No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Indicates an imminently hazardous situation which, if not
avoided, will result in serious injury or death.
Indicates a potentially hazardous situation which, if not
avoided, could result in serious injury or death.
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.
Calls attention to important information, best practices and
tips.
NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.
This document describes the SUN2000-33KTL-US/36KTL-US/40KTL-US (SUN2000 for
short) in terms of its installation, electrical connections, commissioning, maintenance, and
troubleshooting. Understand the safety information and get familiar with the SUN2000
functions and features before installing and operating the SUN2000.
Intended Audience
About This Document
This document is intended for photovoltaic (PV) power plant personnel and qualified
electrical technicians.
Symbol Conventions
The symbols that may be found in this document are defined as follows.
2.4 Working Principle ....................................................................................................................................................... 14
4.3 Determining the Installation Position ......................................................................................................................... 22
4.4 Moving the Inverter .................................................................................................................................................... 27
4.5 Installing the Mounting Plate ...................................................................................................................................... 27
5.1 Preparing OT Terminals .............................................................................................................................................. 38
5.2 Connecting the Ground Cable ..................................................................................................................................... 39
5.2.1 Grounding the SUN2000 over a PE Point ............................................................................................................... 40
5.2.2 PV Side Grounding .................................................................................................................................................. 41
5.3 Opening the Maintenance Compartment Door ........................................................................................................... 42
5.4 Connecting AC Output Power Cables ......................................................................................................................... 44
5.4.1 Connection Through a Pipe ..................................................................................................................................... 45
5.4.2 Common Connection ............................................................................................................................................... 51
5.5 (Optional) Installing the DC Protection Shroud ......................................................................................................... 57
5.6 Connecting DC Input Power Cables ........................................................................................................................... 59
5.7.2 Selecting a Mode for Connecting RS485 Communications Cables ......................................................................... 67
5.7.3 Connecting RS485 Communications Cables Through a Pipe .................................................................................. 70
5.7.4 Connecting the RS485 Communications Cable in a Common Way ........................................................................ 75
5.8 Closing the Maintenance Compartment Door ............................................................................................................ 79
6 System Commissioning ............................................................................................................. 82
6.1 Checking Before Power-On ........................................................................................................................................ 82
6.2 Powering On the SUN2000 ........................................................................................................................................ 82
6.3 Powering Off the SUN2000 ........................................................................................................................................ 88
7.1 Operations with a USB Flash Drive............................................................................................................................ 90
7.1.3 Exporting Data ......................................................................................................................................................... 93
7.2 Operations with a SmartLogger .................................................................................................................................. 96
7.3 Operations with the NMS ........................................................................................................................................... 96
7.4 Operations with the SUN2000 APP ............................................................................................................................ 96
9 Handling the SUN2000 ............................................................................................................ 105
9.1 Removing the SUN2000 ........................................................................................................................................... 105
9.2 Packing the SUN2000 ............................................................................................................................................... 105
9.3 Disposing of the SUN2000 ................................................................................................................................ ....... 105
Before performing operations, read through this manual and follow all the precautions to
prevent accidents. The safety precautions provided in this document do not cover all the
safety precautions. Huawei shall not be liable for any consequence caused by the violation of
the safety operation regulations and design, production, and usage standards.
Declare
Huawei shall not be liable for any consequence caused by any of the following events.
Transportation
The storage conditions do not meet the requirements specified in this document.
Violate the operation instructions and safety precautions in this document for installation,
cable connecting, and maintenance.
Operation in extreme environments which are not covered in this document
Unauthorized modifications to the product or software code
Installation or use in environments which are not specified in related international
standards
Important Safety Instructions
Save These Instructions: This manual contains important instructions for the
SUN2000-33KTL-US/36KTL-US/40KTL-US that shall be followed during installation and
maintenance of the SUN2000.
Caution: Changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Personnel Requirements
Only qualified electrical technicians are allowed to install and operate the SUN2000.
Operation personnel should receive professional training.
Operation personnel should read through this document and follow all the precautions.
Operation personnel should be familiar with the safety specifications about the electrical
system.
Operation personnel should understand the composition and working principles of the
grid-tied PV power system and local regulations.
Do not tamper with any warning signs on the SUN2000 chassis because these signs
contain important information about safe operation.
Do not tamper with the nameplate on the SUN2000 chassis because it contains important
product information.
Do not remove the warranty label from the SUN2000 chassis. Otherwise, product
warranty will be forfeited.
Ensure that the SUN2000 is not connected to a power supply and is not powered on
before starting installation.
Ensure that there are no objects within 300 mm (11.81 in.), 200 mm (7.87 in.), 500 mm
(19.69 in.), 600 mm (23.62 in.), and 1000 mm (39.37 in.) of the left, right, top, bottom,
and front of the SUN2000, respectively. This is to allow sufficient space for installation
and heat dissipation. For ease of installation, ensure that the SUN2000 bottom is at most
730 mm (28.74 in.) from the ground. If you have any questions about the distance,
consult the local technical support engineers.
Ensure that the SUN2000 is installed in a well ventilated environment.
Ensure that the SUN2000 heat sinks are free from blockage.
Open the maintenance compartment door of the chassis before connecting cables. Do not
perform any operation on other components inside the chassis except connecting AC
power cables and communications cables.
Cable Connections
Before connecting cables, ensure that the SUN2000 is securely positioned and not damaged in
any way. Otherwise, electric shocks or fire may occur.
Ensure that all electrical connections comply with local electrical standards.
Obtain approval from the local power supply department before using the SUN2000 to
generate electricity in grid-tied mode.
