Huawei R4815N1 User Manual

1
R4815N1 Rectifier User Manual V1.2
Environmental Specifications
Item Specification
Operating temperature
–40ºC to +75 ºC (referring to Figure 3) (–40°F to +167°F)
Storage temperature
–40ºC to +75ºC (not packaged)
Item Specification
Input
Operating voltage
85–300 V AC Rated: 200–240 V AC and 100–120 V AC
Frequency 45–66 Hz
Rated: 50 Hz and 60 Hz
Maximum input current
6.4 A
Power factor
0.99 (100% load)
THD 3.5% (full load) ;
5% (load ≥ 50%)
Output
Output voltage
42–58 V DC Rated voltage: 53.5 V DC
Output power 1000 W (176–300 V AC);
470 W (85–175 V AC decreased linearly)
Regulated voltage precision
±0.6%Vo
Ripple and noise ≤ 200 mVp-p
(Bandwidth ≤ 20M Hz)
Dynamic response 25-50% or 50-75% load
−Over shoot:≤ ±5%
−Recovery time: ≤ 200 us (±0.6%)
10-90% load;
−Over shoot:≤ ±5%;
−Recovery time: ≤ 1ms (±1%)
Standby power 5 W Turn-on output
delay
3–8s
Hold up time > 10 ms Psophometrically
weighted noise
2 mV
Broad frequency noise voltage
50 mV (3.4–150 kHz) 20 mV (0.15–30 MHz)
Electrical Specifications
Efficiency
The peak point is 94% 93% (230 V AC, 30%–100% load)
Height x Width x Depth
40.8 mm x 95.5 mm x 208 mm
(1.61 in. x 3.76 in. x 8.19 in.) Weight About 1.1 kg Cooling Built-in fan (The rotation of fan depends
on the internal temperature.)
Description
The R4815N1 is a digital rectifier with high efficiency and power density. It converts 85–300 V AC input voltage to
53.5 V DC output voltage. The output voltage can be adjusted by the host.
It performs comprehensive protection functions, supports soft start, and produces low noise. With the latest power monitoring technology, states of the rectifier and load are monitored in real time.
Multiple rectifiers can be paralleled.
Key Features
Input voltage range: 85–300 V AC
Operating temperature range: –40ºC to +75ºC
Total harmonic distortion (THD): ≤ 3.5
Digital control mode
Hot swap
Supports intelligent electric meter
Supports CAN communication
Supports LED display
Supports voltage adjustment,current
adjustment,and current sharing
Meet Rohs requirement
Passes the TUV, CE, UL certifications and gets
the CB certifIcate.
Disconnect above 320 V AC
Note: If the altitude is within the range of 3000 m to 4000 m, the maximum operating
temperature decreases by 1°C (1.8°F ) as the altitude increases by 200 m.
Copyright © Huawei Technologies Co., Ltd. 2016. All rights reserved.
2
R4815N1 Rectifier User Manual V1.2
Item Specification
Protection
Input overvoltage protection
Protection point: > 300 V AC Recovery range: 290-300 V AC
Input undervoltage protection
Protection point: < 80 V AC Recovery range: 70-85 V AC
Output overvoltage protection
56–60V DC (can be set by monitoring unit)
1. If the overvoltage occurs inside the rectifier due to a fault, the rectifier will latch off.
2. If the output voltage is higher than 63 V and lasts for more than 500 ms, the rectifier will latch off.
Output current limiting protection
See Figure 1.
Output short circuit protection
A long term short circuit is allowed. After the fault is rectified, the rectifier is restored to a healthy state automatically.
Over-temperature protection
The module protects against overtemperature.
Safety/EMC/Lightening protection
Safety certification
Passes TUV, CE, UL certifications. Catch the CB certificate. Complies with UL60950-1; IEC60950-1; EN60950-1; CAN/CSA C22.2 No. 60950-1;
EMC EN55022 Class B ;
EN55024; EN61000-3-2; EN61000-3-3; ETSI EN300 386; ETSI EN301489; ITU-T K.20;
Lightning 5 kA
Reliability
MTBF > 500,000 hours
Audible Noise
Specification
≤ 40 dB (25ºC /77°F, full load)
Output Feature
Figure 1 Output feature
Figure 2 Efficiency (Vin = 230 V AC, Vout = 53.5 V, Ta: 25ºC )
Figure 3 Power derating curve
Other Features
0
200
400
600
800
1000
1200
-40 -20 0 20 40 60 80
Po(w)
Ta()
Power Derating Curve
Loading...
+ 2 hidden pages