![](/html/6e/6ec0/6ec05f369e7538d245bf463d3f755307640bb9ff8de6fedc0023bc69b4dfc854/bg2.png)
IGUP-RED-0309
Table of Contents
General Instructions
THIS BOOKLET CONTAINS INFORMATION ON:
General Instructions................................................. 2
Cut & Plan Views....................................................... 3
Installation ................................................................. 4
LEVELING.............................................................................................................. 4
ENDS .................................................................................................................... 4
Plumbing.................................................................... 5
WASTE OUTLET AND P-TRAP .............................................................................. 5
Refrigeration ............................................................. 6
Condenser Ventilation........................................................................................... 6
T-STAT LOCATION.................................................................................................. 7
Electrical .................................................................... 7
WIRING COLOR CODE ......................................................................................... 7
Finishing T ouches ...................................................... 7
START-UP ..............................................................................................................7
Case Specifications ................................................... 8
Condensing Unit Data.............................................. 8
Electrical Schematic................................................. 9
User Information ...................................................... 10
STOCKING.............................................................................................................. 10
CASE CLEANING.................................................................................................... 10
PLEXIGLASS & ACRYLIC CARE.............................................................................. 11
Maintenance .............................................................. 11
ELECTRICAL PRECAUTIONS................................................................................... 11
REPLACING FLUORESCENT LAMPS ....................................................................... 11
TIPS & TROUBLESHOOTING ................................................................................. 11
Appendices ................................................................ 12
APPENDIX A. – Temperature Guidlines.............................................................. 12
APPENDIX B. – Application Recommendations.................................................. 12
APPENDIX C. – Field Recommendations............................................................ 12
APPENDIX D. – Recommendations to user ....................................................... 13
RED A narrow depth multi deck air curtain case designed to
display pre-packaged Deli products. It can be placed at the
end of gondolas or within a gondola by removing a gondola
deck and shelves above from one 4'-0" section.
SHIPPING DAMAGE
All equipment should be thoroughly examined for shipping damage before and during unloading.
This equipment has been carefully inspected at our factory and the carrier has assumed responsibility for safe
arrival. If damaged, either a pparent or concealed, claim must
be made to the carrier.
APPARENT LOSS OR DAMAGE
If there is an obvious loss or damage, it must be noted on
the freight bill or express r eceipt and signed by the carrier’ s
agent; otherwise, carrier may r efuse claim. The car rier will
supply necessary claim forms.
CONCEALED LOSS OR DAMAGE
When loss or damage is not apparent until after equipment
is uncrated, a claim for concealed damage is made. Make
request in writing to carrier for inspection within 15 da ys,
and retain all packaging. The carrier will supply inspection
report and required claim forms.
SHORTAGES
Check your shipment for any possible shortages of material. If a shor tage should exist and is found to be the responsibility of Hussmann Chino, notify Hussmann Chino. If
such a shortage involves the carrier, notify the carrier imme-
diately, and request an inspection. Hussmann Chino will
acknowledge shortages within ten days from receipt of
equipment.
HUSSMANN CHINO PRODUCT CONTROL
The serial number and shipping date of all equipment has
been recorded in Hussmann’s files for warranty and replacement part purposes. All correspondence pertaining
to warranty or parts ordering must include the serial number of each piece of equipment involved, in order to provide the customer with the correct parts.
Keep this booklet with the case at all times for future reference.
/Chino
A publication of
Hussmann® Chino
13770 Ramona A ven ue • Chino, California 91710
(909) 628-8942 FAX
(909) 590-4910
(800) 395-9229
The Hussmann warranty is printed on the back
of this guide.
2
![](/html/6e/6ec0/6ec05f369e7538d245bf463d3f755307640bb9ff8de6fedc0023bc69b4dfc854/bg4.png)
IGUP-RED-0309
Installation
LOCATION
The refrigerated merchandisers have been designed for
use only in air conditioned stores where temperatur e and
humidity are maintained at or below 75°F and 55% relative humidity . DO NO T allow air conditioning, electric fans,
ovens, open doors or windows (etc.) to create air currents around the merchandiser, as this will impair its correct operation.
DO NOT place Self Contained versions
of this case, having the electric evaporator pan, underneath or adjacent to
any flammable structure or structure
housing flammable merchandise!
UNCRA TING THE ST AND
Place the fixture as close to its permanent position as
possible. Remove the top of the crate. Detach the walls
from each other and remove from the skid. Unbolt the
case from the skid. The fixture can now be lifted off the
crate skid. Lift only at base of stand!
EXTERIOR LOADING
These models have not been structurally designed to sup-
port excessive external loading. Do not walk on their
tops; This could cause serious personal injury and damage to the fixture.
SETTING AND JOINING
The sectional construction of these models enable them
to be joined in line to give the effect of one continuous
display. A joint trim kit is supplied with each joint.