Ensure that the cables used in a grid-tied PV power system are properly connected and
insulated and meet specifications.
High voltages may cause electric shocks and serious injuries during SUN2000 operating.
Strictly comply with the safety precautions in this document and associated documents when
operating the SUN2000.
Do not touch an operating SUN2000 because the heat sinks may have a temperature over
60°C (140°F) and may cause burns when the SUN2000 is operating.
Follow local laws and regulations when operating the equipment.
Maintenance and Replacement
High voltages may cause electric shocks and serious injuries during SUN2000 operating.
Therefore, before maintenance, power off the SUN2000 and strictly comply with the safety
precautions in this document and associated documents to operate the SUN2000.
Maintain the SUN2000 with sufficient knowledge of this document and proper tools and
testing equipment.
Before performing maintenance tasks, power off the SUN2000 and wait at least 5
minutes.
Place temporary warning signs or erect fences to prevent unauthorized access to the
maintenance site.
Rectify any faults that may compromise the SUN2000 security performance before
powering on the SUN2000 again.
Observe ESD precautions during the maintenance.
For personal safety, wear insulation gloves and protective shoes.
The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC power
generated by PV strings into AC power and feeds the power into the power grid.
2 Overview
Model
Figure 2-1 describes the model number of the SUN2000-33KTL-US.
Figure 2-1 Model number description
Table 2-1 describes the rated output power and voltage of all models of SUN2000s.
Table 2-1 SUN2000 models and corresponding rated output power and voltage
The SUN2000 applies to grid-tied PV power systems for commercial rooftops and large
power stations. Typically, a grid-tied PV power system consists of PV strings, grid-tied
inverters, AC power distribution units, and isolation transformers.
Figure 2-2 Network application
Power Grid Types
Power grid types supported by the SUN2000 include TN-S, TN-C, TN-C-S, TT, and IT.
Blinking red at
long intervals
(on for 1s and
then off for 4s)
A warning alarm is generated.
Blinking red at
short intervals
(on for 0.5s and
then off for 0.5s)
A minor alarm is generated.
Steady red
A critical alarm is generated.
Local
maintenance
status
Blinking green
at long intervals
(on for 1s and
then off for 1s)
Local maintenance is in
progress.
Blinking green
at short intervals
(on for 0.125s
and then off for
0.125s)
Local maintenance fails.
Steady green
Local maintenance succeeds.
SUN2000 Rear View
Local maintenance refers to operations performed after a universal serial bus (USB) flash drive,
Bluetooth module, or USB data cable is inserted into the USB port of the SUN2000. For example,
local maintenance includes data import and export using a USB flash drive and connecting to the
SUN2000 APP over a Bluetooth module or USB data cable.
If alarming and local maintenance happen concurrently, the alarm/maintenance indicator shows the
local maintenance state first. After the USB flash drive, Bluetooth module, or USB data cable is
removed, the indicator shows the alarm state.
No user serviceable parts inside. Only trained
service personnel are allowed access.
Both AC and DC voltage sources are
terminated inside this equipment. Each circuit
must be disconnected before servicing.
When the photovoltaic array is exposed to light,
it supplies DC voltage to this equipment.
The DC conductors of this photovoltaic system
are ungrounded and may be energized.
The DC conductors of this photovoltaic system
are normally ungrounded but will become
intermittently grounded without indication
when the SUN2000 measures the PV array
isolation.
Burn warning
Do not touch a running SUN2000 because it
generates high temperatures on the shell.
Waterproof cable connector is abbreviated as waterproof connector in the following text.
2.3 Label Description
Warning Signs
Warning signs are available on the SUN2000 side, as described in Table 2-3.
High voltage exists after the SUN2000 is
powered on. Only qualified and trained
electrical technicians are allowed to perform
operations on the SUN2000.
Residual voltage exists after the SUN2000 is
powered off. It takes 5 minutes for the
SUN2000 to discharge to the safe voltage.
Transformerless
inverter
The SUN2000 output does not pass through an
isolation transformer.
Symbols
Symbol
Name
Meaning
PE point
Indicates the position for
connecting the PE cable.
Operation warning
Do not remove the DC
input connector when the
SUN2000 is running.
DC terminal operation
warninga
High voltage exists after
the SUN2000 is powered
on. To avoid electric
shocks, perform the
following system
power-off operations
before plugging or
unplugging DC input
connectors of the
SUN2000:
1. Send a shutdown
command.
2. Turn off the
downstream AC
switch.
3. Turn off the two DC
switches at the bottom.
Warranty label
Never open the host panel
of the SUN2000.
Table 2-4 describes the labels on the SUN2000 chassis and their meanings.
The SUN2000 is heavy
and needs to be carried by
multiple persons.
Note a: Fittings delivered with the SUN2000 contain the label of DC terminal operation
warning. You are advised to attach the label at the bottom of the SUN2000 front side, as
shown in Figure 2-8. You can also select an appropriate place for attaching the label based
on site requirements.
Figure 2-8 Place for attaching
Nameplate
On the side of the SUN2000, there is a nameplate that contains the model information,
technical specifications, and compliance symbols, as shown in Figure 2-9.
Do not dispose of the
SUN2000 as household
garbage.
2.4 Working Principle
Conceptual Diagram
The SUN2000 receives inputs from eight PV strings. Then the inputs are grouped into four
MPPT routes inside the SUN2000 to track the maximum power point of the PV strings. The
DC power is then converted into three-phase AC power through an inverter circuit. Surge
protection is supported on both the DC and AC sides. Figure 2-10 shows the SUN2000
conceptual diagram.
