Hubbell LAL Installation, Operation & Maintenance Data Sheet

Page 1 of 5
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N KIL00921449 FORM NO. K1449 ECO6-012-17 1/17
INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
LAL SERIES LED LUMINAIRE
CAUTION:
Before installing, make sure you are compliant with area classications, failure to do so may result in bodily injury, death and property damage. Do not attempt installation until you are familiar with the following procedures. All installation must comply with the applicable Electrical Code. Make sure that the circuit is de-energized before starting installation or maintenance. Verify that the installation is grounded. Failure to ground will create electrical shock hazards, which can cause serious injury and or death.
IMPORTANT:
Technical information, advice and recommendations contained in these documents are based on information that Killark believes to be reliable. All the information and advice contained in these documents is intended only for use by persons having been trained and possessing the requisite skill and know-how and to be used by such persons only at their own discretion and risk. The nature of these instructions is informative only and do not cover all of the details, variations or combinations in which this equipment may be used, its storage, delivery, installation, check out, safe operation, and maintenance. Since conditions of use of the product are outside of the care, custody and control of Killark, the purchaser should determine the suitability of the product for its intended use, and assumes all risk and liability whatsoever in connection therewith.
ATTENTION:
Avant d’installer le luminaire, s’assurer que le luminaire est conforme à la classication des zones, le non­respect de cette règle risque d’entraîner des dommages corporels et / ou matériels. Ne pas tenter d’entreprendre l’installation avant d’être familiarisé avec les procédures suivantes. Toute installation doit être conforme au code électrique local et / ou national et être effectuée par un électricien qualié. Veiller à ce que le circuit soit mis hors tension avant de commencer l’installation ou la maintenance. Vérier si le luminaire est mis à la terre. S’il n’est pas mis à la terre il pourrait causer des risques de choc électrique susceptibles d’entraîner des blessures graves ou la mort.
Page 2 of 5
3940 Dr. Martin Luther King Drive St. Louis, MO 63113
P/N KIL00921449 FORM NO. K1449 ECO6-012-17 1/17
Conditions for Safe Use
The Luminaire shall only be installed where there is a low risk of mechanical damage. Potential electrostatic charging hazard, clean with damp cloth.
Luminaires are designed to be installed in Hazardous Locations: Class I, Division 2, Groups A, B, C and D; Class II, Division 1, Groups E, F and G; Class III; T4A, T5 or T6 (Class I, Div. 2), T4A (Class II, Div. 1), T4A (Class I, Div 2 / Class II, Div. 1 Simultaneous Exposure); Type 4X; Type 6P; Marine Rated (US only);IP66; IPX7. IEC Zone 2. IEC 60079-0:2012 IEC 60079-15:2010 and IEC 60079-31:2014 Zone 2 type of protection Ex nA (non-sparking), Zone 21 type of protection Ex tb (dust).
STANDARD VERSION EMERGENCY VERSION
II 3G Ex nA IIC T4/T5/T6* Gc II 3G Ex nA IIC T5/T6* Gc
II 2D Ex tb IIIC T95°C/T120°C* Db II 2D Ex tb IIIC T95°C Db
-40°C<Tamb<+65°C < 45W -20°C<Tamb<+50°C
-40°C<Tamb<+40°C/+55°C > 45W
*Depending on wattage and ambient temperature IECEx certicate IECEx QPS 15.0010X. ATEX certicate CML15ATEX4081X (nA) CML15ATEX3082X (tb).
NOTE: Due to the surge protection provided in the xture to protect the internal electronics and LEDs, a branch circuit with the LED xture may false fail a megohmmeter test (sometimes referred to as a megger test). If a megohmmeter test is required, the LED xture should be removed from the branch circuit.
NOTE: Multiple uorescent or LED xtures attached to a single Ground Fault Circuit Interrupter (GFCI) may cause nuisance tripping of the GFCI. Regulatory agencies allow a small amount of leakage current because of the circuitry required to mitigate possible issues with electromagnetic compatibility (reference UL8750 and EN61347). The
summation of these leakage currents from multiple
xtures may be enough to trip a GFCI.
NOTE: For Class I, Division 2 / Class II, Division 1 / Class I, Zone 2 Hazardous Locations, use rigid conduit or appropriate cable connectors/ glands rated for Class I, Division 2 Groups BCD (or IEC Zone 2 IIC, IEC Zone 21 IIIC) hazardous areas.
NOTE: Pour les endroits dangereux Classe I, Division 2 / Classe II, Division 1 / Classe I, Zone 2 utiliser des Conduits rigides.
LAL
LALFP
Loading...
+ 3 hidden pages