Hubbell LX-1500 User Manual

Hubbell Industrial Controls, Inc.
A subsidiary of Hubbell Incorporated
50 Edwards St. Madison, OH 44057
Instruction Manual
Model LX-1500
HUBBELL
Telephone (440) 428-1161
FAX (440) 428-7635
Limited Service
Electric
Publication No. 197
April, 2000
Limited Service Fire Pump Controller
Table of Contents
I Introduction..................................................................................................................................3
II Specifications and Certifications................................................................................................3
Specifications ................................................................................................................................3
Certifications.................................................................................................................................4
III Receiving, Handling, and Storage .............................................................................................4
IV Installation................................................................................................................................. 4
V Sequence of Operation................................................................................................................5
VI Start Up Procedure....................................................................................................................7
VII Maintenance.............................................................................................................................9
Preventive Maintenance.................................................................................................................9
Troubleshooting.............................................................................................................................9
Coil and Contact Replacement.....................................................................................................10
VIII Limited Service Fire Pump Controller Parts....................................................................... 11
Attachments
Typical Controller Schematic Typical Field Connection Diagram
Notes Refer to job drawings for options. For combination Automatic Transfer Switch/Fire Pump Controller applications, refer to Publication No. 186 for the LX-250 Transfer Switch or Publication No. 195 for the LX-350 Transfer Switch, for details.
Page 2 of 12
Limited Service Fire Pump Controller
Line
Suppressor
L1 M1 T1
PLM
CONTROL
I Introduction
The Hubbell Limited Service Fire Pump Controller provides automatic and manual control of small electric motor driven fire pumps and booster pumps of 30 horsepower or less.
All Controller components are inside the cabinet with indicating lights and switch handles located next to the door. A pressure switch initiates automatic starting of the pump motor. The Controller monitors the power phases and voltage. The CIRCUIT BREAKER DISCONNECTING MEANS handle has a door interlock feature to prevent opening the door when the switch is closed. The Controller also has an EMERGENCY MANUAL CONTROL handle to start the fire pump manually.
CIRCUIT
BREAKER
DISCONNECTING
Incoming Phase
MEANS
Pressure Switch
Surge
Control Panel
Figure I-1 Block diagram of LX-1500 showing one phase
II Specifications and Certifications
EMERGENCY MANUAL
To Fire Pump Motor
Control Transformer
Specifications
Voltage Phase Loss/Reversal Module
200 Series 300 Series 400 Series
Maximum Voltage 10% of highest nominal voltage Maximum Frequency Shift 0.1 Hz Phase Loss 18% of low voltage in one phase
208, 240, 380, 480C A-B-C phase rotation 208–240 VAC, 60 Hz, 3 phase
380–415 VAC, 50 Hz, 3 phase 440–480 VAC, 60 Hz, 3 phase
Page 3 of 12
Limited Service Fire Pump Controller
Undervoltage Trip 15% below set point Time Delays Pick-up, 1.5 s, fixed
Drop-out, 1.5 s, fixed
Output Relays 10 A, 120 VAC
5 A, 240 VAC
Indication green LED, on for A-B-C phase rotation
Surge Suppressor
Temperature
650 V rating Operating: −4° F to 104° F (−20° C to 40° C)
Storage: −4° F to 182° F (−20° C to 85° C)
Certifications
The Hubbell Limited Service Electric Fire Pump Controller is built to NFPA 20 requirements. The Controller is listed by:
Underwriters Laboratory Factory Mutual Underwriters Laboratory Canada New York City Canadian Standards Association
III Receiving, Handling, and Storage
1. Immediately upon receipt, carefully unpack and inspect the Controller for damage that may
have occurred in shipment. If damage or rough handling is evident, file a damage claim with the transportation carrier.
2. If the Controller must be stored, cover it and place in a clean, dry location. Avoid unheated
locations where condensation can result in damage to the insulation or corrosion of metal parts.
IV Installation
1. Consult the motor nameplate to determine voltage, current, and horsepower rating and
compare with the Controller nameplate for matching data.
2. Release the door interlock by moving the CIRCUIT BREAKER DISCONNECTING MEANS to the OFF position.
3. Inspect the control transformer’s primary connections for agreement with the line voltage of the incoming power.
4. Exercise all switches and contactors, without power, to see that they operate freely.
5. Choose a location or base for the Controller that is non-combustible and within site of the motor. The base should not be subject to excessive vibration that may cause erratic operation of the PS (pressure switch). The Controller should be leveled so that the PS is level. Sight across the PS cover screws.