The Hunter ET System allows an irrigation program to be created automatically, based on local climate conditions. The program is then operated
via a compatible irrigation controller’s Program A (except ACC controllers, see page 14) and runs automatically, on water days and at start times
set by the system operator. Compatible controllers are Hunter Models SRC/SRC Plus, Pro-C, ICC, and ACC with SmartPort
ET System uses sensors to determine the local “evapotranspiration” (ET) rate of turf and plants. This is a formula which calculates how much water the plants have lost, or consumed, due to local atmospheric conditions. Each ET System can be customized by station (or “zone”) for specific
plant, soil, and sprinkler types.
The result is a new, water-efficient irrigation program every water day, based on local weather conditions.
Once installed, the ET-controlled zones are programmed from the ET Module, rather than the controller itself. The ET Module will display the new
program data for the climate-based irrigation.
The ET System allows manual station starts from the controller, and will also permit connection of an ICR or SRR remote control receiver.
This product is intended for turf and landscaping applications only, not intended for agricultural or scientific use.
Use the ET System Worksheet. One is included with each ET System, and this can also be downloaded free of charge from the Hunter Industries
web site (www.hunterindustries.com at the ET System product page). The ET System Worksheet will help you organize and record your station
settings. This will also help to determine and track any adjustments you may make to the watering settings. If you need Technical Support, the
Hunter technician will also need this information.
®
technology.
1
C.
A.
D.
E.
B.
2
ET SySTEm COmpONENTS ...................................................................................................................
ET System has two major components, and one optional accessory. All
ET System components are low voltage (24 VAC or less).
A. ET Sensor
Sensor platform wired to the ET Module, which senses local
conditions. For external mounting up to 100 ft/33m from the Module. Pole adapters included (requires other hardware for various
mounting options).
B. ET Module
Electronic control and user interface for the ET System.
C. ET Wind (Optional)
Optional anemometer which senses wind speed. Provides more
sensitive ET measurement, especially in arid climates.
D. ET/ACC Adapter (Included)
For connection with ACC series controllers. The adapter is not
required for use with Hunter ICC, Pro-C, and SRC family
controllers.
E. ET Wire
100' (33mm) two-conductor direct burial for connection to ET
Sensor
SySTEm OvErvIEw ANd ET SySTEm OpErATION .........................................................................
The ET System can be simply and easily installed with any Hunter
SmartPort®-equipped irrigation controller. The System consists of the
ET Sensor, installed in an area typical of the irrigated plants, and the
ET Module interface enclosure, installed next to the irrigation controller.
The ET Sensor measures solar radiation, air temperature, and relative
humidity, and calculates the daily Evapotranspiration factor (ET) for
the irrigation zones. This represents the amount of water lost by the
plants to local climatic conditions, which needs to be replaced by
irrigation.
The optional ET Wind sensor will add evapotranspiration loss due to
wind, along with automatic wind shutdown capability.
The ET Sensor also includes a Rain Gauge, which measures rainfall in
either hundredths of an inch, or in millimeters.
Rainfall will stop automatic ET irrigation that may be in progress. A
percentage of the rainfall itself will be added to the soil and subtracted
automatically from the automatic irrigation, to prevent waste.
The ET Module receives the data from the ET Sensor, and applies it
to the individual zones of irrigation. The ET Module has settings to
customize each zone’s plant, soil, and sprinkler types, so that ET data
can be applied proportionately for each unique irrigation requirement.
The ET Module is wired into the controller’s SmartPort and creates
irrigation run times to only replace the amount of water the plants
have lost.
ET Module works by running stations through the local controller. It
will clear Program A in the local controller (except in ACC controllers),
and it will then run the ET run times with manual commands. Program
A is no longer available for "traditional" irrigation scheduling.
How ET System Decides to Water: Using the local ET Sensor readings
and the ET Module’s database of station information, ET System predicts the Management Allowable Depletion of water (MAD) available to
each plant type.
