
2
4
11/
2
A
B
FRONT
Drawing is representative, but some models may vary
41/
16
DIMENSIONS IN INCHES
Return Air
Opening
13/
21/
125/
8
143/
8
H
8
4
J
NOTE: Evaporator “A” coil drain pan dimensions may vary
183/
16
4
J
from furnace duct opening size. Always consult evaporator specifications for duct size requirements.
Furnace is designed for bottom return or side return. Return air through back of furnace is NOT allowed.
Required For Service ALL SIDES Of SUPPLY PLENUM 1² SIDES 0 VENT
Single--Wall Vent 6²
Type B--1 Double--Wall Vent 1² TOP OF FURNACE 1²
*30² clearancerecommendedforcasing removal.
Horizontalposition: Linecontactis permissibleonlybetweenlines formedbyintersectionsoftopandtwosidesof furnace jacket,and buildingjoists, studsorframing.
MATERIALS FOR ALL FURNACES
3²
*24²
281/
2
181/
213/
2
21/
4
J
H
131/
4
4
8
33/
4
2
RIGHT SIDE
281/
2
253/
4
32
131/
11/
2
7
1
4
171/
3
47/
8
Plugged starting hole tocut side duct opening
265/
3
/
4
35
17/
8
25--23--44a1
441 01 2611 06
5
Figure 2
Furnace
ReturnAir
21/
4
131/
4
TOP
51/
LEFT SIDE
Plugged starting hole tocutside duct opening
Dimensions and Clearances (*8MPN/L Models)
F
3
5
1
33/
4
7337
277/
175/
16
271/
2
321/
8
30² Min.
A
B
2
38
FRONT
MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS FOR ALL UNITS
REAR 0 FRONT (combustion air openings
3²
in furnace and structure)
Required For Service
*24²
ALL SIDES Of SUPPLY PLENUM 1² SIDES 0 VENT
Single--Wall Vent 6²
Type B--1 Double Wall Vent 1² TOP OF FURNACE 1²
*30² clearancerecommendedforcasing removal.
Horizontalposition: Linecontactis permissibleonlybetweenlines formedbyintersectionsoftopandtwosidesof furnace jacket,and buildingjoists, studsorframing.
281/
2
181/
33/
4
2
2
3
/
4
213/
17/
8
D
4
265/
BOTTOM
47/
8
11/
8
2
Drawing is representative some models may vary
231/
C
8
41/
16
DIMENSIONS IN INCHES
DIMENSIONAL INFORMATION
Furnace
Model
*8MPN/L050B12 *8MPN/L075B12
*8MPN/L075F16
*8MPN100F14
*8MPN/L100F20 *8MPN/L100J20
*8MPN/L125J20
*8MPN150J20
* Denotes Brand
Cabinet Top Bottom
A B F C D
151/214 6 13/8125/
191/8175/873/421/8143/
223/4211/491/2115/16183/
8
4
4
Return Air
Opening
H
J
J
NOTE: Evaporator “A” coil drain pan dimensions may vary from furnace duct opening size. Always consult evaporator specifications for duct size requirements.
Furnace is designed for bottom return or side return. Return air through back of furnace is NOT allowed.
Furnace Installation
Inspecttheratingplatetobe certainthemodelnumberbegins with “N8MP” or“*8MP”.Thisidentifies the unit as a multi--position fur­naceandcan beInstalledina Upflow,HorizontalRight,Horizontal Left or Downflow position.
RIGHT SIDE
1
37
303/
4
291/
1
/
2
175/
11/
2
7
J
21/
4
265/
H
131/
4
213/
4
8
Plugged starting hole to cut side duct opening
2
16
47/
8
40
17/
8
Upflow
No modifications are required for upflow installation. (See
Figure 3)
6
441 01 2611 06
Figure 3
RETURN
AIR
T y pical Upflow Installation
SUPPLY
AIR
VENT
The horizontal furnaces may be installed directly on combustible woodflooringorsupports, however,itisrecommendedforfurther fireprotectioncementboardorsheetmetalisplacedbetweenthe furnace and the combustible wood floor and extend 12² beyond the front of the furnace louver door. (This is a recommendation only, not a requirement).
This furnace MUST NOT be installed directly on carpeting, tile or other combustible material other than wood flooring or supports.
Downflow
GAS SUPPLY
25--23--17
Horizontal
Ifyou purchased a multi--position furnace, it can be installed hori­zontallyin an attic, basement, crawl space, alcove, or suspended from a ceiling in a basement or utility room in either a right or left airflow position. (see Figure 4)
Horizontally installed furnaces may be vented out the top of the unitoroutthesidefacingup.See“Sideventing” forinstructionsto rotate the vent to the side.
The minimum clearances to combustibles MUST be maintained between the furnace and adjacent construction, as shown in Figure 1 and Figure 2. ONLYthecornerofthecabinetisallowed to contact the rafters as shown in Figure 4. All other clearances
MUST be observed as shown in Figure 1 and Figure 2.
Figure 4
SUPPLY
AIR
Ifthe furnaceisto besuspendedfromthefloorjoistsina basement orcrawlspaceortheraftersinanattic,itis necessary to use steel pipe straps or an angle iron frame to attach the furnace. These straps should be attached to the furnace bottom side with sheet metal screws and to the rafters or joists with bolts. The preferred methodistouse an angle iron frame bolted to the rafters orjoists.
Ifthefurnaceistobeinstalledatgroundlevelinacrawlspace,con­sult local codes. A concrete pad 1² to 2² thick is recommended.
Thirtyinches(30²)isrequiredbetween thefrontofthe furnaceand adjacent construction or other appliances. This should be main­tained for service clearance.
Keep all insulating materials clear from louvered door.Insulating materials may be combustible.
