HP FW0154, 0907, 0306 User Manual

Operating Instructions & Parts Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in per­sonal injury and/or property damage! Retain instructions for future reference.
Pressure Booster Pumps
FW0154
0907
Supersedes
0306
Description
Pressure booster pumps increase water pressure from city mains or private water sys­tems. Applications include providing high water pressure for washing buildings, dairy walls or floors, hog parlors, poultry houses, rinsing or spray cooling equipment, lawn sprinkling and insecticide spraying. Stainless steel models can handle salt-water and contaminated water in reverse osmosis filter and other aggressive water applications.
Unpacking
When unpacking the unit, inspect care­fully for any damage that may have occurred during transit.
NOTE: Use pump with clear water only.
H
Inlet I
Discharge J
G
D
Figure 1
A
C
F
B
E
IL0391
60 Hz Motor Driven Pump Dimensions (See Figure 1) • Chart A
Stainless
Steel Fitted
PB0508S031 PB0512S051 PB0516S071 PB0712S071 PB1014S101 PB1016S151 PB1914S201 PB2711S201 PB3506S201 PB2714S301 PB3508S301
-
-
-
-
Powder-Coated
Cast Iron Fitted
PB0508C031 PB0512C051 PB0516C071 PB0712C071 PB1014C101 PB1016C151 PB1914C201 PB2711C201 PB3506C201 PB2714C301 PB3508C301
-
-
-
-
Cast Iron
Fitted
PB0508A031† PB0512A051†
PB0516A071 PB0712A071 PB1014A101 PB1016A151 PB1914A201 PB2711A201 PB3506A201 PB2714A301 PB3508A301 PB5504A201 PB5506A301 PB8504A201 PB8505A301
Dimensions In Inches Lbs. Ship
AB C DE F GH IJ
3-1/4
3-3/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
3-3/4
10-3/16 13-3/8 16-1/2 13-3/8 16-5/16 17-5/8 18-1/8 15-3/8 13-15/16 18-1/2 17-1/8 13-3/4 18-1/16 16-1/2 19-5/16
3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8
6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2
19-15/16 23-3/8 27 23-7/8 27-1/4 29-3/16 29-11/16 27-1/2 25-7/8 30-9/16 29-3/16 25-15/16 30-3/16 28-5/8 31-1/2
7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8
1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16
2-1/8 2-1/8 2-1/8 2-1/8
3/4 3/4 3/4 3/4 3/4 3/4 3/4
3/4 3/4 3/4 3/4 3/4 3/4 3/4
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
Wt.
35 38 43 42 48 51 51 52 51 54 53 57 57 58 58
50 Hz Motor Driven Pump Dimensions (See Figure 1) •58
PB0508Y031 PB0514Y051 PB0714Y071 PB1020Y101 PB1023Y101 PB2717Y201
­PB1021Y101 PB1920Y151
-
(*) NOTE: Figure 1, holes in mounting base are open slotted 3/8” wide x 1/2” long; dimension A & B are centerline from these open slotted holes. These holes are suitable for 1/4 to 3/8” bolts. Dimensions also apply to three phase models. (†) Equipped with carrying handle. 132079 handle available as an option on other models. Add 1-3/8” to “G” if handle is included.
-
-
-
-
PB1023Z101
-
-
-
-
PB1922Z201
PB0508X031 PB0514X051 PB0714X071 PB1020X101 PB1023X101
-
PB3508X151
-
-
-
3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4
3-3/4 3-3/4 3-3/4 3-3/4 3-3/4 3-3/4 3-3/4 3-3/4 3-3/4 3-3/4
10-3/16 14-7/16 14-15/16 21-11/16 24-3/8 21-5/16 16-13/16 22-1/2 24-1/16 26-1/8
3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8
6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2 6-1/2
20-3/16 25-7/16 25-15/16 33-5/16 36 33-7/16 29-11/16 34-3/16 34-3/8 37-3/16
7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8 7-3/8
1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16 1-7/16
3/4 3/4 3/4 3/4 3/4
3/4 3/4 3/4
3/4 3/4 3/4 3/4 3/4
1
1
1
1 3/4 3/4 3/4
34 41 47 53 55 56 52 54 56 59
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
1
132934
PRESSURE ADDED - PSI 10 20 40 60 80 100 120 140 160 180 200
Stainless
Steel Fitted
PB0512S051 PB0512C051 PB0512A051• 1/2 12 9.8 9.2 8.2 7.3 6.3 5.2 3.5 131 PB0516S071 PB0516C071 PB0516A071 3/4 16 9.9 9.5 8.7 8.0 7.3 6.5 5.8 4.8 3.5 175 PB0712S071 PB0712C071 PB0712A071• 3/4 12 14.0 13.4 12.2 10.9 9.5 7.9 6.0 3.6 152 PB1014S101 PB1014C101 PB1014A101 1 14 * * 14.5 13.4 12.3 11.2 9.8 8.3 6.3 3.3 185 PB1016S151 PB1016C151 PB1016A151 1-1/2 16 * * 14.7 13.8 12.9 11.9 10.8 9.7 8.2 6.6 4.3 211 PB1914S201 PB1914C201 PB1914A201 2 14 27.5 27.0 25.7 24.2 22.6 20.8 18.7 16.2 13.0 7.8 190 PB3506S201 PB3506C201 PB3506A201 2 6 41.5 41.1 40.5 34.2 23.3 90 PB2711S201 PB2711C201 PB2711A201 2 11 * * 31.3 29.3 26.8 23.8 19.8 13.0 150 PB3508S301 PB3508C301 PB3508A301 3 8 41.5 41.1 40.9 40.0 34.2 26.4 10.0 120 PB2714S301 PB2714C301 PB2714A301 3 14 * * 32.2 30.6 28.9 27.0 24.8 22.0 18.4 12.2 190
--
--
--
--
† Example: If PB0508A031 pump is connected to supply line of sufficient capacity, carrying water at 40 PSI, and the output of the pump is held to 7.3 GPM by a
gate valve, the pump will add 40 PSI to line pressure for a total output pressure of 80 PSI.
