hussman IGSS-FMSS-0301 User Manual

Manual
Installation
& Operation
/Chino
FMSS
Rev.0301
Case-front Self Service
FMSS
p/n IGSS-FMSS-0301
INSTALLATION & OPERATION GUIDE
Ta b l e of Contents
IGSS-FMSS-0301

General Instructions

THIS BOOKLET CONTAINS INFORMATION ON:
General Instructions ................................................. 2
Cut & Plan Views ....................................................... 3
Installation (cont.) .................................................... 4
LEVELING.............................................................................................................. 4
Plumbing .................................................................... 5
WASTE OUTLET AND P-TRAP .............................................................................. 5
JOINT TRIM........................................................................................................... 5
Refrigeration ............................................................. 6
T-STAT LOCATION.................................................................................................. 6
Electrical .................................................................... 7
WIRING COLOR CODE ......................................................................................... 7
Wiring Diagram ........................................................ 8
User Information ...................................................... 13
STOCKING.............................................................................................................. 13
CASE CLEANING.................................................................................................... 13
Maintenance .............................................................. 14
ELECTRICAL PRECAUTIONS ................................................................................... 14
REPLACING FLUORESCENT LAMPS ....................................................................... 14
PLEXIGLASS & ACRYLIC CARE .............................................................................. 14
TIPS & TROUBLESHOOTING ................................................................................. 14
Specifications............................................................. 15
Appendices ................................................................ 16
APPENDIX A. – Temperature Guidlines .............................................................. 16
APPENDIX B. – Application Recommendations.................................................. 16
APPENDIX C. – Field Recommendations ............................................................ 16
APPENDIX D. – Recommendations to user ....................................................... 17
FMSS-Remote The FMSS is a single-deck, refrigerated, self-service mer­chandiser, which offers additional related display when positioned in front of a “Parent” service case.
SHIPPING DAMAGE
All equipment should be thoroughly examined for ship­ping damage before and during unloading. This equipment has been carefully inspected at our fac­tory and the carrier has assumed responsibility for safe arrival. If damaged, either apparent or concealed, claim must be made to the carrier.
APPARENT LOSS OR DAMAGE
If there is an obvious loss or damage, it must be noted on the freight bill or express receipt and signed by the carrier’s agent; otherwise, carrier may refuse claim. The carrier will supply necessary claim forms.
CONCEALED LOSS OR DAMAGE
When loss or damage is not apparent until after equipment is uncrated, a claim for concealed damage is made. Make
request in writing to carrier for inspection within 15 days, and retain all packaging. The carrier will supply inspection report and required claim forms.
SHORTAGES
Check your shipment for any possible shortages of mate­rial. If a shortage should exist and is found to be the re­sponsibility of Hussmann Chino, notify Hussmann Chino. If such a shortage involves the carrier, notify the carrier imme- diately, and request an inspection. Hussmann Chino will acknowledge shortages within ten days from receipt of equipment.
HUSSMANN CHINO PRODUCT CONTROL
The serial number and shipping date of all equipment has been recorded in Hussmann’s files for warranty and re­placement part purposes. All correspondence pertaining to warranty or parts ordering must include the serial num­ber of each piece of equipment involved, in order to pro­vide the customer with the correct parts.
Keep this booklet with the case at all times for future reference.
/Chino
A publication of Hussmann® Chino 13770 Ramona Avenue • Chino, California 91710 (909) 628-8942 FAX (909) 590-4910 (800) 395-9229
The Hussmann warranty is printed on the back
of this guide.
2
Rev.0301
*24"

Cut & Plan Views

"
8
/
1
"
2
/
1
13
12
1
n
a
F
/4"
6
*26"
"
2
/
1
*10
*Dimensions adjust at these points to match service case height
16"
FMSS
Remote
Self-Service Shown with
Optional Special Height
Scale = 1"
ASC
PARENT CASE
20"
FMSS
Height Modified to
match the ASC case
Front-Mount Self-Service case. Can be ordered to mount in front
of ANY service case. Base height can be modified to match any
service case bumper height.
“Field” Close Off
FMSS
4 1/2"
"
2
/
1
12
"
2
/
1
3
Elec.
Drain
4'
(VARIABLE LENGTHS)
24"
Ref. Drop In
2 5/8"
"
8
/
7
9
"
16
FMSS
Plan View
Scale = 1/2"
3

Installation (cont.)

