HP Disk Carrier Blade for bh3710, Management LAN Blade for bh7800, bh3710 Installation Manual

hp Carrier Grade Blade Server
bh3710
Installation Guide
Manufacturing Part Number:
USA
© Copyright 2002
Second Edition
ii
Legal Notices
The information in this document is subject to change without notice.
Hewlett-Packard makes no warranty of any kind with regard to this manual, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Hewlett-Packard shall not be held
liable for errors contained herein or direct, indirect, special, incidental or consequential damages in connection with the furnishing, performance, or use of this material.
Restricted Rights Legend. Use, duplication or disclosure by the U.S. Government is subject to restrictions as set forth in subparagraph (c) (1) (ii) of the Rights in Technical Data and Computer Software clause at DFARS 252.227-7013 for DOD agencies, and subparagraphs (c) (1) and (c) (2) of the Commercial Computer Software Restricted Rights clause at FAR 52.227-19 for other agencies.
HEWLETT-PACKARD COMPANY 3000 Hanover Street Palo Alto, California 94304 U.S.A.
Copyright Notices. ©copyright 1983-2002 Hewlett-Packard Company, all rights reserved.
Reproduction, adaptation, or translation of this document without prior written permission is prohibited, except as allowed under the copyright laws.
Contents
iii
1. hp Carrier Grade Server bh3710 Overview
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Network Equipment-Building Systems (NEBS) Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation Guide Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Audience Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Unpacking and Installing the hp Carrier Grade Blade Server bh3710
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Unpacking the Blade Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installing the bh3710 Blade Server in a Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3. hp Carrier Grade Server bh3710 Power and Cooling Component Overview
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DC Power Supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Blade Server Power Supply Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DC Power Input Module and Cable Connector Pinout Information. . . . . . . . . . . . . . . . . . . . . . . . . . 4
Blade Server Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Applying Power to the hp Blade Server bh3710
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
hp Blade Server Initial Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Chassis and Management Blade Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
bp2200 Server Blade Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Blade Server Power-Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Power-Down the bp2200 and Management Blades. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Chassis Power-Down. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5. hp Carrier Grade Server bh3710 Server Blade Installation Information
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Server Blades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Display Panel Blade Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Management Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Management Blade LED Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Management Blade Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Configuring the Management Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Pre-Configuration Assumptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LAN Cabling Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Configuration Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Management Blade Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
bp2200 Server Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GSP Reset and Transfer of Control (TOC) Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
bp2200 Server Blade LED Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
bp2200 Management Processor (MP) Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Configuring the MP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Contents
iv
Pre-Configuration Assumptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
LAN Cabling Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Configuration Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Management Blade Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Management Processor Network Parameters Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Access the MP Console.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Boot Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Boot Console Handler (BCH) Boot Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Boot to the HP-UX Prompt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Rebooting to the HP-UX Prompt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Fibrechannel (FC) and LAN Rear Transition Module (RTM) Blade. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
FC and LAN RTM LED Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
FC and LAN RTM Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
LAN Connectivity to the FC and LAN RTM Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
LAN Connectivity Pre-installation Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fibre Channel (FC) Disk Carrier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
FC Disk Drive LED Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Installing and Removing Blades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Removing and Installing Slot Blockers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Remove the Slot Blocker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Install the Slot Blocker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Installing and Removing Blades With Locking Levers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installing Blades With Locking Levers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Removing Blades With Locking Levers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installing and Removing Carrier Blades. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installing the Carrier Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Removing the Carrier Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6. Communication with the hp Carrier Grade Blade Server bh3710
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Remote Installation of Operating Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Support Tool Manager. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
7. Specifications for the hp Carrier Grade Server bh3710
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
A. LVM Boot Device Hardware PathChange for the hp Carrier Grade Server bh3710
Figures
v
Figure 0-1. Power Supply Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 0-2. hp Blade Server DC Power Supply Input Module (Server Rear View) . . . . . . . . . . . . . . 3
Figure 0-3. hp Blade Server DC Power Supply Output Module (Server Front View) . . . . . . . . . . . . 3
Figure 0-4. DC Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 0-5. DC Power Connector Pin location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 3-6. Cooling Airflow into the Blade Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5-1. Rear View of Chassis With Blades Installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 5-2. Front View of Chassis With Blades Installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 5-3. Management Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 5-4. Management Blade Bulkhead Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 5-5. Identification Legend Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5-6. bp2200 Server Blade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 5-7. bp2200 Blade Bulkhead Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 5-8. bp2200 Identification Legend Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 5-9. FC and LAN RTM Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 5-10. FC and LAN RTM Blade Bulkhead Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 5-11. Fibrechannel and LAN RTM Identification Legend Marking . . . . . . . . . . . . . . . . . . . 14
Figure 5-12. bh3710 Chassis (Rear View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 5-13. FC Disk Carrier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 5-14. FC Disk Carrier Legend Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 5-15. FC Disk Drive Bulkhead Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 5-16. Slot Blocker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 5-17. Align Blades With Card Guides and Push Into Chassis . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 5-18. Insert the Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 5-19. Tighten the Locking Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 5-20. Releasing Locking Levers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 5-21. Loosen Locking Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 5-22. Releasing Locking Levers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 5-23. Pull Blade From Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 5-24. Two-Handled Blade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 5-25. FC Disk Carrier Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figures
vi
vii
Preface
Printing History
The Printing History below identifies the edition dates of this manual. Updates are made to this publication on an unscheduled, as needed, basis. The updates will consist of a complete replacement manual and pertinent on-line or CD-ROM documentation.