441 01 2611 06
T ypical Horizontal Installation
RETURN
AIR
VENT
VENT
GAS SUPPLY
OPTIONAL VENT LOCATION
25-23-18a
!
WARNING
FIRE HAZARD. Failure to install unit on noncombustible subbase
couldresultin death, personalinjuryand/orproperty damage.
Place furnace on noncombustible subbase on downflow applications, unless installing on noncombustible flooring.
If you purchased a Multi--position furnace (*8MP) it may be installed in a downflow configuration, (see Figure 5). The mini­mumclearancestocombustionconstructionMUST bemaintained between the furnace and adjacent construction, as shown in Figure 1 and Figure 2.
In addition to clearances in Figure 1 and Figure 2, c learance for the vent pipe must be considered.
AsubbaseforcombustiblefloorsMUST beusedwhenthefurnace isinstalledasa downflowoncombustiblematerial. See 11.“Duct- work and Filter” (Downflow Section). The outlet flange must be bent flat for downflow installation.
When installing a four--position furnace in the downflow position (not the *8DNL furnace), the logo is to be repositioned so that it is rightside--up as follows:
T8MPN/L
1. Find the door hardware kit that is stored in the furnace and save it.
2. Carefullyremovelogofromtheoutsideof burnercompartment door and save it.
3. Carefullyremovetwosmallplugbuttonsfromoutsideofblow­er compartment door and save them.
4. Removetwo thumbscrews from blower compartment door by cutting apart metal retainer washers on inside of door with smalldiagonalcuttingpliers.Theretainer washers will not un­screwfromthethumbscrews.Savethetwothumbscrewsand two plastic washers.
5. Install two thumbscrews in holes at other end of blower compartment door from where thumbscrews were removed.
a. A plastic washer should be on each of the two thumb-
screwsbeforeinsertingthe thumbscrews intotheblower compartment door holes.
b. After inserting each thumbscrew into the proper hole in
the blower door,push a new metal retainer washer onto each thumbscrew as far as it will go.
6. Install newstrip of rubber gasket on inside of blower compart­ment door on edge that does not already have a gasket.
7. Installlogoretainerpinsintoholesinblowercompartmentdoor from which plug buttons were removed.
8. Installplugbuttonsintoholesin burnercompartmentdoorfrom which logo was removed.
9. Install blower compartment door on furnace with bevel edge and logo at top.
7
10. Install burner compartmentdooron furnacewithbeveledge at bottom.
N8MPN/L, C8MPN/L, H8MPN/L
1. Carefully remove logo from burner compartment door and save it.
2. Turn the logo rightside--up, and install the logo retainer pins into holes in burner compartment door.
3. New labels for rightside--up application on outside of blower compartmentdoormay bepurchasedina kit fromyourdistrib­utor to cover upside--down labels.
locatetheswitch,locate2mountingholesordrillabovetheinducer pressure tap. When drilling the 2 holes make sure to keep the switch and tubing far enough away from the burners or hot sur­facesastonot meltthehose,switch,or wires. Topreventpossible kinking of the pressure switch hose, trim the hose to remove ex­cess length.
Note:Whendrillingnewholesmakesuremetalshavingsdonotfall on or in components, as this can shorten the life of the furnace.
Figure 5
T y pical Downflow Installation
Downflow Venting: The combustion venter MUST be rotated to
ventoutthesideforalldownflowinstallations,(seeFigure 5). Bot­tomventingisnotpermitted.See“Sideventing”forinstructionsto rotatethe venttothe side.Inadditiontorotatingtheventtotheside a Vent Pipe Shield (NAHA002VC) is required to shield the hot vent pipe.
!
WARNING
BURN HAZARD. Vent pipe is HOT and could cause personal injury.
Hot vent pipe is in reach of small children when installed in downflow position.
Install vent pipe shield NAHA002VC.
Pressure Switch Relocation
Ifthe furnaceisinstalledintheupflowposition, thepressureswitch will remain in the same position as installed by the factory unless the inducer is rotated. If the furnace is installed in an orientation that places the pressure switch below the pressure tap on the in­ducerhousing,thentheswitchMUST be relocated. In order to re-
3. Side Venting
This furnace is shipped from the factory with the venter assembly in an upflow configurations (top vent). The venter assembly can easily be rotated to a side vent configurations for use in upflow, horizontal--flow, or downflow application.
See side venting
for venter rotation
Combustible floor base outlet flange adapter
Vent Shield Kit
Figure 6
RETURN
AIR
VENT
OPTIONAL VENT
SUPPLY
AIR
Furnace with Screws
GAS SUPPLY MUST BE OPPOSITE VENT DISCHARGE SIDE
25--23--19
When using a side vent configuration (side outlet instead of top outlet),it may be necessary to relocatethe pressure switch to the alternatepositionontheoppositeside ofthetop panel. Twoscrew holes are provided at the alternate position. Route the pressure switch tubing so the tubing is not kinked and not touching the hot collector box, venter housing, or motor. It may be necessary to shorten the length of the tubing to properly route the tubing and eliminate kinks.
Rotating the Venter Assembly
1. If gas and electrical power have already been connected to unitshutoff gasandremovepower fromunit.Unscrewscrews onburner compartmentdoorandremoveburnercompartment door. See Figure 6.
2. Disconnectpowerleadstotheventermotorandhosetopres­sureswitch.Removethree (3) orfour(4)screws which secure the venter to the collector box, (see Figure 7).
3. Cut webbing with a pair of snips holding the vent plate to the cabinetoneither the leftorrightside ofunitdependingonright or left venting as desired. Discard vent plate, (see Figure 6).