Attention Installer!
Proper case joint sealing is extremely
important to prevent water leaks!
It is the contractor’s responsibility to install
case(s) according to local construction and
health codes.
store floor.
B. When wedges are involved in a lineup, set them
first.
All cases were leveled and joined prior to shipment to
insure the closest possible fit when cases are joined in the
field. When joining, use a carpenters level and shim legs
accordingly.
Case must be raised correctly, under legs
where support is best, to prevent damage to case.
1. Check le vel of floor where cases are to be set.
Determine the highest point of the floor; cases will
be set off this point.
2. Set first case, and adjust legs o ver the highest part of
the floor so that case is level. Prevent damage – case
must be raised under leg or by use of 2x6 or 2x4 leg
brace. Remove side and back leg braces after case is
set.
3. Set second case as close as possible to the first case,
and level case to the first using the instructions in
step one.
4. Apply masking ta pe 1/8" in from end of case on
inside and outside rear mullion on both cases to be
joined.
5. Apply liberal bead of case joint sealant (butyl) to
dotted area shown in (Fig.2, #1) of first case. Apply
heavy amount to cov er entire shaded area.
DO NO T USE PERMAGUM!
6. Slide second case up to first case snugly . Then le vel
second case to the first case so the front bumper
and top fascia are ev en.
7. To compress silicone at joint, use two Jurgenson
wood clamps. Mak e sure case is lev el from front to
back and side to side on inside bulkheads at joint.
8. Bolt tops together behind llight, and close camlocks
usiong a 5/16" allen wrench. Camlocks ar e located in
the rear of the case below air discharge and between the front legs.
LEVELING
IMPORTANT! It is imperative that cases be
leveled fr om front to back and side to side prior
to joining. A level case is necessary to insure
proper operation, water drainage, glass alignment, and operation of the hinges supporting
the glass. Le veling the case corr ectly will solve
most hinge operation problems.
NOTE: A. To avoid removing concrete flooring, begin
lineup leveling from the highest point of the
Do not use cam locks to pull cases together.
ENDS
Bolt the end(s) onto the case using the bolts provided in
the pre-drilled holes on the side(s) of the case.
DO NOT SEAL JOINT TRIM TO FLOOR!
4
![](/html/6e/6ec0/6ec05f369e7538d245bf463d3f755307640bb9ff8de6fedc0023bc69b4dfc854/bg5.png)
Plumbing
WASTE OUTLET AND P-TRAP
The waste outlet is located in the center , 8" from the front
of the case.
A 7/8" P-trap and threaded adapter ar e supplied with each
fixture. The P-trap must be installed to pr event air leakage
and insect entrance into the fixture.
NOTE:PVC-DWV solvent cement is recommended.
Follow Hussmann’s instructions.
INSTALLING CONDENSATE DRAIN
Poorly or improperly installed condensate drains can seriously interfere with the operation of this refrigerator,
and result in costly maintenance and pr oduct losses. Please
follow the recommendations listed below when installing
condensate drains to insure a proper installation:
1. Never use pipe for condensate drains smaller than
the nominal diameter of the pipe or P-trap supplied
with the case.
2. When connecting condensate drains, the P-trap
must be used as part of the condensate drain to
prevent air leakage or insect entrance. Store plumbing system floor drains should be at least 14" off the
center of the case to allow use of the P-trap pipe
section. Nev er use two water seals in series in any
one line. Double P-traps in series will cause a lock
and prevent draining.
3. Always pr ovide as much down hill slope (“fall”) as
possible; 1/8" per foot is the pr eferred minimum.
PVC pipe, when used, must be supported to maintain the 1/8" pitch and to prev ent warping.
4. Avoid long runs of condensate drains. Long runs
make it impossible to pro vide the “fall” necessary for
good drainage.
5. Provide a suitable air break betw een the flood rim of
Rev.0309
the floor drain and outlet of condensate drain. 1" is
ideal.
6. Prevent condensate drains fr om freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should be
insulated with a nonabsorbent insulation material
such as Armstrong’s Armaflex.
b. Where condensate drains ar e located in dead air
spaces (between refrigerators or betw een a
refrigerator and a wall), pr ovide means to prev ent
freezing. The water seal should be insulated to
prevent condensation.
RED (SELF CONTAINED)
The waste outlet and P-trap are the same as the remote
except the case condensate drains to a pump assembly
mounted to the top of the case into the top of the water
evap assembly. Hot air from the condenser is forced
through the water evap assembly, evaporating the water.
Any overflow from the water evap assembly is directed
back to the pump assembly. It is critical that the case
be level to keep the water evap assembly from
overflowing!! The metal cover over the top of the con-
densing unit must be in place to force the hot condenser
air through the water evap assembly.
The condensate pump can be accessed through the front
of the closeoff panel.
5