LOCATION
The refrigerated merchandisers have been designed for use only in air conditioned stores where temperature and humidity are maintained at or below 75°F and 55% rela­tive humidity. DO NOT allow air conditioning, electric fans, ovens, open doors or windows (etc.) to create air cur­rents around the merchandiser, as this will impair its cor­rect operation. Product temperature should always be maintained at a constant and proper temperature. This means that from the time the product is received, through storage, prepa­ration and display, the temperature of the product must be controlled to maximize life of the product.
UNCRATING THE STAND
Place the fixture as close to its permanent position as possible. Remove the top of the crate. Detach the walls from each other and remove from the skid. Unbolt the case from the skid. The fixture can now be lifted off the crate skid. Lift only at base of stand!
EXTERIOR LOADING
These models have not been structurally designed to sup- port excessive external loading. Do not walk on their tops; This could cause serious personal injury and dam­age to the fixture.
SETTING AND JOINING
The case that the FMSS connects to (the parent case) through the rear of the case must be leveled and set prior to installing the FMSS. The sectional construction of these models enable them to be joined in line - to give the effect of one continuous display. A joint Trim Kit is supplied with each case line to cosmetically “mask” the sectional joints. See the “Finishing Touches” section for more information on joint trim.
IGSS-FMSS-0301
Determine the highest point of the floor; cases will be set off this point.
2. Level and set the first case, carefully guiding the electrical, regfrigeration and drain lines through the parent case. Case must be raised under legs where support is best to prevent damage to case. Internal bracing may be removed at this time.
3. Set second case as close as possible to the first case carefully guiding its electrical, refrigeration and drain lines through the parent case, and level case to the first using the instructions in step one.
4. Apply masking tape 1/8" in from end of case on inside and outside rear mullion on both cases to be joined.
5. Apply
liberal bead of case joint sealant (butyl) to
dotted area shown in (Fig.2, #1) of first case. Apply heavy amount to cover entire shaded area.
DO NOT USE PERMAGUM!
Fig. 2, #1

LEVELING

IMPORTANT! It is imperative that cases be lev­eled from front to back and side to side prior to joining. A level case is necessary to insure proper operation, water drainage, glass alignment, and operation of the hinges supporting the glass. Lev­eling the case correctly will solve most hinge op­eration problems.
NOTE: A. To avoid removing concrete flooring, begin lineup
leveling from the highest point of the store floor. B. When wedges are involved in a lineup, set them first.
All cases were leveled and joined prior to shipment to insure the closest possible fit when cases are joined in the field. When joining, use a carpenters level and shim legs accordingly. Case must be raised correctly, under legs where support is best, to prevent damage to case.
1. Check level of floor where cases are to be set.
It is the contractor’s responsibility to install
case(s) according to local construction and
health codes.
6. Slide second case up to first case snugly. Then level second case to the first case so glass front, bumper and top are flush.
Do not use the top bracket on the rear mullion
to pull the cases together.
4
Rev.0301
7. To compress silicone at joint, use two Jurgenson wood clamps. Make sure case is level from front to back and side to side on inside bulkheads at joint.
8. Attach sections together with the two 3/8” bolts provided, below the deck at the mullion towards the rear of the FMSS. Remove clamps.
9. Apply bead of silicone to top of bulkheads and slip on stainless steel bulkhead cap. Also apply silicone to seam between overhead light tubes.
10. VERY IMPORTANT! Apply liberal amounts of black silicone to fill all voids down to bulkhead.
Proper case-joint sealing is extremely important to prevent water leaks!
Installation (cont.)
(apply additional silicone if necessary). Remove tape applied on line #3.