Figure 2-10 SUN2000 conceptual diagram
Working Modes
The SUN2000 can work in standby, operating, or shutdown mode. Figure 2-11 shows the
relationship between the three working modes.
The SUN2000 enters the standby mode when the external environment does
not meet the requirements for starting the SUN2000. In standby mode:
The SUN2000 continuously performs self-check and enters the operating
mode once the operating requirements are met.
If the SUN2000 enters the shutdown mode after detecting a shutdown
command or a fault after startup.
Operating
In operating mode:
The SUN2000 converts DC power from PV strings into AC power and
feeds the power to the power grid.
The SUN2000 tracks the maximum power point to maximize the PV
string output.
The SUN2000 enters the shutdown mode after detecting a fault or a
shutdown command, and enters the standby mode after detecting that the
PV string output power does not meet the requirements for grid-tied
electricity generation.
Shutdown
In standby or operating mode, the SUN2000 enters the shutdown mode
after detecting a fault or shutdown command.
In shutdown mode, the SUN2000 enters the standby mode after detecting
a startup command or that a fault is rectified.
Table 2-6 describes the three working modes shown in Figure 2-11.
Before unpacking the inverter, check the outer packing materials for damage, such as holes
and cracks, and check the inverter model. If any damage is found or the inverter model is not
what you requested, do not unpack the package and contact your supplier as soon as possible.
Figure 4-1 Position of the inverter model label
Package Contents
After unpacking the inverter, check that the contents are intact and complete. If any damage is
found or any component is missing, contact your supplier.
You are advised to remove the packing materials within 24 hours before installing the inverter.
For details about the number of contents, see the Packing List in the packing case.
Install devices in accordance with the installation laws and regulations of the country or
region where the project is located.
4.3 Determining the Installation Position
Basic Requirements
The SUN2000 is protected to Type 4X and can be installed indoors or outdoors.
Do not install the SUN2000 in a place where personnel are easy to come into contact
with its chassis and heat sinks, because these parts are extremely hot during operation.
Do not store the SUN2000 in areas with flammable or explosive materials.
Installation Environment Requirements
The SUN2000 must be installed in a well ventilated environment to ensure good heat
dissipation. When installed under direct sunlight, performance de-rate may be initiated due to
additional temperature rise.
Carrier Requirements
The carrier where the SUN2000 is installed must be fireproof.
Do not install the SUN2000 on flammable building materials.
The SUN2000 weighs 55 kg (121.25 lb). Ensure that installation surface is solid enough
to bear the SUN2000.
In residential areas, do not install the SUN2000 on gypsum boards or walls made of
similar materials which have a weak sound insulation performance because the noises
generated by the SUN2000 disturb residents.
Installation Angle Requirements
The SUN2000 can be installed on a wall, normal support, and tilted support.
Tilt requirements for installing a SUN2000 on a wall and normal support:
Install the SUN2000 vertically or at a maximum back tilt of 15 degrees to facilitate heat
dissipation.
The SUN2000 may operate with power derating if installed with a tilt.
Installation Space Requirements
The SUN2000 dimensions (W x H x D, including the mounting plate) are 930 mm x 550
mm x 283 mm (36.61 in. x 21.65 in. x 11.14 in.). Reserve enough clearance around the
SUN2000 to ensure sufficient space for installation and heat dissipation, as shown in
For ease of installing the SUN2000 on the mounting bracket, connecting cables to the bottom of the
SUN2000, and maintaining the SUN2000 in future, it is recommended that the bottom clearance be
between 600 mm (23.62 in.) and 730 mm (28.74 in.). If you have any questions about the distance,
consult the local technical support engineers.
When installing multiple SUN2000s, install them in horizontal mode if sufficient space
is available and install them in triangle mode if no sufficient space is available. Stacked
installation is not recommended. The following figures show the wall-mounted
installation modes and provide reference for other installation modes.
To prevent device damage and personal injury, keep balance when moving the SUN2000
because the SUN2000 is heavy.
Do not place the SUN2000 with its wiring terminals at the bottom contacting the floor or
any other object because the terminals are not designed to support the weight of the
SUN2000.
When placing the SUN2000 on the floor, put foam or paper under the SUN2000 to protect
its cover.
Procedure
Step 1 Arrange two persons to hold the handles on both sides of the SUN2000.
Figure 4-8 Moving the SUN2000
Step 2 Lift the SUN2000 from the packing case and move it to the installation position.
----End
4.5 Installing the Mounting Plate
Figure 4-9 shows the SUN2000 mounting plate dimensions. Figure 4-10 shows the position
The mounting plate has four groups of tapped holes, each group containing four tapped
holes. Mark any hole in each group based on site requirements and mark four holes in total.
Two round holes are preferred.
Before installing the mounting plate, remove the security torx wrench from the mounting
plate and set it aside.
Figure 4-9 Mounting plate dimensions
Figure 4-10 Position for saving a security torx wrench
4.5.1 Wall-mounted Installation
Procedure
Step 1 Determine the positions for drilling holes using the mounting bracket. Level the hole positions
using a level, and mark the hole positions using a marker.
Figure 4-13 Drilling a hole and installing an expansion bolt
To prevent dust inhalation or contact with eyes, wear safety goggles and an anti-dust
respirator when drilling holes.
Wipe away any dust in or around the holes and measure the hole distance. If the holes are
inaccurately positioned, drill holes again.
Level the head of the expansion sleeve with the concrete wall after removing the bolt,
spring washer, and flat washer. Otherwise, the mounting bracket will not be securely
installed on the concrete wall.
