HP E3610A, E3611A, E3612A Operating And Service Manual

Page 1
Whnt HEWLETT %L'tLM PACKARD
HP E361XA 30W BENCH SERIES DC POWER SUPPLIES
OPERATING AND SERVICE MANUAL FOR MODELS:
HP E3610A, Serials KR20600101 and above HP E3611A, Serials KR20600101 and above HP E3612A, Serials KR20600l01 and above
Table of Contents
1-2 1-2 1-2 1-3 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-5 1-5 1-5 1-5 1-5 1-5 1-6 1-6 1-6
A-1
Manual Part No. B9B9-6304 Microfiche Part No. 5959-5307
Printed:
February, 1992
Page 2
SAFETY SUMMARY
The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specific warnirtgs elsewhere in this manual violates safety standards of design, manufactures, ar>d intended use of the instrument. Hewlett-Packard Company assumes no liability for the customer's failure to comply with these require­ments.
Before Applying Power
Verify that the product is set to match the available line voltage.
Ground The Instrument
This product is a Safety Class I instrument (provided with a protective earth terminal). To minimize shock hazard, the instrument chassis and cabinet must be connected to an electrical ground. The instrument must be connected to the ac power supply mains through a three-corrductor power cable,
with the third wire firmly connected to an electrical grourrd(safety ground) at the power outlet. Any interruption of the protective(grounding) conductor or disconnection of the protective earth terminal will cause a potential shock hazard that could result in personal injury. If the instrument is to be energized via an external autotransformer for voltage reduction, be certain that the autotransformer common terminal is connected to the neutraKearthed pole) of the ac power lines (supply mains).
Do Not Operate in An Explosive Atmosphere
Do not operate the instrument in the presence of flammable gases or fumes.
Keep Away From Live Circuits.
Operating personnel must not remove instrument covers. Component replacement and internal adjustments must be made by qualified service personnel.
Safety Symt>ols
A
IwARNIHcj
Instrument manual symbol; the product will be marked with this symbol when it is necessary for the user to refer to the instruction manual.
Indicate earth(grour>d) terminal.
The WARNING sign denotes a hazard.
It calls attention to a proce-
dure,
practice, or the like, which, if not correctly performed or adhered to,
could result in personal injury. Do not proceed beyond a WAR­NING sign until the indicated
con­ditions are fully understocxJ and met.
The CAUTION sign denotes a haza­rd.
It calls attention to an operating procedure, or the like, which, if not correctly performed or adhered to, could result in damage to or destru­ction of part or all of the product. Do not proceed beyond CAUTION sign until the indicated conditions are fully understood and met.
GENERAL INFORMATION
Description
This operating and service manual covers three dual range HP power supplies, E3610A, E3611A, and E3612A. All models are compact, general purpose bench supplies that are particulariy useful for powering developmental IC circuits, both linear and digital. Unless stated otherwise, all information in this manual applies equally to all three models. The desired output range is selected by the front panel RANGE push button. The output can be continuously adjusted for voltage and current throughout either output range.
The front panel VOLTAGE control can be used to establish the voltage limit when the supply is used as a constant current source arrd the CURRENT control can be used to establish the output current limit when the supply is used as a constant voltage source. The CC SET push button allows the current limit value to be conveniently set using the CURRENT control without shorting the output.
The front panel includes a digital voltmeter/ammeter. A 3 1/2 digit (E3611A 3 digit) voltage display and 3 digit current display accurately show the output voltage and current respectively. The output ratings for each model are shown in the Specifications Table.
1-2
Page 3
Specifications
and
Supplemental Characteristics
INPUT:
115 Vac ±
10%, 47-63 Hz,
0.8 A, 70 W
100
Vac ±
10%, 47-63 Hz,
0.8 A, 70 W
230
Vac
±10%, 47-63
Hz, 0.4 A, 70 W
OUTPUT: E3610A:
0 to 8 V, 0 to 3 A or 0 to 15 V,
0to2
A
E3611 A:
0 to 20 V, 0 to 1.5 A or 0 to 35 V,
0
to
0.85
A
E3612A:
0 to 60 V, 0 to 0.5 A or 0 to 120V,
to 0.25
A
LOAD REGULATION: Constant Voltage - Less than 0.01 % plus
2 mV for a
full load
to rto
load change
in
output current.
Constant Current - Less than 0.01 % plus
1 mA for a
zero
to
maximum change
in
output voltage.
UNE REGULATION: Constant Voltage - Less than 0.01 % plus
2 mV for any
line voltage change within
the
input rating.
Constant Current - Less than 0.01 % plus
1 mA for any
line voltage change within
the
input rating.
RIPPLE AND NOISE: Constant Voltage - Less than
200 uV rms and 2 mV
peak
topeak(10Hz-10MHz)
Constant Current - Less than
200 uA rms and 1 mA
peak
topeak(10Hz-10MHz)
TEMPERATURE RANGE:
0 to
40°C
for
full rated output.
Derate current 1%
per
degree C between 40°C-55°C
'TEMPERATURE COEFFICIENT:.
Constant Voltage - Less than 0.02% plus
1 mV per
degree
C.
Constant Current - Less than 0.02% plus
2 mA per
degree
C.
TRANSIENT RESPONSE TIME: Less than
50
usee
for
output recovery
to
within
10 mV
following a change
in
output current from full load
to
half
load,
or
vice versa.
ISOLATION:
± 240 Vdc
•OUTPUT DRIFT:
Constant Voltage - Loss than 0.1 % plus
5 mV
total drift
for 8 hours after
an
initial warm-up
of 30
minutes.
Constant Current - Less than
0.1%
plus
10 mA
total drift
for 8 hours after
an
initial warm-up
of 30
minutes.
METER ACCURACY: ±0.5%
-i- 2 counts
at
25°C
± S'C
'OVERLOAD PROTECTION:
A continuously acting constant current circuit protects
the
power supply
for all
overioads including a direct short
placed across
the
terminals.