* Operation of pump in this range may result in reduced pump life and/or motor damage.
To keep pump and seal lubricated, a minimum flow of 1.5 GPM must always be maintained through the pump.
Motor voltage: Single Phase 1/3 - 2 HP - 115/230; 3 HP - 230V 60 Hz. Three Phase 1/2 - 2 HP - 208-230/460, 50/60Hz. Three Phase 3 HP - 208-230/460, 60 HZ For three phase models, use suffix “3” on the model no. Example: PB0512A053
• Handle included with these models only.
Powder-
Coated Cast
Iron Fitted
PB0508C031 PB0508A031• 1/3 8 9.5 8.7 7.3 5.8 3.5 87
Cast Iron
Fitted
PB5504A201 2 4 77.6 71.5 PB5506A301 3 6 77.8 74.4 PB8504A201 2 4 105.8 90.0 PB8505A301 3 5 108.8 98.8
HP Stage Output - Gallons per Minute
52.5
65.0
47.0
60.0
31.9
51.1
25.0 60
Max.
Press.
PSI
55 83 49
Suction
Pipe
Pipe Tap
Tap
NPT
3/4” 3/4”
1” 1”
2” 2”
Disch.
NPT
PERFORMANCE SPECIFICATIONS
Single Phase Motor Data 60HZ Chart C
Single Phase† 60 Hz 3450 RPM Capacitor Start
HP
1/3 1/2 3/4
1
1-1/2
2 3
Motor
Voltage
115/230 115/230 115/230 115/230 115/230 115/230
230
Factory
Connected
Motor
Voltage
115V 115V 115V 230V 230V 230V 230V
Service Factor Motor
Amps
Locked Rotor Motor
Amps
115V 230V 115V 230V
8.6
13.0
14.0
18.0
21.0
25.0
-
4.3
6.5
7.0
9.0
10.5
12.5
13.5
26.0
36.0
52.0
78.0
98.0
116.0
-
13.0
18.0
26.0
39.0
49.0
58.0
53.0
Code Letter
K K K
L
J H D
Single Phase Motor Data 50HZ
Single Phase† 50 Hz 2850 RPM Capacitor Start
1/2 3/4
1
1-1/2
2
115/230 115/230 115/230 115/230
230
115V 115V 230V 230V 230V
†Thermal overload protector - automatic reset
10.0
14.4
16.4
23.6
-
5.0
7.2
8.2
11.8
13.2
48.0
64.0
72.0
104.0
-
24.0
32.0
36.0
52.0
55.0
M
L K K H
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
2
Three Phase Motor Data Chart D
Three Phase† 60/50 Hz 3450/2850 RPM Capacitor Start
HP
3/4
1
1-1/2
2
3✝✝
Motor
Voltage
208-230/460 208-230/460 208-230/460 208-230/460 208-230/460
Factory
Connected
Motor
Voltage
230V 230V 230V 230V 230V
Service Factor Motor
Amps
Locked Rotor Motor
Amps
230V 460V 230V 460V
3.5
4.5
5.7
7.4
9.8
1.75
2.25
2.85
3.70
4.90
19.0
26.9
33.5
44.0
48.0
13.5
16.8
22.0
24.0
9.5
Code Letter
K K K K D
✝✝3 HP, 3 Phase motor operable on 60Hz only.
Material Construction Chart E
Component Standard Models* Stainless Steel Models
Motor Rear access - Nema 56J face Rear access - Nema 56J face
Bearings Ball-ball, permanently lubricated Ball-ball, permanently lubricated
Impellers Noryl with 304 stainless steel bearing insert Noryl with 304 stainless steel bearing insert
Diffuser Noryl Noryl
Diffuser plates Delrin Delrin
Pump shaft 416 Stainless steel 304 Stainless steel
Pump shaft coupling 316 Stainless steel 316 Stainless steel
Pump shell 304 Stainless steel 304 Stainless steel
Discharge & inlet casting Cast iron 304 Stainless steel
O-Rings Buna-N Viton
Seal composition Carbon-silicon carbide, stainless steel spring
and Buna-N
*Models with powder coated inlet & discharge also available.
Carbon-silicon carbide, stainless steel spring and Viton
Minimum Wire Size Chart (Gauge) Chart F
Motor
HP
1/3 115/230 1 14/14 14/14 14/14 12/14 12/14 15/15
1/2 115/230 1 12/14 12/14 12/14 12/14 10/14 20/15
3/4 115/230 1 12/14 12/14 10/14 10/12 8/12 20/15
1 115/230 1 10/14 10/14 10/12 8/12 6/10 30/15
1
/2 115/230 1 10/12 8/12 6/12 */10 */10 30/20
1
2 115/230 1 10/12 8/12 6/12 */10 */10 30/20
3 230 1 10 10 10 10 8 30
3/4 230/460 3 14/14 14/14 14/14 14/14 14/14 15/15
1 230/460 3 14/14 14/14 14/14 14/14 12/14 15/15
11/2 230/460 3 14/14 14/14 14/14 12/14 12/14 15/15
2 230/460 3 14/14 14/14 14/14 12/14 10/12 15/15
3 230/460 3 14/14 14/14 14/14 12/14 10/12 15/15
(*) Not economical to run in 115V, use 230V.
Volts Phase
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
0-50 50-100 100-150 150-200 200-300
Distance In Feet From Motor To Service Panel
Breaker Size
(Amps)
Wire Size
3
General Safety Information
Carefully read and follow all safety instructions in this manual and on pump. Keep safety labels in good
condition. Replace missing or damaged safety labels.