Each day, ET System looks at the current depletion level, ET rate,
plant type (crop coefficient and root zone), and whether the next day
is an allowable watering day. The decision to start a specific station
is also based upon a minimum irrigation amount, to prevent shallow
watering. Deeper watering events encourage healthy root systems and
plant growth. The calculation for minimum sprinkler runtime is based
upon the soil type and capacity, where typically the MAD is above
30-50%. For the worst-case scenario, sandy soil with spray heads, the
minimum runtime would then be approximately 7 minutes.
3
INSTALLINg ThE ET SENSOr................................................................................................................
ET Sensor
Additional Tools and Materials
The ET system is supplied with 100’/33m of wire for connection of the
ET Sensor. This wire has been specially tested for ET installations and
is approved to 100’/33m max.
If any other wire is to be used, Hunter recommends 2 x 18 AWG/1mm
wire rated for direct burial, color-coded or other wise marked to
identify the separate conductors. The ET signal is a low-voltage DC
and the conductors must be distinguished from each other to maintain
polarity. Either stranded or solid wire is acceptable (stranded is more
flexible and resists breakage). The ET signal is rated to 100’/33m max
and is not tested or approved to any greater distance.
Choose the Location
ET Sensor should be placed in an area representative of the plants it is
designed to irrigate.
The ET Sensor should be post or pole-mounted in a full-sun turf
grass area, approximately 6 ft./2m above the grass, with approximately 6 ft./2m of turf grass surrounding it on all sides. The ET
Sensor weighs approximately 6 lbs./2.5kg.
This may not always be practical, so choose the actual location
according to the following guidelines:
a) ET Sensor must be mounted within 100 ft./33m of the ET Module
and the controller.
b) Avoid positioning ET Sensor over large areas of concrete, asphalt,
roof tile, or shingles. These surfaces will cause the sensors to
read much higher levels of ET than plants.
c) Choose a sunny location between 6 and 20 feet (2 and 7m) above
the ground.
d) Do not mount the sensor where it will be hit by sprinkler spray or
other irrigation!
4
15 ft/5m Clearance From Any Structure
ICC Controller
ET Module
ET Sensor Wire (Included with ET
System) 100 ft./30m, maximum
e) Do not mount the ET Sensor under a ledge or overhang, and avoid
placing it directly under tree canopies. ET Sensor needs un-
blocked sun and rain to function correctly!
f) Do not mount the ET Sensor within falling distance of power
lines! High voltage shocks can injure and kill.
6 ft/2m
Above
Turf,
Minimum
g) Position the ET Sensor where it can be reached for occasional ser-
vice. The rain gauge should be checked and cleaned once a month
during the warmer months, to ensure that it is free of debris.
h) Avoid mounting sensor near any high intensity light, heat or infra-
red sources as this may add excess ET amounts over time.
The ET Sensor is designed to adapt to steel fence poles (mounting
adapters included, requires 2 x 2"/50mm
2
U-bolts), 4x4"/100mm2 (or
larger) posts, or eaves or walls.
Metal poles or weather-treated wooden posts are preferred, since
ET measurements will be somewhat less accurate if the sensor is
wall or eave-mounted.
ET Sensor Wiring
Locate the screw terminal strip. Connect the two long conductors
(green and black) to the appropriately labeled terminals.
If an ET Wind Sensor is to be installed, this is also the time to connect the wires.
Prevailing Wind Compensation
If ET Wind will not be connected,
a factor for average prevailing
Green and
Black Wires
(ET Module)
Before mounting the ET Sensor, connect the wires to the terminal
strip. This operation is much easier on the ground, prior to mounting
the sensor.
Locate the wiring compartment cover on the bottom of the ET Sensor.
This is a trap door, secured with 2 screws. Remove the wiring com-
White Wire
Blue Wire
(ET Wind only)
partment door screws and set in a safe place, and remove the wiring
compartment door.