1. Drill a hole at a marked hole position in the wall using a hammer drill.
2. Slightly tighten an expansion bolt, vertically insert an expansion bolt into a hole, and
knock the expansion bolt completely into the hole by using a rubber mallet.
3. Partially tighten the expansion bolt.
4. Remove the nut, spring washer, and flat washer.
Step 3 Align the mounting bracket holes with the drilled holes, insert expansion bolts into the holes
through the mounting bracket, and then tighten the expansion bolts.
Step 3 Align the mounting bracket holes with the drilled holes, insert the delivered bolt assemblies
(flat washers, spring washers, and bolts) into the holes through the mounting bracket, and
secure them using the stainless steel nuts and flat washers.
If the screw length does not meet the installation requirements, prepare M12 bolt assemblies by yourself.
Step 3 Align the mounting bracket holes with the drilled holes, insert the delivered bolt assemblies
(flat washers, spring washers, and bolts) into the holes through the mounting bracket, and
secure them using the stainless steel nuts and flat washers.
If the screw length does not meet the installation requirements, prepare M12 bolt assemblies by yourself.
Figure 4-20 Securing a mounting bracket
----End
4.6 Installing the SUN2000
Procedure
Step 1 If the installation position is low and you can mount the SUN2000 onto the mounting bracket,
go to Step 3 and then Step 5.
Step 2 If the installation position is high and you cannot mount the SUN2000 onto the mounting
bracket, perform Step 3 to Step 6.
Step 3 Ensure that two people lift the SUN2000 and turn it upright. Lift the SUN2000 by grasping
the handle at the bottom of the SUN2000 with one hand and the handle at the top with the
other.
To prevent personal injury caused by a falling SUN2000, keep balance when lifting the
SUN2000 because it is heavy.
Before connecting cables, ensure that the two DC switches on the inverter are OFF. Otherwise,
the high voltage of the inverter may result in electric shocks.
The cable colors shown in the electrical connection drawings provided in this chapter are for reference
only. Select cables in accordance with local cable specifications (green-and-yellow wires are used for
grounding only).
Avoid scratching the core wire when stripping a cable.
The cavity formed after the conductor crimp strip of the OT terminal is crimped must wrap
the core wires completely. The core wires must contact the OT terminal closely.
Wrap the wire crimping area with heat shrink tubing or PVC insulation tape. The
following figure uses heat shrink tubing as an example.
When using the heat gun, protect devices from being scorched.
Proper grounding is helpful for resisting the impact of surge voltage and improving the
electromagnetic interference (EMI) performance. Before connecting the AC power cable,
DC power cable, and communications cable, connect ground cables to the PE point and
PV side ground point.
It is recommended that the ground cable be connected to a nearby ground point. Connect
the ground points of all SUN2000s in the same PV array to ensure equipotential
connections to ground cables.
5.2.1 Grounding the SUN2000 over a PE Point
Prerequisites
Both the shell and maintenance compartment of the SUN2000 provide a PE point. Select
either for connecting the ground cable.
If you connect a ground cable to the PE point on the shell, ensure that the ground cable
and OT terminal are available.
− Recommended ground cable: an outdoor copper-core cable with a cross-sectional
area of 6 AWG or more
− OT terminal: M6
If you connect a ground cable to the PE point in the maintenance compartment, prepare
the AC output power cable together with the ground cable. For details, see 5.4
Connecting AC Output Power Cables.
Context
Procedure
Step 1 Prepare the OT terminal.
Step 2 Secure the ground cable using the ground screw.
There are two PE points on the chassis shell and one of them is standby.
Step 1 Remove the two screws from the maintenance compartment door using a security torx wrench
Never open the host panel of the SUN2000.
Before opening the maintenance compartment door, disconnect the AC and DC power
supplies. For processes of disconnecting the power supplies, see 6.3 Powering Off the
SUN2000. After powering off the SUN2000, wait at least 5 minutes before performing
operations on it.
If you need to open the maintenance compartment door in rainy or snowy days, take
protective measures to prevent rain and snow entering the maintenance compartment. If it
is impossible to take protective measures, do not open the maintenance compartment door
in rainy or snowy days.
Do not leave unused screws in the maintenance compartment.
and set them aside.
Figure 5-4 Removing screws
Step 2 Open the maintenance compartment door and adjust the support bar.
Step 3 Remove the AC terminal cover and set it aside.
Figure 5-6 Removing an AC terminal cover
To highlight the involved area, the figure does not show the open door.
----End
5.4 Connecting AC Output Power Cables
An AC switch must be installed on the AC side of the SUN2000 to ensure that the SUN2000
can be safely disconnected from the power grid. See 10 Technical Specifications to select AC
switches of the appropriate specifications.
Copper-Clad
Aluminum Cable or
Aluminum Alloy
Cable
Conductor
cross-sectional area
Value
range
6–2/0 AWG
4–2/0 AWG
Recomm
ended
value
4 AWG
2 AWG
Cable outer diameter
6.3–12.1 mm (0.25–0.48 in.)
Do not connect loads between the SUN2000 and the AC switch.
Connect AC output power cables according to the requirements specified by local power
grid operators.
The AC output power cable can be connected in a common way or through a pipe.
5.4.1 Connection Through a Pipe
Prerequisites
The AC output power cable, OT terminal, and pipe are available.
Use cables that can withstand 90°C (194°F) or 105°C (221°F). The cable that can
withstand 105°C (221°F) is recommended. To facilitate installation, use flexible cables.
If you connect a ground cable to the PE point on the chassis shell in the scenario with no
neutral wire, you are advised to use three (L1, L2, and L3) single-core outdoor cables.
