2112 Fenton Logistics Park Blvd
Fenton, Missouri 63026 USA
P/N KIL00921498 FORM NO. K1498 ECO-6-023-19 R04/19 Page 1 of 4
L1L SERIES LED LUMINAIRE
CAUTION:
Before installing, make sure you are compliant with area classifications, failure to do so may result in bodily injury, death
and property damage. Do not attempt installation until you are familiar with the following procedures. All installation must
comply with the applicable Electrical Code.
Make sure that the circuit is de-energized before starting installation or maintenance.
Verify that the installation is grounded. Failure to ground will create electrical shock hazards, which can cause serious
injury and or death.
IMPORTANT:
Technical information, advice and recommendations contained in these documents are based on information that Killark
believes to be reliable. All the information and advice contained in these documents is intended only for use by persons
having been trained and possessing the requisite skill and know-how and to be used by such persons only at their own
discretion and risk.
The nature of these instructions is informative only and do not cover all of the details, variations or combinations in which
this equipment may be used, its storage, delivery, installation, check out, safe operation, and maintenance. Since
conditions of use of the product are outside of the care, custody and control of Killark, the purchaser should determine the
suitability of the product for its intended use, and assumes all risk and liability whatsoever in connection therewith.
ATTENTION:
Avant d’installer le luminaire, s’assurer que le luminaire est conforme à la classification des zones, le non- respect de
cette règle risque d’entraîner des dommages corporels et / ou matériels. Ne pas tenter d’entreprendre l’installation avant
d’être familiarisé avec les procédures suivantes. Toute installation doit être conforme au code électrique local et / ou
national et être effectuée par un électricien qualifié.
Veiller à ce que le circuit soit mis hors tension avant de commencer l’installation ou la maintenance.
Vérifier si le luminaire est mis à la terre. S’il n’est pas mis à la terre il pourrait causer des risques de choc électrique
susceptibles d’entraîner des blessures graves ou la mort.
WARNING:
Incorrect installation of this Luminaire might cause potential ignition sources from optical radiation. Follow
INSTALLATION, OPERATION & MAINTENANCE DATA SHEET.
INSTALLATION, OPERATION &
MAINTENANCE DATA SHEET
L1L SERIES LED LUMINAIRE

2112 Fenton Logistics Park Blvd
Fenton, Missouri 63026 USA
P/N KIL00921498 FORM NO. K1498 ECO-6-023-19 R04/19 Page 2 of 4
Luminaires are designed to be installed in Hazardous Locations: Class I, Division 1 & 2, Groups A, B, C and D; Class 1,
Zones 1 & 2, Groups IIB, IIA; Class II, Div. 1 & 2, Groups E, F, G; Class III; IP66 Suitable for Wet Locations; Suitable for
paint spray booths. T-Code T6 40C & 55C CID1; T6 CIID1 40C; T5 CIID1 55C.
IECEx certificate IECEx QPS 19.0005X. ATEX certificate CML 19ATEX1289X
Ex db op is IIB+H2 T6...T5 Gb Ta: -20°C to +40°C, or Ta: 20°C to +55°C
Ex db op is IIB+H2 T6...T5 Gb Ta: -0°C to +40°C, or Ta: 0°C to +48°C
Ex tb op is IIIC T85°C... T100°C Db -20°C to +40°C, or Ta:
-20°C to +55°C
Ex tb op is IIIC T85°C... T100°C Db -0°C to +40°C, or Ta: 0°C to +48°C
Light Output Rating: 50Watts-100 Watts. (IECEx and ATEX Certifications are for 120-277VAC 50-60 Hz. 1.22A-.95A
input versions only.)
Protection Standards: IECEx: (IEC) 60079-0:2017, Edition 7.0; 60079-1:2014, Edition 7.0;60079-28:2015, Edition
2.0;60079-31:2013, Edition 2.0. ATEX: (EN) 60079-0:2017; 60079-1:2012; 60079-28:2006; 60079-31:2010.
ATEX Declaration: The equipment is declared to meet the provisions of the ATEX directive (2014/34/EU) by reason of the
EC Type Examination and compliance with the Essential Health and Safety Requirements. T. Michalski : Certifications
Manager
Note: Due to the surge protection provided in the fixture to protect the internal electronics and LEDs, a branch
circuit with the LED fixture may false fail a megohmmeter test (sometimes referred to as a megger test). If a
megohmmeter test is required, the LED fixture should be removed from the branch circuit.
Note: Multiple fluorescent or LED fixtures attached to a single Ground Fault Circuit Interrupter (GFCI) may cause
nuisance tripping of the GFCI. Regulatory agencies allow a small amount of leakage current because of the circuitry
required to mitigate possible issues with electromagnetic compatibility (reference UL8750 and EN61347). The
summation of these leakage currents from multiple fixtures may be enough to trip a GFCI.
NOTE- For Class I, Division 1 / Class II, Division 1 / Class I, Zone 1 Hazardous Locations, use rigid conduit
or appropriate cable connectors/ glands rated for Class I, Division 1 Groups BCD
NOTE – Pour les endroits dangereux Classe I, Division 1 / Classe II, Division 1 / Classe I, Zone 1 utiliser des
Conduits rigides.
L1L INSTALLATION INSTRUCTIONS:
A. A channel is incorporated in the housing for 5/16” or M8 hex bolts or nuts. (See Figure 1)
1. 5/16” or M8 hex bolts can be slid into channels for direct mounting; or used to attach brackets which
include L- brackets, Wall Brackets, Ceiling Brackets, Beam Clamps, and Suspension Chains etc…
2. 5/16” hex nuts or M8 hex nuts can be slid into channels and used with eyebolts, threaded rod
etc…
B. The End Caps also have provisions for surface or suspension mounting. (See Figure 2)
C. The “Earthquake Safety Chain” can be attached to the housing using an optional eye bolt. (See
Figure 2).
Figure 1 Figure 2 (Top View)
Special Conditions for Safe Use
The Luminaire shall only be installed where there is a low risk of mechanical damage.