The
constant voltage circuit
limits
the
output voltage
in
constant current operation.
•OUTPUT TERMINALS:
Three output terminals
are
provided
on the
front panel.
They are isolated from the chassis and either the positive
or
negative terminal may be connected
to
the ground terminal.
•OUTPUT CHARACTERISTICS
A
Veitt
Vo,
^2
loi
Pour
MAX
30 Watts
1^2
Cmrrcnt
NOTE:
Output voltages higher than
VQJ
are possible
at low
current when
the
high current range
is
selected.
E3610A: Vn,
=15 V V,
01
E3611A: Voi=35
V
E3612A:Voi=120V
'02-
^02
=
Vo2
'oi=2A
lo,
= 3
A
'02
= 8
V
20
V
= 60V 1(5, =0.25
A lo2
01 =0.85 A IQ2 = 1.5
A
= 0.5
A
•METER RESOLUTION Voltage: E3610A
10 mV
E3611A
100 mV
E3612A
100 mV
Current: E3610A
10 mA
E3611A
10 mA
E3612A
1 mA
•DOWN PROGRAMMING
SPEED:
Maximum time
for
output
voltage
to
change between
100% to
0.1%
of
maximum
rated output voltage
at NO
LOAD condition.
E3610A: maximum
2.5 sec
E3611 A: maximum
1.0 sec
E3612A: maximum
1.5 sec
•RESOLUTION: Minimum output voltage
or
current change
that
can be
obtained using panel controls.
E3610A: Voltage
10 mV
Current
5 mA
E3611 A: Voltage
10 mV
Current
5 mA
E3612A: Voltage
100 mV
Current
2 mA
COOLING: Convection cooling
is
employed.
WEIGHT:
8.4
lbs/3.8
Kg net, 9.3
lbs/4.2
Kg
shipping.
(NOTE) * SUPPLEMENTAL CHARACTERISTICS
1-3
Page 4
D
88.1 mm
3.469
in
269.2 mm 10591
in
m
•I
m
212 3 mm
^ 8.354
in
1
1
1
iill iiiilll
l_J
l-o '
318 4 mm
12.534
in
FIGURE 1: OUTLINE DIAGRAM
Options
The following factory installed options are available with this instrument.
Option Description 0E3 Input Power
:
230 Vac 4^/10%, 47-63 Hz, Single Phase
0E9 Input Power
:
100 Vac
-^/-10%,
47-63 Hz, Single Phase
Instrument Identification
Hewlett-Packard power supplies are identified by one serial number. The letter "KR" designates Korea as the country of manufacture,
the
first digit indicates
the
year
(1=91,
2 =
92,
etc), the second two digits indicate the week, and
the last five digits
of
the serial number are a different
sequential number assigned to each power supply.
If the serial number on your instrument does not agree with those on the title page
of
this manual, a yellow change
sheet may be included
if
a design change has affected the
contents of this manual.
INSTALLATION
Inspection
When you receive your power supply, inspect
it
for any obvious damage that may have occurred during shipment. If there
is
damage, notify the carrier and the nearest HP Sales Office immediately. Warranty information is printed on the inside front cover
of
this manual. Save the shipping carton and packing materials in case the supply has to be returned to Hewlett-Packard in the future.
If
you return the supply for service, attach a tag identifying the owner and model number. Also include a brief description
of the
problem.
The "Turn-On Checkout Procedure" in this manual can be used as an incoming inspection check
to
verify that the supply is operational. See the appendix for tests that verify the supply's specifications.
Location And Cooling
Figure 1 shows the outline shape and dimensions
of
the
unit.
It
is shipped ready for bench operation after connec-
tion
to an ac
power source. The supply
is air
cooled.
Sufficient space should be allotted so that a free flow
of cooling air can reach the rear of the instrument when it is in operation.
It
should be used in an area where the ambient temperature does not exceed 40 degrees C. The current derates 1% per degree C between 40°C-55°C.
Input Power Requirements
Depending on the line voltage option ordered, the supply is ready to be operated from one of the power sources listed in the Specification Table. The input voltage range, and the input current ar>d power at high line voltage and full load is listed for each option.
Power Cord
This instrument is equipped with a three conductor power cable.
The third corKiuctor
is
the grourxl conductor and when the cable is plugged into an appropriate receptacle, the instrument
is
grour>ded. The offset pin on the power cable three prong connector is the ground connection. In no event should this instrument
be
operated without
an
adequate cabinet ground connection.
The power supply was shipped with a power cord for the type of outlet used at your location.
If
the appropriate cord was not included, contact your nearest HP Sales Office to obtain the correct
cord.
1-4
Page 5
HEWLETT E36WA 0-ew.M/o-nr.aA PACKARD DC KMCtt SUrPLT
]:
. ON
OFF
± 2«1 VDC MAX TO 1
FIGURE 2: FRONT PANEL CONTROLS AND INDICATORS
OPERATION
Turn-On Checkout Procedure
The following checkout procedure describes the use of the front panel controls and indicators illustrated in Figure 2 arxJ ensures that the supply is operational: a. Push LINE button to ON. b. Set RANGE push button to desired range. c. Turn VOLTAGE control fully counter clockwise to
ensure that output decreases to 0 Vdc then fully clockwise to ensure that output voltage increases to the maximum output voltage.
d.
While depressing CC SET push button, turn the
CURRENT control fully counter clockwise and then fully clockwise to ensure that the current limit value can be set from zero to maximum rated value.
e. Connect load to output terminals.
WARNING
Constant Current Operation
To set up a power supply for a constant current operation, proceed as follows: a. Turn CURRENT control fully counter clockwise to
ensure that output decreases to 0 A, and then turn on power supply.
b. Adjust VOLTAGE controKno load connected) for
maximum output voltage allowable(voltage limit), as determined by load cor>ditions. During actual opera­tion,
if a load change causes the voltage limit to be
exceeded,
the power supply will automatically cross­over to constant voltage operation at the preset voltage limit and output current will drop proportion­ately.
c. Adjust CURRENT control for desired output current
while depressing CC SET button(CC LED will not light
until the supply is loaded)
Connecting Loads
The output of the supply is isolated from earth ground. Either output terminal may be grounded or the output can be floated up to 240 volts off grour>d.