8
Vent Plate
Screws (2)
25--23--45
441 01 2611 06
Figure 7
Venter Gasket
Entry
Main Line
25--23--52b
25--23--52c
4. Combustion & Ventilation Air
! CARBON MONOXIDE POISONING HAZARD. Failure to provide adequate combustion and
ventilationaircouldresultindeathand/orpersonal injury.
Use methods described here to provide combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for propercombustion and ventilation of flue gases. All duct or open ­ingsforsupplyingcombustionandventilationairmustcomplywith thegascodes,orin the absenceoflocalcodes,the applicable na­tional codes.
Combustion and ventilation air must be supplied in accordance with one of the following:
1. Section8.3, AirforCombustionandVentilation,of theNational Fuel Gas Code, (NFGC), ANSI Z223.1--2002/NFPA54--2002 in the U.S.,
2. Sections7.2,7.3,7.5, 7.6,7.7,and7.8 of NationalStandardof Canada, Natural Gas and Propane Installation Code (NSCNGPIC), CSA B149.1--00 in Canada,
3. Applicable provisions of the local building code.
When the installation is complete, check that all appliances have adequate combustion air and are venting properly. See Venting AndCombustionAirCheckin“5.GasVentInstallation” Section i n this manual.
Contaminated Combustion Air
Installationsincertainareasortypes ofstructurescould causeex­cessive exposure to contaminated air having chemicals or halo­gens that will result in safety and performance related problems and may harm the furnace. These instances must use only out­door air for combustion.
Thefollowingareasor types of structuresmaycontainorhave ex­posure to the substances listed below. The installation must be
441 01 2611 06
WARNING
4. Replace venter gasket (part # 1013540, if needed) to venter assembly with adhesive in the same location as the old one.
5. Rotate venter assembly 90 ° right or left from original location depending on venting configurations.
6. Tightenthe three (3) or four (4) screws that secure the venter assembly to the collector box. Do tighten screws enough to compress venter gasket.
7. Replace power leads to venter motor and reconnect hose to pressure switch.
NOTE:Unused open vent hole must be covered. A VentCover is suppliedwithVentPipeShieldKit NAHA002VC.A5 VentCoveri s availableseparatelyfromyourdistributor,or onecan be fabricated with sheet metal for all side vent installations.
evaluated carefully as it may be necessary to provide outdoor air for combustion.
5
/16² diameter
· Commercial buildings.
· Buildings with indoor pools.
· Furnaces installed in laundry rooms.
· Furnaces installed in hobby or craft rooms.
· Furnaces installed near chemical storage areas.
· Permanent wave solutions for hair.
· Chlorinated waxes and cleaners.
· Chlorine based swimming pool chemicals.
· Water softening chemicals.
· De--icing salts or chemicals.
· Carbon tetrachloride.
· Halogen type refrigerants.
· Cleaning solvents (such as perchloroethylene).
· Printing inks, paint removers, varnishes, etc.
· Hydrochloric acid.
· Sulfuric Acid.
· Solvent cements and glues.
· Antistatic fabric softeners for clothes dryers.
· Masonry acid washing materials.
Outdoor Combustion Air Method
Aspace havinglessthan50cubicfeetper1,000BTUHinputrating forallgasappliancesinstalledin thespacerequiresoutdoorairfor combustion and ventilation.
Air Openings and Connecting Ducts
1. Total input rating for all gas appliances in the space MUST be considered when determining free area of openings.
2. Connect ducts or openings directly to the outdoors.
3. When screens are used to cover openings, the openings MUST be no smaller than
4. The minimumdimensionof air ducts MUST NOT be less than 3² .
5. Whensizingagrille,louverorscreenusethefreeareaofopen­ing. If free area is NOT stamped or marked on grill or louver, assumea20%freeareafor woodand60%for metal. Screens shall have a mesh size not smaller than
1
/4² mesh.
1
/4².
9
Requirements
BTU
H
1. Providethespacewithsufficientairforpropercombustionand ventilation of flue gases using horizontal or vertical ducts or openings.
2. Figure 8illustrateshowtoprovidecombustionand ventilation
airwhentwopermanentopenings,oneinletandone outlet,are used.
a. One opening MUST commencewithin12² of the floor
and the second opening MUST commence within 12² of the ceiling.
b. Size openings and ducts per Table 1.
Figure 8
Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
This installation NOT approved in Canada
Gas Vent
Minimum OneInlet and One Outlet AirSupply isRequired
Inlet Air OpeningMust be Within12²(300mm) of floor Outlet Air OpeningMust be Within12²(300mm) of ceiling (1) 1 Square Inch(6cm (2) 1 Square Inch(6cm
VentilatedAttic
TopAbove Insulation
Outlet Air (1)
Furnace
VentilatedCrawl Space
May bein and Combination Shown
2 2
c. Horizontal duct openings require 1 square inch of free
areaper2,000BTUH(1,100mm2/kW)ofcombinedinput for all gas appliances in the space (see Table 1).
d. Verticalduct openings oropeningsdirectlycommunicat-
ing with the outdoors require 1 square inch of free area per4,000 BTUH (550 mm gas appliances in the space (see Table 1).
3. When one permanent outdoor opening is used, the opening requires:
a. 1 sq. in of free area per 3,000 BTUH (700 mm
combined input of all gas appliances in the space (see Table 1) and
Gable Ve nt
Inlet Air (1)
) per 4000BTUH ) per 2000BTUH
Optional InletAir (1)
Soffit Vent
2
/kW)for combined input of all
b. notlessthanthesumoftheareasofallventconnectorsin
the space.
