Hoshizaki WF27A01, SR36A15M, WR27AD2, UR27ALP, WR27A User Manual

...
Page 1
Service Manual
Steelheart Series Refrigerated Kitchen Equipment
Models Undercounter Worktop Prep Table
hoshizakiamerica.com
Number: 73217 Issued: 11-2-2018
Page 2
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No service should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
Page 3
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this booklet carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this booklet for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 4
I. Construction and Refrigeration Circuit Diagram ................................................................. 8
A. Construction .................................................................................................................. 8
B. Refrigeration Circuit Diagram ........................................................................................ 9
II. Sequence of Operation and Service Diagnosis ............................................................... 10
A. Sequence of Operation Flow Chart ............................................................................. 10
1. Undercounter and Work Top: Refrigerator .............................................................. 10
2. Prep Table: Refrigerator ..........................................................................................11
3. Undercounter and Work Top: Freezer .................................................................... 12
B. Service Diagnosis ....................................................................................................... 13
C. Control Module Check ................................................................................................. 18
D. Diagnostic Table .......................................................................................................... 20
III. Controls and Adjustments ............................................................................................... 23
A. Temperature Settings .................................................................................................. 23
B. Defrost ......................................................................................................................... 23
C. Safety Devices ............................................................................................................ 25
D. Perimeter and Mullion Heaters .................................................................................... 25
IV. Refrigeration Circuit and Component Service Information.............................................. 26
A. Refrigeration Circuit Service Information .................................................................... 28
B. Component Service Information .................................................................................. 31
V. Preparing the Appliance for Periods of Non-Use ............................................................. 32
VI. Disposal .......................................................................................................................... 33
VII. Technical Information ..................................................................................................... 34
A. Electrical and Refrigerant Data ................................................................................... 34
B. Wiring Diagrams .......................................................................................................... 35
1. Undercounter and Worktop: Refrigerator ................................................................ 35
2. Prep Table .............................................................................................................. 36
3. Undercounter and Work Top: Freezer .................................................................... 37
3
Page 4