Shock Hazard
Disconnect ac power before making
output terminal connections.
Constant Voltage Operation
To set up a power supply for a constant voltage operation,
proceed as follows: a. Turn on power supply and adjust 10-turn VOLTAGE
control for desired output voltage(output terminals open). CV LED should light.
b. While depressing CC SET push button, adjust 10-turn
CURRENT control for maximum output current allow­able (current limit). During actual operation, if a load change causes the current limit to be exceeded, the power supply will automatically crossover to constant current mode artd output voltage will drop propor­tionately.
Each load should be connected to the power supply output terminals using separate pairs of connecting wires. This will minimize mutual coupling effects between loads and will retain full advantage of the low output impedance of the power supply. Each pair of connecting wires should be as short as possible and twisted or shielded to reduce noise pickupdf a shield is used, connect one end to the power supply ground terminal and leave the other erxl unconnec­ted.).
Operation Beyond Rated Output
The output controls can adjust the voltage or current to values above(up to 5%) the rated output as indicated on the front panel display. Although the supply can be operated in the 5% overrange region without being damaged, it can not be guaranteed to meet all of its performance specifications in this region.
1-5
Page 6
Pulse Loading Consklerations
The power supply will automatically cross over from constant-voltage to constant-current operation in response to an increase(over the preset limit) in the output current. Although the preset limit may be set higher than the average output current, Ngh peak currents(a8 occur in pulse loading) may exceed the preset current limit and cause crossover to occur. If this crossover limiting is not desired, set the preset limit for the peak requirement and not the average.
Capacitive Loads
An internal capacitor, across the output terminals of the power supply, helps to supply high-current pulses of short duration during constant voltage operation. Any capacitance added externally will improve the pulse current capability.
but will decrease the safety provided by the current limiting
circuit. A high-current pulse may damage load components t>efore the average output current is large enough to cause the current limiting circuit to operate.
Reverse Current Loading
Active loads connected to the power supply may actually deliver a reverse current to the power supply during a portion of its operating cycle. An external source can not be allowed to pump current into the supply without loss of
regulation and possible darnage to the output capacitor. To avoid these effects, it is necessary to preload the supply
with a dummy load resistor so that the power supply delivers current through the entire operating cycle of the load devices.
1-6
Page 7
APPENDIX
SERVICE INFORMATION
AC
NPUT
XFMR
DISPUY
POWER SUPPLY
••+5V
•GND
CVrtX h»cv
INDICATOR
ORCUIT U-CC
REFERENCE ANO
BIASSIPPLY
+12
V
+5V
— CREF
-12
V
RECTinEfl
FILTER
SERIES
REGULATOR
Ofl
GATE
+«V —
GND -
CURRENT
OISPWY CIRCUIT
VOLTAGE
DISPLAY
CIRCUIT
CONSTANT
CURRBtT
ERROR AMP
.^VS^
CREFO-
CCSET ORCUIT
u
CONSTANT
VOLTAGE
ERROR AMP
DRIVER
METER
INPUT
ORCurr
DC
OUTPUT
Figure
A-1.
Block Diagram
PRINCIPLES OF OPERATION
Throughout this discussion, refer to both the block diagram of Figure A-1 and the schematic diagram at the rear of the manual. The input AC line voltage is stepped down by the power transformer and applied to the rectifier and filter. The rectifier-filter converts the AC input to raw DC which is fed to the positive output terminal via parallel series regulator(Q1 and Q3) and current sampling resis­tor(R2). The regulator, part of the feedback loop, is made to alter its conduction to maintain a constant output voltage or current. The voltage developed across the current sampling resistor is the input to the constant current error amplifier. The constant voltage error amplifier obtains its input by sampling the output voltage of the supply.
Any changes in output voltage or current are detected, amplified by the error amplifier and driver and applied to the series regulator in the correct phase and amplitude to counteract the change in output voltage or current.
Two error amplifiers are included in a CV/CC supply, one for controlling output voltage, the other for controlling output current. Since the constant voltage amplifier tends to achieve zero output impedance and alters the output current whenever the load resis­tance changes, while the constant current amplifier causes the output impedance to be infinite and changes the output voltage in response to any load resistance change, it is obvious that the two amplifiers can not operate simultaneously. For any given value of load resistance, the power supply must act either as a constant
voltage source or as a constant current source - it can not be
both; transfer between these two modes Is accomplished at a value of load resistance equal to the ratio of the output voltage control setting to the output current control setting.
The reference and bias circuit provides stable reference voltages which are used by the constant voltage/current error amplifier circuits for comparison purpose. The digital meter circuit provides an indication of output voltage and current for constant voltage or constant current operating modes.
The display power circuit provides voltage which is used by A/D converter and LED drive.
Diode CR3 is connected across the output terminals in reverse polarity. It protects the output electrolytic capacitor and the series regulator transistor from the effects of a reverse voltage applied across the output terminals.
PERFORMANCE TEST
The following provides the test procedure in high currant range for verifying the unit's compliance with the specifications and character­istics of Table in page 1-3. The same test procedure may be applied to low current range.
Test Equipment Required
The following Table lists the equipment required to perform the tests and adjustments. You can separately identify the equipment for performance tests, or calibration in the USE column of the Table.
A-1
Page 8
Table
A-1.