9. Do not insert finger or any object into pump or motor openings.
10. Secure the discharge line before starting the pump. An unsecured discharge line will whip, possibly causing per­sonal injury and/or property damage or puncture.
symbol on the pump or in the manual, look for one of the following signal words and be alert to the potential for per­sonal injury or property damage.
personal injury, death or major property damage if ignored.
personal injury or death, if ignored.
personal injury, product or property damage if ignored.
This is a SAFETY ALERT SYMBOL. When you see this
Warns of hazards that WILL cause serious
!
Warns of hazards that CAN cause serious
Warns of hazards that MAY cause minor
IMPORTANT: Indicates factors concerned with operation, installation, assembly or maintenance which could result in damage to the machine or equipment if ignored. NOTE: Indicates special instructions which are important but are not related to hazards.
!
Hazardous volt­age. Can shock, burn or cause death. Ground
pump before con­necting to power supply.
Follow wiring instructions in this manual when connect-
ing to power lines.
!
performing any work on or near the motor or its connected load.
Do not use to pump flammable or explosive fluids such as gasoline, fuel oil, kerosene, etc. Do not use in flam­mable and/or explosive atmospheres.
Hazardous pressure! Install pressure relief valve in discharge pipe. Release all pressure on system before work­ing on any component.
Wire motor for correct voltage. See “Electrical” section and Motor Data Charts C&D of this manual, and motor nameplate.
Ground motor before connecting to power supply.
Meet United States National Electrical Code and local codes for all wiring.
Do not handle a pump or pump motor with wet hands or when standing on a wet or damp surface or in water.
Always disconnect power source before
1. Make workshop child proof - use padlocks, master switches; remove starter keys.
2. Wear safety glasses when working with pumps.
3. Wear a face shield and proper apparel when pumping hazardous chemicals.
4. Keep work area clean, uncluttered and properly lighted; replace all unused tools and equipment.
5. Provide guarding around moving parts.
6. Keep visitors at a safe distance from the work area.
7. Periodically inspect pump and system components.
8. Protect electrical cord. Replace or repair damaged or worn cords immediately.
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
engine. They are designed to operate at high temperatures.
!
the State of California to cause cancer and birth defects or other reproductive harm.
!
been investigated for use in swimming pool areas. NOTE: Pumps with the “CSA-CUS” mark are tested to UL stan­dard UL778 and certified to CSA standard C22.2 No. 108.
Do not touch an operating motor or
This product contains chemicals known to
Risk of Electric Shock. This pump has not
Pre-Installation
HANDLING
1. Use handle supplied to lift pump.
2. Avoid impact on pump or motor. In particular, avoid impact on discharge end of pump or rear motor access cover.
LOCATION
!
age and/or personal injury might result from an inoperative or leaking pump due to power outages, discharge line block­age, or any other reason, a backup system(s) should be used.
1. Locate pump as close to the fluid source as possible, keep­ing the inlet pipe short as possible.
2. Place unit where the pump and piping are protected from the weather and extremes of heat, humidity and below freezing temperatures.
3. Mount unit in a dry location that is easily accessible for inspection and maintenance. If a dry location is not avail­able, mount it on a foundation well above the wet floor.
4. Allow ample clearance around unit for free air circulation.
SUCTION LIMITATIONS
1. Units are non self-priming.
2. Pressure booster pumps are not recommended for suction lift applications.
PIPING
1. Use galvanized piping, rigid plastic or other suitable pipe that will not collapse under suction or rupture due to pres­sure.
forced industrial type that is rated higher than the shutoff pressure of the system. Ordinary garden hose will collapse and starve the pump of water.
2. The diameter of the inlet and discharge pipe should be no smaller than the corresponding ports of the pump (See Figure 1). Smaller pipe will reduce the capacity of the pump. Increase pipe size on long runs.
3. Avoid air pockets in inlet piping or air will accumulate at high points, making priming difficult.
4. Use pipe compound on all joints and connections. Use Teflon tape or plastic joint stik, on plastic pipe. Draw all pipe up tightly.
IMPORTANT: The entire system must be air and water tight for efficient/proper operation.
4
In any installation where property dam-
If hose is used, make sure it is the rein-
Installation
PUMP INSTALLATION IMPORTANT: Pump is built to handle
clear water only; it is not designed to handle water containing sand, silt or other abrasives.
1.Refer to Figures 6, 7, and 8 for typi­cal installations.
No Sags
Sags Allow Air Pockets
No Air Leaks In Inlet Pipe
If Air Flows Water Won’t
Pipe Joint Compound Will Damage Plastic
IL0419
piping when assembling and when installed. Failure to do so may cause piping to break, pump to fail, motor bearing failures, etc.
Support pump and
2. If the pump is used as part of a per­manent installation, bolt to a rigid foundation.
!
nents that are rated for maximum pres­sure pump can produce when used in boosting system or any other system. Do not exceed the total maximum pressure boost as listed per model in Performance Charts B.
Use only compo-
PRESSURE BOOST SYSTEMS
1. On pressure boost systems, locate the pump so that there will always be a positive supply of water to the pump (See Figures 6, 7 and 8).
2. For service convenience, install a gate valve and union in the inlet and discharge line.
valve or other restricting type of valve that will seriously restrict the pumps discharge capacity.
Do not use a globe
3. Install a check valve as shown in Figure 6. Be sure check valve flow arrows point in the direction of water flow.
4. Whenever dirt, sand or debris is present in the supply water, install a strainer or filter on the inlet side of the pump (See Figure 7).
NOTE: For heavy amounts of sedi­ment, install a trap filter on the inlet side of the pump (See Figure 5). NOTE: Pressure gauges installed before and after the filter will show pressure differential indicating the need for filter replacement or clean­ing.
If Air Pockets Form, Water Won’t Flow
Figure 2 - No Air Pockets in Inlet Pipe
Mount pump in correct position or pump failure will result.