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
DANGER
WARNING
NOTICE
IMPORTANT
Indicates a hazardous situation that, if not avoided, will result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
Indicates a situation that, if not avoided, could result in damage to the appliance or property.
Indicates important information about the use and care of the appliance.
DANGER
Risk of Fire or Explosion
Flammable Refrigerant Used
• Follow handling instructions carefully in compliance with U.S. government regulations.
• Do not use mechanical devices to defrost.
• Do not puncture refrigerant tubing. Risk of re or explosion due to puncture of refrigerant tubing; follow handling instructions carefully.
• Component parts shall be replaced with like components.
• Servicing shall be done by factory authorized service personnel to minimize the risk of possible ignition due to incorrect parts or improper service.
• Consult instruction manual/ service manual before attempting to install or service this product. All safety precautions must be followed.
• Dispose of properly in accordance with federal or local regulations.
• Do not place any potential ignition sources in or near the appliance.
Risque De Feu Ou D'Explosion
Le Frigorigène Est Inammable
• Suivre attentivement les instructions de manipulation conformément à la réglementation gouvernementale.
• Ne pas utiliser d'appareils mécaniques pour dégivrer le réfrigérateur.
• Ne pas perforer la tubulure contenant le frigorigène. Risque de feu ou d'explosion si la tubulure contenant le frigorigène est perforée; suivre les instructions de manutention avec soin.
• Les pièces des composants doivent être remplacées par des pièces et accessoires équivalents.
• L’entretien doit être effectué par le personnel de service autorisé par le fabricant an de minimiser les risques d’inammation attribuables à l’installation d’une pièce inadéquate ou à la mauvaise exécution du service.
• Consulter le manuel du propriétaire/ guide de réparation avant de tenter une réparation. Toutes les mesures de sécurité doivent être respectées.
• Éliminer conformément aux règlements fédéraux ou locaux.
• Ne placez aucune source d’inammation potentielle dans ou près de l’appareil.
4
Page 5
WARNING
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service the appliance.
• Wear appropriate personal protective equipment (PPE) when servicing the appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• Appliance is heavy. Use care when lifting or positioning. Work in pairs when needed to prevent injury or damage. Do not lift using the top section or the doors/drawers.
• To reduce the risk of electric shock, do not touch the plug with damp hands.
• Unplug the appliance before servicing.
• The appliance requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE APPLIANCE MUST BE GROUNDED. The appliance is equipped
with a NEMA5-15 three-prong grounding plug shock hazards. It must be plugged into a properly grounded, independent 3-prong wall outlet. If the outlet is a 2-prong outlet, it is your personal responsibility to have a qualied electrician replace it with a properly grounded, independent 3-prong wall outlet. Do not remove the ground prong from the power cord and do not use an adapter plug. Failure to follow these instructions may result in death, electric shock, or re.
• Do not use an extension cord.
• Do not use an appliance with a damaged power cord. The power cord should not be altered, jerked, bundled, weighed down, pinched, or tangled. Such actions could result in electric shock or re. To unplug the appliance, be sure to pull the plug, not the cord, and do not jerk the cord.
• The GREEN ground wire in the factory­installed power cord is connected to the appliance. If it becomes necessary to remove or replace the power cord, be sure to connect the power cord's ground wire.
• Do not splash, pour, or spray water directly onto or into the appliance. This might cause short circuit, electric shock, corrosion, or failure.
• Do not make any alterations to the appliance. Alterations could result in electric shock, injury, re, or damage to the appliance.
• The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
to reduce the risk of potential
5
Page 6
WARNING, continued
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or doors/drawers or allow children or animals to do so. Do not climb into the appliance or allow children or animals to do so. Death or serious injury could occur or the appliance could be damaged.
• Be careful not to pinch ngers when opening and closing the doors/drawers or rail cover (prep table models) or when handling food pans. Be careful when opening and closing the doors/drawers or rail cover when children are in the area.
• Open and close the doors/drawers and rail cover (prep table models) with care. Opening the doors/drawers or rail cover too quickly or forcefully may cause injury or damage to the appliance or surrounding equipment.
• Do not use combustible spray or place volatile or ammable substances in or near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the equipment.
• Do not block air inlets or outlets, otherwise cooling performance may be reduced.
• Do not tightly pack the cabinet. Allow some space between items to ensure good air ow. Also allow space between items and interior surfaces.
• Do not put warm or hot foods in the cabinet. Let them cool rst, or they will raise the cabinet temperature and could deteriorate other foods in the cabinet or overload the appliance.
• Food storage and handling must comply with applicable codes and regulations.
• All foods should be wrapped in plastic lm or stored in sealed containers. Otherwise foods may dry up, pass their smells onto other foods, cause frost to develop, result in poor appliance performance, or increase the likelihood of cross-contamination. Certain dressings and food ingredients, if not stored in sealed containers, may accelerate corrosion of the evaporator, resulting in failure.
• Do not store items near air outlets. Otherwise, items may freeze up and crack or break causing a risk of injury or contamination of other food.
• Do not throw anything onto the shelves or load any single shelf with more than 120lb. (54.5 kg) of product. They might fall off and cause injury.
• Do not load any single drawer with more than 75 lb. (34 kg) of product. Depending on the weight of product in the drawers, secure the unit as necessary to prevent it from overturning. Do not open more than one drawer at a time.
• The appliance is designed only for temporary storage of food. Employ sanitary methods. Use for any other purposes (for example, storage of chemicals or medical supplies such as vaccine and serum) could cause deterioration of stored items.
6
Page 7
WARNING, continued
Additional Warnings for Prep Table Models
• The entire rail must always be covered by rail dividers and pans (1/6 size, up to 6"(15cm)deep). Otherwise, the appliance will not cool properly.
• Use only 1/6 size pans up to 6"(15cm) deep. Do not use damaged pans.
• Ingredients must be pre-chilled to 37°F (3°C) or less before placing in rail.
• Keep the rail cover closed when not actively preparing food.
NOTICE
• Protect the oor when moving the appliance to prevent damage to the oor.
• Keep ventilation openings, in the appliance enclosure or in the built-in structure, clear of obstruction. Do not place anything on top of the appliance in an undercounter installation. There must be at least 1.5" (4 cm) overhead clearance for proper ventilation. The factory-installed rear bumpers must be in place to ensure proper rear clearance. Blockage of airow could negatively affect performance and damage the appliance.
• The rail is for keeping ingredients cool while preparing food. If not actively preparing food for a long period such as overnight, seal pans with plastic wrap in addition to closing the rail cover. Depending on conditions, the cabinet temperature setting may need to be adjusted to prevent items from freezing. Alternatively, seal ingredients and store them in a refrigerator or freezer.
• Do not allow the appliance to bear any outside weight.
• To prevent deformation or cracks, do not spray insecticide onto the plastic parts or let them come into contact with oil.
• To avoid damage to the gasket, use only the door/drawer handle when opening and closing.
• To avoid damage to the top seal, do not lift the appliance by the top panel or remove the top panel.
Additional Notice for Prep Table Models
• Do not place anything on top of the rail hood or rail cover and do not lift the appliance by the rail hood or rail cover. The rail hood and rail cover are not designed to bear any outside weight.
7
Page 8

I. Construction and Refrigeration Circuit Diagram

A. Construction

1. Undercounter, Worktop, Prep Table Common Parts
• Evaporator
• Evaporator Fan
• Evaporator Fan Shroud Nameplate
Thermometer
Door
Rear Panel
Control Module Cover
Cabinet Temperature Control Dial
Model Shown: UF60A
Control Module
Compressor
Door Gasket
Condenser
Condenser Fan Motor
Model Shown: UF60A
8
Page 9

B. Refrigeration Circuit Diagram

Condenser
High-Pressure Switch
Capillary Tube
Condenser Fan
Evaporator Fans (1, 2, or 3 depending on model)
Drier
Compressor
Evaporator
Cabinet Thermostat Bulb
Prep Table and Freezer Models: Defrost Heater, Defrost Safety Thermostat, and Defrost Thermistor
9
Page 10

II. Sequence of Operation and Service Diagnosis

The steps in the sequence are as outlined below. See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Approximate Default Temperature
Control Setting
Undercounter Worktop
Between 4 and 5 Refrigerator: 34°F (1°C)
Freezer: -5°F (-21°C)
Prep Table Between 4 and 5 34°F (1°C)