The opening shall commence within 12² of the top of the enclo­sure.Appliancesshallhaveclearancesofatleast1² fromthesides andbackand6² from the front.Theopeningshalldirectly commu-
Table 1
Input
Rating
50,000 25 sq. in. 16.7 sq. in. 12.5 sq. in. 4²
75,000 37.5 sq. in. 25 sq. in. 18.75 sq. in. 5² 100,000 50 sq. in. 33.3sq.in. 25 sq. in. 6² 125,000 62.50 sq. in. 41.7 sq. in. 31.25 sq. in. 7² 150,000 75 sq. in. 50 sq. in. 37.5 sq. in. 7²
EXAMPLE: Determining Free Area
Furnace 100,000 Furnace 100,000
Free Area
TwoHorizontal Ducts
(sq. in./2,000 BTUH)
Water Heater
+
+
30,000
Water Heater
30,000
10
Gable Ve nt
Soffit Vent
Inlet Air (2)
Outlet Air (1)
Inlet Air (1)
Inlet Air (1)
Gas Vent
VentilatedAttic
TopAbove Insulation
Outlet Air (1)
Furnace
nicatewiththeoutdoorsorshallcommunicatethroughaverticalor horizontalductto the outdoorsorspaces(crawlor attic)thatfreely communicate with the outdoors.
4. Combination of Indoor and Outdoor Air shall have: a. Indoor openings that comply with the Indoor Combus-
tion Air Method below and
b. Outdoor openings located as required in the Outdoor
Combustion Air Method above and
2
/kW) for
c. Outdoor openings sized as follows.
1) Calculate the Ratio of all Indoor Space volume divid­edby requiredvolumeforIndoorCombustionAirMeth­od. Outdoor openings sized as follows.
2) Outdooropeningsizereduction Factor is1 minusthe Ratio in 1) above.
3) Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor.
Minimum FreeAreaRequiredfor Each Opening or Duct to Outdoors
Single Opening
(sq. in./3,000 BTUH)
Total Input
=
(130,000 ¸ 4,000)
Total Input
=
(130,000 ¸ 2,000)
==32.5 Sq. In. Vertical
65 Sq. In. Horizontal
Gas Vent
Furnace
TwoVertical Ducts or Openings
(sq. in./4,000BTUH)
Outlet Air (2)
Inlet Air (2)
Round Duct
(sq. in./4,000
BTUH)
441 01 2611 06
Indoor Combustion Air
Standard and Known--Air--Infiltration Rate Methods
ã NFPA&AGA
Indoor air is permitted for combustion and ventilation, if the Standard or Known--Air--Infiltration Rate Method is used.
!
CARBON MONOXIDE POISONING HAZARD. Failure to supply adequate combustion air could
result in death and/or personal injury. Mosthomeswillrequireadditionalairfrom outdoors
for combustion and ventilation. A space with atleast
WARNING
The Standard Method may be used, if the space has no less vol­umethan50cubicfeetper1,000BTUHof the maximum input rat­ings for all gas appliances installed in the space. The standard method permits indoor air to be used for combustion and ventila­tion air.
The Known Air Infiltration Rate Method shall be used if the in­filtration rate is known to be less than 0.40 air c hanges per hour (ACH) and equal to or greater than 0.10 ACH. Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space, and add the volumes together to get the total minimum required vol­ume for the space.
50 cubic feet per 1,000 BTUH input rating or homes with tight construction may need outdoor air to supplement air infiltration for proper combustion and ventilation of flue gases.
MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS (ft3)
Table 2
ACH
0.60 1,050 1,400 1,750 1,250 1,875 2,500 3,125 3,750
0.50 1,260 1,680 2,100 1,500 2,250 3,000 3,750 4,500
0.40 1,575 2,100 2,625 1,875 2,813 3,750 4,688 5,625
0.30 2,100 2,800 3,500 2,500 3,750 5,000 6,250 7,500
0.20 3,150 4,200 5,250 3,750 5,625 7,500 9,375 11,250
0.10 6,300 8,400 10,500 7,500 11,250 15,000 18,750 22,500
0.00 NP NP NP NP NP NP NP NP
Other Than Fan-Assisted Total
(1,000’sBtuh)
30 40 50 50 75 100 125 150
Fan-assistedTotal
(1,000’sBtuh)
NP = Not Permitted Table 2MinimumSpaceVolumesweredetermined by usingthe
following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54--2002, 8.3.3.2:
1. For other than fan--assisted appliances such as a draft hood--equipped water heater,
(
1000 Btu / hr
(
1000 Btu / hr
I
I
other
fan
)
)
3
Volume
other
2. For fan--assisted appliances such as this furnace,
Volume
If:
I
I
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
=
fan
= combined input of all other than fan--assisted
other
appliances in Btu/hr
=combinedinputofallfan--assisted appliancesinBtu/hr
fan
21 ft
=
ACH
3
15 ft
ACH
· Adjoining rooms can be considered part of a space, if there
are no closable doors between rooms.
· An attic orcrawlspacemaybeconsidered a space thatfreely
communicateswiththeoutdoorsprovidedthereareadequate ventilationopeningsdirectly tooutdoors.Openings MUST re­mainopenandNOThaveanymeansofbeingclosed off.Ven-
tilation openings to outdoors MUST be at least 1 square inch offreeareaper4,000BTUH of totalinputratingforall gas ap­pliances in the space.
· In spaces that use the Indoor Combustion Air Method, in-
filtration should be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings withunusuallytightconstruction,additional air MUST bepro­vided using the methods described in section titled Outdoor Combustion Air Method:
· Unusually tight construction is defined as Construction with:
1. Wallsand ceilings exposed to the outdoors have a con­tinuous,sealed vapor barrier.Openingsaregasketed or sealed and
2. Doors and openable windows are weather stripped and
3. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall--ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Ventilation Air
Someprovincialcodesandlocal municipalities requireventilation ormake--up airbe brought into the conditioned space asreplace­mentair.Whichevermethodisused,the mixedreturnairtempera­ture across the heat exchanger MUST not fall below 60° continuously,or55° onanintermittentbasis so that flue gases will not condense excessively in the heat exchanger.Excessive con­densation will shorten the life of the heat exchanger and possibly void your warranty.
