Hubbell’s non-automatic, LX-440, and automatic, LX-450, transfer switches are available in 2, 3, and 4
pole models with ampere ratings of 100 to 1250 A. The transfer switches are available as open type or
in an individual cabinet.
The automatic transfer switch has a Solid State Transfer Control Module, LX-301, that monitors voltage
and controls the transfer to and from the normal and emergency sources. The non-automatic transfer
switch has a selector switch to manually initiate transfer. A handle is included with all transfer switches
to manually close the normal or emergency contacts.
Emergency
Source
Normal
Source
PRM
optional
Control
Module
(LX-301)
To engine
start contacts
(If generator backup)
Normal Source
Transformer
Transfer Control
Relay Board
TSE
TSN
To load
Switching
Mechanism
Emergency Source
Transformer
Figure 1-1 Block Diagram of automatic transfer switch showing one phase
Page 3 of 16 Pages
Transfer Switch
2.0 Specifications and Certifications
Specifications
Switch MechanismSolenoid Actuation
Short Circuit Ratings of Transfer Switches
100 A
200 A
260, 400, 600 A
800, 1000, 1250 A
Control Voltage120 VAC
Pick-up Voltage90% of normal source voltage
Drop-out Voltage84% of normal source voltage
Auxiliary Contacts10 A, 125/250 VAC
Note
Time delay settings and voltage pick-up and drop-out levels are set at the factory and should not be
changed without consulting the factory.
RMS Symmetrical Amperes
42,000
50,000When protected by
65,000a circuit breaker.
85,000
90% of emergency source voltage
84% of emergency source voltage
Certifications
Hubbell’s Automatic transfer switches meet the requirements for all of the certifications listed below.
UL 1008 Standard for Safety for automatic transfer
switches
NEC Article 517, Health Care facilities
NEC Article 702, Optional Standby Systems
NEC Article 701, Legally Required Standby
Systems (LX-450 only)
NFPA 20 Installation of Fire Pumps
3.0 Installation
Refer to the transfer switch nameplate to ensure that the voltage, current, and horsepower ratings are
compatible with the load.
Refer to the receiving, handling, storage, installation, and inspection procedures in the Instruction
Manual that accompanies the combination Fire Pump Controller and automatic transfer switch. Many of
the procedures in the installation section are applicable to the automatic transfer switch in the adjoining
cabinet. For automatic transfer switches sold as an individual unit, and for additional information,
follow the procedures below.
Page 4 of 16 Pages
Transfer Switch
Receiving and Storage
After receiving the transfer switch inspect the cabinet for any damage that may have occurred during
shipping. If the transfer switch is not installed immediately, cover the cabinet and store in a dry area.
Condensation can corrode the contacts and other metal parts.
Location
The transfer switch should be located as close as possible to the engine generator or to the alternate
power source. If possible, there should be a clear line of sight between the transfer switch and the
engine generator.
Line Connections
Refer to the drawings posted inside the cabinet door and in the drawing packet for customer
connections.
Before drilling and punching holes in the cabinet for wiring connections cover the transfer switch with a
protective covering. Small debris falling into the automatic transfer switch may jam the switching
mechanism or may cause electrical failure.
Ensure that the normal (primary), emergency (alternate), and load isolation switches are open before
making connections. Connect the load, normal source, and emergency source power cables in the same
phase sequence. Refer to the latest NFPA 70 and Field Connections Wiring Diagram for cable sizes and
torque requirements.
All other standard customer connections are made to PTB1 on the left side of the mounting panel. Use
approved 14-gauge wire for all control connections. Typical field connections are shown below.
Terminal ConnectionsDescription
PTB1-1 and –2Engine Start Contact, for generator set
PTB1-5 and -6TSNa4 contacts closed, normal position
PTB1-7 and -8TSNa3 contacts closed, normal position
PTB1-9 and -10TSEa4 contacts closed, emergency position
PTB1-11 and -12TSEa3 contacts closed, emergency position
After installation is complete, perform a transfer test as described in section 6.0 Maintenance.
4.0 Operation
Refer to the schematic and wiring diagrams that are provided with the transfer switch. These drawings
are provided in a packet, along with this manual. A schematic is also posted on the inside of the cabinet
door.
Page 5 of 16 Pages
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.