A. Sequence of Operation Flow Chart

1. Undercounter and Work Top: Refrigerator

Refrigerator Sequence Flow Chart
1. Startup/Cool Down
CTh above setpoint
CTh in control
Power on Red LED On (5 sec. Delay)
*
2-min. Comp on timer starts
Green LED Flashes If Red LED ashes, check CTh
Comp energized ConFM energized EvapFM energized
2. Cool Down Achieved
CTh cools to setpoint
*
2-min. Comp off timer starts
Green LED Flashes If Red LED ashes, check CTh
Comp de-energized ConFM de-energized EvapFM de-energized
Off cycle defrost between run cycles
CTh above
setpoint
Legend: Comp-compressor ConFM-condenser fan motor CTh-cabinet thermistor EvapFM-evaporator fan motor
Note: Delays
*
a) 2-min. minimum Comp on timer starts when Comp energizes. b) 2-min. minimum Comp off timer starts when Comp de-energizes.
10
Page 11

2. Prep Table: Refrigerator

5. Defrost Termination
Defrost Termination:
46°F (7.7°C) achieved or
45 min. backup defrost
timer terminated.
Evap. temp. below
50°F (10°C)
4. Defrost
6-hr. DT terminates
Defrost:
Time/Temp achieved.
DTh in control
setpoint CTh above
Defrost
Evap. Temp.
Terminated
reaches 46°F (7.7°C)
DH de-energized
*
6-hr DT starts
After DOT Delay:
Comp energized
ConFM energized
After FDD
*
EvapFM energized
*
*
6-hr. DT terminates
5-min. min. DT starts
45-min. max. DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
*
2-min. Comp off
3. Cool Down Achieved
CTh cools to setpoint
timer starts
EvapFM energized
Comp de-energized
CTh in control
ConFM de-energized
Prep Table Top Sequence Flow Chart
*
*
2-min. Comp on
2. Cool Down
1. Startup
CTh above setpoint
Red LED Off
Green LED Flashes
timer starts
If Red LED Flashes,
check CTh or DTh
Comp energized
EvapFM energized
ConFM energized
EvapFM energized
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 45-min. maximum defrost time.
e) DOT (drip off time) 1-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 30-sec. EvapFM delay timer terminates or DTh reaches 40°F (4.4°C).
Note: Delays
g) If evaporator temperature raises above 50°F (10°C) during the cooling cycle, 6-hr. DT resets.
Power on
Red LED On
(5 sec. Delay)
11
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DT-defrost timer
DTh-defrost thermistor
EvapFM-evaporator fan motor
Page 12

3. Undercounter and Work Top: Freezer

Defrost
5. Defrost Termination
Defrost Termination:
50°F (°10C) achieved or
1 hr. backup defrost timer
terminated.
DH de-energized
DTh in control
Terminated
8-hr. DT starts
*
After DOT Delay:
Comp energized
ConFM energized
MH energized
PH energized
*
After FDD
EvapFM energized
Defrost Initiation:
3. Defrost
Time/Temp achieved.
CTh warms
above
setpoint
8-hr. DT terminates
Evap. temp. below 41°F (5°C)
8-hr. DT terminates
Evap. temp. below 41°F (5°C)
5-min. min. DT starts
60-min. max. DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
PH de-energized
MH de-energized
Freezer Sequence Flow Chart
2. Cool Down Achieved
Achieved
2-min. Comp off
timer starts
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
Setpoint
*
CTh in control
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 1-hr. maximum defrost time.
e) DOT (drip off time) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 7-min. EvapFM delay timer terminates or DTh reaches 25°F (-4°C).
1. Startup/Cool Down
Red LED off
Green LED Flashes
If Red LED ashes,
check CTh or DTh
6-hr. or 8-hr. DT starts
2-min. Comp on
timer starts
Note: Delays
Comp energized
Power on
Red LED On
(5 sec. Delay)
ConFM energized
EvapFM energized
MH energized
PH energized
12
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DT-defrost timer
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
Page 13

