hussman IGUP-AB-0904 User Manual

Manual
Installation
& Operation
/Chino
AB
REV. 0904
UPRIGHT MEAT DISPLAY CASE
AB
P/N IGUP-AB-0904
INSTALLATION & OPERATION GUIDE
Ta b l e of Contents
IGUP-AB-0904
General Instructions
THIS BOOKLET CONTAINS INFORMATION ON:
General Instructions ................................................. 2
Important Information ............................................. 3
Cut & Plan Views ....................................................... 4
NSF Installation Requirement ................................. 5
Installation ................................................................. 6
Plumbing .................................................................... 6
WASTE OUTLET AND P-TRAP .............................................................................. 6
Fractal Humidity System ......................................... 7
CONTROLLER SETTINGS ........................................................................................ 9
MODELS “SCH & SCHMS” - EMITTER NOZZLE CLEANING INSTRUCTiONS ........... 10
TROUBLE SHOOTING GUIDE ................................................................................ 11
MAJOR SYSTEM COMPONENTS .............................................................................. 11
Refrigeration ............................................................. 12
T-STAT LOCATION.................................................................................................. 12
Electrical .................................................................... 13
WIRING COLOR CODE ......................................................................................... 13
ASHRAE COLOR CODE .......................................................................................... 13
User Information ...................................................... 14
NON-GLARE GLASS ............................................................................................... 14
Maintenance .............................................................. 16
ELECTRICAL PRECAUTIONS ................................................................................... 16
REPLACING FLUORESCENT LAMPS ....................................................................... 16
Electrical and Refrigeration Specifications ............ 16
TIPS & TROUBLESHOOTING ................................................................................. 16
Electrical Schematics ............................................... 17
Appendices ................................................................ 22
Appendix A. – Temperature Guidelines Refrigerated ........................................ 22
Appendix B. – Application Recommendations Refrigerated .............................. 22
Appendix C. – Field Recommendations - Refrigerated ................................... 22
Appendix D. – Recommendations To User - Refrigerated ................................ 23
AB Upright Refrigerated Meat Display Case
SHIPPING DAMAGE
All equipment should be thoroughly examined for ship­ping damage before and during unloading. This equipment has been carefully inspected at our fac­tory and the carrier has assumed responsibility for safe arrival. If damaged, either apparent or concealed, claim must be made to the carrier.
APPARENT LOSS OR DAMAGE
If there is an obvious loss or damage, it must be noted on the freight bill or express receipt and signed by the carrier’s agent; otherwise, carrier may refuse claim. The carrier will supply necessary claim forms.
CONCEALED LOSS OR DAMAGE
When loss or damage is not apparent until after equipment is uncrated, a claim for concealed damage is made. Make
request in writing to carrier for inspection within 15 days, and retain all packaging. The carrier will supply inspection report and required claim forms.
SHORTAGES
Check your shipment for any possible shortages of mate­rial. If a shortage should exist and is found to be the re­sponsibility of Hussmann Chino, notify Hussmann Chino. If such a shortage involves the carrier, notify the carrier imme- diately, and request an inspection. Hussmann Chino will acknowledge shortages within ten days from receipt of equipment.
HUSSMANN CHINO PRODUCT CONTROL
The serial number and shipping date of all equipment has been recorded in Hussmann’s files for warranty and re­placement part purposes. All correspondence pertaining to warranty or parts ordering must include the serial num­ber of each piece of equipment involved, in order to pro­vide the customer with the correct parts.
Keep this booklet with the case at all times for future reference.
/Chino
A publication of Hussmann® Chino 13770 Ramona Avenue • Chino, California 91710 (909) 628-8942 FAX (909) 590-4910 (800) 395-9229
The Hussmann warranty is printed on the back
of this guide.
This equipment is to be installed to comply with the applicable NEC, Federal, State, and Local Plumbing and Construction Code having jurisdiction.