If you connect a ground cable to the PE point in the maintenance compartment in the
scenario with no neutral wire, you are advised to use four (L1, L2, L3, and PE)
single-core outdoor cables.
If you connect a ground cable to the PE point on the chassis shell in the scenario with a
neutral wire, you are advised to use four (L1, L2, L3, and N) single-core outdoor cables.
If you connect a ground cable to the PE point in the maintenance compartment in the
scenario with a neutral wire, you are advised to use five (L1, L2, L3, N, and PE)
single-core outdoor cables.
The pipe specifications should comply with the waterproof connector specifications. For
example, for a 2-inch waterproof connector, prepare a 2-inch pipe.
Figure 5-7 Pipe
The pipe appearance is for reference only. The actual pipe prevails.
Figure 5-8 shows the diameters of the cable holes at the bottom of the chassis after the
waterproof connectors are removed.
Following are the reference torque values for the waterproof connector and pipe. Observe the
requirements of the specific manufacturer, if any.
AC OUTPUT and COM ports: 7.5 N·m (plastic) or 10 N·m (metal)
RESERVE port: 3.75 N·m (plastic) or 6.25 N·m (metal)
Figure 5-10 OT terminal direction (using one cable as an example)
Step 4 Connect the AC output power cable and secure it using a socket wrench with an extension
rod.
Verify that the AC output power cable is connected securely. Otherwise, the SUN2000 may
fail to operate or experience any fault that will cause the damage of the terminal block. For
example, the SUN2000 may generate heat during operating due to unreliable connection.
Copper-Clad
Aluminum Cable or
Aluminum Alloy
Cable
Conductor
cross-sectional area
Range
6–2/0 AWG
4–2/0 AWG
Recomm
ended
value
4 AWG
2 AWG
Cable outer diameter range
supported by the AC OUTPUT
waterproof connector
37–44 mm (1.46–1.73 in.)
The cable colors in figures are for reference only. Select appropriate cables according to the local
standards.
Step 5 Connect the conduit and fitting of the pipe.
Step 6 Check that the cables are connected correctly and securely. Then take appropriate measures to
ensure that the pipe conduit and fitting are secured reliably, and seal the cable hole using
firestop putty.
Step 7 Secure the AC filter using screws.
Step 8 Clear foreign matter from the maintenance compartment.
----End
5.4.2 Common Connection
Prerequisites
The AC output power cable and OT terminal are available.
Use cables that can withstand 90°C (194°F) or 105°C (221°F). The cable that can
withstand 105°C (221°F) is recommended. To facilitate installation, use flexible cables.
If you connect a ground cable to the PE point on the chassis shell in the scenario without
the neutral wire, you are advised to use a three-core (L1, L2, and L3) outdoor cable.
If you connect a ground cable to the PE point in the maintenance compartment in the
scenario without the neutral wire, you are advised to use a four-core (L1, L2, L3, and PE)
outdoor cable.
If you connect a ground cable to the PE point on the chassis shell in the scenario with the
neutral wire, you are advised to use a four-core (L1, L2, L3, and N) outdoor cable.
If you connect a ground cable to the PE point in the maintenance compartment in the
scenario with the neutral wire, you are advised to use a five-core (L1, L2, L3, N, and PE)
outdoor cable.
Step 4 Connect the AC output power cable and secure it using a socket wrench with an extension
rod.
Verify that the AC output power cable is connected securely. Otherwise, the SUN2000 may
fail to operate or experience any fault that will cause the damage of the terminal block. For
example, the SUN2000 may generate heat during operating due to unreliable connection.
The cable colors in figures are for reference only. Select appropriate cables according to the local
standards.
Step 5Tighten the waterproof connector to a torque of 7.5 N•m.
----End
Follow-up Procedure
Check that the cables are connected correctly and securely. Then apply firestop putty to the
waterproof connectors and cable holes. Clear foreign matter from the maintenance
compartment.
5.5 (Optional) Installing the DC Protection Shroud
Context
To avoid electric shocks, you are advised to install a DC protection shroud in a rooftop PV
plant.
Before connecting DC input power cables, ensure that the DC voltage is within the safe
range (lower than 60 V DC) and that the two DC switches on the SUN2000 are OFF.
Otherwise, the high voltage may result in electric shocks.
When the SUN2000 is grid-tied, it is not allowed to maintain DC input power cables, such
as connect or disconnect a string or a module in a string. Otherwise, electric shocks may
occur.
Ensure that the following conditions are met. Otherwise, the SUN2000 will be damaged, or
even a fire disaster will be caused.
The highest open-circuit voltage of each PV string is always lower than or equal to 1000 V
DC.
The positive and negative terminals of a PV module connect to the positive and negative
DC input terminals of the SUN2000 respectively.
If the DC input power cable is reversely connected, do not operate the DC switches and
positive and negative connectors immediately. Wait until the solar irradiance declines at
night and the PV string current reduces to below 0.5 A. Then, turn off the two DC switches,
remove the positive and negative connectors, and correct the polarity of the DC input
power cable.
Ensure that the PV string is well insulated to the ground. If the SUN2000 is directly
connected to the power grid with a neutral wire connected to the PGND cable (for
example, a low-voltage power grid or a power grid with a neutral wire grounded), do not
ground the positive and negative terminals of PV strings. Otherwise, the SUN2000 may be
damaged. The caused equipment damage is beyond the warranty scope.
During the installation of PV strings and SUN2000, the positive or negative terminals of
PV strings may be grounded if power cables are not properly installed or routed. In this
case, an AC or DC short circuit may occur and damage the SUN2000. The caused
equipment damage is beyond the warranty scope.