441 01 2611 06
11
5. Gas Vent Installation
!
CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD.
Failure to properly vent this furnace could result in death, personal injury and/or property d amage.
Read and follow all instructions in this section.
Install the vent in compliance with codes of the country having ju­risdiction, local codes or ordinances and these instructions.
This Category I furnace is fan--assisted. Afan assisted appliance isanapplianceequipped withanintegralmechanicalmeans toei­ther draw or force products of combustion through the heat ex­changer.
Category I furnace definition: A central furnace which operates with a non--positive vent static pressure and with a flue loss not lessthan17percent. These furnaces are approved forcommon-­venting and multi--story venting with other fan--assisted or draft hood--equipped appliances in accordance with the NFGC or NSCNGPIC
Category I Safe Venting Requirements
Category I furnace vent installations shall be in accordance with Parts 10 and 13 of the National Fuel Gas Code (NFGC), ANSI Z223.1--2002/NFPA54 --2002;and/orSection7andAppendixCof the CSA B149.1--00, National Standard of Canada, Natural Gas and Propane Installation Code; the local building codes; furnace and vent manufacturer’s instructions.
NOTE: The following instructions comply with the ANSI Z223.1/NFPA54 National Fuel Gas Code and CSA B149.1Natu­ral Gas and Propane Installation code, based on the input rate on the furnace rating plate.
1. If a Category I vent passes through an attic, any concealed space or floor, use ONLY Type B or Type L double wall vent pipe.Ifventpipepasses through interior wall, useTypeB vent pipe with ventilated thimble ONLY.
2. Do NOT vent furnace into any chimney serving an open fire­place or solid fuel burning appliance.
3. Use the same diameter Category I connector or pipe as per­mitted by:
· the National Fuel Gas Code Code (NFGC) ANSI
· the NationalStandard of Canada Natural Gas and Pro-
4. Push the vent connector onto the furnace flue collar of the venterassemblyuntilittouchesthebead(atleast and fasten with at least two field--supplied, corrosion--resist­ant, sheet metal screws located at least 140° apart.
5. Keep vertical Category I vent pipe or vent connector runs as short and direct as possible.
6. Verticaloutdoor runs of Type--B or ANY single wall vent pipe below the roof line are NOT permitted.
7. Slopeallhorizontalruns upfromfurnace totheventterminal a minimum of
WARNING
Z223.1--2002 / NFPA54--2002 sections 10 and 13 vent­ing requirements in the United States
or
pane Installation Code (NSCNGPIC) CSA B149.1--00 section7andappendixCventing requirements inCana­da.
5
/8² overlap)
1
/4² per foot (21 mm/m).
8. Rigidlysupportallhorizontalportionsoftheventingsystemev­ery6¢ orlessusingproperclampsandmetalstrapsto prevent sagging and ensure there is no movement after installation.
9. Checkexistinggas ventorchimneyto ensuretheymeetclear­ances and local codes. See Figure 1
10. The furnace MUST be connected to a factorybuilt chimney or vent complying with a recognized standard, or a masonry or concretechimneylined withaliningmaterialacceptable tothe authority having jurisdiction. Venting into an unlined ma-
sonrychimneyor concretechimneyis prohibited.Seethe
6. Masonry Chimney Venting section in these instruc­tions.
11. Fan--assisted combustion system Category I furnaces shall not be vented into single--wall metal vents.
12. Category I furnaces must be vented vertically or nearly verti­cally, unless equipped with a listed mechanical venter.
13. VentconnectorsservingCategoryIfurnaces shallnotbecon­nectedintoanyportionofmechanical draft systems operating under positive pressure.
A4--to-- 3 inchreducerispermitted attheflue collarwheninstalling a50,000Btuhgasinputfurnace, iftheinstallationmeets allthefol­lowing requirements for sizing the vent connectors and vents:
1. The National Fuel Gas Code, ANSI Z223.1/NFPA--54--2002, sections 10.5.3.1(1),
10.6.3.1(2), 10.10.3.1, 13.1.2, 13.1.10, and 13.2.21(1) through (3) in the U.S. or
2. The Natural Gas and Propane Installation Code CSA B149.1--00, sections 7.13.1(b), 7.13.2(b), 7.18.5(b), and Appendix C--GVR no. 2. in Canada.
12
441 01 2611 06
Venting and Combustion Air Check
NOTE: When an existing Category I furnace is removed or re­placed,theoriginalventingsystemmaynolongerbesizedtoprop ­erly vent the attached appliances, and to make sure there is adequate combustion air for all appliances, MAKE THE FOL-
LOWING CHECK.
Figure 9
Typical Gas Water Heater
Vent Check
Draft HoodVent Pipe
Match
!
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each
applianceconnectedtothe venting systembeingplaced into operation, could result in carbon monoxide poisoning or death:
The followingsteps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1.Seal any unused openings in the venting system.
2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or CSA B149.1, Natural Gas and Propane Installation Code and these instructions. Deter -
minethatthereisnoblockageorrestriction,leakage,cor­rosionandotherdeficiencieswhichcouldcauseanunsafe condition.
3.As far as practical, close all building doors and windows andalldoors between thespaceinwhich theappliance(s) connected to the venting system are located and other spaces of the building.
4.Close fireplace dampers.