Test Equipment Required
TYPE
Oscilloscope
RMS Voltmeter
Multimeter
Electronic Load
Load Re8istor(For high current range)
Current Sampling Resistor
Variable Voltage Auto Transformer
REQUIRED CHARACTERISTICS
Sensitivity : 2 mV Bandwidth : 10 MHz/100 MHz Input : Differentia), 50 ohm, 100 ohm
True rms, 10 MHz bandwidth Sensitivity : 1 mV Accuracy : 5%
Resolution : 100 nV Accuracy : 0.0035%
Voltage Range : 240 Vdc Current Range : 10 Adc Open and short switches Transient on/off
2.6 ohm 50 W, 13.3 ohm 50 W, 120 ohm 50W
0.1 ohm
0.1%
low, 1 ohm 1% 10 W
Range : 85-130 and 200-260 Volts
USE
P
P
P.A
P,A
P
P.A
P
RECOMMENDED MODEL
HP54600A
HP3400A
HP3456A
HP6063A
P = Performance testing
A =
Calibration adjustments.
Constant Voltage(CV) Test
The measuring device must
be
connected
as
close
to the
output
terminals
as
possible when measuring
the
output impedance,
transient response, regulation,
or
ripple
of the
power supply
in
order
to achieve valid measurements. A measurement made across
the
load includes
the
impedance
of the
leads
to the
load
and
such lead
lengths
can
have
an
impedance several orders
of
magnitude greater
than
the
supply output impedance, thus Invalidating
the
measure-
ment.
For all CV
tests
set the
output current
at
full rated output
to
assure
CV
operation.
Load Effect(Load Regulation)
Definition:
CV
Load Effect
is the
change
in dc
output voltage when
load resistance changes from open circuit
to
full load
or
from full load
to open circuit.
Test Parameters: Measured Variable: Output Voltage
Expected Results: Less than 0.01 % plus
2 mV
Test Procedure:
a. Connect
the
test equipment
as
shown
in
Figure A-2. Operate
the electronic load
in
constant current mode
and set its
current
to the
full rated value
of the
power supply (E3610A:
3.0
A,
E3611
A: 1.5 A,
E3612A:
0.5 A).
b. Turn
the
unit's power
on and
turn CURRENT control fully
clockwise.
c. Turn
up
output voltage
to the
full rated value (E3610A:
8.0
V.
E3611
A: 20 V,
E3612A:
60 V) as
read
on the
digital
voltmeter.
d.
Record
the
output voltage
at the
digital voltmeter.
e. Operate
the
electronic load
in
Opendnput
Off)
mode.
f.
When
the
reading settles, record
the
output voltage again.
Check that
the two
recorded readings differ
no
more than
0.01
% of
output voltage plus
2 mV .
POWER SUPPLY
UNDER TEST
+
-
2^^
\
DIGITAL
VOLTMt.
ILR
TO
DVM
6
ELECTRONIC
LOAD
Rs= 0.1 ohm
0.1%
10 W
Figure A-2. Basic Test Setup
Source EffectlLine Regulation)
Definition:
Source effect
is the
change
in dc
output voltage when
the
ac input voltage changes from a minimum
to
maximum value!
± 10%
of nominal voltage).
Test Parameter: Measured Variable: Output Voltage Expected Results: Less than 0.01% plus
2 mV
Test Procedure:
a. Connect
the
test equipment
es
shown
in
Figure A-2. Operate
the electronic load
in
constant current mode
and set its
A-2
Page 9
current to the full rated value of power supply.
b. Connect the unit to the ac power line through a variable
autotransformer which is set for low line voltage(104 Vac for
115 Vac).
c. Turn the unit's power on and turn CURRENT control fully
clockwise.
d.
Turn up output voltage to the full rated value as read on the
digital voltmeter. e. Record the output voltage at the digital voltmeter. f. Adjust autotransformer to high line voltage) 127 Vac for
115 Vac).
g.
When the reading settles, record the output voltage again.
Check that the two recorded readings differ no more than
0.01%
of output voltage plus 2 mV.
Load Transient Recovery Time
d.
Set the electronic load to transient operation mode between
one half of unit's full rated value and unit's full rated value at a 1 KHz rate with 50% duty cycle.
e. Set the oscilloscope for ac coupling, internal sync and lock on
either the positive or negative load transient. f. Adjust the oscilloscope to display transients as in Figure A-3. g.
Check that the pulse width of the transients at 10 mV from
the base line is no more than 50 usee as shown.
PARD(Ripple and Noise)
Definition:
Periodic ar>d random deviation(PARD) in the unit's output ripple and noise combine to produce a residual ac voltage superim­posed on the dc output voltage. Constant voltage PARD is specified as the root-mean-square(rms) or peak-to-peak(pp) output voltage in a frequency range of 10 Hz to 10 MHz.
Definition : This is the time for the output voltage to return to within a specified band around its voltage following a step change in
load.
Test Paramater: Measured Variable: Output Voltage Transients Expected Results: Less than 50 usee (at 10 mV from base line)
Test Procedure:
a. Connect the test equipment as shown in Figure A-2, but
replace the DVM with the oscilloscope. Operate the electronic load in constant current mode.
b. Turn the unit's power on and turn CURRENT control fully
clockwise.
c. Turn up output voltage to the full rated value.
PARD(RMS) Measurement
Test Parameter:
Measured Variable: Output Voltage(rms) Expected Results: Less than 200 uV rms
Test Procedure:
a. Connect the test equipment as shown in Figure A-4. b. Turn the unit's power on and turn CURRENT control fully
clockwise.
c. Turn up output voltage to the full rated value. Check that the
unit's CV indicator remains lighted. Reduce VOLTAGE control if not lighted.
d.
Check that the rms noise voltage at the true rms voltmeter is
no more than 200 uV.
hp
Stopped
....
'
-••
1
—1 - •••
\ j
1 •/-
1 / •
•\-j
rvW-^
1 1-— 1
^ -1
1
-H 1
!-:•
.
4
f.
.
-'<••
\i
\
1
\
•—+—
-'•>•••
...
, ,
i
i
....
" ...