Correct
IL0418
Use Teflon Tape
Figure 3 - Inlet Pipe Must Not Leak
Incorrect
Figure 4A Figure 4B
SAND AND SEDIMENT TRAP FILTER
Standard Pressure Tank - 42 Gallon Or Larger
Outlet
Inlet
Sand Settles To The Bottom
Figure 5
Clean Out
IL0421
IMPORTANT: Clean all filters and strainers on a regular schedule.
IL0420
IL0315
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
5
Installation (Continued)
5. A pressure gauge installed in the
inlet pipe close to the inlet port, (See Figure 6) will show if enough water is being supplied to the pump. See Operation Section - Priming, Pressure Boost Installations.
6. On installations that are using noz­zles for mist spraying, install a filter in the discharge plumbing to prevent the nozzles from becoming plugged. Multiple filters should be plumbed in parallel.
!
relief valve on any installation where pump pressure can exceed the pressure tank’s maximum working pressure or on systems where the discharge line can be shut off or obstructed. Extreme over pressure can result in personal injury or property damage.
waterproof and is not intended to be used in showers, saunas or other potentially wet locations. The motor is designed to be used in a clean dry location with access to an adequate supply of cooling air. Ambient tem­perature around the motor should not exceed 104ºF (40ºC). For outdoor installations, motor must be protected by a cover that does not block airflow to and around the motor. This unit is not weatherproof nor is it able to be submersed in water or any other liq­uid.
To avoid dangerous or fatal elec­trical shock, turn off power to motor before working on electrical connec­tions.
Supply voltage must be within ± 10% of nameplate voltage. Incorrect voltage can cause fire or seriously damage motor and voids warranty. If in doubt, consult a licensed electrician.
Install a pressure
This unit is not
Pump used to boost incoming city pressure (automatic operation).
Street Supply
Check Valve
Gate/Ball Valve (Normally open)
Union
IL0422
Figure 6
Union
Pressure Gauge
Check Valve
Service Tee
Inlet
Outlet
Pressure Switch
Drain
Gate/Ball Valve (Normally open)
To size tank properly - Match drawdown of tank to capacity of pump
Pressure Switch
Main Power Box
Fuse Box or Switch
Union
Pressure Gauge
Pressure Relief Valve
IMPORTANT: A contained air pressure tank and pressure switch is required to keep the pump from rapid cycling and prevent the motor from over heating. Install the tank and switch on the house side of system.
Pump used to boost water pressure in mist spray applications (automatic opera­tion).
Fuse Box or Switch
Pressure Gauge
Thermostat
Gate/Ball Valve
From Water Source
Line Filter Pressure Relief Valve
Solenoid Valve
Gate/Ball Valve (Normally open)
Use wire size specified in wiring Chart F. If possible, connect pump to a separate branch circuit with no other appliances on it. If motor wiring diagram differs from diagram shown below, follow diagram on motor.
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
To Nozzles
Figure 7
To Drain
IL0423
NOTE: Install solenoid valve on discharge side of pump. IMPORTANT: Clean all filters and strainers on a regular schedule.
6
Installation (Continued)
!
Hazardous voltage. Can shock, burn or cause death.
Ground pump before connecting to power supply.
pump impeller is critical on three phase motors. See Motor Rotation under Operation section and Figure 12.
WIRING
1. Install, ground, wire and maintain this pump in accordance with your local electrical code and all other codes and ordinances that apply. Consult your local building inspector for local code information.
2. Ground the pump permanently using a wire of size and type specified by local or United States National Electrical Code. Do not ground to
a gas supply line.
3.Connect ground wire first. Connect
to ground first, then to green ground­ing terminal provided on the motor frame, identified as GRD. Ground con­nection MUST be made to this termi­nal. Do not connect motor to electrical power supply until unit is permanently grounded; otherwise serious or fatal electrical shock hazard may be caused.
4. Connect the other end of the ground wire to a properly grounded service panel or to a control panel ground bar if it is connected to the power supply ground.
IMPORTANT: Check local and/or United States National Electric Codes for proper grounding information.
the power supply conforms to the elec­trical specifications of the motor sup-
plied. See Motor Data Charts.
Ground motor before connecting to electrical power sup­ply.
Failure to ground motor can cause severe or fatal electri­cal shock hazard.
Do not ground to a gas supply line.
Proper rotation of
Make certain that
Pump used to boost incoming pressure from a wall hydrant (manual operation).
Hose Adapter
Wall Hydrant
Pressure Gauge
Pressure Relief Valve
Hose Adapter
High Pressure Reinforced Hose
Service Tee
Inlet
Outlet
IL0424
Spray Nozzle
High Pressure Reinforced Hose
Figure 8
L1
Y E L L O
W
230 Volts
Single Phase
Line
A
B
W
G
H
R
I
A
T
Y
E
R
T
E
A
D
N
IL0180
115 Volts
Single Phase
Line
L1
A
Y
W E L L
O W
G
H
R
I
A
T
Y
E
L2 L2
B
R
T
E
A
D
N
NOTE: Dual voltage motors, change the red and
gray wire to the voltage required.
Figure 9 - Wiring Diagram for Single Phase 1/3 - 2 HP Motors
230 Volts
Single Phase
Line
L1 L2
AB
Y
E
L
L
O W
NOTE: Single voltage (230V) motor, and can not be connected to 115V.
