hussman Reach-in Merchandisers User Manual

®
IIMMPPOORRTTAANNTT
Keep in store for
future reference!
Installation &
Operation Manual
Shipped With Case Data Sheets
Impact Series
October 2007
Reach-in Merchandisers
Medium and Low Temperature Cases
Merchandisers
iii
P/N 0387183_D
Table of Contents
INSTALLATION
NSF Certification . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Shipping Damage . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Exterior Loading . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Merchandisers Shipped With End Installed . . . . 1-2
Shipping Braces . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Remove Front Panel . . . . . . . . . . . . . . . . . . . . . . 1-2
Leveling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Door Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Joining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Installing Splashguard Brackets . . . . . . . . . . . . . 1-4
Installing Bumpers . . . . . . . . . . . . . . . . . . . . . . . . 1-5
REFRIGERATION / ELECTRICAL
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Branch Line Piping . . . . . . . . . . . . . . . . . . . . . . . 2-2
Expansion Valve Adjustment . . . . . . . . . . . . . . . 2-3
Refrigeration Thermostat . . . . . . . . . . . . . . . . . . . 2-3
Defrost Termination Thermostat . . . . . . . . . . . . . 2-5
Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Merchandiser Electrical Data . . . . . . . . . . . . . . . 2-8
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Electrical Connections . . . . . . . . . . . . . . . . . . . . 2-8
Identification of Wiring . . . . . . . . . . . . . . . . . . . 2-8
Wiring Color Code . . . . . . . . . . . . . . . . . . . . . . . 2-8
DRIP PIPING AND SPLASHGUARDS
Waste Outlet and Water Seal . . . . . . . . . . . . . . . . 3-1
Installing Drip Piping . . . . . . . . . . . . . . . . . . . . . 3-1
Installing Splashguards . . . . . . . . . . . . . . . . . . . . 3-2
Sealing Splashguard to Floor . . . . . . . . . . . . . . . 3-3
START UP / OPERATION
Start up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Stocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Load Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Load Limit Profiles . . . . . . . . . . . . . . . . . . . . . . . 4-1
Installing FDA/NSF Required Thermometer . . .4-2
MAINTENANCE
Care and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Cleaning Honeycomb Assemblies . . . . . . . . . . . . 5-2
Cleaning Under Merchandisers . . . . . . . . . . . . . 5-2
Removing Scratches from Bumper . . . . . . . . . . . 5-2
SERVICE
Replacing Fan Motors and Blades . . . . . . . . . . . 6-1
Replacing Electric Defrost Heaters . . . . . . . . . . 6-3
Replacing Drain Pan Heater . . . . . . . . . . . . . . . . 6-5
RLT with Gas Defrost Only: Replacing
Slave Plate Heater . . . . . . . . . . . . . . . . . . . . . . 6-6
Removing RLT Return Air Bracket . . . . . . . . . . 6-7
Replacing Lamp Ballast (other than RLT) . . . . . 6-8
Replacing RLT Lamp Ballast . . . . . . . . . . . . . . . 6-9
Servicing Vertical Lighting . . . . . . . . . . . . . . . 6-10
Servicing Doors and Frames . . . . . . . . . . . . . . 6-10
Replacing Door or Door Frame Parts . . . . . . . 6-10
Replacing Damaged Drain Fitting . . . . . . . . . . . 6-11
Repairing Aluminum Coils . . . . . . . . . . . . . . . 6-12
WARRANTY
IMPORTANT
KEEP IN STORE FOR FUTURE REFERENCE
Quality that sets industry standards!
12999 St. Charles Rock Road • Bridgeton, MO 63044-2483
U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900
www.hussmann.com
© 2007 Hussmann Corporation
®
®
INSTALLATION
TOOL LIST
Unloading From Trailer:
Lever Bar (also know as a Mule,
Johnson Bar, J-bar, Lever Dolly, and pry lever)
Moving Dolly
Setting Case Line-Up:
Level, 4 ft suggested
Ratchet
1
/
4 in. Socket
5
/16 in. Socket
1
/2 in. Socket
Battery Drill/Screw Gun
Caulking Gun
10 in. Adjustable Crescent Wrench
REVISION D — SEPTEMBER 2007
1. Added front panel text and illustration, Page 1-2.
2. Clarified shimming directions, page 1-3.
3. Added RLT information throughout.
4. Added note to remove bumper protective film, Page 1-6.
5. Added information on Always*Clear™ glass, page 5-1.
6. Removed reference to Anthony doors, Page 6-5.
7. Added repairing aluminum coil, Page 6-12.
8. Changed warranty page.
9. Added Installation Tool List, page iv.
10. Added revision history, page iv.
REVISION C — JUNE 2002
1. Added NSF information,pages 1-1,4-2 through 4-4.
2. Sections 2 through 6 are completely rewritten.
3. Changed warranty to March 15,2002.
P/N 0387183_D
iv CONTENTS