5.Turnonclothesdryersandanyappliancenotconnectedto the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6.Followthelightinginstructions.Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7.Test for spillage from draft hood equipped appliances at thedraft hoodreliefopeningafter5minutesof mainburner operation.Use the flame of a matchor candle. (Figure 9)
8.If improper venting is observed, during any of the above tests,the ventingsystemmustbecorrectedinaccordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/orCSAB149.1,NaturalGasand PropaneInstallation Code.
9.After it has been determined that each appliance con ­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use.
WARNING
NOTE: If flame pulls towards draft hood, this indicates
sufficient infiltration air.
Venting to Existing Masonry Chimney
Dedicated venting of one fan assisted furnace into any ma­sonry chimney is restricted. A chimney must first be lined with
either Type B vent sized in accordance with NFGC tables 13.1 or
13.2 or a listed, metal lining system, or venting into a masonry chimneyispermittedasoutlinedwith use of an optional listed ma­sonry chimney kit. (See Section 7 Masonry Chimney Venting of these instructions.)
Listed, corrugated metallic chimney liner systems in masonry chimneysshallbesizedbyusing NFGC tables per13.1.7fordedi­cated venting and per 13.2.19 for common venting with the maxi­mum capacity reduced by 20% (0.80 X maximum capacity) and theminimumcapacityasshownintheapplicabletable.InCanada, use the NSCNGPIC, appendix C, section 10. Corrugated metal vent systems installed with bends or offsets require additional re­ductionof 5%oftheventcapacityforeach bendupto45° and10% of the vent capacity for each bend from 45° up to 90°.
NOTE:Two(2)45° elbows are equivalent to one (1) 90° elbow.
Combined Venting into a Masonry Chimney
Ventingintoamasonryorconcretechimneyisonlypermitted as outlined in the NFGC or NSCNGPIC venting tables. Follow
all safe venting requirements.
Note: See section “7. Masonry Chimney Venting”.
441 01 2611 06
13
6. Horizontal Venting
Category I Furnaces With External Power Venters
InordertomaintainaCategory Iclassificationof fan--assistedfur­naceswhenventedhorizontallywithsidewalltermination,apower venter is REQUIRED to maintain a negative pressure in the vent­ing system.
In the U.S.: Per the NFGC, a listed power venter may be used, when approved by the authority having jurisdiction.
In Canada: Only power venters approved by the appliance manufacturer and where allowed by the authority having jurisdic­tion may be used
PleaseconsulttheFieldsControlsCo. or Tjernlund Products, Inc. for power venters certified for use with our furnaces.
Vent Termination
VentingThrough a Non--Combustible and Combustible Wall
Consult External Power Venter manufacturer instructions.
SelectthepowerventertomatchtheBtuhinputofthefurnacebe­ingvented. Followallof thePowerVenter manufacturer’s installa­tion requirements included with the power venter for:
· venting installation,
· vent terminal location,
· preventing blockage by snow,
· protecting building materials from degradation by flue gases,
· see Figure 1 0 for required vent termination.
NOTE: It is the responsibility of the installer to properly terminate theventandprovideadequateshielding. This is essential inorder to avoid water/ice damage to building, shrubs and walkways.
14
441 01 2611 06
Figure 10
Other than Direct Vent Termination Clearance
N
V
V
D
E
V
B
V
C
F
B
V
VENT TERMINAL
Item Clearance Descriptions Canadian Installation(1)
A Clearance above grade, veranda, porch,deck,balcony,or
anticipated snow level
B Clearance to awindowor door that may be opened 6² (15 cm) forappliances £ 10,000 BTUH (3kW), 12² (30
C Clearance toapermanently closed window D Verticalclearance toa ventilated soffitlocatedabovethe ter-
minal within a horizontal distance of 2¢ (61cm) from thecent­erline of theterminal
E Clearance to anunventilated soffit F Clearance to anoutsidecorner G Clearancetoan inside corner H Clearance toeachside ofthecenterline extended above elec-
trical meter or gas service regulator assembly
I Clearance to service regulator vent outlet 3¢ (91cm)
J Clearance tonon--mechanical air supply inlet to building or the
combustion air inlet to anyotherappliance
K Clearance to amechanical air supply inlet 6¢ (1.83 m) 3¢ (91cm)aboveif within 10¢ (3mhorizontally) L Clearance under a veranda, porch, deck, orbalcony 12² (30 cm) +
M Clearanceto eachsideofthe centerline extended above or
below vent terminal of thefurnace toadryer or water heater vent, or otherappliance’s direct vent intake or exhaust.
N Clearance from aplumbingventstack 3¢ (91cm) 3¢ (91cm)
(1.) In accordance with the current CSAB149.1,Natural Gas andPropane Installation Code (2.) In accordance with the currentANSIZ223.1/NFPA54, National Fuel Gas Code #18² (46cm)aboveroof surface + Permitted only if veranda, porch, deck, or balcony is fully open ona minimum of twosides beneath thefloor.
B
V
B
B
X
AIR SUPPLYINLET
12² (30cm) # 12² (30cm)
cm) for appliances > 10,000Btuh(3 kW) and£ 100,000 Btuh (30kW),36² (91 cm) for appliances > 100,000Btuh(30 kW)
* * * *
* * * * * *
3¢ (91cm) within15¢ (4.5 m) above the meter/regulator assembly
6² (15 cm) forappliances £ 10,000 BTUH (3kW), 12² (30 cm) for appliances > 10,000Btuh(3 kW) and £ 100,000 Btuh (30kW),36² (91 cm) for appliances > 100,000 Btuh (30kW)
* *
B
X
J
A
H
I
L
K
AREA WHERE TERMINAL ISNOTPERMITED
G
X
V
4¢ (1.2m) below ortothe side of the opening. 1¢ (30 cm) above theopening.