2
Rev. 0904
Important Information
The AB Meat merchandisers are easy to work, attractive merchandising display cases capable of maintaining superb product quality, with the installation of the proper controlling devices. These should be set according to the manufacturer’s specifications and combined with a properly maintained humidity system. Incorrect settings and failure to maintain the humidity system will result in short product life from dehydration, shrinkage and discoloration. Below are a few guidelines to ensure optimum performance and product life.
•Review the Case Specification in this book to verify thermostat setting. Do not set temperature too cold, as this causes product dehydration.
•Temperatures should be achieved by a t-stat and suction solenoid at each case. Do not use EPR valves, liquid line solenoids or electronic control devices of any kind. These controls allow temperature
swings causing product dehydration and excessive energy consumption.
Defrost cycles should be set according to the Case Specifications in this book
•Clean humidity system a minimum of every 90 days
for proper system operation.
•Work and rotate product – not to exceed a four (4) hour period.
•At night turn off case lights and cover product with
moistened cheesecloth or fabric towels.
•Keep meat holding box at 32°.
•Keep meat prep room refrigerated at 55°.
Meat bloom box (if applicable) should be at 36°.
Meat must enter the case at 40° or below. Product
deterioration is very rapid above 40
°.
Maintain sanitary conditions throughout the meat holding, prep and working areas.
Do not display product directly within the air discharge.
Turn and rotate the meat. The blood which
gives the pink color works down in time which causes surface discoloration and dehydration. When turned before this condition occurs the other side is kept in good color (bloom) condition. The meat can even be turned (3) three and (4) four times.
It is not required at night to remove the product from the case. Turn the lights off at night and cover the product. We recommend you use a moistened cheesecloth or towels. This helps slow down the product dehydration process by taking the moisture from the cloth and not from the product. This is an old method that meat shops have used for many years. It works and helps to gain extended product life.
Cold coils remove heat and moisture from the case and deposit it as frost on the coil. Thus a defrost is required to remove this frost. Our humidity system adds moisture to the case and helps slow down the dehydration process. The only other moisture in the case is in the product. A single level of meat in a case will dry out much faster than a fully loaded case with three to four levels of meat.
The colder the case, the faster the product loses its moisture and shelf life. It is very important to maintain a constant even product temperature (see Case Specifications).
3
WIRE RACK
IGUP-AB-0904
Cut & Plan Views
28 1/8"
1.2” Komacel walls
49"
85 5/16"
ELECTRICAL
WATER SUPPLY TO HAND VALVE
BALLAST & TERMINAL BLOCKS
BALLAST
6”
28"
60" (72")
HUMIDITY SYSTEM
BALLAST LOCATION
T5 LAMP
HUMIDITY SYSTEM
DRAIN
28 1/8"
SLIDING DBL-PANE
GLASS DOOR
44.5" X 54" (44.5" X 66")
4
Rev. 0904
NSF Installation Requirement
PER NSF INSTALLATION REQUIREMENT SEAL AROUND CASE TO BASE PERIMETER WITH NSF APPROVED SEALANT
5
Installation
LOCATION
The refrigerated merchandisers have been designed for use only in air conditioned stores where temperature and
humidity are maintained at or below 75°F and 55% rela-
tive humidity. DO NOT allow air conditioning, electric fans, ovens, open doors or windows (etc.) to create air cur­rents around the merchandiser, as this will impair its cor­rect operation. Product temperature should always be maintained at a constant and proper temperature. This means that from the time the product is received, through storage, prepa­ration and display, the temperature of the product must be controlled to maximize life of the product.
Plumbing
IGUP-AB-0904
UNCRATING THE STAND
Place the fixture as close to its permanent position as possible. Remove the top of the crate. Detach the walls from each other and remove from the skid. Unbolt the case from the skid. The fixture can now be lifted off the crate skid. Lift only at base of stand!
EXTERIOR LOADING
These models have not been structurally designed to sup- port excessive external loading. Do not walk on their tops; This could cause serious personal injury and dam­age to the fixture.
DO NOT SEAL JOINT T RIM T O FLOOR!
