The Hunter ET System allows irrigation programs to be created automatically, based on local climate conditions. These programs are then loaded
into a compatible irrigation controller’s Program A (except ACC controllers, see page 14) and run automatically, on water days and at start times
set by the system operator. Compatible controllers are Hunter Models SRC/SRC
ET System uses sensors to determine the local “evapotranspiration” (ET) rate of turf and plants. This is a formula which calculates how much wa
ter the plants have lost, or consumed, due to local atmospheric conditions. Each ET System can be customized by station (or “zone”) for specific
plant, soil, and sprinkler types.
The result is a new, water-efficient irrigation program every water day, based on local weather conditions.
Once installed, the ET-controller zones are programmed from the ET Module, rather than the controller itself. The ET Module will display the new
program data for the climate-based irrigation.
The ET System allows manual station starts, and will also permit connection of an ICR or SRR remote control receiver.
This product is intended for turf and landscaping applications only, not intended for agricultural or scientific use.
Plus, Pro-C, ICC, and ACC with SmartPort® technology.
-
C.
A.
D.
B.
ET SySTEm COmpONENTS ...................................................................................................................
ET System has two major components, and one optional accessory. All
ET System components are low voltage (24 VAC or less).
A. ET Sensor
Sensor platform wired to the ET Module, which senses local
conditions. For external mounting up to 100 ft/33m from the Mod
ule. Pole adapters included (requires other hardware for various
mounting options).
B. ET Module
Electronic control and user interface for the ET System.
C. ET Wind (Optional)
Optional anemometer which senses wind speed. Provides more
sensitive ET measurement, especially in arid climates.
D. ET/ACC Adapter (Included)
For connection with ACC series controllers. The adapter is not
required for use with Hunter ICC, Pro-C, and SRC family
controllers.
SySTEm OvErvIEw ANd ET SySTEm OpErATION .........................................................................
The ET System can be simply and easily installed with any Hunter
SmartPort®-equipped irrigation controller. The System consists of the
ET Sensor, installed in or near an area typical of the irrigated plants,
and the ET Module inter face box, installed next to the irrigation con
troller. The ET Sensor measures solar radiation, air temperature, and
relative humidity, and calculates the daily Evapotranspiration factor
(ET) for the irrigation zones. This represents the amount of water lost
by the plants to local climatic conditions, which needs to be replaced
by irrigation. The optional ET Wind sensor will add evapotranspiration
loss due to wind, along with automatic wind shutdown capability.
The ET Sensor also includes a Rain Gauge, which measures rainfall
in either hundredths of an inch, or in millimeters. Rainfall will stop
automatic irrigation which may be in progress, and a percentage of
the rainfall itself will be added to the soil and subtracted automatically
from the automatic irrigation, to prevent waste.
The ET Module receives the data from the ET Sensor, and applies it
to the individual zones of irrigation. The ET Module has settings to
customize each zone’s plant, soil, and sprinkler types, so that ET data
can be applied intelligently for each unique irrigation requirement. The
ET Module is plugged into the controller’s SmartPort and adjusts ir
rigation run times to only replace the amount of water the plants have
-
lost, at a rate at which they can absorb it. ET Module works by rewrit
ing Program “A” of the local controller on a daily basis except the ACC
controller (where it works independently of any programs).
-
How ET System Decides to Water: Using the local ET Sensor readings
and the ET Module’s database of station information, ET System pre
dicts the Management Allowable Depletion of water (MAD) available
to each plant type (ideally, a MAD of 30 to 50% is recommended for a
healthy landscape).
Each day, ET System looks at the current depletion level, ET rate, plant
type (crop coefficient and root zone), and whether the next day is an
allowable watering day. Then the system performs a “look ahead” on
the allowable watering days, to see if not watering now would take the
MAD below 50% by the time a watering day is scheduled.
Finally, the decision to start a specific station is also based upon a
minimum irrigation amount, to prevent shallow watering. Deeper
watering events encourage healthy root systems and plant growth.
The calculation for minimum sprinkler runtime is based upon the soil
type and capacity, where typically the MAD is between 30-50%. For
the worst-case scenario, sandy soil with spray heads, the minimum
runtime would then be approximately 7 minutes.
-
-
INSTALLINg ThE ET SENSOr ..............................................................................................................
Additional Tools and Materials
2 x 18 AWG/1mm dia. wire, solid or stranded (stranded preferred for
flexibility). Provide enough wire to connect the Sensor to the Module
(up to 100 ft/30m, green/black).