Context
The PV strings must meet the following requirements if they need to be grounded:
A three-phase isolation transformer is installed on the output side.
One isolation transformer must be installed only for one SUN2000. Do not connect two or more
SUN2000s to the same isolation transformer. Otherwise, the SUN2000s may fail to work due to the
loop current generated between them.
Set Isolation to Input grounded, with TF on the SUN2000 APP, SmartLogger, or NMS.
DC terminal selection
Figure 5-27 shows the DC terminals at the bottom of the SUN2000. Table 5-3 describes
the requirements for DC terminal selection.
The SUN2000 provides two DC switches, namely, DC SWITCH 1 and DC SWITCH 2. DC SWITCH 1
controls the first to fourth routes of DC input terminals, whereas DC SWITCH 2 controls the fifth to
eighth routes of DC input terminals.
Use the DC input terminals provided with the SUN2000. If the terminals are lost or
damaged, purchase DC input terminals of the appropriate model from Huawei or MC4,
Amphenol HH4, or Amphenol H4 DC input terminals from other vendors.
DC input terminals not of the previous models may be incompatible with the SUN2000,
which may cause serious consequences. The caused equipment damage is beyond the
warranty scope.
After crimping the positive and negative metal terminals, ensure that the cables are
crimped tightly such that they cannot be pulled out by a force less than 400 N.
Insert the crimped metal terminals of the positive and negative power cables into the
appropriate positive and negative connectors. Then pull back the DC input power cables to
ensure that they are connected securely.
Figure 5-28 Preparing a connector
Step 2 Ensure that the DC input voltage of each PV string does not exceed 1000 V DC using a
multimeter and check that the polarities of the DC input power cable are correct.
If the voltage is a negative value, the PV string is reversely connected. Correct the
polarity.
If the voltage is greater than 1000 V DC, too many PV modules are configured. Remove
some PV modules.
If the DC input power cable is reversely connected, do not operate the DC switches and
positive and negative connectors immediately. Otherwise, the SUN2000 will be damaged. The
caused equipment damage is beyond the warranty scope. Wait until the solar irradiance
declines at night and the PV string current reduces to below 0.5 A. Then, turn off the two DC
switches, remove the positive and negative connectors, and correct the polarity of the DC
input power cable.
----End
Follow-up Procedure
Before removing the positive and negative connectors, ensure that the two DC switches are
OFF.
To remove the positive and negative connectors from the SUN2000, insert a removal wrench
into the notch and press the wrench with an appropriate force, as shown in Figure 5-31.
The SUN2000 can connect to the SmartLogger over RS485 or to a PC through the
SmartLogger to implement communication. You can use the SUN2000 APP, SmartLogger,
embedded WebUI, or the network management software (such as the NetEco) on the PC to
query information about the SUN2000, such as energy yield, alarms, and running status.
Figure 5-32 shows the communication mode for a single SUN2000.
Figure 5-32 Communication mode for a single SUN2000
Figure 5-33 shows the communication between multiple SUN2000s.
If multiple SUN2000s are used, connect all the SUN2000s in daisy chain mode over an
RS485 communications cable.
Figure 5-33 Communication mode for multiple SUN2000s
The RS485 communication distance between the SUN2000 at the end of the daisy chain and the
SmartLogger cannot exceed 1000 meters.
If multiple SUN2000s need to communicate with one another and are connected to a PC over the
SmartLogger2000, a maximum of six daisy chains can be configured.
To ensure the system response speed, it is recommended that the number of devices on each daisy
chain be less than 30.
PLC Communication
The PLC communication board loads communication signals onto power cables for
transmission. For details about how to install the PLC, see the PLC CCO01A User Manual
and SmartLogger2000 User Manual.
The built-in PLC module in the SUN2000 does not need to be connected with cables.
Selecting a Communication Mode
The RS485 and PLC communication modes are mutually exclusive.
If the PLC communication mode is selected, do not connect the RS485 communications
cable. In addition, you need to set PLC communication to Enable on the SUN2000
APP.
If the RS485 communication mode is selected, do not connect the PLC CCO module to
the AC power cable. In addition, you are recommended to set PLC communication to
Disable on the SUN2000 APP.
PLC communication is set to Enable by default.
5.7.2 Selecting a Mode for Connecting RS485 Communications
Cables
Description
RRS485 communications cables can be connected in two ways:
− Terminal block connection
You are advised to use the DJYP2VP2-22 2x2x1 computer cable or a
communications cable with a conductor cross-sectional area of 18 AWG and an
outer diameter of 14–18 mm (0.55–0.71 in.).
You are advised to use a CAT 5E outdoor shielded network cable with an outer
diameter less than 9 mm (0.35 in.) and internal resistance not greater than 1.5
ohms/10 m (1.5 ohms/393.70 in.), as well as a shielded RJ45 connector.
Select either connection way in practice. Connecting to a terminal block is recommended.
The RS485 communications cable can be connected in a common way or through a pipe.
Before installation, prepare materials based on the connection mode.
If you choose connection through a pipe, ensure that the RS485 communications cable and 3/4–inch
pipe are available.
If you choose common connection, ensure that the RS485 communications cable is available.
When laying out communications cables, separate them from power cables and avoid large
signal interference sources to protect communication from being affected.
Terminal Block Pin Definitions
Figure 5-34 shows an RS485 terminal block.
Figure 5-34 Terminal block
Table 5-5 describes pin definitions of the RS485 terminal block.
Step 2 Route the communications cables through the conduits and then fittings of the pipes.
Step 3 Remove the cable terminal base from the terminal block. Connect the communications cables
to the terminal base.
