LINKOSITYTM POWER DISTRIBUTION ASSEMBLY (PSDA)
MULTI-OUTLET ASSEMBLIES INSTALLATION INSTRUCTIONS
• Disconnect power before installing or servicing.
• CAUTION: RISK OF ELECTRIC SHOCK OR FIRE: The
LinkosityTM supply connection is not rated for current
rupture and MUST NOT be used for disconnection under
load.
• For installation by a qualified personnel in accordance with
applicable codes and standards for the jurisdiction in which the
LINKOSITY™ power system is to be installed.
• Confirm device rating is proper for application.
• Verify all connections are properly secured.
• Enclosure Type 1. Intended ONLY for fixed installation in
dry, indoor locations. Ensure contaminants do not enter into the
unsafe condition may result.
LINKOSITY TM is a trademark of Lockheed Martin.
• MUST be mounted to a structure with mechanical fasteners.
• When connecting to LINKOSITYTM connectors the coupling nut is to
be made wrench tight; ¼ turn beyond hand-tight.
Supplementary Protec ti on
• When provided, an outlet type PSDA may contain a Type CC
supplementary fuse of the 20-amp, ceramic body, fast blow, 1.25” x
0.25” type and has a voltage rating equal to or greater than 125 VAC.
• This fuse is included to provide localized, coordinated protection.
• Using engineering principles and practices it may be desirable in
certain applications to lower the ampere value of the supplementary
fuse to accommodate a specific circumstance or connected load.
Reference:
LINKOSITY™ Power System Installer’s Guide