hussman IGSV-ASCS-0303 User Manual

Manual
Installation
& Operation
/Chino
ASCS
REV.0303
DELI, MEAT, FISH SERVICE CASE
ASCS
SERVICE CASE
P/N IGSV-ASCS-0303
INSTALLATION & OPERATION GUIDE
Ta b l e of Contents
IGSV-ASCS-0303

General Instructions

THIS BOOKLET CONTAINS INFORMATION ON:
General Instructions ................................................. 2
Cut & Plan Views ....................................................... 3
Installation ................................................................. 3
LEVELING.............................................................................................................. 4
Plumbing .................................................................... 6
WASTE OUTLET AND P-TRAP .............................................................................. 6
Manifold Flush System ............................................. 7
Humidity System ...................................................... 9
Refrigeration ............................................................. 10
T-STAT LOCATION.................................................................................................. 11
Electrical .................................................................... 12
WIRING COLOR CODE ......................................................................................... 12
ASHRAE COLOR CODE .......................................................................................... 12
Finishing Touches ...................................................... 13
JOINT TRIM........................................................................................................... 13
User Information ...................................................... 14
STOCKING.............................................................................................................. 14
CASE CLEANING.................................................................................................... 14
NON-GLARE GLASS ............................................................................................... 15
PLEXIGLASS and ACRYLIC CARE........................................................................... 15
REPLACING FLUORESCENT LAMPS ....................................................................... 16
Maintenance .............................................................. 16
TIPS and TROUBLESHOOTING .............................................................................. 16
LIFT UP GLASS ..................................................................................................... 17
Electrical and Refrigeration Specifications ............ 19
Electrical Schematics ............................................... 20
Appendices ................................................................ 35
APPENDIX A. – Temperature Guidelines ............................................................ 35
APPENDIX B. – Application Recommendations.................................................. 35
APPENDIX C. – Field Recommendations - ......................................................... 35
APPENDIX D. – Recommendations to user - .................................................... 36
ASCS refrigerated, service deli, meat, fish mechandiser
SHIPPING DAMAGE
All equipment should be thoroughly examined for shipping damage before and during unloading. This equipment has been carefully inspected at our factory and the carrier has assumed responsibility for safe arrival. If damaged, either apparent or concealed, claim must be made to the carrier.
APPARENT LOSS OR DAMAGE
If there is an obvious loss or damage, it must be noted on the freight bill or express receipt and signed by the carrier’s agent; otherwise, carrier may refuse claim. The carrier will supply necessary claim forms.
CONCEALED LOSS OR DAMAGE
When loss or damage is not apparent until after equipment is uncrated, a claim for concealed damage is made. Make
request in writing to carrier for inspection within 15 days, and retain all packaging. The carrier will supply inspection report and required claim forms.
SHORTAGES
Check your shipment for any possible shortages of material. If a shortage should exist and is found to be the responsibility of Hussmann Chino, notify Hussmann Chino. If such a shortage involves the carrier, notify the carrier immediately, and request an inspection. Hussmann Chino will acknowledge shortages within ten days from receipt of equipment.
HUSSMANN CHINO PRODUCT CONTROL
The serial number and shipping date of all equipment has been recorded in Hussmann’s files for warranty and replacement part purposes. All correspondence pertaining to warranty or parts ordering must include the serial number of each piece of equipment involved, in order to provide the customer with the correct parts.
Keep this booklet with the case at all times for future reference.
/Chino
A publication of Hussmann® Chino 13770 Ramona Avenue • Chino, California 91710 (909) 628-8942 FAX (909) 590-4910 (800) 395-9229
The Hussmann warranty is printed on the back
of this guide.
2
Rev.0303

Cut & Plan Views

1
6
/4"
3
8
/4"
" 1
3
0
3
/4"
"
8
"
/
1
3 2
0 2
1
1
/2"
1
Single Deck Refrigerated Service
1
9
2
/2"
5
4
"
ASCS
Scale = 1/2"
1
"
8
/
5
"
5
4
4
3
4
"
11"
1"
8"
MECHANICAL
STUB UP AREA
19" X 19"
DRAIN
CASE FRONT
(VARIABLE LENGTHS)
ASCS
Plan View
Scale = 1/4"
8'-2"
WATER, ELEC.
& REFRIG.
MECHANICAL
STUB UP AREA
19" X 19"
45"
1"
ASC with 22 1/2º Wedge
ASC with 22 1/2º Wedge