3¢ (91cm) within15¢ (4.5 m)abovethe meter/regulator assembly
*
4¢ (1.2m) below ortothe side of opening: 1¢ (30cm) above opening.
*
M
A
V
25--24--65--2
U.S. Installation (2)
* For clearances not specified in ANSI Z223.1/NFPA 54orCSA B149.1, clearances shall be inaccordancewithlocalinstallation codes andtherequirements of thegassupplier and themanufacture’s
installation instructions.
Notes:
1. The ventforthis appliance shall not terminate a. Over public walkways; or b. Near soffit vents orcrawlspacevents or otherareaswhere condensate orvapor could create anusiance or hazard orpropertydamage; or c. Where condensate vapor could cause damage or could bedetrimental to theoperationof regulators, relief valves, or other equipment.
2. When locatingvent terminations,considerationmust begivento prevailingwinds,location, andother conditions which may causerecirculation of thecombustiob products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heatexchangers.
441 01 2611 06
15
7. Masonry Chimney Venting
Chimney Inspection
All masonry chimney construction must conform to Standard ANSI/NFPA211--2003 and to any state or local codes applicable. The chimney must be in good condition and a complete chimney inspectionmustbeconductedpriortofurnace installation.Ifthein­spection reveals damage or abnormal conditions, make neces­sary repairs or seek expert help. See Figure 11 “The Chimney Inspection Chart”. Measure inside area of tile --liner and exact height of chimney from the top of the c himney to the highest ap­pliance flue collar or drafthood outlet.
Connector Type
To reduce flue gas heat loss and the c hance of condensate prob­lems, the vent connector must be double--wall Type B vent.
VentingRestrictions for Chimney Types
Interior Chimney -- has no sides exposed to the outdoors below the roofline. All installations can be single furnace or common vented with another draft hood equipped Category I appliance.
Exterior Chimney -- has one or more sides exposed to the out­doors below the roof line. All installations with a 99% Winter De­sign Temperature*below17°F must be common vented only with a draft hood equipped Category I appliance.
The 99% Winter Design Dry--Bulb (db) temperatures are found in the
*
1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States)and2(Canada),orusethe99.6% heatingdb temperaturesfound in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada).
!
CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD.
Failure to properly vent this furnace could result in death, personal injury and/or property d amage.
These furnaces are CSA (formerly AGA and CGA) design--certified for venting into exterior clay tile--lined masonry chimneys with a factory accessory Chimney Adapter Kit. Refer to the furnace rating plate for correct kit usage. The Chimney Adapter Kits are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate.
WARNING
Ifa claytile--linedmasonrychimneyisbeingusedanditisexposed to the outdoors below the roof line, relining might be required. Chimneys shall conform to the Standard for Chimneys, Fire­places, Vents, and Solid Fuel Burning Appliances ANSI/NFPA 211--2003 in the United States and to a Provincial or Territorial Building Code in Canada (in its absence, the National Building Code of Canada) and must be in good condition.
U.S.A.--Refer toSections13.1.9or13.2.20ofthe NFGCortheau­thorityhavingjurisdictiontodeterminewhetherreliningisrequired. If relining is required, use a properly sized listed metal liner, Type--B vent, or a listed alternative v enting design.
NOTE: See the NFGC, 13.1.9 and 13.2.20 regarding alternative venting design and the exception, which cover installations such as the Chimney Adapter Kits NAHA001DH and NAHA002DH.
The Chimney Adapter Kits are listed alternative v enting designs for these furnaces. See the kit instructions for complete details.
Canada(and U.S.A.)--Thisfurnaceispermittedtobeventedintoa clay tile--lined masonry chimney that is exposed to the outdoors below the roof line, provided:
1. Ventconnector is Type--B double--wall, and
2. This furnace is common vented with at least 1 draft hood-­equipped appliance, and
3. The combined appliance input rating is less than the maxi­mum capacity given in Table A, and
4. Theinputratingofeachspace--heatingapplianceisgreater than the minimum input rating given in Table B for Masonry Chimneys for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input ratingsofthesefurnaces. SeefootnoteatbottomofTableB, and
5. The authority having jurisdiction approves.
Ifall of these conditions cannot be met, an alternative venting de­sign shall be used, such as the listed chimney adapter kit with a furnace listed for use with the kit, a listed chimney--lining system, or a Type--B vent.
These furnaces are CSA design--certified for use in exterior clay tile--lined masonry chimneys with a factory accessory Chimney AdapterKit. Refer to the furnace ratingplateforcorrectkitusage. The Chimney Adapter Kits are listed alternative v enting designs andarefor use withONLY furnaces having aChimneyAdapterKit number marked on the furnace rating plate.
16
441 01 2611 06
Figure 11
CHIMNEY INSPECTION CHART
ForadditionalrequirementsrefertotheNationalFuelGasCodeNFPA54/ANSIZ223.1--2002andANSI/NFPA211--2003Chimneys,Fireplaces, Vents,andSolidFuel BurningAppliancesin the U.S.A. or to the Canadian InstallationCodeCSAB149.1--00 in Canada.
Crown
condition:
Missingmortar
or brick?
No
Is
Chimney properly lined
with clay tile
liner?
Yes
Is liner and top seal in good
condition
Yes
Debris in
cleanout? Mortar,tile,
metal vent, fuel oil
residue?
No
Yes
No
Repair
No
liner or topseal
or reline chimney as
necessary.
Yes
Remove metal vent orliner.
Repair
Rebuild
crown
Mortar or
tile debris?
Reline
No
Yes
Remove mortar
and tile debris?
Clay tile misalignment, missingsections,
gaps?
No
Condensate
drainage at bottom
of chimney?