Average Wind Factor Settings. Switch #4 is not used, and position does not matter.
winds in the installation area can be entered while the wiring door is
removed. The factory default setting is 5 mph (8 kph). With the wiring
cover removed, a DIP switch is visible allowing other prevailing
average wind speeds to be set, according to the Table 1 (note
that Switch 4 is not used).
If the optional ET Wind sensor is installed, mount
the ET Wind sensor according to its instructions,
and connect the blue and white conductors from
the ET Sensor to the appropriately labeled terminals and secure their screws. Do not reverse the
blue and white wire connections from ET Wind…
connect as shown!
Replace the wiring compartment door and secure
with the screws.
Metal Fence Pole
Steel adapters are supplied for most popular sizes
of galvanized steel fence posts, 2" diameter and
smaller.
Additional materials (not supplied): 2 x 2" galvanized or stainless steel U-bolts, 3" long or greater
4 nuts and washers for U-bolts
Bag of concrete
If pole is new construction for specific purpose
of mounting ET Sensor, dig approximately 12" x
12" hole and fill with approximately one 90 lb. bag
of concrete, or place as required by local code.
Insert pole, check with level and straighten, and
brace until concrete is firmly set.
Insert U-bolts around pole through steel pole
adaptors, and through mating holes in ET Sensor
back plane. Add washers, thread nuts onto U-bolt,
and tighten. Do not overtighten.
Route ET Sensor wire to ground surface or burial trench, and run back
to ET Module.
6
External mounting in outdoor low voltage conduit
(for the above-ground exposed portion of the wire
run) is recommended for protection from the elements.
100mm x 6mm dia. x 3,8cm long galvanized or
stainless steel lag bolts and washers
Nut driver for lag bolts
Bag of concrete
Dig approximately 12" x 12"/30cm x 30cm hole (or greater, as
local code dictates) and fill with approximately one bag of concrete.
Insert post, check with level and straighten, and brace until concrete
is firmly set.
Level, mark, and drill pilot holes for 4 lag screws through back of ET
Sensor holes. Insert lag bolts and washers through mounting hole in
backplane of ET Sensor and tighten. Do not overtighten.
Route ET Sensor wire to ground surface or burial trench, and run back
to ET Module.
External mounting in outdoor low voltage conduit (for the aboveground exposed portion of the wire run) is recommended for protection from the elements.
Wall or Eave
Additional materials (not supplied): 4 x ¼" dia. x 1.5" (100mm x 6mm
x 40mm) long galvanized or stainless steel lag bolts and washers.
Nut driver for lag bolts.
Level, mark, and drill pilot holes for 4 lag screws through back of ET
Sensor holes. Insert lag bolts and washers through mounting hole in
backplane of ET Sensor and tighten. Do not overtighten.
Route ET Sensor wire to ground surface or burial trench, and run back
2
Orange, or Blue-And-White-Striped
in some versions
Controller Connections
(ET System Only)
Blue: REM
White: AC2
Red: AC1
To ET Sensor
Green
Black
to ET Module. External mounting in outdoor low voltage conduit (for
the above-ground exposed portion of the wire run) is recommended
for protection from the elements.
In all cases, ensure that any exposed wire loop from the ET Sensor to
INSTALLINg ThE ET mOduLE ..............................................................................................................
immediately next (6 ft./2m) to the Hunter SmartPort-equipped irrigation controller (including models SRC, Pro-C, ICC, and ACC). The ET
Module is low-voltage only and does not require a separate highvoltage power connection.
The ET Module is connected to the ET Sensor via the two conductor
sheathed wires supplied with the ET System (up to 100 ft./30m away),
and then wired into the SmartPort wiring terminals inside the controller.
To wall mount the ET Module, choose a location within 6 ft./2m of the
controller. Avoid direct sunlight when possible (to enhance visibility of
the LCD display). Verify that the wallboard construction is of sufficient
strength to securely mount the small, lightweight enclosure.
The 6-conductor umbilical cord extends through the shielded hole in
the bottom of the enclosure. Verify that it remains clear and accessible
when securing the enclosure to the wall.