.1:^^
1
10.0
nV/div
offseli-600
uV
1.000:1
ac
-100.000
us
VBiarker2( 1 ) 7.813 VaarkerK 1 ) -2. 188
delta V( 1 ) 10.001
0.00000 s
20.0 us/div mV stop marker mV start marker mV
delta t
1/de1ta
t
100,000 us
12.4000US
-13.2000US
25.6000US
39.0625kHi
1 "^ 30.00 nV
Figure A-3. Load Transient Recovery Waveform
A-3
Page 10
POWER SUPPLY
UNDER TEST
-1-
-
^
RL
L^VWV—
1
\
E3610A E3611A
E3612A
-O - TRUE _(-,,
VOLB
RL
2.6 ohm
13.3 ohm 120 ohm
-RMS
/lETER
Figure A-4. RMS Measurement Test Setup
PARD(Peak-to-Peak) Measurement
Test Parameter:
Measured Variable: Output voltage(peak-to-peak) Expected Results: Less than 2 mV p-p
Test Procedure:
a. Connect the test equipment as shown in Figure A-5. b. Turn the unit's power on and turn CURRENT control fully
clockwise.
c. Turn up output voltage to the full rated value. Check that the
unit's CV Indicator remains lighted. Reduce VOLTAGE control if not lighted.
d.
Set the oscilloscope to AC mode and bandwidth to 10 MHz.
e. Check that the peek-to-peak noise is no more than 2 mV.
the load current is fed to the extremes of the wire leading to the resistor while the sampling terminals are located as close as possible to the resistance portion itself. Generally, any current sampling
resistor should be of the low noise, low temperature coefficient type arxl should be used at no more than 5% of its rated power so that its temperature rise will be minimized.
Load Effect(Load Regulation)
Definition : CC Load Effect is the change in dc output current when load resistance changes from short circuit to full load or from full load to short circuit.
Test Parameter:
Measured Variable: Output Current Expected Results: Less than 0.01% plus 1 mA
Test Procedure:
a. Connect the DVM across R, in Rgure A-2. Operate the
electronic load in constant voltage mode and set its voltage to the full rated value of power supply.
b. Turn the unit's power on and turn VOLTAGE control fully
clockwise.
c. Turn up output current to the full rated value. Check that the
AMPS display reads full rated values and CC indicator remains lighted.
Reduce CURRENT control if not lighted.
d.
Record the voltage across Rs and convert it to current
through dividing by R,. e. Operate the electronic load in short(input short mode). f. When the reading settles, record voltage across R, again.
Check that the two' recorded readings differ no more than
0.01%
of output current plus 1 mA.
Source Effect(Line Regulation)
Definition:
Source Effect is the change in dc output current when the ac input voltage changes from the minimum to maximum val­ue( ± 10% of nominal voltage).
POWER SUPPLY
UNDER TEST
RL
LAAAAr-l
-^1—Q-
0.01 uF
0.01
uF V_
-O-i­"O-
DIFFERENTIAL
-0+ OSCILLOSCOPE
-O-
RL
E3610A E3611A E 3612 A
2.6 ohm
• 13.3 ohm
• 120 ohm
Figure A-5. Peak-to-Peak Measurement Test Setup
Test Parameter:
Measured Variable: Output Current Expected Results: Less than 0.01% plus 1 mA
Test Procedure:
a. Connect the DVM across R, in Figure A-2. Operate the
electronic load in constant voltage mode and set its voltage to the full rated value of power supply.
b. Connect the unit to the ac power line through a variable
autotransformer that set for low line voltage(104 Vac for
115 Vac).
c. Turn the unit's power on and turn VOLTAGE control fully
clockwise.
d.
Turn up output current to the full rated value. Check that the
AMPS display reads full rated values and CC IrKlicator remains lighted.
Reduce CURRENT control if not lighted.
e. Record output voltage across Rs and convert it to current
through dividing by R, .
f. Adjust autotransformer to the high line voItage(127 Vac for
115 Vac).
g.
When the reading settles, record the voltage across R, again.
Check that the two recorded readings differ no more than
0.01%
of output current plus 1 mA.
Constant Current(CC) Tests
For output current measurements the current sampling resistor must be treated as a four terminal device. In the manner of a meter shunt.
PARD(Ripple and Noise)
Definitioii:
Periodic and rarxJom deviation(PARD) in the unit's output
ripple and noise combine to produce a residual ac current as well as
A-4
Page 11
an ac voltage superimposed on the dc output. Constant Current PARD is specified as the root-mean-square(rms) output current in a frequency range of 10 Hz to 10 MHz with the unit in CC operation.
PARD{RMS) Measurement
Test Parameter: Measured Variable: Output Current(rms) Expected Results: Less than 200 uA rms
Test Procedure:
a. Connect the test equipment as shown in Figure A-6. b. Turn the unit's power on and turn the VOLTAGE control fully
clockwise.
c. Turn up output current to the full rated value. Check that the
CC indicator remains lighted. Reduce CURRENT control if not lighted.
d.
Record rms voltage across R^ ar>d convert it to current through
dividing by R,.
e. Check that the rms noise current is no more than 200 uA.
PARD(Peak-to-Peak) Measurement
Test Parameter:
Measured Variable: Output Current(peak-to-peak)
Expected Results: Less than 1 mA p-p
Test Procedure:
a. Connect the test equipment as shown in Figure A-6, but
replace the RMS voltmeter with oscilloscope. b. Set the oscilloscope to AC mode and bandwidth to 10 MHz. c. Turn the unit's power on and turn the VOLTAGE control fully
clockwise. d.
Turn up output current to the full rated value. Check that the
CC indicator remains lighted. Reduce CURRENT control if not
lighted. e. Record peak-to-paak voltage across R^ and convert it to
current through dividing by R^. Check that the peak-to-peak
noise current is no more than 1 mA.
POWER SUPPLY
-t-
o o
< < <
>"^
R5 =
1
ohm. 1
TRUE-RMS
VOLTMETER
9 9
,i.
10 W
CALIBRATION PROCEDURE
To calibrate ammeter and full scale current, connect test equipments as shown in Rgure A-7.
POWER SUPPLY
O
-I­O
DIGITAL
VOLTMETER
-E
Q 0
Rs= 0.1 ohm.
0.1%.