WASTE OUTLET AND P-TRAP
The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture. A P-trap must be installed to prevent air leakage and in­sect entrance into the fixture. (P-traps are not supplied with these cases.)
NOTE: PVC-DWV solvent cement is recommended.
Follow the manufacturer’s instructions.
INSTALLING CONDENSATE DRAIN
Poorly or improperly installed condensate drains can se­riously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:
1. Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-trap supplied with the case.
2. When connecting condensate drains, the P-trap must be used as part of the condensate drain to prevent air leakage or insect entrance. Store plumb­ing system floor drains should be at least 14" off the center of the case to allow use of the P-trap pipe section. Never use two water seals in series in any
one line. Double P-traps in series will cause a lock and prevent draining.
3. Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to main­tain the 1/8" pitch and to prevent warping.
4. Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.
5. Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.
6. Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.
b. Where condensate drains are located in dead air
spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing. The water seal should be insulated to prevent condensation.
6
Rev. 0904
Fractal Humidity System
GENERAL INFORMATION
The Service Case Humidification system is an automatic moisture maintenance system designed to raise humidity levels in any new or existing service case counter or refrigerated floral display. It delivers a damp fog into the service case or floral display at selected intervals by using a combination of air and water. The system consists of a humidification nozzle assembly, water filtration/regulator unit, remote timer, and air compressor unit (see attached diagram).
PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION
1. Installation of Regulator Assembly and water hookup
Procedure ­a. Tie into the water supply line under or near the
service case or floral display by using either a compression or sweat “Tee” fitting with a 1/2" FPT. (In cases of new store construction, the appropriate 1/2" FPT fitting may already be stubbed up under the case).
b. Screw the provided 1/4" x 1/2" MPT gray plastic
push-in filing into the 1/2" FPT water fitting.
c. To connect tubing for water, push one end of the
1/4" black poly tubing into the plastic push-in fitting at the Tee”. Measure and cut tubing to length and insert the opposite end of tubing into the 1/4" push-in fitting on the Regulator Assembly marked “CITY WATER”.
d. Connect another length of black poly tubing to
the push-in fitting (or plastic push-in “Tee” for SCH-2) labeled ‘WATER” on the Regulator Assembly. Measure and cut this piece of tubing to length and connect the opposite end to the push-in elbow fitting on the back of the nozzle assembly. It may be necessary to drill access holes through the bottom of the case for the tubing lines - if so, ensure these holes are sealed with silicon or similar substance.
TECHNICAL PROCEDURES ARE NOW COMPLETE
2. Start-up, Testing and Adjustment Procedures a. Turn water on. Pressure gauge on Regulator
Assemblies should read approximately 1-4 psi.
b. Set Timer at each station for a 60 second “On
Time” and I minute “Off Time” cycle. (SEE ATTACHED CONTROLLER SETTING INSTRUCTIONS!) This setting, is for testing, on] and will allow enough time for the water to 1111 the line and reach the nozzle.
c. Plug in the Controller to the 115V outlet.
Compressor and solenoid valves will activate and plumes from nozzles will independently appear shortly thereafter.
d. If humidity plume is too light or too heavy. Adjust
the Regulator accordingly. Adjust water pressure by lifting up the yellow locking cap on the top of the Regulator and turn clockwise (to increase pressure) or counter- clockwise (to decrease pressure). Make Regulator adjustments ONLY when system is running. Push down on cap to relock the regulator on the desired pressure.
e. A desired setting would be a pressure that
provides a solid constant plume from the nozzle(s), but shuts off cleanly when the cycle ends. If the nozzle(s) continue to emit a stream of water or drip at shut-off, the pressure should be decreased.
f. On completion of testing/adjustment, reset
Controller to recommended “On/Off ’ settings as per Owner’s Guide which is included in the packing carton.
g. Carry out training on tip cleaning and Timer
settings with department manager and/or staff.
3.