Installation

LOCATION
The refrigerated merchandisers have been designed for use only in air conditioned stores where temperature and humidity are maintained at or below 75°F and 55% relative humidity. DO NOT allow air conditioning, electric fans, ovens, open doors or windows (etc.) to create air currents around the merchandiser, as this will impair its correct operation. Product temperature should always be maintained at a constant and proper temperature. This means that from the time the product is received, through storage, preparation and display, the temperature of the product must be controlled to maximize life of the product.
UNCRATING THE STAND
Place the fixture as close to its permanent position as possible. Keep in place, attached case until ready to set/
bolt to adjoining case.
TIGHTEN GLASS SCREWS
Tighten screws along clamshell located on the underside of glass before placing unit into operation.
EXTERIOR LOADING
These models have not been structurally designed to support excessive external loading. Do not walk on their tops. This could cause serious personal injury and damage to the fixture.
SETTING AND JOINING
The sectional construction of these models enable them to be joined in line to give the effect of one continuous display. A joint trim kit is supplied with each joint.
3
Installation (continued)
IGSV-ASCS-0303

LEVELING

Important! It is imperative that cases be leveled from front to back and side to side prior to joining. A level case is necessary to insure proper operation, water drainage, glass alignment, and operation of the hinges supporting the glass. Leveling the case correctly will solve all hinge operation and glass alignment problems.
NOTE: A. To avoid removing concrete flooring, begin lineup
leveling from the highest point of the store floor.
B. When wedges are involved in a lineup, set them first.
All cases were leveled and joined prior to shipment to insure the closest possible fit when cases are joined in the field. When joining, use a carpenters level and adjust legs accordingly. The legs on the ASCS are adjustable and do not require shims. Simply screw the leg up or down to adjust height.
1. Using case blueprints, measure off and mark on the floor the exact dimensions of where the cases will sit. Snap chalk line for front and back positions of base rail or pedestal. Mark the location of each joint front and back. Find the highest point throughout the lineup. FLOORS ARE NORMALLY NOT LEVEL! Determine the highest point of the floor; cases will be set off this point. All cases in the entire lineup must be brought up to the highest level of the case sitting at the highest point in the lineup. This may be done a few different ways. 1) Walk the floor looking for any mounds or dips.
2) Use a string level. 3) Use a transit. If a wedge is used in the middle of a lineup, the wedge must be set on the highest point on the floor FIRST, with the rest if the lineup being leveled from it. The ASCS case has
adjustable legs to allow for leveling.
NOTE: The mock pedestal option supplies panels that
clamp on to adjustable legs.
2. Set first case over the highest part of the floor and adjust legs so that case is level. Remove side and back leg braces after case is set and joined.
3. Set second case within one foot (1’) of the first case, and remove end shipping support. Keep the supports along the length of the case and far end of case. Level case to the first using the instructions in step one.
4. Apply masking tape 1/8" in from end of case on inside and outside rear mullion on both cases to be joined.
5. Apply liberal bead of case joint sealant (butyl) to first case. Sealant area is shown using a dotted line in illustration in Step 8. Apply heavy amount to cover entire shaded area.
DO NOT USE PERMAGUM
Butyl
ASCS
Butyl Locations
Butyl
4
Rev.0303
Installation (continued)
It is the contractor's responsibility to install
case(s) according to local construction and
health codes.
6. Slide second case up to first case snugly. Then level second case to the first case so glass front, bumper and top are flush.
Do not use bolts to pull cases together!
7. To compress butyl at joint, use two Jurgenson wood clamps. Make sure case is level from front to back and side to side on inside bulkheads at joint.
8. Attach sections together via the bolts pictured in the illustration below.
1/4” Binding Post
5/16” Bolts
ASCS
Bolt Locations
9. Apply bead of butyl to top of bulkheads and slip on stainless steel bulkhead cap. Also apply silicone to seam between overhead light tubes.
10. Use finger to smooth silicone as thin as possible at masking tape on inside and outside of rear mullion
(apply additional silicone if necessary). Remove tape applied on line #4.
11. Remove front, back and end shipping braces.
INSIDE REFRIGERATED WEDGES
Line up taper pins with holes on adjoining case. Turn camlock to lock in. Two camlocks are located at the rear of the case behind the air discharge and behind the lower electrical raceway access panel. Bolt the wedge into the adjoining case in the front. If the adjoining case is refrigerated, the bolt is located under the pans in the front. When the adjoining case is a hot case, the cases are bolted together by mans of a bracket located behind the front panel. Remove the front panel by lifting it up and out..
COMMON END BETWEEN UNLIKE CASES AND HOT CASES
Bolt the end onto the case using the bolts provided in predrilled holes behind the front of the panel through the bracket provided and in the rear behind the rear access panel on the bottom Common ends between refrigerated cases are also bolted together behind the air discharge panel. Remove the discharge panel by lifting up and out. Hot cases are only bolted in two places, in the rear of the case, behind the access panel, and in the front of the case behind the front panel.
OUTSIDE REFRIGERATED WEDGE:
Ta per pin and camlock locations are the same as a standard case.
INSIDE DRY WEDGES
Bolt the wedge into the sides of the adjoining case. Use the bolts provided
INSIDE PEDESTAL WEDGES
Set the wedge on adjoining case’s mounting brackets located at the base of the unit, and bolt down. Drive screws provided through the sides of the wedge (4 screws per side), accessible through the back of the wedge.
1. Secure the joint backer located behind the cart bumper support at the joints. To adjust the front panel. Loosen the screws holding the bumper on the case on either side the joint, and slide the extrusion to the center of the joint.
2. Starting from a center case in a lineup or wedge, align the front panels. Front panels can be loosened and adjusted laterally by loosing the screws holding the case bumper channel.
5
ARM STRUT
GUSSET
IGSV-ASCS-0303
Installation (cont.)
Corner wedges are attached via front and rear camlocks. Use a 7mm Allen wrench to turn the locks. Do not overtighten! Join the top by using a joint bracket (included in joint kit) with 3/8" bolts.
WEDGE BRACKET