Shielded Wire: If wire runs absolutely must extend beyond 100
ft./30m, or the wire will be run through electrically noisy (high volt
age) environments, trouble can be minimized by using foil-shielded
wire. If shielded wire is to be used, attach the shielding to the black
wire on the sensor platform, ONLY. Do not ground the shield at each
end, only at the sensor.
There is no benefit in using larger conductor wires. Shielding is of
much greater benefit for longer runs of sensor wire. It may be pos
sible to double the recommended distance with shielded wire but this
is not guaranteed. If possible, extend the wire above-ground first and
test in the actual location, before proceeding with a permanent instal
lation.
-
-
Choose the Location
ET Sensor should be placed in an area representative of the plants it is
designed to irrigate.
The ET Sensor should be
grass area, approximately 6 ft./2m above the grass, with approxi-
mately 6 ft./2m of turf grass surrounding it on all sides. The ET
Sensor weighs approximately 6 lbs./2.5kg.
This may not always be practical, so choose the actual location ac
cording to the following guidelines:
a) ET Sensor must be mounted within 100 ft./30m of the ET Module
and the controller.
b) Avoid positioning ET Sensor over large areas of concrete, asphalt,
roof tile, or shingles. These surfaces will cause the sensors to
read much higher levels of ET than plants.
c) Choose a sunny location between 6 and 20 feet (2 and 7m) above
the ground.
post or pole-mounted in a full-sun turf
-
15 ft/5m Clearance From Any Structure
ICC Controller
ET Module
-
2 x 18 AWG/1mm,
100 ft/30m, Maximum
d) Do not mount the sensor where it will be hit by sprinkler spray or
other irrigation!
e) Do not mount the ET Sensor under a ledge or overhang, and avoid
placing it directly under tree canopies.
blocked sun and rain to function correctly!
f)
Do not mount the ET Sensor within falling distance of power
lines! High voltage shocks can injure and kill.
ET Sensor
Minimum
ET Sensor needs un-
6 ft/2m
Above
Turf,
g) Position the ET Sensor where it can be reached for occasional ser-
vice. The rain gauge should be checked and cleaned once a month
during the warmer months, to ensure that it is free of debris.
h) Avoid mounting sensor near any high intensity light, heat or infra
red sources as this may add excess ET amounts over time.
The ET Sensor is designed to adapt to steel fence poles (mounting
adapters included, requires 2 2" U-bolts), 4x4 (or larger) posts, or
eaves or walls.
Metal poles or weather-treated wooden posts are preferred, since
ET measurements will be somewhat less accurate if the sensor is
wall or eave-mounted.
Locate the 6-position screw terminal strip. Connect the two long
conductors (18 AWG, green and black) to the appropriately labeled
terminals. If an ET Wind Sensor is to be installed, this is also the time
to connect the wires.
-
Prevailing Wind Compensation
If ET Wind will not be connected,
a factor for average prevailing
winds in the installation area
Green and
Black Wires
ET Sensor Wiring
Before mounting the ET Sensor, connect the 18 AWG wires to the
terminal strip. This operation is much easier on the ground, prior to
mounting the sensor.
Locate the wiring compartment cover on the bottom of the ET Sensor.
This is a trap door, secured with 2 screws. Remove the wiring com
partment door screws and set in a safe place, and remove the wiring
compartment door.
can be entered while the wiring door is removed. The factory default
setting is 5 mph (8 kph). With the wiring cover removed, a DIP switch
is visible allowing other prevailing average wind speeds to be set,
according to the Table 1 (note that Switch 4 is not used).
If the optional ET Wind sensor is installed, mount the
ET Wind sensor according to its instructions, and
connect the blue and white conductors from the
ET Sensor to the appropriately labeled terminals
and secure their screws. Do not reverse the blue
and white wire connections from ET Wind…con
nect as shown!
Replace the wiring compartment door and secure
with the screws.
-
Metal Fence Pole
Steel adapters are supplied for most popular sizes
of galvanized steel fence posts, 2" diameter and
smaller.
Additional materials (not supplied): 2 x 2" galva-
nized or stainless steel U-bolts, 3" long or greater
4 nuts and washers for U-bolts
90 lb. bag of concrete
If pole is new construction for specific purpose
of mounting ET Sensor, dig approximately 12" x
12" hole and fill with approximately one 90 lb. bag
of concrete, or place as required by local code.
Insert pole, check with level and straighten, and
brace until concrete is firmly set.