B. Service Diagnosis

DANGER
Risk of Fire or Explosion
Flammable Refrigerant Used
• Follow handling instructions carefully in compliance with U.S. government regulations.
• Do not use mechanical devices to defrost.
• Do not puncture refrigerant tubing. Risk of re or explosion due to puncture of refrigerant tubing; follow handling instructions carefully.
• Component parts shall be replaced with like components.
• Servicing shall be done by factory authorized service personnel to minimize the risk of possible ignition due to incorrect parts or improper service.
• Consult instruction manual/service manual before attempting to install or service this product. All safety precautions must be followed.
• Dispose of properly in accordance with federal or local regulations.
• Do not place any potential ignition sources in or near the appliance.
Risque De Feu Ou D'Explosion
Le Frigorigène Est Inammable
• Suivre attentivement les instructions de manipulation conformément à la réglementation gouvernementale.
• Ne pas utiliser d'appareils mécaniques pour dégivrer le réfrigérateur.
• Ne pas perforer la tubulure contenant le frigorigène. Risque de feu ou d'explosion si la tubulure contenant le frigorigène est perforée; suivre les instructions de manutention avec soin.
• Les pièces des composants doivent être remplacées par des pièces et accessoires équivalents.
• L’entretien doit être effectué par le personnel de service autorisé par le fabricant an de minimiser les risques d’inammation attribuables à l’installation d’une pièce inadéquate ou à la mauvaise exécution du service.
• Consulter le manuel du propriétaire/ guide de réparation avant de tenter une réparation. Toutes les mesures de sécurité doivent être respectées.
• Éliminer conformément aux règlements fédéraux ou locaux.
• Ne placez aucune source d’inammation potentielle dans ou près de l’appareil.
WARNING
• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Wear appropriate personal protective equipment (PPE) when servicing the appliance.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Appliance is heavy. Use care when lifting or positioning. Work in pairs when needed to prevent injury or damage.
• Make sure all food zones are clean after the appliance is serviced.
13
Page 14
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation and proper voltage per nameplate.
See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Control Setting
Undercounter Worktop
Prep Table Between 4 and 5 34°F (1°C)
Between 4 and 5 Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation and proper voltage per nameplate. Conrm that the appliance location meets factory requirements:
• This appliance is not intended for outdoor use. Normal operating ambient
temperature should be within 45°F to 86°F (7°C to 30°C).
• The appliance should not be located next to ovens, grills, or other high heat
producing equipment. Check CM using the steps in "II.C. Control Module Check."
Note: • When checking voltage (115VAC), always choose a neutral white (W) wire to
establish a good neutral connection.
• CM has high and low voltage protection. If off on either protection, no LED is
visible and all components are off. High Voltage: 135VAC Low Voltage: 90VAC
• Solid red LED for 5 sec. at startup.
• Flashing green LED: Normal operation.
• Flashing red LED: check cabinet thermistor and defrost thermistor (if applicable).
• CM has a 2 min. minimum on time and 2 min. minimum off time for Comp.
1) Unplug the appliance from the electrical outlet.
2) Remove the rear panel.
3) Plug the appliance back into the electrical outlet. If appliance was in defrost when power supply was disconnected, defrost is terminated and normal cooling cycle begins when power supply is reconnected.
4) Startup/Cool Down–There is a slight delay (solid red LED for 5 sec., then ashing green LED). Temperature above setpoint at CTh and if applicable, conrm appliance is not in a defrost cycle (PT and Freezers). Comp, CondFM, and EvapFM energize. 2-min. Comp on timer starts. Freezers: PH, and MH energize.
a) CTh Diagnosis: If CTh fails, a red LED ashes along with the green LED on the CM.
Conrm CTh is properly connected to CM. Check Ohm reading of CTh. Replace as needed.
b) TD Diagnosis: Conrm TD is set between 4 and 5. Check Ohm reading of TD.
Replace as needed.
14
Page 15
c) CM Diagnosis: Conrm green LED is ashing. If not, check for 115VAC between
CM 2 (L) black (BK) wire and CM 3 (N) neutral white (W) wire. If 115VAC is not present, check power cord connections and breaker/fuse. Conrm wiring connections are secure for both CM 2 (L) black (BK) (power supply) and CM 3 (N) white (W) (neutral). If 115VAC is present and green LED is not ashing, replace CM.
d) Comp/CondFM Diagnosis: Check that Comp and ConFM energize. If not, conrm
that the temperature is above setpoint. Next, check for 115VAC at CM 1 (C) brown(BR) wire to neutral white (W) wire. If 115VAC is not present, replace CM. If 115VAC is present, check HPS continuity (if applicable). See "f) HPS Activation" below. Comp: If 115VAC is present, check Comp external overload, start cap, start relay, and Comp motor windings. Replace as needed. CondFM: If 115VAC is present, check fan blade for binding, then check ConFM motor windings.
e) EvapFM Diagnosis: Check that EvapFM(s) energize. If not, check for 115VAC at
CM 5 (F) dark blue (DBU) wire to neutral white (W) wire. If 115VAC is not present, replace CM. If 115VAC is present, check fan blades for binding, then check EvapFM motor windings.
f) HPS Activation: Check continuity of HPS. If open, allow time for system pressure
to equalize and HPS to reset. If HPS does not reset, replace HPS and diagnose reason for HPS activation. Conrm ConFM is energized and fan blade turns freely. Check that the condenser coil is not clogged or restricted. Check that there are no restrictions in the refrigeration circuit (drier).
g) PH and MH Diagnosis (Freezer only): PH and MH follow Comp operation. When