No
Chimney
exposed to outdoors
below roof line?
No
Chimneyis
acceptable for use
Yes
Yes
Yes
No
Is Chimney
lined with properly
sized, listed liner or
Type--B vent?
Yes
Is Chimney to
be dedicated toa
single furnace?
Consult
Part B ofchimney
adapter venting instructionsfor
application
suitability.
Suitable
Yes
Install chimney
adapter per
instructions.
No
Not Suitable
Not Suitable
Consult
Part C ofchimney
adapter venting
instructionsfor
application
suitability.
Line chimney with properly
sized, listed flexible metal
liner or Type--B vent per NFGC or
NSCNGPIC VentSizing Tables
and liner orventmanufacturer’s
installation instructions.
Suitable
Install chimney
adapter per
instructions.
441 01 2611 06
17
Exterior Masonry Chimney,
G
6
o
7
o
5
4
t
1
o
r
FAN+NAT Installations with
Type--B Double--Wall Vent Connectors
ã
ã NFPA&AGA
ãã
Table A--
Combined Appliance
Maximum Input Rating in
Thousands of Btu per Hr
VENT
HEIGHT
(FT)
6 74 119 178 257
8 80 130 193 279 10 84 138 207 299 15 NR 152 233 334 20 NR NR 250 368 30 NR NR NR 404
INTERNAL AREA OF CHIMNEY
(SQ IN.)
12 19 28 38
Table B--
Minimum Allowable Input Rating of
Space--Heating Appliance in
Thousands of Btu per Hr
VENT
HEIGHT
(FT)
Local 99% Winter Design Temperature: 17 to 26°°°° F*
6 0 55 99 141
°
°F
°
°
8 52 74 111 154
6
10 NR 90 125 169
o2
15 NR NR 167 212
7t
1
20 NR NR 212 258 30 NR NR NR 362
Local 99% Winter Design Temperature: 5 to 16°°°° F*
6 NR 78 121 166 8 NR 94 135 182
°
°F
°
°
16
10 NR 111 149 198 15 NR NR 193 247
5t
20 NR NR NR 293 30 NR NR NR 377
Local 99% Winter Design Temperature: --10 to 4°°°° F*
6 NR NR 145 196
°
°F
°
°
8 NR NR 159 213
4
10 NR NR 175 231
to
15 NR NR NR 283
10
--
20 NR NR NR 333 30 NR NR NR NR
-- 1 1 °°°° F lower
Local 99% Winter Design Temperature: --11°°°° For
or
INTERNAL AREA OF CHIMNEY
(SQ IN.)
12 19 28 38
lower*
Not recommended for any vent configuration
* The 99% Winter Design Dry--Bulb (db) temperatures are found in the
1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and 2 (Canada), or use the 99.6% heating db temperaturesfound in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada).
Inspectionsbeforethesaleandatthetimeofinstallationwilldeter­minetheacceptabilityofthechimney or the need for repair and/or (re)lining. Refer to the Chimney Inspection Chart to perform a chimney inspection.
18
If the inspection of a previously used tile--lined chimney:
a. Showssignsof ventgascondensation,thechimneyshould
be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner, Type--B vent, or a listed chimney adapter kittoreducecondensation. Ifacondensatedrainisrequired bylocalcode,refer totheNFGC,Section 10.9foradditional information on condensate drains.
b. Indicates the chimney exceeds the maximum permissible
sizeinthe tables, thechimneyshould berebuiltorrelined to conform to the requirements of the equipment being installed and the authority having jurisdiction.
Achimneywithoutaclaytileliner,which is otherwise in good con­dition,shallberebuilttoconformtoANSI/NFPA211orbelinedwith a UL listed (ULC listed in Canada) metallinerorULlistedType--B vent. Relining with a listed metal liner or Type--B vent is consid­ered to be a vent--in-- a--chase.
If a metal liner or Type--B vent is used to line a chimney,no other appliance shall be vented into the annular space between the chimney and the metal liner.
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, ad­justed, and operated properly, the venting system and/or the ap­pliances should not suffer from condensation and corrosion. The ventingsystemandallappliancesshall beinstalledinaccordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Condi­tioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air--Conditioning Engineers; or other approved engineering methods. Excessive oversizing of the fur­nace could cause the furnace and/or vent to fail prematurely.
Whena metalventormetallinerisused,thevent orlinermustbein goodcondition andbeinstalled inaccordancewiththevent orliner manufacturer’s instructions.
To prevent condensation in the furnace and vent system, the fol­lowing precautions must be observed:
1. Thereturn--airtemperaturemustbe at least60°Fdbexcept forbriefperiodsoftimeduringwarm--up from setback atno lower than 55°F db or during initial start--up from a standby condition.
2. Adjust the gas input rate per the installation instructions. Lowgas inputrate causeslowventgastemperatures,caus­ing condensation and corrosion in the furnace and/orvent­ing system. Derating is permitted only for altitudes above 2000¢.
3. Adjust the air temperature rise to the midpoint of the rise rangeorslightly above. Lowairtemperaturerisecancause low vent gas temperature and potential for condensation problems.
4. Set the thermostat heat anticipator or cycle rate to reduce short cycling.
Air for combustion must not be contaminated by halogen com­poundswhichincludechlorides,fluorides, bromides, andiodides. These compounds are found in many common home products suchas detergent,paint,glue,aerosolspray,bleach,cleaningsol­vent,salt, and air freshener, and can cause corrosion of furnaces and vents. Avoidusing such products in the combustion--air sup­ply. Furnace use during construction of the building could cause thefurnace tobe exposedtohalogencompounds,causingprema­ture failure of the furnace or venting system due to corrosion.
441 01 2611 06
Loading...
+ 39 hidden pages