NSF CERTIFICATION

These merchandisers are manufactured to meet ANSI / National Sanitation Foundation (NSF®) Standard #7 requirements. Proper installation is required to maintain certification. Near the serial plate, each case carries a label identifying the type of application for which the case was certi­fied.
ANSI/NSF-7 Type I – Display Refrigerator / Freezer
Intended for 75°F / 55%RH Ambient Application
ANSI/NSF-7 Type II – Display Refrigerator / Freezer
Intended for 80°F / 55%RH Ambient Application
ANSI/NSF-7 – Display Refrigerator
Intended for Bulk Produce

LOCATION

These merchandisers are designed for displaying products in air conditioned stores where tempera­ture is maintained at or below the ANSI/NSF-7 specified level and relative humidity is maintained at or below 55%.
Placing refrigerated merchandisers in direct sun­light, near hot tables or near other heat sources could impair their efficiency.
Like other merchandisers, these are sensitive to air disturbances. Air currents passing around mer­chandisers will seriously impair their operation. Do NOT allow air conditioning, electric fans, open doors or windows, etc. to create air currents around the merchandisers.
To prevent sweating on the exterior surfaces of merchandisers, there must be
A MINIMUM
CLEARANCE OF
4 INCHES (102 MM) between the
merchandisers and other fixtures or walls.
Product should always be maintained at proper temperature. This means that from the time the product is received, through storage, preparation and display, the temperature of the product must be controlled to maximize the life of the product.

SHIPPING DAMAGE

All equipment should be thoroughly examined for shipping damage before and during unload­ing.
This equipment has been carefully inspected at our factory. Any claim for loss or damage must be made to the carrier. The carrier will provide any necessary inspection reports and/or claim forms.

Apparent Loss Or Damage

If there is an obvious loss or damage, it must be noted on the freight bill or express receipt and signed by the carrier’s agent; otherwise, carrier may refuse claim. The carrier will supply neces­sary forms.
Concealed Loss Or Damage
When loss or damage is not apparent until after equipment is uncrated, a claim for concealed damage is made. Upon discovering damage, make request in writing to carrier for inspection within 15 days and retain all packing. The carrier will supply inspection report and required claim forms.
Reach-In
P/N 0387183_D 1-1
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.

INSTALLATION

Do not walk or put heavy objects on case.
CAUTION
!

EXTERIOR LOADING

Do NOT walk on top of merchandisers or dam-
age to the merchandisers and serious personal injury could occur. T
HEY ARE NOT STRUCTURALLY
DESIGNED TO SUPPORT EXCESSIVE EXTERNAL
LOADING
such as the weight of a person. Do not
place heavy objects on the merchandiser.

MERCHANDISERS SHIPPED WITH END INSTALLED

If the case was shipped with the end installed, two long bolts were used to hold the shipping brace to the end. If the shipping bolts are reinserted after removing the brace, they will extend into the product area and may damage the coil. T
HEREFORE, BE SURE TO REPLACE
THESE BOLTS WITH THE SHORTER BOLTS
PROVIDED
.
Be careful not to damage the factory-installed end while moving the merchandiser. Make sure that tools are positioned past the end and beneath the merchandiser’s support bar.