Comp is energized, PH and MH are energized. If 115VAC is present, check amp draw of PH and MH. If an amp reading is not present, check the continuity of PH and MH. If defective, replace PH or MH.
If Comp, ConFM, and EvapFM are energized and the cabinet does not cool down,
check for a restriction in the refrigeration circuit, low refrigerant charge, or inefficient Comp.
5) Cool Down Achieved–Temperature cools to setpoint. Comp and ConFM de-energize. UC/WT Refrigerators and Freezers: EvapFM de-energizes. Prep Table: EvapFM continues. Diagnosis: If temperature setpoint achieved and Comp, ConFM, and EvapFM(except PT models) does not de-energize, check CTh and TD continuity. If CTh or TD is defective, replace. If CTh and TD are good and either the Comp, ConFM, and/or EvapFM (except PT models) continue, or if EvapFM on PT models de-energizes, replace CM.
15
Page 16
6) Defrost–Manually initiated defrost, off cycle defrost, and time-initiated temperature-terminated heated defrost.
1a) Manually-Initiated (All): Turn the TD all the way to the right. Wait 1 to 3 sec. then
back to original setting. Defrost initiated. If defrost does not initiate, wait 1 to 2 min. and repeat process.
1b) Off Cycle-Initiated (UC/WT Refrigerators): Off cycle between cooling cycles.
CTh cools below TD setting. TD setting satised. Comp, CondFM, and EvapFM de-energize.
1c) Temp/Time-Initiated (Heated) (Prep Table and All Freezers): 6-hr. Prep Table or
8-hr. Freezer DT terminates.
(1) Prep Tables: Comp and ConFM de-energizes, EvapFM continues. DH energizes.
5-min. minimum DT starts and 45-min. maximum DT starts.
(2) Freezers: Comp, ConFM, PH, MH, and EvapFM de-energize. DH energizes.
5-min. minimum DT starts and 1-hr maximum DT starts.
Note: When DTh is above 50°F (10°C) on Prep Tables or above 41°F (5°C) on
Freezers, defrost will not initiate and Prep Table 6-hr. DT and Freezer 8-hr. DT resets and starts once DTh temperature cools below 50°F (10°C)on Prep Tables or cools below 41°F (5°C) on Freezers.
2a) Manually-Terminated: Turn the TD all the way to the right. Wait 1 to 3 sec. then
back to original setting. Defrost terminated. If DH continues or Comp does not energize, make several more attempts of manual termination.
2b) Off Cycle-Terminated: CTh warms above TD setting. Comp, CondFM, EvapFM
energize.
2c) Temperature or Time-Terminated: DTh achieves termination temperature or
backup DT terminates.
(1) Prep Tables: 46
°F (7.7°C) achieved or 45-min. backup DT terminates. DH
de-energizes. IfCTh calling for cooling, 1-min. Comp delay timer starts (drip time) and 90-sec. EvapFM delay timer starts. 1-min. Comp delay timer terminates. Comp and ConFM energize. 30 sec. later, 90-sec. EvapFM delay timer terminates and EvapFM energizes. Note: If DTh achieves 40°F before 90-sec. EvapFM delay timer terminates, 90-sec. EvapFM delay timer terminates and EvapFM energizes.
(2) Freezers: 50°F (10°C) achieved or 1-hr. DT terminates. DH de-energizes. If CTh
calling for cooling, 3-min. Comp delay timer starts (drip time) and 7-min. EvapFM delay timer starts. 3-min. Comp delay timer terminates. Comp and ConFM energize. 4min. later, 7-min. EvapFM delay timer terminates and EvapFM energizes. Note: If DTh achieves 25°F before 7-min. EvapFM delay timer terminates, 7-min. EvapFM delay timer terminates and EvapFM energizes.
16
Page 17
Defrost Diagnosis:
1) Manual-Initiation: TD rotated to max. position and back. Prep Table 6-hr. DT or Freezer 8-hr. DT terminates. After rotating TD several times and defrost still not activated, wait 1 to 2 min. and repeat process. Replace TD as needed.
(2) CM Diagnosis: Conrm DH energizes (if applicable) and Comp, ConFM, and
EvapFM (if applicable) de-energize. If not, replace CM.
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize. If not,
check for 115VAC at CM 1 (C) (BR) to neutral (W). If 115VAC is present, Check DTh continuity. Replace as needed. If DTh conrmed, replace CM.
(4) EvapFM (if applicable): Conrm EvapFM de-energizes. If not, check for 115VAC
at CM 5 (F) (DBU) to neutral (W). If 115VAC is present, conrm Comp and ConFM de-energized. Next, check DTh continuity. Replace as needed. If DTh conrmed, replace CM.
2) Off Cycle Defrost: Off cycle defrost. Has CTh warmed above temperature setpoint? Ifnot, conrm CTh continuity. Replace as needed. If CTh conrmed, replace CM.
3) Heated Defrost Diagnosis: Initiation; Conrm Comp is energized, then manually initiate defrost. Rotate TD all the way to the right. Wait 1 to 5sec. then rotate back to original setting. Defrost initiated.
a) Prep Table: Check that Comp and ConFM de-energize. DH energizes.
EvapFMcontinues.
b) Freezer: Check that Comp, ConFM, PH, MH, and EvapFM de-energize.
DHenergizes.
(1) TD: If Comp and ConFM continue, wait 1 to 2 min. and make several more
attempts of manual initiation. Ifmanual initiation fails, replace TD. (2) CM: If TD conrmed and Comp and ConFM continue, replace CM. (3) DH: If Comp and ConFM de-energize, check that DH energizes. Check for
115VAC at CM 4 (H) (R) to CM 3 (N) (W). If 115VAC is not present, replace CM.
If115VAC is present, and DH is not energized, check for 115VAC at DST black
(BK) wire to any neutral white (W) wire. If 115VAC is not present, DST is open.
Letcool and reset. If DST does not reset (close), replace DST. If 115VAC is
present, check continuity of DH. Replace as needed.
4) Heated Defrost Diagnosis: Termination; a) Prep Table
(1) DTh: DTh warms to 46°F (7.7°C). DH de-energizes. Conrm continuity of DTh. Replace as needed. If DTh is good and DH continues after DTh achieves 46°F (7.7°C), replace CM.
b) Freezer
(1) DTh: DTh warms to 50°F. (10°C) DH de-energizes. Conrm continuity of DTh. Replace as needed. If DTh is good and DH continues after DTh achieves 50°F (10°C), replace CM.
Legend: Comp–compressor; ConFM–condenser fan motor; CM–control module;
CTh–cabinet thermistor; DH–defrostheater; DST–defrost safety thermostat; DT–defrost timer; DTh–defrost thermistor; EvapFM–evaporator fan motor; HPS–high-pressure switch; MH–mullion heater; PH–perimeterheater;
TD–temperature dial
17
Page 18