Plumbing

WASTE OUTLET AND P-TRAP

The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture. A 1-1/2" P-trap and threaded adapter are supplied with each fixture. The P-trap must be installed to prevent air leakage and insect entrance into the fixture.
NOTE: PVC-DWV solvent cement is recommended.
Follow the Hussmann’s instructions.
INSTALLING CONDENSATE DRAIN
Poorly or improperly installed condensate drains can seriously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:
1. Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-trap supplied with the case.
2. When connecting condensate drains, the P-trap must be used as part of the condensate drain to prevent air leakage or insect entrance. Store plumbing system floor drains should be at least 14" off the center of the case to allow use of the P-trap pipe section. Never use
two water seals in series in any one line. Double P­traps in series will cause a lock and prevent draining.
3. Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to maintain the 1/8" pitch and to prevent warping.
4. Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.
5. Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.
6. Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.
b. Where condensate drains are located in dead air
spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing. The water seal should be insulated to prevent condensation.
6
Rev.0303

Manifold Flush System

GENERAL DESCRIPTION
The flush system generates a high pressure water stream meant to flush most residue buildup from the bottom of the manifold chamber. This is the area that residue builds and expands. Frequency of this periodic maintenance will vary depending on water mineral content and sanitary conditions.
MANUAL FLUSH SYSTEM
Water valve is located on the outside of the case, in the rear, on the left hand side as viewed from the rear.
AUTOMATIC FLUSH SYSTEM
Electrical components are located within the electrical raceway. Electrical components in this area are 115V AC. Step-down transformer is located in the wireway, and is controlled by pump switch. Water flow for flush system is rated at 0.25 GPM at 60 PSI water pressure. Flush nozzle located in the rear of the case.
BASIC SYSTEM OPERATION:
1. Filtered water is supplied to the 115V solenoid valve.
2. At a time of day determined by you, the 115V time clock will energize the solenoid for two (2) minutes.
PROGRAMMING THE TIMER
The circular keypads are positioned to provide a sequential [at for programming. Starting the Prog. button to select a program clockwise to ON/OFF, h for hour, m for minute, and finally Day to select the day for days of the week you wish the flush to operate on. If one of these selections is omitted, the control will flash when the clock or program key is depressed. The missing entry must be completed before the programming can resume.
•A program consists of
1. ON/OFF
2. Hour and minute
3. Day or multiple days on which it is to occur.
Res. is the reset key and will erase the current program.
The ±h key adjusts the set clock time for daylight savings time.
•Military time (24 hr clock) or 12 hour clock may be selected by pressing and holding the h key while depressing the ±h key.
•A flashing light indicated a missing selection in the program or a low battery. Check to make sure the timeclock’s program is complete (ON/OFF, time, and days)