SHIPPING BRACES

Move the merchandiser as close as possible to its permanent location and then remove all packag­ing. Check for damage before discarding packag­ing. Remove all separately packed accessories such as kits and shelves.
Locate the shipping block in the center of the heat exchanger (see illustration), and remove it before piping the merchandiser. This block was installed to minimize shipping vibration.
REMOVE FRONT PANEL (D
OES NOT APPLY TO RLT)
Before setting case, remove the front panel as follows: remove screws from front panel tabs, then lift the front panel. Refer to the illustration below. Set panel and screws aside to reinstall once all electrical work is complete.
At completion of all electrical work, installation contractor shall re-install the panels using care to ensure all panels are centered and properly fastened.
1-2 INSTALLATION
P/N 0387183_D WWW
.HUSSMANN.COM
Shipping Block
Heat Exchanger
Top View of Merchandiser
Edge Fits Over Raceway
Tabs Fit in Retainer Slots
Front Panel
Remove Screws

LEVELING

Merchandisers must be installed level to ensure proper operation of the refrigeration system and to ensure proper drainage of defrost water. When leveling merchandisers, use a carpenter’s level as shown.
Metal leveling shims or wedges are provided with each merchandiser for use if needed.
NOTE: B
EGIN LINEUP LEVELING
FROM THE HIGHEST POINT OF THE
STORE FLOOR
.
Place shims under the rail and make sure that they are positioned at a base component (crossbar). This transfers the weight directly from the loaded case through to the floor. Placing shims at other locations will cause uneven distribution of weight leading to piping leaks, as well as sagging or wracked doors.
Reach-In
P/N 0387183_D 1-3
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
5-Door Island Shown
Bottom Front
Support
Skid/External Base
Electrical Wireway
Electrical Wireway
Shim
Here
NO SHIM
HERE
Approximately Centered
Rear of Reach-in
Shim Here
Base Component
Base Component
Shim Here

DOOR ADJUSTMENT

After leveling and joining the merchandisers, adjust and level doors according to manufacturer’s instructions shipped with each product. Factory settings are lost due to vibration during shipment.

JOINING

Sectional construction means that two or more merchandisers may be joined in line yielding one long continuous display requiring only one pair of ends. Joining kits and instructions are
shipped with each merchandiser.
To join like fixtures, a joining kit is required. To join unlike fixtures, or like fixtures operating at different temperatures, a 1
1
/
2 inch (38 mm)
partition kit is required. To join same temperature fixtures on different defrost cycles, a plexiglass partition kit is required.
A
LL JOINTS MUST BE AIR-TIGHT TO PREVENT
FORMATION OF ICE OR CONDENSATION
.
Refer to separate joining instruction shipped with each case

INSTALLING SPLASHGUARD BRACKETS

1. Attach splashguard retainer and splashguard retainer support to splashguard support brack­et using two screws per bracket.
2. I
NSTALL SPLASHGUARD SUPPORT BRACKETS
BEFORE PIPING CASE. The leveling brackets
have a maximum extension of one (1) inch (25 mm) for uneven floors.
DO NOT
PLACE SHIMS UNDER SPLASHGUARD
BRACKETS
.
1-4 INSTALLATION
P/N 0387183_D WWW
.HUSSMANN.COM
Splashguard Retainer Support
Splashguard Support Bracket
Screw
Splashguard Retainer
Bumper Retainer
Screw
Base Rail

INSTALLING BUMPERS

Offsetting the bumpers and top rails helps to disguise the joint locations, giving the lineup a smoother look.
Begin at the left end of the line-up. A starter bumper is factory-installed with end kits. Insert the internal joint trim, then add the full-length bumper.
Align each bumper section with its retainer and push into place, working from the end of the line­up. Install full length bumpers and internal joint trims offset across joints. Make sure that no gaps exist between sections. Continue installing bumpers the length of the line up.
Do NOT install the last bumper sections at this time. These sections will be installed in the last step.
Once all except the last section of bumper have been installed, refrigerate the case line-up for at least six (6) hours. The last sections of bumper should be kept inside a refrigerated case or cooler during this time to allow the bumpers to contract.
Before installing the last full-length section, measure the remaining space. Use a miter box and fine-tooth saw to cut last bumper to length. Install the last section.
Reach-In
P/N 0387183_D 1-5
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Merchandiser Joint
Full Length Bumpers
Starter Bumper
Merchandiser Joint
Internal Joint Trims
Bumper
Miter Box
Remove protective film from bumpers once installation is complete.
Optional end bumpers are factory-installed.
1-6 INSTALLATION
P/N 0387183_D WWW
.HUSSMANN.COM
Reach-In

REFRIGERANT

The correct type of refrigerant will be stamped on each merchandiser’s serial plate which is located on the left-hand end of the interior top liner.

