LINKOSITYTM POWER DISTRIBUTION ASSEMBLY (PSDA)
MULTI-OUTLET ASSEMBLIES INSTALLATION INSTRUCTIONS
Wiring Device-Kellems
Disconnect power before installing or servicing.
CAUTION: RISK OF ELECTRIC SHOCK OR FIRE: The
LinkosityTM supply connection is not rated for current rupture and MUST NOT be used for disconnection under load.
For installation by a qualified personnel in accordance with
applicable codes and standards for the jurisdiction in which the LINKOSITY™ power system is to be installed.
Confirm device rating is proper for application.
Verify all connections are properly secured.
Enclosure Type 1. Intended ONLY for fixed installation in
dry, indoor locations. Ensure contaminants do not enter into the
unsafe condition may result.
LINKOSITY TM is a trademark of Lockheed Martin.
MUST be mounted to a structure with mechanical fasteners.
When connecting to LINKOSITYTM connectors the coupling nut is to
be made wrench tight; ¼ turn beyond hand-tight.

Supplementary Protec ti on

When provided, an outlet type PSDA may contain a Type CC
supplementary fuse of the 20-amp, ceramic body, fast blow, 1.25” x
0.25” type and has a voltage rating equal to or greater than 125 VAC.
This fuse is included to provide localized, coordinated protection.
Using engineering principles and practices it may be desirable in
certain applications to lower the ampere value of the supplementary fuse to accommodate a specific circumstance or connected load.
Reference:
LINKOSITY™ Power System Installer’s Guide Websites: http://www.hubbell-wiring.com