C. Control Module Check

1. Control Module
Before replacing a CM that does not show a visible defect and that you suspect is bad, conduct the following check procedure. This procedure will help you verify your diagnosis. Always choose a neutral (W) to establish a good power supply and neutral connection to CM: 115VAC at CM 2 (L) (BK)
2. Startup/Cool Down
At startup, CM displays a solid red LED for 5 sec. After 5 sec. CM turns red LED off and begins ashing a green LED. This is normal operation. If a red LED ashes (fault code), check CTh or DTh for continuity and good connection to CM.
1) Check all wiring connections.
2) Be sure the power supply is connected to the electrical outlet.
3) Conrm the CTh and DTh are properly connected (no red LED ashing). A Red LED turns on for 5 sec. at startup. After 5 sec. the red LED turns off and a green LED starts ashing. This is normal operation. If the red LED starts ashing, check CTh and DTh continuity. Replace as needed.
4) Check that Comp, ConFM, and EvapFM energize (PH and MH on freezers). If not check CTh status. If CTh ohm reading is in proper range, Comp and ConFM and PH and MH (freezers); check for 115VAC at CM 1 (C) (BR) to neutral white (W). If 115VAC is not present, replace CM. If 115VAC is present and Comp energized and ConFM did not, check ConFM blades for binding and motor winding continuity. If PH or MH (freezers) does not energize, check continuity, replace as needed. EvapFM; Check for 115VAC at CM 5 (F) (DBU) to neutral white (W). If 115VAC is not present, replace CM. If115VAC is present, check EvapFM blades for binding and motor winding continuity.
3. Defrost initiation
5) Manual Defrost Check: Turn the TD all the way to the right. Wait 1 to 3 sec. then back to original setting. Defrost initiated. If Comp and ConFM continue, wait 1 to 2 min. and repeat process of manual initiation. If Comp remains energized, replace CM.
6) Conrm Comp, ConFM, EvapFM (UC/WT refrigerator and freezer), PH and MH (freezers) de-energize. If not, for Comp, ConFM and PH and MH (freezers), check for 115VAC at CM 1 (C) (BR) to neutral white (W) wire and for EvapFM (if applicable) CM 5 (F) (DBU) to neutral white wire (W). If 115VAC is present, replace CM. Note: EvapFM continues on Prep Table models.
7) Heated Defrost: Conrm DH energizes. Check for 115VAC at CM 4 (H) (R) to neutral white (W) wire. If 115VAC is not present, replace CM.
18
Page 19
4. Defrost Termination
8) Check that all components restart after defrost termination. a) UC/WT Refrigerator: CTh above setpoint. Cool cycle starts. Comp, ConFM, and
EvapFM energize.
b) Prep Table: DTh warms to 46°F (7.7°C). DH de-energizes. Conrm continuity of DTh.
Replace as needed. If DTh is good and DH continues after DTh achieves 46°F (7.7°C), replace CM.
c) UC/WT Freezer: DTh warms to 50°F (10°C). DH de-energizes. Conrm continuity of
DTh. Replace as needed. If DTh is good and DH continues after DTh achieves 50°F (10°C), replace CM.
Legend: Comp–compressor; ConFM–condenser fan motor; CM–control module;
CTh–cabinet thermistor; DH–defrost heater; DTh–defrost thermistor; EvapFM–evaporator fan motors, MH–mullion heater; PH–perimeter heater
19
Page 20