NOTE: If the h and m keys are held down longer than 2 seconds, the numbers will advance rapidly. Press and hold the (2) day during the following: (If Daylight Savings Time is In effect, press ±1h first).
1. Press the Prog. key.
1 2 4 5 6 7 AM– –:– –
will appear in display.
2. Press the key between ON/OFF. The word ON will
appear.
3. Press h to select hour for initial system startup.
4. Press m to select the minute the system starts up (30
for 10:30)
5. Select the days desired with the Day key.
1. If the program is to occur every day of the week,
ignore Day and press Prog. key to advance to next program.
2. If specific, 7 day time control is desired, press Day and 1-5 will appear for Mon. - Fri. Pressing Day again will display 6,7 for Sat. and Sun.
6. Press the key between ON/OFF to select the cycle
termination time. The word OFF will appear.
7. Press h to select hour the system terminates.
8. Press m to select the minute the system terminates.
9. Repeat with the days.
10. Press Prog. key and repeat steps 2 thru 11 for
additional defrost schedules.
11. After programming press clock key to enter run mode.
NOTE: If the days are flashing, it indicates the day of the week was not set when setting the time. The timer cannot be programmed unless the day of the week is entered.
±
1
Off
h
r
.
Sa
Su
Fr
h
m
. g o
r P
Ref.
On
Mo Tu We
GRÄSSLIN
Th
Day
START UP:
1. Manually move time clock to initiate a flush cycle.
2. Observe that flush nozzle is spraying down center of manifold chamber.
3. Set clock to correct time of day.
4. Set trip pins to the “time of day system is to flush” (NOTE: Two [2] flushes per day!)
7
These two components are now assembly
NOZZLE - MONARCH Model #: H-545-R2-0.72-360 303SS
# 225-01-2004-SS
NIPPLE (1/2) 3" LONG 304 SS PIPE # 225-01-0602
USE WASHERS (IF REQUIRED)
ELBOW 90° 1/4" NPT x 1/4" NPT # 225-01-0336
WASHER # 038222
PERMAGUM SEAL
COMPRESSION FITTING PVC - 1/4" NPT x 1/2" OD # 225-01-1323
part # 225-01-0603
(HOCKEY-POCK SPACER)
POLYURETHANE COAT
INSULATION @ CENTER OF CASE
(FRONT TO BACK)
CASE BOTTOM LINER (16 GA. GALV)
1/2" OD POLY TUBING # 225-01-0003
Nozzle and Components with Part Numbers
1/2" OD POLY TUBING # 225-01-0003 LEAVE AT LEAST 10' FOR FIELD CONNECTION
WASHER / PIPE ASSEMBLY 304 STAINLESS # 225-01-0603
NOZZLE - MONARCH Model #: H-545-R2-0.72-360 303SS # 225-01-2004-SS
ELBOW 90°- BRASS 1/4" NPT x 1/4" NPT # 225-01-0336
COMPRESSION FITTING PVC - 1/2" OD x 1/2" NPT # 225-01-1322
SOLENOID VALVE ALCO 222CB- B- B-AMS # 225-01-1340
COMPRESSION FITTING PVC - 1/2" OD x 1/2" FPT # 225-01-1327
(FIELD CONNECTION)
HAND BALL VALVE PVC - 1/2" FPT - FULL BORE - # 225-01-2122
IGSV-ASCS-0303
Nozzle count to change
according to case length.
COMPRESSION FITTING PVC - 1/4" NPT x 1/2" OD # 225-01-1323
Water Flush Fittings with Part Numbers
#5-32 SELF TAP SCREW
COMPRESSION FITTING PVC - 1/2" OD x 1/2" NPT # 225-01-1322
SOLENOID VALVE BODY ALCO 222CB- B­# 225-01-1340
#5-32 SELF TAP SCREW
UNION TEE COMPRESSION PVC - 1/2" OD x 1/2" OD # 225-01-1324
BRACKET # 038244
COMPRESSION FITTING PVC - 1/2" OD x 1/2" NPT # 225-01-1322
BRACKET # 038244
#5-32 SELF TAP SCREW
#5-32 SELF TAP SCREW
WATER PRESSURE REGULATOR SPRAY SYSTEMS CO. 6815-1/2 # 225-01-1403
IN-LINE STRAINER - CLEAR BOWL - NYLON 1/2" MPT TEEL 2P131 # 225-01-2133
SOLENOID COIL ALCO- AMS
COMPRESSION FITTING PVC - 1/2" OD x 1/2" NPT # 225-01-1322
Solenoid Valve and Part Numbers
8
Rev.0303