Figure 10 - Wiring Diagram for Single Phase 3 HP Motors
G R A Y
IL0181
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
7
Installation (Continued)
5.Specific Wiring Procedure (Refer to Figures 9, 10, & 11 and Minimum Wire Size Chart).
a. Select the voltage you are to use, either 115V or 230V
single phase, 230V or 460V three phase.
b. The 1/3, 1/2 and 3/4 HP single phase pumps are factory
connected for 115V at the motor. The 1, 1 HP pumps are factory connected for 230V at the motor. Three phase models are factory connected for 230V at the motor.
c. If the motor wiring must be changed to conform to your
specific voltage requirements then the motor, pressure switch or other controls should be rewired to conform to one of the wiring diagrams (either 115V or 230V, single phase; 230V or 460V, three phase). Single phase 3 HP motors are 230V only and cannot be wired for 115V service.
d. The motor wiring diagrams are Figures 9, 10, & 11 and
also are located on the motor label of the pump.
6. Remove the rear access cover of the motor.
7. Make the wiring change and replace the rear access cover.
!
or operating pump. Failure to do so can result in personal injury.
Replace rear access cover before starting
IMPORTANT: Do not use an extension cord or splice wires. Joints should be made in an approved junction box. If the above information or the following wiring diagrams are con­fusing, consult a licensed electrician.
8. All units are not supplied with pressure switches, float devices, on/off switches, or the like (control devices). Controls should be wired in at this time, utilizing whatever instructions come with the controls. All units supplied with cords, will run whenever cord is plugged into power and will turn off whenever cord is disconnected from power.
MOTOR PROTECTION
All single phase motors have built in thermal protection for all voltages. The overload protects the motor against burn­out from overload of low voltage, high voltage and other causes. The device is automatic and resets itself once the temperature has dropped to a safe point. Frequent tripping of the device indicates trouble in the motor or power lines and immediate attention is needed.
!
touch the motor before disconnecting the main electrical supply switch. The thermal device may have opened the electrical circuit.
Never examine, make wiring changes or
Three phase motors do not have a built in thermal protec­tion. It is recommended that a properly sized magnetic or manual starter (both with properly sized heaters) be used with all three phase motors. Install starters following instruc­tions of the starter manufacturer. See Motor Rotation under Operation Section for changing rotation on three phase motors. All motors (single and three phase) should be equipped with a correctly fused disconnect switch to provide protec­tion. Consult local or United States National Electric Codes for proper fuse protection based on motor data chart (See Charts C, D and Wire chart F).
1
/2, 2 and 3
Low Voltage 230V High Voltage 460V
456
7
1
L
1
1 - Tan 4 - Yellow 7 - Purple
2 - Red 5 - Black 8 - Gray
3 - Orange 6 - Blue 9 - White
CONNECTION FOR 3 PHASE, 9 LEADS. IF YOUR 3 PHASE LEADS ARE COLOR CODED, MATCH NUMBER ABOVE TO THE CORRESPONDING COLOR. NOTE: To reverse rotation, interchange any two incoming lines (Power) leads.
Figure 11 - Wiring Diagram for Three Phase Motors
8
2
L
2
9
3
L
3
IL0182
4
7
1
L
1
5
8
2
L
2
6
9
3
L
3
Operation
ing. Do not run dry, or against a closed discharge. Do not pump dirty water or abrasive liquids. To do so will cause pump failure and will void the warranty.
VALVES
The inlet valve should be in the full open position and the discharge valve should be partially open, permitting some back pressure to be exerted against the pump when starting up. Open valve after start up is completed.
PRIMING NOTE: Before starting the pump it is absolutely necessary that both the pump and the inlet pipe be completely filled with water.
PRESSURE BOOST INSTALLATIONS Priming is automatic when pump is connected to a pressure source such as a hydrant or city main (See Figures 6, 7 & 8).
1. Open valves or nozzle on inlet and discharge side of pump.
2. To relieve trapped air, allow water supply to run a mini­mum of 30 seconds before starting the pump.
IMPORTANT: An adequate flow of water going into the pump is required so that the pumps impellers and shaft seal do not run dry and fail.
3. If you installed a pressure gauge at the pump inlet, a read­ing of 2 psi minimum should show whenever the pump is in operation (See Figures 6, 7 & 8).
This reading insures that there is an ample supply of water into the pump inlet housing.
Unit must be full of fluid before operat-
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
8
Operation (Continued)
MOTOR/PUMP ROTATION
1. Single phase models are one (1) rotation only (counter­clockwise when facing the pump end) and cannot be reversed.
2. Proper rotation of pump impeller is critical for three phase pumps. Pump motor should turn counterclockwise (CCW) when facing pump end. Momentarily “bump” (apply power for less than a second) the motor to check for proper rotation. To change rotation on three phase units, interchange any two (2) incoming line (power) leads.
Do not go over recommended maximum operating pressure (see Specifications), while maintaining minimum flow of 1.5 GPM thru the pump. Do not restrict the inlet line to the pump. If driver (electric motor) is overloaded, a valve can be installed in the discharge line to increase the back pressure and reduce driver loading.
START - UP PROCEDURE
Once the preceding instructions have been completed, the pump can be started.
1. During the first few hours of operation, inspect the pump,
piping and any auxiliary equipment used in connection with the unit.
2. Check for leaks, excessive vibration or unusual noises.
IL0539
Figure 12 - Correct Motor/Pump Rotation (all units)
NOTE: See rotation arrow on inlet casting.
Maintenance
Disconnect power supply and depressur­ize system before servicing pump or removing any compo­nent.
ROUTINE
Pump should be checked routinely for proper operation. Replace or clean all filters and line strainers on a regular basis.
DRAINING
This pump cannot be completely drained because of internal design. Most of the liquid can be drained by tilting the dis­charge forward after removing discharge casting; or, the liq­uid can be drained through the inlet port. Store in heated areas.
CLEANING
If used for spraying insecticides, pump should be thoroughly flushed with clean water after using.
LUBRICATION
The motor has prelubricated bearings. No lubrication is required.
SERVICING THREE-PHASE UNITS
Loctite (thread sealer) is used on the threads between the motor shaft and the pump shaft coupling. When reassem-
bling, reapply thread sealer.