10 W
Figure A-6. RMS Measurement Test setup
Figure A-7. Calibration Test Setup
Calibration in High Current Range
a. Turn VOLTAGE and CURRENT control fully clockwise. b. Set RANGE push button to high current range. c. Turn on power supply and adjust R31 so that DVM indicates
exactly as follows (5% over rated current):
E3610A: 0.315 V E3611
A:
0.158 V E3612A:
0.053
V
d.
Adjust R3 on the display board so that the displayed value on
the front panel is equal to DVM value divided by R,.
e. While depressing CC SET push button, adjust R20 so that the
displayed value on the front panel is equal to DVM value divided by R,.
Calibration in Low Current Range
a. Set RANGE push button to low current range. b. Adjust R32 so that DVM indicates exactly as follows (5% over
rated current).
E3610A:0.21V E3611 A: 0.089 V E3612A: 0.026 V
Calibration of VOLTS Meter
a. Disconnect the current shunt(Rj) and connect DVM across
output of supply.
b. Set RANGE push button to low current range at no
load.
c. Adjust VOLTAGE control till DVM indicates exactly as
follows (full rated voltage):
E3610A:15V E3611A:35V E3612A:120V
d.
Adjust RIO on the display board so that the value of the front
panel display is the same as the value of DVM.
A-5
Page 12
E361XA REPLACEABLE PARTS LIST
Reference
Designation
E361XASTD/0E9 E361XA0E3
E3610AQ1.3 E3611AQ1,3 E3612AQ1,3
82 S3 SI E3610ASTDT1 E3610A0E9T1 E3610A 063X1 E3611ASTDT1
E3611A0E9T1 E3611A0E3T1 E3612ASTDT1
E3612A0E9T1
E3612A0E3T1
E3aiXASTD/0E9F4 E361XA0E3F4
Cl E3610AC2 E3611AC2 E3612AC2 E3610AC3 E3611AC3 E3612AC3 C4,5 E3810A,11AC6 E3612A C6 C7 E3aiOA.11AC10 E3612AC10 Cll.16 C8,14,18 C9,15.19 E3610AC12 E3611AC12 E3612AC12 C13
HP Part Number
ESaiXA 0403-0424 5041-8602 6041-8603 5041-8604 0371-3806 0371-3807 5959-5304 8120-1378 8120-1689 9220-4867 9220-4868
ESe
1X60001 0340-0140 0340-0168 0515-0926 0515-1162 0515-1711 0535-0007
1400-0307 1854-0611 1854-1257 1855-0536 2190-0585 2190-0586 2190-0587 3050-0894 3101-3070 3101-2985 3101-3115 9100-4959 9100-4958 9100-4957 9100-4956 9100-4955 9100-4954 9100-4996 9100-4995 9100-4994 0890-1788 5062-3403 04700357 08901788
5062-3401 0360-0268 0515-0910 1252-4214 21100702 2110-0599 5021-8105
E361X-60002
0160-7077 0180-4352 01804361 0180-4351 0180-4355 0180-3595 01803937 01600269 01607548 0160-4787 01804085 01607547 01603585 0160-6225 01607449 01803970 0160-7456 01607080 01607082 0180-4355
Qty
.
1 2 8 2 2 4 4 6 2 2 2 4 2 2 2
.240
3
3 3
2 3 3
1
1
1 1
IDescription
E361XA POWEX SUPPLY BUMPER FOOT-AEJH MTG f^VRCAP TOP COVER BOTTOM COVER KEYCAP-WH KEY CAP-GRANITE OPERATION AND SERVICE MANUAL POW^I CORD OPT903 POWER COM) OPT902 PAD-PACtCAGING.FRONT PAD-PACKAGING.FSAR
MAIN BODY ASSY
INSULATOR-XSTR MICA INSULATOR BUSHING SCR-MACH IM4X0.7 SCR-MACH M5X08 SCR-MACH M3.5X06 NUT-HEX DBL-CHAM M3.5X0.6 CABLE TIE
XSTR
NPN
2N6055 SI DARL TO-3 XSTR NPN BU323A SI DARL TO-3 XSTR MOSFET IW^40
N-CHAN
TO-3 VreHR-LK M3.5 ID Vt/SHR-LK M4.0 ID Vy^HR-LK M5.0 ID WreHR-FL MTLC 5.0 SW-PBDPOT6A250V SW-PBDPST4A250V SW-PB .5A 250VAC TRANSFORMER, E3610A 115V TRANSFORMER, E3610A lOOV TRANSFORMEa E3810A 230V TRANSFORMER, E3611A 115V TRANSFORMER. E3611A 100V TRANSFORMER
E361
IA 230V
TRANSFORMER.