D. Diagnostic Table

Before consulting the diagnostic tables, check the following:
• Check the cabinet temperature control setting. See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Control Setting
Undercounter Worktop
Prep Table Between 4 and 5 34°F (1°C)
Between 4 and 5 Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
• Make sure the doors are not left open or opened too often and that they are sealing properly.
• On prep tables, pans and rail dividers must be in place. Otherwise, the rail will not cool properly.
• Make sure product is not blocking airow and that the cabinet is not overloaded with warm or hot product. Product should be allowed to cool before putting in the appliance. On prep tables, only load ingredients that have been pre-chilled to 37°F (3°C) or less.
• Check for correct installation and proper voltage per appliance nameplate. This appliance is not intended for outdoor use. Normal operating ambient temperature: – Undercounter and Worktop 45°F to 100°F (7°C to 38°C) – Prep Table 45°F to 86°F (7°C to 30°C)
• The appliance should not be located next to ovens, grills, or other high heat producing equipment. A minimum of 1.5" (38 mm) overhead clearance is required for proper ventilation.
20
Page 21
1. Appliance Not Cooling
Appliance Not Cooling - Possible Cause
Power Supply
1.
Power Supply Cord and Plug
2.
Wiring
3.
Cabinet Thermostat or Cabinet
4.
Thermistor Cabinet Temperature Dial
5.
Defrost Timer or Control Module
6.
(if applicable)
Evaporator Fan Motor
7.
Condenser Fan Motor
8.
Compressor External Protector
9.
Compressor
10.
Condenser
11.
Evaporator
12.
Refrigerant/Refrigerant Lines
13.
High-Pressure Switch
10. (if applicable)
Thermostatic Expansion Valve
11.
(not adjustable)
Unplugged, blown fuse, or tripped or defective circuit breaker.
a)
Loose connection.
b)
Not within specications.
c)
Loose connection.
a)
Defective.
b)
Loose connection or open.
a)
Faulty.
b)
Loose, disconnected, or defective.
a)
Loose, disconnected, or defective.
a)
Defrost timer defective. If applicable.
a)
Control module in alarm (red LED ashing). If applicable.
b)
Control module defective. If applicable.
c)
Defective.
a)
Fan blade binding.
b)
Defective.
a)
Fan blade binding.
b)
Dirty condenser.
a)
Condenser fan motor not operating.
b)
Defective.
c)
Start relay defective.
d)
Low charge.
e)
Start capacitor (if applicable) defective.
f)
Defective.
a)
Dirty.
a)
Dirty or frozen up.
a)
Gas leak.
a)
Refrigerant lines or components restricted.
b)
Dirty condenser.
a)
Ambient temperature too warm.
b)
Condenser fan motor not operating.
c)
Refrigerant overcharge.
d)
Refrigerant lines or components restricted.
e)
Bad contacts.
f)
Defective.
a)
21
Page 22
2. Evaporator is Frozen Up
Evaporator is Frozen Up - Possible Cause
Evaporator
1.
Evaporator Fan Motor
2.
Refrigerant Charge
3.
Defrost Heater (if applicable)
4.
Defrost Timer or Control Module
5.
(if applicable) Defrost Safety Thermostat Open
6.
(if applicable) Thermostatic Expansion Valve
7.
(not adjustable)
Dirty.
a)
Defective.
a)
Fan blade binding.
b)
Low.
a)
Defective.
a)
Defective.
a)
Defective.
a)
Defective.
a)
3. Defrost Fails to Initiate or Terminate
Defrost Fails to Initiate or Terminate - Possible Cause
Defrost Thermistor (if applicable)
1.
Defrost Timer or Control Module
2.
(if applicable) Defrost Heater (if applicable)
3.
Defective.
a)
Defective.
a)
Defective
a)
22
Page 23

III. Controls and Adjustments

A. Temperature Settings

1. Temperature Reading
A thermometer with both °F and °C scales is mounted in the cabinet. See Fig. 1.
2. Cabinet Temperature
The appliance features a cabinet temperature control dial (TD). The warmest setting is 1and the coldest setting is 7. See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Control Setting
Undercounter Worktop
Prep Table Between 4 and 5 34°F (1°C)
Between 4 and 5 Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
Fig. 1
Warmer Colder
Cabinet Temperature Control Dial

B. Defrost

There are 2 types of defrost: Off Cycle Defrost and Heated Defrost.
Manual Initiation (All Models): Turn the TD all the way to the right. Wait 3 sec. then
back to original setting. Defrost initiated. Refrigerator Off Cycle Defrost Automatic Initiation: Compressor cycles off with cabinet setpoint temperature achieved. Heated Defrost Automatic Initiation: Temperature achieved and defrost timer terminates. Manual Termination: Turn the TD all the way to the right. Wait 3 sec. then back to original setting. Defrost terminated. Automatic Termination: Cabinet temperature above setpoint, or defrost thermistor above termination temperature, or backup defrost timer terminates.
Thermometer
1. Undercounter and Worktop Refrigerators
Off-Cycle Defrost: Undercounter and worktop refrigerators defrost naturally between run cycles.
23
Page 24
2. Prep Table and Freezer
Temperature/Time-Initiated Defrost Cycle: Defrost cycle occurs once every 6hrs. for prep tables or 8 hrs. for freezers when defrost initiation temperature achieved (50 Prep Tables or 41
°F (5°C) for the Freezers). Defrost cycle initiation and termination are
°F (10°C) for
controlled by the control module and defrost thermistor. Prep Table Refrigerators: The defrost heater energizes, the evaporator fan motor
remains energized, and all other components de-energize during the defrost cycle. There is an in-line defrost safety thermostat.
Freezers: The defrost heater energizes and all other components de-energize during the defrost cycle. There is an in-line defrost safety thermostat.
Minimum Defrost Time is 5 min. Maximum Defrost Time is 45 min. for Prep Tables and 1 hr. for Freezers.
To initiate a manual defrost cycle follow the steps below.
1) Rotate TD all the way to the right. Wait 1 to 5sec. then rotate back to original setting. Defrost initiated. See Fig. 2.
2) Repeat step 1 to terminate defrost.
Fig. 2
24
Page 25

C. Safety Devices

1. Compressor External or Internal Protector (All Models)
If combined temperature/amperage value is above the limit specied by the compressor manufacturer, the compressor protector operates independently to turn off the compressor. The compressor protector de-energizes the compressor until the temperature/amperage value returns to an acceptable level.
2. High-Pressure Switch
If pressure on the high-side of the appliance exceeds Hoshizaki specications, the high-pressure switch activates and interrupts the compressor circuit, de-energizing the compressor until the pressure returns to an acceptable level. If the condenser fan motor is operating and the compressor is off, it is most likely that the compressor protector opened. If both the compressor and condenser fan motor are off, it is most likely the appliance is off or the high-pressure switch has opened.

