HP D9N46A, D9N44A, D9N45A, D9N52A, D9N47A Specifications

...
HP Remote Monitoring Power Distribution Units (PDU) provide rack level power monitoring over the network. With billing grade accuracy these PDUs are excellent choices for data centers wanting to make the most of circuit capacity or for co-location facilities needing to precisely track power usage for billing purposes.
The low profile single piece design on these PDU's provides multiple mounting options and ease of access to rear devices for maintenance. They are designed for HP racks but will also work in a large variety of third party racks as well using standard button and keyhole mounting. They can be installed on either side of the rack with outlets facing the back of the rack for easy access and improved clearance. Also for higher power density they can be installed side by side on both sides of the rack with the outlets facing in towards the center of the rack. HP Remote Monitored PDUs are available in 1U and vertical form factors in single and 3-phase models and are back by HP's limited 3-year warranty.
Monitored PDU, 1UModels (D9N46A shown)
Monitored PDU, Half Height Models (D9N45A shown)
Monitored PDU, Mid Height Models (D9N47A/D9N48A shown)
Monitored PDU, Full Height Models (D9N58A/D9N59A shown)
QuickSpecs
HP Remote Monitored Power Distribution Units (mPDU)
Overview
DA - 14669 North America — Version 7 — May 9, 2014
Page 1
HP Remote Monitoring Power Distribution Units
1U Models
HP 3.6kVA 200-240 Volt Detachable C20 Input (12xC13) WW Monitored PDU
D9N46A
HP 4.9kVA 208 Volt L6-30 Input (12xC13) NA/JP Monitored PDU
D9N44A
Half Height Models
HP 3.6kVA 200-240 Volt Detachable C20 Input (16xC13) WW Monitored PDU
D9N45A
Mid Height Models
HP 4.9kVA 208 Volt L6-30 Input (20xC13/4xC19) NA/JP Monitored PDU
D9N47A
HP 5.7kVA 208 Volt L21-20 3-Phase Input (18xC13/3xNEMA 5-20R) NA/JP Monitored PDU
D9N52A
HP 8.6kVA 208 Volt L21-30 3-Phase Input (20xC13/3xC19/3xNEMA 5-20R) NA/JP Monitored PDU
D9N53A
HP 8.6kVA 208 Volt L15-30 3-Phase Input (18xC13/3xC19) NA/JP Monitored PDU
D9N51A
Full Height Models
HP 8.3kVA 208 Volt CS8265C Input (30xC13/3xC19) NA Monitored PDU
D9N49A
HP 16.6kVA 400 Volt IEC309 30A 3-Phase Input (30xC13/3xC19) NA Monitored PDU
D9N61A
HP 17.3kVA 208 Volt IEC309 60A 3-Phase Input (24xC13/3xC19) NA/JP Monitored PDU
D9N54A
HP 14.4kVA 208 Volt CS8365C 3-Phase Input (12xC13/12xC19)NA Monitored PDU
D9N58A
HP 16.6kVA 400 Volt IEC309 30A 3-Phase Input (12xC13/12xC19) NA Monitored PDU
D9N62A
HP 17.3kVA 208 Volt IEC309 60A 3-Phase Input (12xC13/12xC19) NA/JP Monitored PDU
D9N59A
480/277 Volt Models
HP 19.9kVA 480 Volt 3-Phase (30 Outlet) NA Monitored PDU
D9N63A
QuickSpecs
HP Remote Monitored Power Distribution Units (mPDU)
Models
DA - 14669 North America — Version 7 — May 9, 2014
Page 2
Key Features List
Remote power monitoring with billing grade 99% accuracy Local or LDAP authentication LCD Display on the PDU for local monitoring Ultra-thin one piece design does not interfere with rear maintenance 1U and vertical form factors with flexible mounting options Industry standard button and keyhole mounting of vertical models for easy drop in installation Color coded load segment designations Daisy chain up to 2 PDUs on the same IP address Optional environment sensor measures temperature and humidity Models range from 2.8kVA to 22kVA
Billing grade accuracy
All HP Remote Monitoring PDUs meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in power monitoring of:
Amperage Voltage Wattage Kilowatts per hour
A LCD screen on the HP Remote Monitored PDU provides local monitoring and local alert indications.
Remote monitoring and management is available via Telnet or a standard web browser.
Flexible Software
Easy to use CLI and web interfaces Local and LDAP security with multiple access levels HTTP, HTTPS, Telnet/SSH protocols IPv4 and IPv6 compatible SNMPv1 and SNMPv3 compatible Email alert notifications User settable alert thresholds Event logs
QuickSpecs
HP Remote Monitored Power Distribution Units (mPDU)
Standard Features
DA - 14669 North America — Version 7 — May 9, 2014
Page 3
Multiple models for flexible installation
The HP Remote Monitoring PDUs are available in four form factors for a variety of racks and environments. All HP Remote Monitoring PDUs can be mounted to stay completely out of the critical rear maintenance path needed to service IT equipment in the rack. All vertical models use industry standard button and keyhole mounting for simple drop in installation in HP 11000 G2 and Intelligent Series racks and many third party racks.
1U PDUs
Mounts in 1U of space in any EIA standard rack. Available in either a low voltage model with twelve NEMA 5-20 receptacles or high voltage models with twelve IEC C13 outlets.
Vertical PDUs
A variety of sizes meet the needs of many environments Mounts vertically on either side in the rear of the rack using industry standard button and keyhole mounting. Standard mounting faces the outlet towards the rear of the rack. This configuration fully prevents interference in the maintenance zone between rear RETMA rails. Using the optional configuration of facing the outlets into the rack, multiple PDUs can be mounted on one side of the rack for higher power density.
*
NOTE:
Facing the outlets into the rack will interfere with the lower few rack U spaces of the rear
maintenance zone due to breakers on the PDUs.
Vertical PDU Form Factors
Half Height PDU
Designed to fit in 22U and taller racks Up to 4 Half Height PDUs can be mounted in one side of a 42U or 47U rack using the optional inward facing configuration.
Mid Height PDUs
Designed to fit in 36U and taller racks New Three Phase Dual Voltage models provide three NEMA 5-20 convenience outlets for low voltage equipment in high voltage racks.
Full Height PDUs
Designed for 42U and taller racks.
480V PDUs
Full height form factor for 42U and taller racks 480V three phase 5 wire input provides 277V single phase output. Unique outlets prevent connection of non-277V compatible equipment.
NOTE:
When mounted in the standard rear facing configuration only 1 Mid or Full Height PDU can be mounted per side of the rack. Up to 2 Half Height PDUs can be mounted per side in the standard rear facing configuration in a 42U or taller rack.
Environmental monitoring
An optional environmental sensor attaches to the HP Remote Monitoring PDU and can measure air temperature and humidity in the front or rear of the rack. The environmental senor will send alerts over the network based on user defined thresholds.
QuickSpecs
HP Remote Monitored Power Distribution Units (mPDU)
Standard Features
DA - 14669 North America — Version 7 — May 9, 2014
Page 4