Page 2 of 5
3940 Dr. Martin Luther King Drive
St. Louis, MO 63113
P/N KIL00921449 FORM NO. K1449 ECO6-012-17 1/17
Conditions for Safe Use
The Luminaire shall only be installed where there is
a low risk of mechanical damage.
Potential electrostatic charging hazard, clean with
damp cloth.
Luminaires are designed to be installed in
Hazardous Locations: Class I, Division 2, Groups A,
B, C and D; Class II,
Division 1, Groups E, F and G; Class III; T4A, T5 or
T6 (Class I, Div. 2), T4A (Class II, Div. 1), T4A (Class
I, Div 2 / Class
II, Div. 1 Simultaneous Exposure); Type 4X; Type
6P; Marine Rated (US only);IP66; IPX7.
IEC Zone 2. IEC 60079-0:2012 IEC 60079-15:2010
and IEC 60079-31:2014 Zone 2 type of protection
Ex nA (non-sparking), Zone 21 type of protection Ex
tb (dust).
STANDARD VERSION EMERGENCY VERSION
II 3G Ex nA IIC T4/T5/T6* Gc II 3G Ex nA IIC T5/T6* Gc
II 2D Ex tb IIIC T95°C/T120°C* Db II 2D Ex tb IIIC T95°C Db
-40°C<Tamb<+65°C < 45W -20°C<Tamb<+50°C
-40°C<Tamb<+40°C/+55°C > 45W
*Depending on wattage and ambient temperature
IECEx certicate IECEx QPS 15.0010X.
ATEX certicate CML15ATEX4081X (nA)
CML15ATEX3082X (tb).
NOTE: Due to the surge protection provided in the
xture to protect the internal electronics and LEDs,
a branch circuit with the LED xture may false fail
a megohmmeter test (sometimes referred to as a
megger test). If a megohmmeter test is required,
the LED xture should be removed from the branch
circuit.
NOTE: Multiple uorescent or LED xtures
attached to a single Ground Fault Circuit Interrupter
(GFCI) may cause nuisance tripping of the GFCI.
Regulatory agencies allow a small amount of
leakage current because of the circuitry required
to mitigate possible issues with electromagnetic
compatibility (reference UL8750 and EN61347). The
summation of these leakage currents from multiple
xtures may be enough to trip a GFCI.
NOTE: For Class I, Division 2 / Class II, Division 1
/ Class I, Zone 2 Hazardous Locations, use rigid
conduit or appropriate cable connectors/ glands
rated for Class I, Division 2 Groups BCD (or IEC
Zone 2 IIC, IEC Zone 21 IIIC) hazardous areas.
NOTE: Pour les endroits dangereux Classe I,
Division 2 / Classe II, Division 1 / Classe I, Zone 2
utiliser des Conduits rigides.
LAL
LALFP