Figure 5-39 Connecting cables to a terminal base
Step 4 Install the terminal base on the terminal block, and connect the shield layers to the ground
point.
When connecting the shielded cables, choose whether to crimp the OT terminal based on site
requirements.
Step 6 Connect the conduits and fittings of the pipes.
----End
Connecting Cables to the RJ45 Network Port
Step 1 Install the pipe fitting.
1. Remove the locking cap and plug from the waterproof connector, and then remove the
waterproof connector.
2. Secure the pipe fitting to the chassis using the nut delivered with the pipe.
Figure 5-42 Installing pipe fitting
Step 2 Route the communications cables through the conduit and then fitting of the pipe.
Step 3 Insert the RJ45 connectors into the RJ45 network ports in the SUN2000 maintenance
Step 5 Connect the conduit and fitting of the pipe.
----End
Follow-up Procedure
Check that the cables are connected correctly and securely. Then take appropriate measures to
ensure that the pipe conduit and fitting are secured reliably, and seal the cable hole using
firestop putty. Clear foreign matter from the maintenance compartment.
5.7.4 Connecting the RS485 Communications Cable in a Common
Way
Connecting Cables to the Terminal Block
Step 1 Route the communications cables through the waterproof connectors.
Figure 5-45 Routing cables
Step 2 Remove the cable terminal base from the terminal block. Connect the communications cables
Step 3 Bind communications cables after connecting them.
Figure 5-51 Binding communications cables
Step 4Tighten the waterproof connector to a torque of 7.5 N•m.
----End
Follow-up Procedure
Check that the cables are connected correctly and securely. Then apply firestop putty to the
waterproof connectors and cable holes. Clear foreign matter from the maintenance
compartment.
If you perform Step 2 before Step 1, the SUN2000 reports a fault about abnormal shutdown.
The SUN2000 can start normally after the fault is automatically rectified. The default alarm
clearance time is 1 minute. You can modify the time over the NMS software installed on the
PC that connects to the SUN2000.
Step 2 Turn on the DC switches at the bottom of the SUN2000 chassis.
Step 3 (Optional) Measure the temperatures at the joints between DC terminals and connectors using
a point-test thermometer.
To ensure that the DC terminals are in good contact, check the temperatures at the joints
between DC terminals and connectors after the SUN2000 has been running for a period of
time. Ensure that the temperature rise does not exceed 40°C (104°F).
Step 4 Connect the SUN2000 to the mobile phone that runs SUN2000 app (app for short) through a
Bluetooth module or USB data cable.
Mobile phone operating system: Android 4.0 or later, iOS 7.0 or later. When the iOS is
used, the app supports only Bluetooth connection.
When you use a Bluetooth module to set up the connection, ensure that the mobile phone
and SUN2000 are at most 5 meters (196.85 inches) away from each other. Otherwise, the
communication quality between them will deteriorate.
The screen snapshots in this document correspond to app V200R001C20SPC010
(Android).
Figure 6-1 Bluetooth module connection (Android and iOS)
Purchase the Bluetooth module bundled with the SUN2000. A Bluetooth module purchased from any
other source may not support communication between the SUN2000 and the app.
The Android system supports the Bluetooth module USB-Adapter2000-B and BF4030.
The iOS system supports the Bluetooth module USB-Adapter2000-B.
After you select Use by default for this USB accessory, the message will not appear if you connect the
app to the SUN2000 again without removing the USB data cable.
Step 5 Tap the user name area to switch between the common user, advanced user, and special user.
The login password is the same as that for the SUN2000 connected to the app and is used only when
the SUN2000 connects to the app.
The initial passwords for Common User, Advanced User, and Special User are all 00000a. Use the
initial password upon first login. To ensure account security, change the password immediately after
login.
During the login, if an incorrect password is entered for five consecutive times (the interval between
two consecutive invalid password entries is less than 2 minutes), the account will be locked for 10
minutes. The password consists of six digits.
Step 6 Enter the password and tap Log In.
Step 7 After the successful login, the Quick Settings screen or Function Menu screen is displayed.
If you log in to the app after the device connects to the app for the first time or factory defaults are
restored, the Quick Settings screen will be displayed on which you can set basic parameters. After
the settings take effect, you can enter the main menu screen and modify the parameters on the
Settings screen. By default, the SUN2000 can be grid-tied and you do not have to set parameters.
You are advised to log in to the Quick Settings screen as an advanced user for parameter settings.
Figure 6-8 Quick Settings screen (logging in as an advanced user)
Set the power grid code that applies to the country or region where the power station is located and
the inverter model.
Set user parameters based on the current date and time.
Set Baud rate, RS485 protocol, and Address based on site requirements. Baud rate can be set to
4800, 9600, or 19200. RS485 protocol can be set to MODBUS RTU, and Address can be set to any
value in the range of 1 to 247.
When multiple SUN2000s communicate with the SmartLogger over RS485, the addresses for all the
SUN2000s on each RS485 route must be within the address range set on the SmartLogger and
cannot be duplicate. Otherwise, the communication will fail. In addition, the baud rates of all the
SUN2000s on each RS485 route must be consistent with the SmartLogger baud rate.
If two SUN2000s share the same AC switch on the AC side, power off the two SUN2000s.
After the SUN2000 powers off, the remaining electricity and heat may still cause electric
shocks and body burns. Therefore, put on protective gloves and begin servicing the
SUN2000 five minutes after the power-off.
Procedure
Step 1 Run a shutdown command on the SUN2000 APP, SmartLogger, or NMS.
For details, see the SUN2000 APP User Manual, SmartLogger2000 User Manual, or
iManager NetEco 1000S User Manual.