Warranty Conditions -
The SCH system carries a 1 year limited Parts Only warranty. Fractal Inc. will replace component parts that are found to be defective through normal operation or workmanship during manufacture.
b. Performance problems that are directly related
to poor water quality are not the responsibility of the manufacturer.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR EQUIPMENT PERFORMANCE PROBLEMS (DURING OR AFTER INSTALLATION). IF INSTALLATION, ADJUSTMENT, AND TRAINING IS NOT CARRIED OUT IN ACCORDANCE WITH THESE INSTRUCTIONS. INSTALLING CONTRACTORS SHOULD BE AWARE THAT 24 HOUR SERVICE ASSISTANCE IS AVAILABLE BY CALLING THE ABOVE TELEPHONE NUMBERS.
7
IGUP-AB-0904
8
Rev. 0904
Recommended operation times: You should adjust your humidification time for your stores needs~ This is because each service case and floral display differs in temperature, humidity, case style and volume. See chart below for sample timings,
APPLICATION OFF TIME ON TIME
Seafood 5 min 30 sec
Meat 5 min 30 sec.
Deli 10 min. 30 sec.
Floral 10 min. 60 sec
Humidification nozzle assembly:
The humidification nozzle assembly is typically located at one end of the service case aimed towards the opposite end. The humidification nozzle is specially designed to precisely mix air and water providing the desired humidity level.
System maintenance and cleaning: (See also attached Cleaning Instructions) It is recommended
that you clean the humidification nozzle (tip) periodically, especially in areas with water that contain a high content of solids. Unscrew the hex nut and remove the air and fluid caps from the main nozzle body, Soak the caps in a hot water and Efferdent@ solution for approximately 20 minutes, rinse and replace.
Remote timer operation; (See also cdtached Timer Setting Instructions) The remote timer has two dials
used for setting times. The dial labeled “T ON” represents the amount of time the operating cycle is to remain on. Each number equals one minute, The dial labeled “T OFF” represents the delay between operating cycles. Each number equals one minute. Example: If you want two minutes of mist every ten minutes, set the dial labeled “T ON” at 2 and set the dial labeled “T OFF” of 10. Tr oubleshooting:
See attached drawings and helpful tips, however should any further assistance be required, please call Fractal Inc, Service Dept. at 1-800-338 6478.
CONTROLLER SETTINGS
FOR SERVICE CASE HUMIDIFICATION SYSTEM
MODELS SCH1/SCH2 - SINGLE STATION
The SCH controller should be installed using the suggested factory settings for the mist “OnTime” and “Off Time” as outlined in the Owner’s Guide. However, it is up to the department manager’s discretion to adjust these settings to best suit each application. The left column of switches controls “Off Time” in minutes and the right column of switches controls “On Time” time in seconds.
2. To adjust mist “OFF TIME”: Set the desired interval of Mist by sliding the appropriate numbered switch to the right, or “On” position.
NOTES:
1. To delete previous settings, slide switches back to the left or “Off” position.
2. Numbers can be combined for total time “On” or “Off” by sliding more than one switch to the “On” position. Power light should be illuminated at all times when power is connected.
4. “On Cycle” light will illuminate only during Misting cycle.
5. For manual operation or for testing, slide switch marked “Test” to the “On” position and slide all other switches to the “Off” position.
OFF TIME
IN MINUTES
TEST
ON TIME
IN MINUTES
1 2 4
1 3 5 10 21 48 85
OFF ON
POWER
WARNING: Controller must be properly
grounded to ensure proper operation. Electrical power must be disconnected prior to hook-up or service. Follow all applicable local electrical codes.
FOR SERVICE:
Call your local Authorized Service Agency or contact:
FRACTAL INC. 9375 SW Commerce Circle #9 Wilsonville, OR 97070 (503) 682-9515 (800) 338-MIST (6478)
OFF ON
POWER
8 16 32 64 128 256 512
1. To adjust mist “ON TIME”: Set the desired length of Mist by sliding the appropriate numbered switch to the right, or “On” position.
9
Loading...
+ 18 hidden pages