PUMP DISASSEMBLY
To disassemble the pump, refer to the exploded parts view, Figures 17 & 18 Tools Required
• Block of wood (2” x 4” x 12”) Piece of 3/4” pipe (12” to 24” long)
• Pipe wrench
• Strap wrench
• 1/4” Dowel rod (about 24” long)
• 9/16” Open end wrench
• 3/8” Open end wrench
1. To stabilize pump during disassembly, place block of wood underneath pump barrel.
2. Thread pipe into pump inlet port. This acts as a handle.
3. Using the pipe wrench, remove the discharge head, turn­ing CCW (counter clockwise).
4. With the strap wrench, loosen the barrel, turning CCW (counter clockwise). DO NOT use pipe wrench on pump barrel.
5. Holding the impeller stack in place, position pump in upright position, standing unit on the motor end cover.
6. Use the 1/4” dowel rod to hold the stages down and in place on the pump shaft. Remove pump barrel.
7. Slide the stages off the pump shaft onto the 1/4” dowel rod. Leave stages on rod and carefully set aside.
NOTE: There may be some small .010” shim washers located next to the pump shaft coupling. Keep these shims for re­assembly.
8. Through the side opening of the mounting frame, hold the motor shaft with 9/16” wrench. Remove the shaft and coupling from the motor using the 3/8” wrench on the hex shaped pump shaft.
NOTE: If the hex shaft comes free, leaving the coupling attached to the motor, use vise grips to free the coupling.
MECHANICAL SEAL REPLACEMENT
1. Follow instructions under “Pump Disassembly”.
2. Remove the mechanical seal assembly. a. The rotary portion of the seal assembly (carbon ring,
Buna-N gasket and spring will slide easily off the end of shaft).
b. Using two (2) screwdrivers, pry the ceramic seal and rub-
ber gasket from the recess of the mounting ring (See Figure 14).
The precision lapped faces of the mechan­ical seal are easily damaged. Handle the replacement seal carefully. Short seal life will result if seal faces (ceramic & carbon) are nicked, scratched or dirty.
3. Clean the seal cavity of the mounting ring and the motor
thoroughly.
4. Wet outer edge of rubber cup on ceramic seat with liquid
soap solution. Use sparingly (one drop only).
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
9
Maintenance (Continued)
NOTE: Liquid soap solution - one drop of liquid soap com-
bined with one teaspoonful of water.
5. With thumb pressure, press ceramic seal half firmly and squarely into seal cavity. Polished face of ceramic seat is up. If seal will not seat correctly, remove, placing seal face up on bench. Reclean cavity. Seal should now seat correctly (See Figure 14).
6. If seal does not seat correctly after recleaning cavity, place a cardboard washer over polished seal face and carefully press into place using a piece of standard clean 3/4” pipe as a press (See Figure 15).
IMPORTANT: Do not scratch seal face.
7. Dispose of cardboard washer and recheck seal face to be sure it is free of dirt, foreign particles, scratches and grease.
8. Inspect shaft to be sure it is free of nicks and scratches.
9. Apply liquid soap solution sparingly (one drop is suffi­cient) to inside diameter of rubber rotating member.
10. Slide rotating seal member (carbon face down toward ceramic face) and spring over the shaft.
IMPORTANT: Do not nick or scratch carbon face of seal when handling.
MOTOR REPLACEMENT
The motor can be replaced with any standard Nema 56J jet pump motor (of proper HP for each pump) by referring to the following instructions.
1. Follow steps as outlined under Rotary Seal Replacement and Pump Disassembly.
2. Remove cap screws that connect the motor to the mounting ring and pull motor away.
3. Replace motor with standard Nema 56J jet pump motor by positioning motor against the mounting frame and assembling with four (4) cap screws.
IMPORTANT: Because damage to the shaft seal can occur in disassembly, a new seal will be necessary.
PUMP REASSEMBLY
Before reassembling the pump, carefully inspect the com­ponent parts of the cartridge (stage) assembly, looking for damage, wear or heat distortion. Pay careful attention to spacing direction of components, and location of shims. Refer to Figure 16 for proper facing and parts arrangement. If damage to Stage components is evident, a complete car­tridge assembly or individual stage assemblies are available for replacement (See Replacement Parts List).
1. Reassembly should follow the reverse order of the disas-
sembly procedure with special care given to replacement of the rotary seal.
2. Check top and bottom of o-rings for damage. It is recom-
mended that new o-rings be used.
3. Do not use pipe compound of Teflon tape on barrel
threads. The o-rings will prevent pump from leaking.
4. After pump is reassembled, tighten the discharge head to
a torque of 45-50 ft/lbs. If torque wrench is not available, tighten firmly but avoid distortion or damage to plastic internal parts.
5. After reassembly, apply power momentarily to unit (15 to
30 seconds). The pump and motor should rotate freely or with a light rubbing.
Figure 13 - Remove Mechanical Seal Figure 14 - Press In Seal
3/4” Pipe Press Carefully
Cardboard Washer Protects Seal Face
Seal Cavity
IL0554
Figure 15 - If Necessary, Press With Cardboard And Pipe
Seal
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
10
Troubleshooting Chart
Symptom Possible Cause(s) Corrective Action
Pump won’t start or run at full speed
Pump oper­ates, but delivers little or no water
1. Blown fuse or open circuit breaker 1. Replace fuse or close circuit breaker. See wire size chart for proper break/fuse size
2. Power supply in OFF position 2. Turn power on
3. Incorrect voltage at motor (check volt-
age with motor running)
4. Loose, broken or incorrect wiring 4. Rewire any incorrect circuits. Tighten connections, replace
5. Defective motor 5. Replace motor
6. Pump hydraulic components clogged/
worn/damaged
1. Manual or solenoid valves plumbed
into system restricting flow
2. In-line filter restricting flow 2. Check all in-line filters to be sure they are not plugged or
3. Low line voltage 3. See low line voltage corrective action (above)
3. Low voltage
a. Voltage must be within ± 10% of motor rated voltage.