REFRIGERANT PIPING

Connection Location

The refrigerant line connections are at the right­hand end of the merchandiser (as viewed from the front) beneath the display pans.
After connections have been made, seal this out­let thoroughly. Seal both the inside and the out­side. We recommend using an expanding polyurethane foam insulation.

Multiplexing

Piping of merchandisers operating on the same refrigeration system may be run from merchan­diser to merchandiser through the end frame saddles provided for this purpose. D
O NOT
RUN
REFRIGERANT LINES THROUGH MERCHANDISERS
THAT ARE
NOT ON THE SAME REFRIGERATION
SYSTEM
as this may result in poor refrigeration
control and compressor failure.
NOTE: If Gas defrost is used, the liquid line will need to be increased two sizes larger inside the merchandiser area. This is necessary to ensure even liquid drainage from all evaporators during defrost.

Line Sizing

Refrigerant lines should be sized as shown on the refrigeration legend that is furnished for the store or according to ASHRAE guidelines.

Oil Traps

P-traps (oil traps) must be installed at the base of all suction line vertical risers.

Pressure Drop

Pressure drop can rob the system of capacity. To keep the pressure drop to a minimum, keep the refrigerant line run as short as possible using a minimum number of elbows. Where elbows are required,
USE LONG RADIUS ELBOWS ONLY.

INSULATION

With GAS Defrost

The suction and liquid lines should NOT contact each other and should be insulated separately for a minimum of 30 ft (9144 mm) from the merchandiser.

With OTHER Than Gas Defrost

The suction and liquid lines should be clamped or taped together and insulated for a minimum of 30 ft (9144 mm) from the merchandiser.

With All Defrost

Additional insulation for the balance of the liquid and suction lines is recommended wherever condensation drippage is objectionable or the lines are exposed to ambient conditions.
P/N 0387183_D 2-1
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.

REFRIGERATION / ELECTRICAL

When brazing pipes be sure to use the
insulation blanket shipped with the
merchandiser to prevent damage to
the plastic case bottom.
Refrigeration lines are under pressure and should be depressurized before attempting
to make any connections.
!
WARNING
CAUTION
!

BRANCH LINE PIPING

Suction Line – All Defrosts
• Pitch in direction of flow.
• May be reduced by one size at one third of case run load and again after the second third. Do NOT reduce below evaporator connection size.
• Suction returns from evaporators enter at the top of the branch line.
Liquid Line – Off-time and Electric Defrost
• May be reduced by one size after one half the case load run. Do not reduce below evaporator connection size.
• Take-offs to evaporators exit the bottom of the liquid line. Provide an expansion loop for each evaporator take-off (minimum 3 in. (76 mm) diameter).
Liquid Line – Koolgas Defrost
• Maximum of 6 evaporators per Branch System.
• Increase the liquid line size inside the case by two sizes over the branch size.
Branch Size In Case Size
1
/2
7
/8
5
/8 11/8
7
/
8 1
3
/
8
11/81
5
/8
13/8 21/8
• Take-offs to evaporators exit the bottom of the liquid line. Provide an expansion loop for each evaporator take-off (minimum 3 in. (76 mm) diameter).
2-2 REFRIGERATION / ELECTRICAL
P/N 0387183_D WWW
.HUSSMANN.COM
The following information is applicable only
for piping Hussmann merchandisers to
Hussmann refrigeration equipment.
CAUTION
!
Suction Line Return
3-In. Loop (76 mm)
Liquid Line Take Off
Koolgas Defrost Liquid Line Two Sizes Larger in Merchandiser
Electric or Offtime Defrost Liquid Line
From Liquid Manifold
To Suction Manifold
Loading...
+ 28 hidden pages