E361
2A 115V TRANSFORMER, E3612A 100V TRANSFORMER, E3612A 230V SLEEVING FLEXIBLE WIRE HARNESS ASSY-DISPLAY SIUCONE RUB8ER-RTV SLEEVING FLEXIBLE
HFAT SINK ASSY TEre*SOLDER LUG SCR-MACH M4X0.7 CONNECTOR-AC POW/ER FUSE 2A 250V NTD FUSE 250V IA HEAT SINK-DIECASTING
MAIN BOARD ASSY CAP0.1UF 630V 10% POLYE-MET CAP 10000UF SOV 20% AL-ELEC CAP4700UF 100V 20% AL-EUC CAP 1000UF 250V 20% AL-EUC CAP 470UF 50V 20% AL-ELEC CAP 220UF 100V 20% AL-ELEC CAP 100UF 250V 20% AL-ELEC CAP0.1UF500V20%CER CAP 2200PF 50V 10% CER CAP22PF100V5%CER CAP 330UF 35V 20% AL-ELEC CAP 1000PF 500V 5% CER
CAP 1UF 250V 20% AL-ELEC CAP .33UF 250V 10% POLYE-MET
CAP.33UF50V10%PE CAP 1UF 50V 20% AL-EIEC CAP180PF50V5%CER CAP 220PF 50V 5% CER CAP 120PF 50V 5% CER CAP 470UF SOV 20% AL-ELEC
Mfr
Code
28480 28480 28480 28480 28480 28480
28480 28480 28480
28480
28480
28480 28480
28480
28480
28480 28480 28480 04713 04713 04713 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480
28480 28480 28480 28480 28480 28480
28480 28480 28480
28480 28480
28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480
Mfr Part
Number
2N605S BU323A ire:44o
A-6
Page 13
E361XA REPLACEABLE PARTS LIST
Reference
[>esignation
C17 C20 E3612AC22,23 E3610AR1 E3611AR1 E361
2A Rl £361 OA R2 E3611AR2 E3612AR2 R3 R4,25 R5 E3610A,11AR6 E3612AR6 E3610A,11AR8 E3612AR8 E3610A,11AR10 E3612AR10,38,39 E3611A.12ARn,12 E3610AR12 E3eiOA.nAR13 E3612AR13 R14 E3610AR15 E3611AR15 E3612AR15 R16,26 R17 E3610AR18 E3611A,12AR18 R20 E3610A.11AR22,23 E3612AR22,23 R24 E3610AR27 E3611AR27 E3612AR27 E3610A.11AR28 E3612AR28 R29,30 R31.32 E3610AR33 E3611AR33 E3612AR33 E3610AR34 E3611AR34 E3610AR35,36 E3611AR35,36 E3612AR35,36 R40 R41 E3612AR43 E3612AR44,45 F1,2 F3 Ul U2 U3 U4 U5 U6 U7 02 E3612AQ4,5 CR2 CR3 CR4,5 CR6,7,10,11 CR8 CR9,13
HP
Part
Number
018O3990 01606071 01604832 0811-1806 0811-2188 0699-3105 0811-3478 0811-3839 0811-3861 0699-2882 0698-4254 0698-4002 0699-3266 81504920 0698-4254 0698-4002 0698-4254 0757-0398 0757-0442 81504920 0813-0001 0811-2188 0698-4254
0698.4307 0757 0290 0811-3873 0698-4278 0699-1063 0698-8020 0757-0288 2100-4306 0698-6250 0757-0440 0698-4009 0698-8812 0699-3200 81504920 0757-0439 0757-0290 0761-0021 21004305 0698-4440 0698-0063 0698-4471 0698-8957 0698-8825 0811-3864 0811-3874 0811-3886 0698-4531 0698-3155 0698-8020 0698-3160 21100665 0699-2715 1826-0961 1826-0147 1826-1297 1826-1075 1826-0412 1826-0221 1826-0144 1853-0041 1854-0477 1906-0255 1901-0848 1901-0461 1901-0033 1901-0327 1906-0284 03602359 0515-0911 0515-0918
Qty
2
2
3 2
2
2 2
2
2
2 2 2 1 1 1 2 2 1 1 1 1 1 1 1 1 1
2
1
1 2 4
1 2
10
1 3
Description
CAP
4700UF
25V 20%
AL-ELEC
CAP18PF
100V 5% CER CAPO1UF50V20%CER RES 2K 5% 3W PWI RES 5K 5% 3W
PWrt RES 45K 5% 2W MO RES.1
1%5WPWN
RES .2
1%5W/PWN
RES 1.78
1%5WPWN
RES 1.2K 1%
.5WTF
RES IK 5%
.125W/TF
RES5K
1%
.125WTF
RES1.5M5%
.125WTF
JUMPER WIRE 22AWG
1X2
RES IK 5%
.125WTF
RES5K
1%.125WTF
RES IK 5%
.125WTF
RES 75 1%
.125WTF
RES 10K 1%
.125WTF
JUMPER
WIRE,
22AWG
1X22
RES IK 5%
3WPVVI RES 5K 5% 3W PWI RES IK 5%
.1.25WTF RES 14.3K 1%
.125WTF
^i
RES6.19K
1%
.125WTF
.'
RES3.65K
1%
3WPWN
RES 10K5%
.125WTF
RES900K
1%
.125WTF
RES 100K 1%
.125WTF
RES9.09K
1%
.125WTF
RES-TMMR
50K 10% 25T
RES2.5K
1%
.125WTF
RES7.5K
1%
.125WTF
RES50K
1%
.125WTF
RES 1 1%
.125WTF
RES 6.8 1%
.125WTF
JUMPER WARE 22AWG
1X22 RES 6.8 IK 1% .125WTF-- ' RES6.19K
1%
.125WTF RES IK 5% 1WM0 RES-TMMR
10K 10% 25T
RES
3.40K
1%
..125WTF
<.