First Edition April 2002
Second Edition September 2002
What’s New?
Customer documentation is reviewed, updated, and republished to ensure that information that was either unknown or omitted from the previous edition, is included. Changes/additions in this edition are described as follows:
All chapters/appendices were reviewed and changes were made to correct format, grammar, and spelling.
Chapters 3, 4, and 5 have been revised and realigned as follows:
— Chapter 3 now includes power and cooling system information, only.
— Chapter 4 is now the power application chapter. It was Chapter 5, initially.
— Chapter 5 is now Blade installation information and has been expanded to include more graphics,
new procedures, and configuration information. Server blade installation/removal instructions are also included in this chapter.
An index is included.
viii
Chapter 1
hp Carrier Grade Server bh3710 Overview
Introduction
1-1
1 hp Carrier Grade Server bh3710 Overview
Introduction
The hp Carrier Grade Blade Server bh3710 (called “blade server” in this manual) provides customers with a single chassis that houses one server blade and up to four Fibre Channel disks in two dual Fibre Channel disk carrier blades, controlled by one Management Blade. The form factor for all the blades uses the Compact PCI standard. The chassis mounts in a standard 19 and/or 23-inch EIA two column rack. The chassis will accommodate 10 full size Compact PCI cards (6U x 160mm) in the front slots and 10 half size Compact PCI cards (6U x 80mm), called Rear Transition Modules (RTM), in the rear slots.
Network Equipment-Building Systems (NEBS) Compliance
This system is compliant with NEBS Level 3 requirements as defined in GR63 and GR1089 standards.
Installation Guide Contents
Before installing your blade server, familiarize yourself with the components that comprise the bh3710. Use the following reference to determine where you would like to start.
Chapter 1 - Introduction.
Chapter 2 - provides information for unpacking, inventorying, and rack installation.
Chapter 3 - presents an overview of blade server power and cooling components.
Chapter 4 - explains power-up and power-down procedures for the blade server and server blades.
Chapter 5 - includes information about the types of server blades used in this system, configuration information, LAN cabling requirements, boot procedures, and procedures for the installation and removal of server blades and storage components.
Chapter 6 - discusses remote communication with the blade server.
Chapter 7 - lists blade server System Specifications.
Audience Assumptions
This guide is written for the person who installs, administers, and troubleshoots servers. Hewlett-Packard Company assumes that you are qualified to service computer equipment and that you are trained to recognize the dangers in working with products that have hazardous energy levels.
Chapter 1
hp Carrier Grade Server bh3710 Overview
Introduction
1-2
Chapter 2
Unpacking and Installing the hp Carrier Grade Blade Server bh3710
Introduction
2-1
2 Unpacking and Installing the hp Carrier
Grade Blade Server bh3710
Introduction
This chapter is intended as a quick reference for blade server installation. Some components and steps may not apply to all configurations. Steps that do not apply may be skipped.
For more detailed operational and system information, refer to the hp Carrier Grade Blade Server bh3710 Service Manual.
Site Preparation
Prepare the site for installation as described in the hp Carrier Grade Blade Server bh3710 Site Preparation Guide.
Unpacking the Blade Server
The following information is provided for blade server unpacking:
Electrostatic Discharge (ESD) Precautions. When handling any electronic component or assembly (such as the chassis, backplane, blades, and peripheral components) observe all antistatic precautions. An ESD kit (HP PN A3025-80004 is available or supplied with this system. The kit contains one wrist strap, one conductive sheet, and one antistatic foam pad.
Always wear a grounded wrist strap when working on the equipment or printed circuit boards.
Treat all assemblies, components, and interface assemblies as static sensitive.
Avoid working in carpeted areas and keep body movement to a minimum while removing or installing components to minimize buildup of static charge.
WARNING The blade server weighs approximately 29 kg (65 lbs) when fully loaded. At least two
people are required to lift the blade server into the cabinet and a third to secure it. It is recommended that a mechanical assistance device be used to lift the blade server into position. Failure to heed this warning may result in serious injury and destruction of the blade server.
Chapter 2
Unpacking and Installing the hp Carrier Grade Blade Server bh3710
Installing the bh3710 Blade Server in a Rack
2-2
Step 1. Unpack the blade server from its shipping container.