Humidity System

GENERAL DESCRIPTION
One contributor to the spoilage of fresh meats is dehydration, which causes loss in weight and volume (shrinkage) and product discoloration. As the refrigeration system removes heat from the case, it also removes critical moisture from the air, and any unwrapped products in the case. The Humidity System replaces the moisture in the air, in order to compensate for the moisture taken by the refrigeration system, and disposed of down the drain line. The system is built into the discharge plenum, and mixes moisture laden air with refrigerated air before the air is passed through - and around the product. The system is constructed almost entirely of PVC pipe, and uses air that is subcooled to approximately the same temperature as the case. The sub-cooling of air inhibits the formation of growth found to be a problem in other humidification systems. Maintenance is almost unnecessary if you follow a few simple rules:
1. Keep the case clean.
2.Keep the water filter clean, and change it every six to twelve months or sooner, depending on the kind of water found in your area.
3. Flush the header every six (6) months, by loosening the connecting “L”, then removing it from the case, and flushing with a hose.
**IMPORTANT INFORMATION** The ASCS is capable of maintaining superb product quality with the installation of the proper controlling devices. These devices should be set according to the Hussmann’s specifications. The humidity system should be properly maintained. Incorrect settings and failure to maintain the humidity system will result in short product life. Below are a few guidelines for optimum performance and product life:
Set thermostat to cut in at the discharge temperature designated in the case specifications section of the appropriate installation guide or spec. sheet. Maintain the recommended product temperature for Deli, Meat, and Fish. DO NOT set temperature too cold, as this causes product dehydration.
•Temperatures should be achieved by means of a T-Stat and Suction Solenoid at each case. DO NOT use EPR valves, Liquid Line Solenoids, or electronic control devices of any kind. These controls allow temperature swings that cause dehydration and excessive energy consumption.
Set defrost cycles as listed in the Case Specifications Data for your particular case. The number of defrosts per day should never change. The duration of the
defrost cycle may be adjusted to meet conditions present at your location.
•Clean humidity system a minimum of every 90 days for proper system operation.
•Work and rotate product - not to exceed a four (4) hour period.
•At night, turn off case lights, and cover unwrapped product with moistened cheesecloth or fabric towels.
•Keep meat holding box at 32°F.
•Keep meat prep room refrigerated at 55°F.
Meat Bloom Box (if applicable) should be at 36°F.
Meat must enter the case at 40°F or below. Product deteriorates rapidly above 40°F.
•Clean, sanitary conditions are required throughout the meat holding, prep, and work areas.
Do not display product directly within the air discharge
•Turn and rotate meat. The blood works down through the meat over time, which causes the top surface to discolor and dehydrate. Turn meat 3-4 times per day.
It is not required to remove product from case overnight. Turn off case lights, and cover product with moistened cheesecloth or fabric towel. This helps slow down product dehydration, by taking moisture from the cloth and not the product. This is an old method used by meat shops for many years, as it extends product life.
Cold coils remove heat and moisture from the case and deposit this as frost onto the coil. Thus a defrost is required to remove this frost. Our humidity system induces moisture into the case, and helps slow down the dehydration process. The only other moisture in the case is that which is in the product. A single level of meat will dry out faster than a fully loaded case with 3-4 levels of meat.
The colder the case, the faster the product loses its moisture and shelf life. It is very important to maintain a constant, even, correct, product temperature.
HUMIDIFICATION SYSTEM HOOKUPS
Remove the raceway panel on the lower back of the case. The pre-piped water shut-off valve and the water filter are located on the left hand side of the case. The water line (which is a 1/4" OD copper fitting) can be connected to the ball shut-off valve, by means of a compression fitting (supplied). The line should be one size larger than the supply line. The line can then be run from one case to another from within the raceway(s) using Tee connectors. Before connecting the water to the humidity system, it is best to
9
Humidity System (cont.)
purge the line to flush any debris that may clog the water filter. If the water line requires purging after the cases are hooked together, it is not necessary to check each one. Simply shut ball valves to each humidity system, remove the water line from the last case in the flow, and purge. By doing this as a precautionary measure, you may avoid problems and repeat servicing.
START-UP
Turn on the fan circuit. Check to see if the fan for the humidity system is running. Remove the right hand bottom pan (when facing the front of the case), then the TXV cover. The fan is located up against the right hand side of the case, as viewed from the front, under the fan plenum (see diagram). View the blade, and make sure the fan rotation agrees with the air flow arrows. Turn on the water, by turning the ball valve in the direction of the flow (OFF is at 90° to the direction of flow). After a few minutes, check the spray header by sliding the honeycomb to the left to expose the discharge tube located on the right hand side of the case (when viewed from the rear), by lifting the 4'-0" section of honeycomb with both ends, until the bottom clears. Pull up and set aside. The spray header will be exposed. Grasp the header and pull it loose from the 90° “L” until you see the misting nozzle, which should be spraying. If not, check the following:
1. Make sure the water is feeding the nozzle.
2. Remove the nozzle, and purge the water.
IGSV-ASCS-0303
3. Check strainer at entrance to nozzle.
Reinsert the header into the 90° “L”, making sure that the nozzle is in the center of the pipe when totally inserted, and the holes in the header are facing the front of the case at a level angle. The discharge tube can easily be pulled to service.
MAINTENANCE
•Clean humidity system a minimum of every 90 days for proper system operation.
1/8" 100 X 1/8FPT SW ADAPTER 225-01-3220
SPRAY HEADER
RUNS LENGTH OF CASE
REAR INTERIOR WALL OF CASE
VIEWED FROM FRONT
WATER
SUPPLY
1/4"MPT X 1/4" OD
COMP ADAPTER
225-01-1312
BALL VALVE
HAMMON
225-01-2026
HAGO-M1 NOZZLE 225-01-3221
1/4"MPT X 1/4" COMP PVC ADAPTER
225-01-2026
WATER FILTER
3 STAGE #00015
225-01-2026
HUMIDITY SYSTEM as viewed from the front. Note: The axial fans included in the humidity system must be replaced as a unit.
1/4" 100 X 1/8FPT SW ADAPTER 225-01-2089A
2ND FAN USED
IN 12' CASE
1/4" OD X 1/8" FPT
SW ADAPTER
225-01-3059
1/8" MPT X 1/4" COMP
PVC ADAPTER
225-01-3059
PAN AND ACCESS PANEL
3" AXIAL FAN
225-01-2026