Check incoming voltage. Contact power company
b. Make certain that voltage of motor matches voltage of
power supply. See motor name plate and motor wiring diagrams
c. Check wire size from main switch to pump. See wire
size chart for correct wire size
defective wires
6. Replace worn parts or entire pump. Clean parts if required
1. a Check all valves on pump inlet and discharge sides of system to be sure they are opened properly to allow flow to and from the pump
b. Bleed trapped air in pump which keeps water from
reaching the pump. (Normally due to closed valve in discharge plumbing)
restricted
4. Inadequate water supply to booster pump
5. Undersized piping 5. Replace undersized piping
6. Leak on inlet side of system 6. Make sure connections are tight. Repair leaks as necessary
7. Inadequate, defective or plugged foot valve and/or strainer
8. Worn or defective pump parts or pump.
9. Suction lift too great 9. Pump should be operated under
10. Pump not primed 10. Prime pump - Make certain inlet pipe is drawn up tight and
11. Incorrect rotation, motor running backwards
Excessive noise while pump in
Pump leaks 1. Worn mechanical seal (leaks at shaft) 1. Replace shaft (rotary) seal
1. Pump not secured to firm foundation 1. Secure properly
2. Piping not supported 2. Make necessary adjustments
3. Restricted inlet line 3. Clean or correct
4. Cavitation (noise like marbles in pump) 4. a. Reduce speed on direct drive
5. Worn motor bearings 5. Replace bearings or motor
2. Worn o-ring seals 2. Replace o-ring seals, located inside both ends of the stainless
4. Check pressure on inlet side of booster to be sure positive pressure is maintained to the booster pump
7. Clean, repair or replace as needed
8. Replace worn parts or entire plugged impeller Clean parts if
flooded suction only
pump and pipe are full of water
11. Reverse motor rotation can occur on three phase units. To correct, interchange any two incoming power leads.
b. Increase inlet pipe size
c. Too viscous (material being pumped too thick
steel shell
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
11
Booster Pump Parts Drawing
1A 1
10A
10
ITEM NO. DESCRIPTION
1 Motor
1A †Governor
1B †Switch Motor
2 Seal, Rotary 3 Barrel 4 Discharge Head
4A Discharge Bearing
5 O-ring (2)
6A Plate, Diffuser
6B Impeller 6C Diffuser
6D Diffuser Bearing
6E Shim as Required
7 Shaft and Coupling Assembly 8 Mounting Ring 9 Hex Head Bolts (4)
10 †MotorAccess Cover
10A †Screws, Access Cover (2)
*See note below parts included in cartridge assembly.
†ODP Motor Only
1B
9
2
5
7
6A
6E
6D
8
6A
5
4A
4
6B
6C
3
IL0593
Internal Parts Detail
IL0308
Figure 16 - Cartridge Assembly Includes Discharge Bearing, Shaft & Coupling Assembly, Diffuser Plate, Impellers, Diffuser Bearings, Diffusers and O-rings
NOTE: Illustration shows only two stages. Pump has multiple stages. Individual parts are not available separately.
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
12
PRESSURE BOOSTER PUMP REPAIR PARTS
(For Pricing Refer To Repair Parts Price List)
Replacement Motors
9
10
IL0565
FORM NO. FW0045
SUPERSEDES 0206
PAGE 4-7A REPAIR PARTS
0907
ITEM REPLACEMENT MOTORS QTY CAST IRON
ODP NEMA J 1/3 HP ODP NEMA J 1/2 HP 96J105 96J105 96S105 96J305 96J305 96S305 ODP NEMA J 3/4 HP 96J107 96J107 96S107 96J307 96J307 96S307
9
ODP NEMA J 1 HP 96J110 96J110 96S110 96J310 96J310 96S310 ODP NEMA J 1-1/2 HP 96J115 96J115 96S115 96J315 96J315 96S315 ODP NEMA J 2 HP 96J120 96J120 96S120 96J320 96J320 96S320 ODP NEMA J 3 HP 96J630 96J630 96S630 96J330 96J330 96S330
10 Motor Cover w/Screws 1 136132R 136132R 136132R 136132R 136132R 136132R
* Screws, Motor Cover 2 136133 136133 136133 136133 136133 136133
ODP NEMA J 1/3 HP ODP NEMA J 1/2 HP 96J005 96J005 96S005 96J305 96J305 96S305 ODP NEMA J 3/4 HP 96J007 96J007 96S007 96J307 96J307 96S307
9
ODP NEMA J 1 HP 96J010 96J010 96S010 96J310 96J310 96S310 ODP NEMA J 1-1/2 HP 96J015 96J015 96S015 96J315 96J315 96S315 ODP NEMA J 2 HP 96J820 96J820 96S820 96J320 96J320 96S320
10 Motor Cover w/Screws 1 136132R 136132R 136132R 136132R 136132R 136132R
* Screws, Motor Cover 2 136133 136133 136133 136133 136133 136133
TEFC NEMA J 1/2 HP TEFC NEMA J 3/4 HP 021008 021008 021012 021012 TEFC NEMA J 1 HP 021009 021009 020688 020688