RES
5.23K
1%
.125WTF
-
RES7.15K
1%
.125WTF RES500K
1%
.125WTF
RES681K
1%
.125WTF
RES.6
5%5WPWN
RES 1.2 5%
5WPW/N RES 10 1 % 3W PWN RES267K
1%
.125WTF
RES4.64K
1%
.125WTF
RES 100K 1%
.125WTF
RES31.6K
1%
.125WTF
FUSE
IA 125V
FUSIBLE
RES 1 OHM 5% .5W ICLF411CN-0PAMP IC V
RGLTR FXD11.5/1
2.5
TO-220
IC
LM336BZ5.0V RGLTR TO-92
IC
LF442CN-0P
AMP
DUAL 8 DIP-P
IC 393
8-DIP-P
PKG
IC
MC791 2CT-V RGLTR TO-220
IC MC
7805CT-V RGLTR TO-220
XSTR
PNP SI
XSTR
NPN
2N2222ASIT0-18
DIOOE-FW BRDG 600V
6A
DIODE-PWR RECT 400V
3A
DIOOE-GEN
PRP 10V .2A
DIODE-GEN
PRP 180V .2A
DIOOE-PWR RECT 200V
1A
DIODE-FW BRDG
100V 1A TERMINAL-TEST POINT SCREW-MACH M3X0.5 SCREW-MACH M3.5X0.6
Mfr
Code
28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480
28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 27014 04713 27014 27014 27014 04713 04713 04713 04713 28480 04713 27014 27014 28480 28480 28480 28480 28480
Mfr
Part
Number
LF411CN MC7812CT LM336BZ LF442CN LM393N MC7912CT MC7805CT
2N2222A KBPC606 MR854
1N4148 1N645
A-7
Page 14
E361XA REPLACEABLE PARTS LIST
Reference
Designation
HP Part Number
Qty
Description
Mfr
Code
Mfr Part Number
E3610A.11A
Jl
E3610A.11A Ll E3612A JP1 E3610A.11A JP2
R19 E3610A.11AR37 E3612AR37
E3610A
E3611A
£3612A
E3610A
£361
IA
£3612A
1205-0595 1251-7406 2190-0584
2190-0585 5002-0202 91700894 81504920 8150^920
E361X-60003 2100^503 2100^308 210O.4307
5002-0203
5021-8104 5041-8601 E361080001 E361.1-80O01 £3612-80001 8151-0013
15100135
15100136 03703222 29500144
£3610-60005 £3611-60005 E3612-60005
.025 2
1 2 3
1 1 1
HEAT SINK SGL PLSTC
CONNECTOR-POST TYPE 10P WSHR-LK IM3.0 ID WSHR-LX M3.5 ID
HEAT SINK- BRIDGE DIODE
CORE-SHLO BEAD
JUMPER WIRE 22AWG 1X22
JUMPER WARE 22AWG 1X22
FRONT PANQ. ASSY
RES-VAR 10K 5% 10TURN CEPNET
RES-VAR 50K 5% 10TURN WW
RES-VAR 10OK 5% 10TURN WW
LUG-GROUND
PLATE WflNDOW
FRONT FRAME
LABEL FRONT PANEL
LABEL FRONT PANEL
LABEL FRONT PANEL
COPPER WIRE 22 AWG 1X22
BINDING POST.RED
BINDING POST.BLACK
KNOB
NUT-HEX-DBL-CHAM
DISPLAY BOARD ASSY, E3610 lOP
MSFLAY BOARD ASSY, E3611 lOP
DISPLAY BOARD ASSY, EMU lOP
28480 28480 28480 28480 28480 28480 28480 28480
28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480 28480
28480 28480 28480
A-8
Page 15
Component
C2 03 C6 CIO C12
022.23 Rl R2 R6 R8 RIO RII R12 R13 R15 RIB R22,23 R27 R28 R33 R34 R35,36 R37 R38.39 R43 R44.45 Q4,5 JP1 JP2
Model 1
E3610A
lOOOOuF 50V 20% AL-ELEO 470uF 50V 20% AL-ELEO 2200pF 50V 10% CER
lOOOpF 500V 5% OER
180pF50V5%0ER
2K 5% 3W PWI
0.1
1 %
5W PWN
1.5M5%0.125WTF
1KB%0.125WTF
1K5%0.125WTF
JUMPER WIRE
IK 5% 3WPWI
14.3K 1%0.125WTF
100K 1%0.125WT7
2.5K 1%0.125WTF
1 1 % 0.125W TF
6.81K 1%0.125WTF
3.40K 1%0.125WTF SOOK 1 % 0.1 25W TF
0.6 5% SW PWN 50K5%
10-TURN WW
JUMPER WIRE
E3611A
4700uF 100V 20% AL-ELEC 220uF 100V 20% AL-ELEC 2200pF SOV 10% CER lOOOpF 500V S% CER 220pF SOV S% OER
5K S% 3W PWI
0.2 1% SWPWN
1.SM5%0.12SWTF 1K5%0.12SWTF 1K5%012SWTF 10K 1%0.12SWTF lOK 1%0.12SWTF IK 5% 3WPWI
6.19K 1%0.12SWTF
9.09K1%0.12SWTF
2.SK 1%0.12SWTF
6.8 1%0.125WTF
6.81K1%0.125WTF
5.23K 1%0.125WTF 681K 1%0.12SWTF
1.2 5% SWPWN S0K5%
10-TURN WW
JUMPER WIRE
E3612A
lOOOuF 250V 20% AL-ELEO lOOuF 2S0V 20% AL-ELEC 22pF 100V 5% CER 1uF260V 20% AL-ELEC
120pF SOV 5% CER O.luF SOV 20% OER 4SK S% 2W MO
1.78 1% SWPWN JUMPER WIRE 6K 1%0.125WTF
75 1%0.12SWTF 10K 1%0.125WTF 10K 1%0.125WTF
6K 5% 3W PWI
3.6SK 1 % 3W PWN
9.09K 1%0.125WTF
7.SK 1%0.12SWTF JUMPER WIRE
6.19K 1%0.12SWTF
7.15K 1%0.12SWTF
10 1% SWPWN 100K5% 10-TURN WW 75 1%0.12SWTF 100K 1%0.12SWTF
31.6K 1%0.12BWTF XSTR NPN 2N2222A SI TO-18 JUMPER WIRE
• COMPONENT VALUE TABLE
NOTES:
1.
The values of all component * marked are shown in the at>ove comporwnt value table.
2.
All resistors are 0.125W. 6%. and ohms, unless otherwise specified.
3. All capacitors are mk;rofarads. unless otherwise specified.
4.
SIA CO SET switch shown is OFF position.
5. S2B RANGE selector switch shown is high current range.
6. Voltages between TP2 and TP4 in tow current rangs are:
Model E3610A
E3611A
E3612A
Voltage 2SV±10%
47V±10%
152V±10%
A-9
Page 16
ncc
nc
fe^
Tl I F3
CV/CC Indicator Ci rcu11
r
> Jl (S) CC INDICRTCR
I • Jl O)
DOicnroR comoN
* Jl (7) CV DOICHTO)
« Sin CC SET ^^.O > Jl (5) I*
Jl (G) I-
Meter Input
C i rcu11
> Jl (3> v+ > Jl {^) V-
Flgure A-8. Schmatic Diagram
Loading...