Refrigeration

REFRIGERANT TYPE
The standard refrigerant will be R-22 unless otherwise specified on the customer order. Check the serial plate on the case for information.
PIPING
The refrigerant line outlets are located under the case. Locate first the electrical box, the outlets are then on the same side of the case, but at the opposite end. Insulate suction lines to prevent condensation drippage.
REFRIGERATION LINES
LIQUID SUCTION
1/2" O.D. 5/8" O.D.
NOTE: The standard coil is piped at 5/8" (suction); however,
the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be
5
/8", 7/8", or 11/8". Refer to the particular case you are
hooking up.
Refrigerant lines should be sized as shown on the refrigeration legend furnished by the store.
P-traps (oil traps) at the base of all suction line vertical
Install risers. Pressure drop can rob the system of capacity. To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.
CONTROL SETTINGS
See the “Case Specs” section of this guidebook for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product temperatures. Product temperature should first be measured in the morning, after having been refrigerated overnight. For all multiplexing, defrost should be time terminated. Defrost length and frequency should as directed in the Case Specifications section of this guide. The number of defrosts per day should never change. The duration of the defrost cycle may be adjusted to meet conditions present at your location.
10
Rev.0303
ACCESS TO TX VALVES AND DRAIN LINES
MECHANICAL - Remove product from case. Remove pans. TX valve (mechanical only) and drain are located under the pans within the case. ELECTRONIC - The electronic expansion valve master and slave cylinder(s) are located within the electrical access panel(s) in the rear of case. Rear panels lift up and out. NOTE: Duplex receptacles must be detached before removing rear panels.
ELECTRONIC EXPANSION VALVE (OPTIONAL)
A wide variety of electronic expansion valves and case controllers can be utilized. Please refer to EEV and controller Hussmann’s information sheet. Sensors for electronic expansion valves will be installed on the coil inlet, coil outlet, and in the discharge air. (Some supermarkets require a 4th sensor in the return air). Case controllers will be located in the electrical raceway or under the case.
THREE THERMOSTATIC EXPANSION VALVES
ALCO balanced port expansion valves are furnished as standard equipment, unless otherwise specified by customer.
EXPANSION VALVE ADJUSTMENT
Expansion valves must be adjusted to fully feed the evaporator. Before attempting any adjustments, make sure the evaporator is either clear or very lightly covered with frost, and that the fixture is within 10°F of its expected operating temperature.
pressure gauge at the evaporator outlet.
2. From a refrigerant pressure temperature chart, determine the saturation temperature at the observed suction pressure.
3. Measure the temperature of the suction gas at the thermostatic remote bulb location.
4. Subtract the saturation temperature obtained in step No. 2 from the temperature measured in step No. 3.
3. The difference is superheat.
5. Set the superheat for 5°F - 7°F.