9
TEFC NEMA J 1-1/2 HP 020692 020692 020647 020647 TEFC NEMA J 2 HP 020693 020693 020689 020689 TEFC NEMA J 3 HP 021010 021010 020690 020690
* Not Shown
1
1
1
96J103 96J103 96S103
96J003 96J003 96S003
POWDER
COATED
SINGLE PHASE 60 HZ THREE PHASE 60 HZ
SINGLE PHASE 50 HZ THREE PHASE 60/50 HZ
SINGLE PHASE 60/50 HZ THREE PHASE 60/50 HZ
020691 020691 021011 021011
STAINLESS
STEEL
CAST IRON
POWDER
COATED
STAINLESS
STEEL
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
13
FORM NO. FW0046 0907 SUPERSEDES 0206 PAGE 4-8A REPAIR PARTS
PRESSURE BOOSTER PUMP REPAIR PARTS
(For Pricing Refer To Repair Parts Price List)
10
8
9
3
6
7
1
4
2
IL0565
ITEM DESCRIPTION QTY CAST IRON
5 - 7 - 10 - 19 GPM,
60 HZ & 50 HZ
27 - 35 GPM,
60 HZ & 50 HZ
55 - 85 GPM,
60 HZ & 50 HZ
ALL SERIES
60 HZ & 50 HZ
(†) Buna N - Carbon/Silicon Carbide (‡) Viton - Carbon/Silicon Carbide () Buna N () Viton (*) Not Shown (8) 132079 Handle available as an option
MATERIAL
ITEM DESCRIPTION MATERIAL PART NUMBER
5 Cartridge Assembly ‡
6 Shaft & Coupling Assembly
7 Barrel/Shell CI, PC & SS 135162 132003 138448 132003 134997 135815
MATERIAL
ITEM DESCRIPTION MATERIAL PART NUMBER
5 Cartridge Assembly ‡
60 HZ MODELS
6 Shaft & Coupling Assembly
7 Barrel/Shell CI, PC & SS 137223 135628 136630 136627 136633
MATERIAL CAST IRON CI PB5504XX PB5506XX PB8504XX PB8505XX
ITEM DESCRIPTION MATERIAL PART NUMBER
5 Cartridge Assembly ‡ CI 022293 022294 022295 022296 6 Shaft & Coupling Assembly CI 022289 022287 022288 022287 7 Barrel/Shell CI, PC & SS 022291 022292 138151 022290
MATERIAL
ITEM DESCRIPTION MATERIAL PART NUMBER
5 Cartridge Assembly ‡
6 Shaft & Coupling Assembly
7 Barrel CI, PC & SS 135162 138151 138151 135098 020279 135912
MATERIAL
50 HZ MODELS
ITEM DESCRIPTION MATERIAL PART NUMBER
5 Cartridge Assembly ‡
6 Shaft & Coupling Assembly
7 Barrel CI, PC & SS 020094 138947 136633 021016 139436
(‡) Cartridge assembly includes: impellers, diffusers and shaft & coupling assembly. Components not available individually. Sold as assembly only.
1 Discharge Head 3/4” NPT 1 132000 136905 136640 2 Mounting Ring 3/4” NPT 1 132002 136904 136639
1 Discharge Head 1” NPT 1 136635 137796 139166 2 Mounting Ring 1” NPT 1 136634 137794 139100
1 Discharge Head 2” NPT 1 021585 - ­2 Mounting Ring 2” NPT 1 021584 - -
3 Seal, Rotary w/Spring 1 131100 † 131100 † 136682 ‡
O-Ring 2 131925 131925 136607
4
* Hex Head Cap Screws 3/8” x 3/4” 4 121106 121106 121106
CAST IRON CI PB0508AXXX PB0512AXXX PB0516AXXX PB0712AXXX PB1014AXXX PB1016AXXX POWDER COATED PC PB0508CXXX PB0512CXXX PB0516CXXX PB0712AXXX PB1014CXXX PB1016CXXX STAINLESS STEEL SS PB0508SXXX PB0512SXXX PB0516SXXX PB0712SXXX PB1014SXXX PB1016SXXX
CI & PC 135163 132939 138447 134097 134998 135814
SS 136683 138450 136684 136685 136686
CI & PC 135161 133336 138446 133336 134996 135813
SS 138938 136636 138449 136636 136637 136638
CAST IRON CI PB1914AXXX PB2711AXXX PB2714AXXX PB3506AXXX PB3508AXXX POWDER COATED PC PB1914CXXX PB2711CXXX PB2714CXXX PB3506CXXX PB3508CXXX STAINLESS STEEL SS PB1914SXXX PB2711SXXX PB2714SXXX PB3506SXXX PB3508SXXX
CI & PC 137222 135627 136629 136626 136632 SS 139162 139163 138946 139164 139165 CI & PC 137221 136624 136628 136625 136631 SS 139159 139157 137535 139156 139158
CAST IRON CI PB0508XXXX PB0514XXXX PB0714XXXX PB1020XXXX PB1022XXXX PB1023XXXX
POWDER COATED PC PB0508ZXXX PB0514ZXXX PB0714ZXXX PB1020ZXXX PB1022ZXXX PB1023ZXXX
STAINLESS STEEL SS PB0508YXXX PB0514YXXX PB0714YXXX PB1020YXXX PB1022YXXX PB1023YXXX
CI & PC 135163 138150 021032 135907 135911 SS 138682 021033 138683 020280 138684 CI & PC 135161 138149 138149 135906 020278 135910 SS 138938 138444 138444 138154 020278 137103
CAST IRON CI PB1920XXXX PB2717XXXX PB3508XXXX PB3514XXXXT
POWDER COATED PC PB1920ZXXX PB2717ZXXX PB3508ZXXX PB3514ZXXXT PB1922ZXXX
STAINLESS STEEL SS PB1920YXXX PB2717YXXX PB3508YXXX PB3514YXXXT
CI & PC 020982 020980 136632 021017 139435 SS 020095 138949 139165 021026 * CI & PC 020971 020916 136631 021015 139434 SS 020093 138948 139158 021020 021425
4
POWDER
COATED
STAINLESS
STEEL
See
replacement
motors.
ITEMS 9 & 10
FLINT & WALLING, INC. • 95 North Oak St. • Kendallville, IN 46755 • www.flintandwalling.com
14
Loading...