Use two anchors or self-tapping screws of minimum #12 (5.5mm)
diameter to secure the ET Module enclosure to the wall.
Turn off AC power to the irrigation controller, before connecting the
ET Module to the controller! The ET System receives its power from
the SmartPort connection to the Hunter controller. Do not connect the
ET Module to the controller while AC power is turned on.
ET Module Wiring
The 6-conductor umbilical cord from the ET Module is color-coded to
simplify connections.
Do NOT connect 110/230V high-voltage power to the ET System!
Make all wiring connections with approved butt splices or wire nuts
for the ET wire, and place the splices in a suitable junction box. Conduit is recommended for both indoor and outdoor installations.
the wire routing conduit does not swing freely in the wind, as this will
shorten its life.
The ET Module is designed to be wall-mounted, either in or outdoor,
Install CR2032 backup battery for date/time backup in event of power
failure (battery included with mounting hardware). Batter y must be
installed with + visible, facing toward the installer.
If connecting the ET System to an ACC series controller, see ACC
section for special installation instructions.
ICC, Pro-C, and SRC controllers (ACC special instructions in next
section): Connect the supplied wires from the ET Module to the ET
Install CR2032 lithium batter y (included)
under cover for time/date backup.
Install CR2032 battery
7
AC AC RRSCMV 123456
9 V Battery
RESET
BlueRed
White
BlueRed
White
Blue
Red
White
Sensor with appropriately sized butt splices or wire nuts. These two
wires may be extended up to 100 ft./30m to reach the sensor.
SRC or SRC
Plus Controller
Connection
If no wireless
remote control
receiver will be
installed, the
Orange wire
(or Blue-AndWhite-Striped
wire in some
versions) from
the ET Module
is not used.
Connect the red wire from the ET Module to the bottom left of the two
terminals on the power module labeled “24VAC” (or just AC, on older
units).
Connect the white wire from the
ET Module to the second to the
right of the two terminals on the
power module labeled “24VAC” (or
just AC, on older units)..
Connect the blue wire from the
ET Module to the terminal in the
controller labeled “R”.
If no wireless remote control
receiver will be installed, the blueand-white striped wire from the ET
Module is not used.
Pro-C Controller Connection
Connect the red wire from the ET
Module to the terminal in the controller labeled AC1.
8
Connect the white wire from the ET Module to the terminal in the
controller labeled AC2.
Connect the blue wire from the ET Module to the terminal in the controller labeled REM.
ICC Controller Connection
Connect the red wire from the ET Module to the bottommost of the
terminals on the power module labeled “AC”.
Connect the white wire from the ET Module to the upper of the two
terminals on the power module labeled “AC”.
Connect the blue wire from the ET Module to the terminal in the controller labeled REM.
SmartPort
for ICR Receiver
Blue: REM
Connect orange
(or blue-and-white-striped)
wire from module,
to blue wire from SmartPort
White: AC2
Red: AC1
To ET Sensor
Green
Black
Controller Connections
(SmartPort with ET and ICR)
Remote Control Connection
If a remote control (either Hunter ICR or SRR) receiver is to be connected, connect the Orange wire (or Blue-And-White-Striped wire in
some versions) from the ET Module, to the blue ICR/SRR receiver
wire. The SmartPort wiring that connects ET Module to the controller
will complete the connection for the remote receiver.
ACC Controller Connection
The ET System is shipped with a special adapter for use with the ACC
series of controllers.
The ACC controllers have an integrated SmartPort for remote receivers
(such as the Hunter ICR remote control) on the side of the cabinet in
the metal cabinet configurations, and inside the pedestal in the plastic
pedestal configurations.
All ET System connections are made within the enclosed ET/ACC
adapter, which is then plugged into the SmartPort. The adapter allows
both ICR remote receivers and the ET System to be connected to the
ACC controller at the same time.
When installing ET System with an ACC controller, the ET Sensor connections are also made at the terminal strip inside the adapter, NOT to
the ET Module cable directly. This is only true for ACC connections.
9
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.