Insert U-bolts around pole through steel pole
adaptors, and through mating holes in ET Sensor
back plane. Add washers, thread nuts onto U-bolt,
and tighten. Do not overtighten.
Route ET Sensor wire (2 x 18 AWG conductors) to
ground surface or burial trench, and run back to ET Module.
External mounting in outdoor low voltage conduit (for the above-
ground exposed portion of the wire run) is recom
mended for protection from the elements.
Wooden Post
Additional materials (not supplied): 4x4" pres-
sure-treated, outdoor, direct-burial grade 4x4" or
larger post.
4 x ¼" dia. x 1½" long galvanized or stainless steel
lag bolts and washers
Nut driver for lag bolts
90 lb. bag of concrete
Dig approximately 12" x 12" hole (or greater, as lo
cal code dictates) and fill with approximately one 90 lb.
bag of concrete. Insert post, check with level and straighten,
and brace until concrete is firmly set.
Level, mark, and drill pilot holes for 4 lag screws through back of ET
Sensor holes. Insert lag bolts and washers through mounting hole in
backplane of ET Sensor and tighten. Do not overtighten.
Route ET Sensor wire (2 x 18 AWG conductors) to ground sur face or
burial trench, and run back to ET Module.
External mounting in outdoor low voltage conduit (for the aboveground exposed portion of the wire run) is recommended for protec
tion from the elements.
Wall or Eave
Additional materials (not supplied): 4 x ¼" dia. x 1.5" long galvanized
or stainless steel lag bolts and washers.
Nut driver for lag bolts.
Level, mark, and drill pilot holes for 4 lag screws through back of ET
Sensor holes. Insert lag bolts and washers through mounting hole in
backplane of ET Sensor and tighten. Do not overtighten.
Route ET Sensor wire (2 x 18 AWG conductors) to ground sur face or
burial trench, and run back to ET Module.
-
-
-
Orange, or Blue-And-White-Striped
in some versions
Controller Connections
(ET System Only)
Blue: REM
White: AC2
Red: AC1
To ET Sensor
Green
Black
External mounting in outdoor low voltage conduit (for the aboveground exposed portion of the wire run) is recommended for protec
tion from the elements.
INSTALLINg ThE ET mOduLE ..............................................................................................................
The ET Module is designed to be wall-mounted, either in or outdoor,
immediately next (6 ft./2m) to the Hunter SmartPort-equipped irriga
tion controller (including models SRC, Pro-C, ICC, and ACC). The ET
Module is low-voltage only and does not require a separate high-volt
age power connection.
The ET Module is connected to the ET Sensor via the two 18 AWG con
ductors (up to 100 ft./30m away), and then wired into the SmartPort
wiring terminals inside the controller.
To wall mount the ET Module, choose a location within 6 ft./2m of the
controller. Avoid direct sunlight when possible (to enhance visibility of
the LCD display). Verify that the wallboard construction is of sufficient
strength to securely mount the small, lightweight enclosure.
The 6-conductor umbilical cord extends through the shielded hole in
the bottom of the enclosure. Verify that it remains clear and accessible
when securing the enclosure to the wall.
Use two anchors or self-tapping screws of minimum #12 (5.5mm)
diameter to secure the ET Module enclosure to the wall.
Turn off AC power to the irrigation controller, before connecting the
ET Module to the controller! The ET System receives its power from
the SmartPort connection to the Hunter controller. Do not connect the
ET Module to the controller while AC power is turned on.
ET Module Wiring
The 6-conductor umbilical cord from the ET Module is color-coded to
simplify connections.
Do NOT connect 110/230V high-voltage power to the ET System!
Make all wiring connections with approved butt splices or wire
nuts for 18 AWG/1mm wire, and place the splices in a suitable
junction box. Conduit is recommended for both indoor and
outdoor installations.
In all cases, ensure that any exposed wire loop from the ET Sensor to
the wire routing conduit does not swing freely in the wind, as this will
shorten its life.
Install CR2032 backup battery for date/time backup in event of power
-
failure (battery included with mounting hardware). Battery must be
installed with + visible, facing toward the installer.
-
If connecting the ET System to an ACC series controller, see ACC
section for special installation instructions.
-
ICC, Pro-C, and SRC controllers (ACC special instructions in next
section): Connect the green and black 18 AWG/1mm wires from the
Install CR2032 lithium battery (included)
under cover for time/date backup.
Inst all CR 2032 bat ter y
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.