JOINT TRIM

After cases have been leveled and joined, and refrigera­tion, electrical, and wasted piping work completed, install the splashguards. Fasten along the top edge, or center, with #10 X 3/3" sheet metal screws.
D
O NOT SEAL JOINT T RIM T O FLOOR!
11.Use finger to smooth silicone as thin as possible at masking tape on inside and outside of rear mullion

Plumbing

WASTE OUTLET AND P-TRAP

The waste outlet is located at the left hand end of these fixtures allowing drip piping to be run under the fixture lengthwise. A 1" P-trap and threaded adapter are supplied with each fixture. The P-trap must be installed to prevent air leakage and insect entrance into the fixture.
INSTALLING CONDENSATE DRAIN
Poorly or improperly installed condensate drains can se­riously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:
1. Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-trap supplied with the case.
2. When connecting condensate drains, the P-trap must be used as part of the condensate drain to prevent air leakage or insect entrance. Store plumb­ing system floor drains should be at least 14" off the center of the case to allow use of the P-trap pipe
section. Never use two water seals in series in any one line. Double P-traps in series will cause a lock and prevent draining.
3. Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to main­tain the 1/8" pitch and to prevent warping.
4. Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.
5. Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.
6. Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.
b. Where condensate drains are located in dead air
spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing. The water seal should be insulated to prevent condensation.
5

Refrigeration

REFRIGERANT TYPE
The standard refrigerant will be R-404 unless otherwise specified on the customer order. Check the serial plate on the case for information. Piping for more than one case on a condensing unit is run underground with either common suction and liquid lines from the machine room or individual suction and liquid lines joined together in the machine room.
REFRIGERATION LINES
LIQUID SUCTION 3/8" O.D. 5/8" O.D.
NOTE: The standard coil is piped at 5/8" (suction); however,
the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be
5
/8", 7/8", or 11/8". Refer to the particular case you are
hooking up.
Refrigerant lines should be sized as shown on the refrig­eration legend furnished by the store. Install P-traps (oil traps) at the base of all suction line ver­tical risers. Pressure drop can rob the system of capacity. To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.
For refrigerators with KOOLGAS defrost, suction, and liquid lines should not contact each other and should be insulated for a minimum of 30' from the refrigera­tor. Additional insulation for the balance of liquid and suction lines is recommended and required wherever condensation and dripping would be objectionable.
CONTROL SETTINGS-Remote
See the “Case Specs” section of this guidebook for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product tempera­tures. Product temperature should be measured first thing in the morning, after having been refrigerated overnight. Defrost times should as directed in the Case Specifica­tions section of this guide. The number of defrosts per day should never change. The duration of the defrost cycle may be adjusted to meet conditions present at your loca­tion.
CONTROL SETTINGS-Self Contained
On Self Contained cases all functions, defroat, fans, tem­perature are controlled by Pagon ERC-2 controller. See case spects for proper temperature and defrost settings.
ACCESS TO TX VALVES & DRAIN LINES
MECHANICAL - Remove product from end of case. Remove product racks. Remove refrigeration and drain access panels (labeled). TX valve (mechanical only) and drain are located under each access panel at end of the case.
IGSS-FMSS-0301
ELECTRONIC - The Electronic Expansion valve master and slave cylinder(s) are located within the electrical access panel(s).
ELECTRONIC EXPANSION VALVE (OPTIONAL)
A wide variety of electronic expansion valves and case controllers can be utilized. Please refer to EEV and con­troller manufacturers information sheet. Sensors for elec­tronic expansion valves will be installed on the coil inlet, coil outlet, and in the discharge air. (Some supermarkets require a 4th sensor in the return air). Case controllers will be located in the electrical raceway or under the case
THERMOSTATIC EXPANSION VALVE LOCATION
This device is located on the same side as the refrigera­tion stub. A balanced port expansion valve model is fur­nished as standard equipment.
EXPANSION VALVE ADJUSTMENT
Expansion valves must be adjusted to fully feed the evapo­rator. Before attempting any adjustments, make sure the evaporator is either clear or very lightly covered with frost, and that the fixture is within 10°F of its expected operat­ing temperature.
MEASURING THE OPERATING SUPERHEAT
1. Determine the suction pressure with an accurate pressure gauge at the evaporator outlet.
2. From a refrigerant pressure temperature chart, determine the saturation temperature at the observed suction pressure.
3. Measure the temperature of the suction gas at the thermostatic remote bulb location.
4. Subtract the saturation temperature obtained in step No. 2 from the temperature measured in step No. 3.
3. The difference is superheat.
5. Set the superheat for 5°F - 7°F.

T-STAT LOCATION

Thermostats are located within the electrical raceway. The raceway location is dependent on the style of the front
6
Loading...
+ 14 hidden pages