Step 2 Turn off the AC switch between the SUN2000 and the power grid.
Step 3 Set the two DC switches to OFF.
Step 4 (Optional) Install locks on the DC switches.
The ciphertext varies depending on the login password of the
SUN2000 APP.
3
Script validity
period
The script validity period varies depending on the script export
time.
4
Command
Different command settings can produce different commands.
Configuration export command: export param.
Configuration import command: import param.
Data export command: export log.
Upgrade command: upgrade.
LED Indicator
Status
Meaning
Green off
There is no operation with
a USB flash drive.
Blinking green at long intervals (on
for 1s and then off for 1s)
There is an operation with
a USB flash drive.
Blinking green at short intervals (on
for 0.125s and then off for 0.125s)
An operation with a USB
flash drive has failed.
Steady green
An operation with a USB
flash drive is successful.
Step 3 Import the boot script file to the root directory of a USB flash drive.
Step 4 Connect the USB flash drive to the USB port. The system automatically identifies the USB
flash drive and executes all commands specified in the boot script file. View the LED
indicator to determine the operating status.
Verify that the ciphertext in the boot script file matches the login password of the SUN2000
APP. If they do not match and you insert the USB flash drive for five consecutive times, the
user account will be locked for 10 minutes.
Table 7-1 LED indicator description
Step 5 Insert the USB flash drive into a computer and check the exported data.
Blinking green at long intervals (on
for 1s and then off for 1s)
There is an operation with
a USB flash drive.
Blinking green at short intervals (on
for 0.125s and then off for 0.125s)
An operation with a USB
flash drive has failed.
When the configuration export is complete, the boot script file and exported file are in the root directory
of the USB flash drive.
----End
7.1.2 Importing Configurations
Prerequisites
A complete configuration file has been exported.
Procedure
Step 1 Generate a boot script file by choosing Tool Kit > Local maintenance script > Inverter
maint script > Inverter Command Settings on the SUN2000 app. For details, see the
SUN2000 APP User Manual.
Step 2 Import the boot script file to a PC.
Step 3 Replace the exported boot script file in the root directory of the USB flash drive with the
imported one.
Replace the boot script file only and keep the exported files.
Step 4 Connect the USB flash drive to the USB port. The system automatically identifies the USB
flash drive and executes all commands specified in the boot script file. View the LED
indicator to determine the operating status.
Verify that the ciphertext in the boot script file matches the login password of the SUN2000
APP. If they do not match and you insert the USB flash drive for five consecutive times, the
user account will be locked for 10 minutes.
An operation with a USB
flash drive is successful.
LED Indicator
Status
Meaning
Green off
There is no operation with
a USB flash drive.
Blinking green at long intervals (on
for 1s and then off for 1s)
There is an operation with
a USB flash drive.
Blinking green at short intervals (on
for 0.125s and then off for 0.125s)
An operation with a USB
flash drive has failed.
Steady green
An operation with a USB
flash drive is successful.
----End
7.1.3 Exporting Data
Procedure
Step 1 Generate a boot script file by choosing Tool Kit > Local maintenance script > Inverter
maint script > Inverter Command Settings on the SUN2000 app. For details, see the
SUN2000 APP User Manual.
Step 2 Import the boot script file to the root directory of a USB flash drive.
Step 3 Connect the USB flash drive to the USB port. The system automatically identifies the USB
flash drive and executes all commands specified in the boot script file. View the LED
indicator to determine the operating status.
Verify that the ciphertext in the boot script file matches the login password of the SUN2000
APP. If they do not match and you insert the USB flash drive for five consecutive times, the
user account will be locked for 10 minutes.
Table 7-3 LED indicator description
Step 4 Insert the USB flash drive into a PC and check the exported data.
After the data is exported, the boot script file and exported file are in the root directory of the USB flash
drive.
The activation starts when either of the preceding two
conditions is met.
Local upgrade of the SUN2000
APP
Remote upgrade over the
SmartLogger
The PV input voltage is greater than 500 V.
The output power is greater than 1 kW.
The activation starts when either of the preceding two
conditions is met.
Remote upgrade over the NMS
7.1.4 Upgrading
Context
Upgrade delay is mainly used in the upgrade scenarios where the PV power supply is
disconnected at night due to no solar radiation or unstable at dawn or dusk due to poor solar
radiation.
After the SUN2000 upgrade starts, if Upgrade delay is set to Enable, the upgrade package is
loaded first. After the PV power supply recovers and the activation conditions are met, the
SUN2000 automatically activates the upgrade.
Upgrade delay is set to Enable by default, which means that the upgrade can take place at day or night.
After enabling Upgrade delay, start the SUN2000 upgrade over the USB, SmartLogger, or NMS. The
SUN2000 upgrade process contains the following two stages:
1.
2.
Table 7-4 Conditions for starting delayed activation
The monitoring component caches and loads the upgrade package.
Upgrade package activation starts when the following conditions are met.
When upgrading the SUN2000 remotely, do not perform local operations for the SUN2000.
If the SUN2000 needs to be upgraded when the PV power supply is unavailable at night due to no
solar radiation or unstable at dawn or dusk due to poor solar radiation, ensure that the SUN2000 AC
output connects to the power grid.
Procedure
Step 1 Log in to http://support.huawei.com/carrier/ and browse or search for SUN2000 on the
Product Support tab page. Download the required upgrade package (for example, SUN2000
V200R002C20SPCXXX) from the Software tab page.
Step 2 Decompress the upgrade package.
After obtaining the upgrade package SUN2000V200R002C20SPCXXX_package.zip,
decompress it and ensure that the extracted files include:
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.