T-STAT LOCATION

T- Stats are located in the electrical section; behind the rear panel, on the right-hand side of the case (facing the back of the case).
T-Stat
Electrical Raceway
After case has been brought to
running temperature, tighten glass screws
along clamshell.
MEASURING THE OPERATING SUPERHEAT
1. Determine the suction pressure with an accurate
11

Electrical

WIRING COLOR CODE

GREEN GROUND PURPLE ANTI-SWEAT ORANGE LIGHTS YELLOW RECEPTACLE RED / BLACK T-STAT /SOLENOID230V BLACK / WHITET-STAT / SOLENOID 115V BROWN FAN MOTORS
CASE MUST BE GROUNDED
NOTE: Refer to label affixed to case to determine the actual
configuration as checked in the “TYPE INSTALLED” boxes.
ELECTRICAL CIRCUIT IDENTIFICATION
Standard lighting for all models will be full length fluorescent lamps located within the case at the top. The switch controlling the lights, the plug provided for digital scale, and the thermometer are located at the rear of the case mullion. The receptacle that is provided on the exterior back of these models is intended for computerized scales with a five amp maximum load, not for large motors or other high wattage appliances. It should be wired to a dedicated circuit.
CASE-TO CASE CONNECTORS
HUSSMANN/CHINO now provides “CASE-TO-CASE” locking electrical connector fittings on the ASCS service cases. These connectors greatly simplify field installation thereby saving time and electrical installation costs.
NOTE: The total case electrical draw must not exceed 30 Amps ampacity at 115V in one connected lineup.
IGSV-ASCS-0303
BEFORE SERVICING
Always Disconnect Electrical
Power at the Main Disconnect
when servicing or replacing any
electrical component.
This includes (but not limited to) Fans, Heaters,
Thermostats, and Lights.
FIELD WIRING AND SERIAL PLATE AMPERAGE
Field wiring must be sized for component amperes printed on the serial plate. Actual ampere draw may be less than specified. Field wiring from the refrigeration control panel to the merchandisers is required for refrigeration thermostats. Most component amperes are listed in the “Case Specs” section, but always check the serial plate.
BALLAST LOCATION
Ballasts are located within the access panel that runs the length of the rear of the case. Refer to diagram on page 6.
WIRING AND SERIAL PLATE AMPERAGE
Field wiring must be sized for component amperes stamped on the serial plate. Actual ampere draw may be less than specified. Field wiring from the refrigeration control panel to the merchandisers is required for refrigeration thermostats. Most component amperes are listed in the "Case Specs" section, but always check the serial plate.
ELECTRICAL SERVICE RECEPTACLES (WHEN APPLICABLE)
The receptacles located on the exterior of the merchandiser are intended for scales and lighted displays. They are not intended nor suitable for large motors or other external appliances.

ASHRAE COLOR CODE

NOTE: All other manufacturers; no known sensor codes
Case Control Systems
Manufacturer ® > EIL CPC Location Coil Inlet
Coil Outlet
Discharge Air
Return Air
Defrost Term.
Liquid Line
SENSOR COLORS
Color
Part#
Color
Part#
Color
Part#
Color
Part#
Color
Part#
Color
Part#
Blue Blue 225-01-1755 225-01-3255 Red Red 225-01-1757 225-01-3123 Green Green 225-01-1756 225-01-3260 Purple Green 225-01-1758 225-01-3260 White Orange 225-01-0650 225-01-3254 White Blue 225-01-0650 225-01-3255
12
Loading...
+ 28 hidden pages