Step 2. Compare the contents with the packing list to ensure that all required components have been
received, as listed in Table 2-1.
Step 3. Use two or more people, or a mechanical device, to move the blade server to the installation site.
Step 4. Prepare the rack for mounting the blade server chassis.
NOTE Quantity depends on ordered configuration.
Installing the bh3710 Blade Server in a Rack
The racking kit enables the installation of the bh3710 chassis into a rack. Rack kit installation documentation is shipped with each server inside the rack kit box. Racking information may also be found at
the Web site: http://www.hp.com/racksolutions.
Table 2-1 Blade Server Components
Qty Part No.
Exchange
Part No.
Component
1 A6715-62001 A6715-69003 6 EIA unit blade server chassis with backplane and
N+1 fan tray assembly
2 A6790-62004 A6790-69004 DC power supply
2 A6780-60001 A6780-69001 Fibre channel (FC) and LAN RTM blade
1-4 5065-7804 A6783-69001 18GB fibre channel disk
1-2 A6711-62001 A6711-69001 FC disk carriers
2 to 4 A6709-60001 A6709-69001 256 MB DIMM
1 A6708-62001 A6708-69001 bp2200 Blade (2 slot) (front load only)
1 A6712-60001 A6712-69001 Management blade
0 to 2 A6707-00014 N/A DIMM filler (for bp2200 server blade)
1 A6715-70001 N/A Kit, spare slot blockers (2 front, 2 rear)
2 A6715-63001 N/A DC external power input cable
Chapter 3
hp Carrier Grade Server bh3710 Power and Cooling Component Overview
Introduction
3-1
3 hp Carrier Grade Server bh3710 Power and
Cooling Component Overview
Introduction
Blade server power and cooling elements are described in Chapter 2, Table 2-1. All components ordered are pre-installed and configured at the factory. This section provides a summary and location of them.
Chapter 3
hp Carrier Grade Server bh3710 Power and Cooling Component Overview
DC Power Supplies
3-2
DC Power Supplies
Power supplies come in two parts and reside in the lower bay of the chassis. They are accessed from both the front and rear of the chassis as illustrated in Figure 0-1.
Each power supply has two LEDs located on the front of the blade server that are used to determine the operating condition. The top LED is green and illuminates whenever DC power is present and within operating specifications. The bottom LED is red and illuminates whenever the power supply is in a fault condition.
Figure 0-1 Power Supply Locations
Front Power Supply Sections (Output Modules)
Rear Power Supply Sections
Earth Ground Lug
(Input Modules)
Chapter 3
hp Carrier Grade Server bh3710 Power and Cooling Component Overview
DC Power Supplies
3-3
Grounding
The blade server must be grounded to earth via the ground lug provided on the chassis to ensure safe operation, to prevent damage from electrostatic discharge, and to assure compliance with electromagnetic compatibility requirements. The location is shown in Figure 0-1, Rear Power Supply view.
CAUTION The DB9 connector shown in Figure 0-2 marked “For Manufacturing Use Only”, was installed
for use during the manufacturing process. It cannot be used for anything else. If an RS232
-type plug is used in this receptacle, it could cause the power supply to reset, thereby losing data being transmitted to the blades.
DO NOT USE THIS RECEPTACLE FOR ANY PURPOSE!
Figure 0-2 hp Blade Server DC Power Supply Input Module (Server Rear View)
Figure 0-3 hp Blade Server DC Power Supply Output Module (Server Front View)
Power supplies are hot swappable. Hot swap remove and replace details are found in the hp Blade Server bh 3710 Service Guide.
For Manufacturing Use Only
Chapter 3
hp Carrier Grade Server bh3710 Power and Cooling Component Overview
DC Power Supplies
3-4
Blade Server Power Supply Connector
DC Power Input Module and Cable Connector Pinout Information
The power supply connector on the input module is a Positronics PLB06. The cable supplied for each power supply is a 5-wire cable. All 4 wires on each cable must be connected. Two wires (red and black) are connected to the –48VDC source and the remaining two wires (white and green) are connected to the DC return. All four wires from the same power cord must be connected to the same power source. Each power supply filter module may be connected to a different –48VDC source to provide power source redundancy.
Figure 0-4 DC Power Cable
Pin
Number
Function Color
1 Negative DC Supply (-48vdc) Red
2 DC Return (0vdc) White
3 Functional Earth Not Connected
4 Negative DC Supply (-48vdc) Black
5 DC Return (0vdc) Green
6 Functional Earth Not Connected
Chapter 3
hp Carrier Grade Server bh3710 Power and Cooling Component Overview
DC Power Supplies
3-5
Power cable pin-out information is illustrated as follows:
Figure 0-5 DC Power Connector Pin location