D. Perimeter and Mullion Heaters

Freezers are equipped with perimeter and mullion heaters. If condensation occurs, check continuity of heaters.
25
Page 26

IV. Refrigeration Circuit and Component Service Information

DANGER
Risk of Fire or Explosion Flammable Refrigerant Used
• Follow handling instructions carefully in compliance with U.S. government regulations.
• Do not use mechanical devices to defrost.
• Do not puncture refrigerant tubing. Risk of re or explosion due to puncture of refrigerant tubing; follow handling instructions carefully.
• Component parts shall be replaced with like components.
• Servicing shall be done by factory authorized service personnel to minimize the risk of possible ignition due to incorrect parts or improper service.
• Consult instruction manual/service manual before attempting to install or service this product.
• Dispose of properly in accordance with federal or local regulations.
• Do not place any potential ignition sources in or near the appliance.
Risque De Feu Ou D'Explosion Le Frigorigène Est Inammable
• Suivre attentivement les instructions de manipulation conformément à la réglementation gouvernementale.
• Ne pas utiliser d'appareils mécaniques pour dégivrer le réfrigérateur.
• Ne pas perforer la tubulure contenant le frigorigène. Risque de feu ou d'explosion si la tubulure contenant le frigorigène est perforée; suivre les instructions de manutention avec soin.
• Les pièces des composants doivent être remplacées par des pièces et accessoires équivalents.
• L’entretien doit être effectué par le personnel de service autorisé par le fabricant an de minimiser les risques d’inammation attribuables à l’installation d’une pièce inadéquate ou à la mauvaise exécution du service.
• Consulter le manuel du propriétaire/guide de réparation avant de tenter une réparation. Toutes les mesures de sécurité doivent être respectées.
• Éliminer conformément aux règlements fédéraux ou locaux.
• Ne placez aucune source d’inammation potentielle dans ou près de l’appareil.
26
Page 27
WARNING
• Wear appropriate personal protective equipment (PPE) when servicing the appliance.
• Technician must utilize a combustible gas leak detector at all times.
• Notify everyone in the immediate area that you are working with ammable refrigerant.
• Do not work on appliance in a conned space. Conrm area is well ventilated.
• Identify and eliminate all possible ignition points in a 10 ft. (3 m) area around service area.
• Do not use mechanical devices to defrost.
• Use non-sparking tools.
• Class B dry chemical re extinguisher or equivalent must be available.
• Do not pressurize system above 200 PSIG during leak check procedure or prior to evacuating refrigeration system.
• This appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• To reduce the risk of electric shock, do not touch the plug with damp hands.
• Unplug the appliance from the electrical outlet before servicing.
• Make sure all food zones in the appliance are clean after the appliance is serviced.
27
Page 28

A. Refrigeration Circuit Service Information

WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-290 as a mixture with pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 minutes when replacing or servicing parts. The Polyol Ester (POE) oils used in R-290 appliances can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
Refrigerant leaks must be repaired as soon as they are discovered. If not, refrigerant charge should be recovered from the system until the leak can be repaired. When repairing a leak:
• Repair the leak properly – Remove the refrigerant, examine the leak source, determine the reason for the leak, and carry out the proper course of action.
• Before repairing the leak, ensure that the refrigerant has been recovered and the system purged with nitrogen when brazing.
• Be sure to remove piercing valves attached to the system after repairs are made.
1. Refrigerant Recovery
Using proper refrigerant practices, place piercing valves toward the end (crimped area) of the high and low-side process tubes, then recover the refrigerant into an approved container or device.
28
Page 29
2. Brazing
DANGER
Risk of Fire or Explosion Flammable Refrigerant Used
• Servicing shall be done by factory authorized service personnel to minimize the risk of possible ignition due to incorrect parts or improper service.
Risque De Feu Ou D'Explosion Le Frigorigène Est Inammable
• L’entretien doit être effectué par le personnel de service autorisé par le fabricant an de minimiser les risques d’inammation attribuables à l’installation d’une pièce inadéquate ou à la mauvaise exécution du service.
WARNING
• Wear appropriate personal protective equipment (PPE) when servicing the appliance.
• You must have a combustible gas leak detector in the immediate work area at all times.
• You must have a Class B chemical re extinguisher available at all times.
• Notify all persons in the immediate area that you are working with a ammable refrigerant.
• Do not use silver alloy or copper alloy containing arsenic.
• Be sure the area is clear of refrigerant vapor before brazing.
1) Braze/repair/replace damaged component or tting.
2) Purge with nitrogen gas for 2 min. Then braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 5 PSIG.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
3) Use soap bubbles to check for leaks. Raise the pressure using nitrogen gas (190 PSIG). Do not use any refrigerant as a mixture with pressurized air for leak testing.
4) Once leak checking is complete, release the nitrogen gas from the system.
29
Page 30
3. Evacuation
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both high and low-side refrigerant piercing valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump, then open the gauge manifold valves. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum (500 microns). Evacuating period depends on pump capacity.
4) Close the low-side valve and high-side valve on the gauge manifold.
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the nameplate. Hoshizaki recommends only virgin or reclaimed refrigerant which meets ARI Standard 700 (latest edition) be used.
4. Recharge
6) R-290 can be charged in either the liquid or vapor state. Liquid charge is preferred. Ifrefrigerant charging is done in the liquid state, place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) Close the high-side valve on the gauge manifold. If charging is complete, skip to step 10.
9) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side refrigerant access valve with the compressor running. Close the refrigerant
cylinder valve and let the low-side refrigerant equalize to the system, then close the low-side manifold gauge. Move the power switch to the "OFF" position (if applicable) or unplug the appliance from the electrical outlet.
10) Pinch off (crimp down) the process tubes just below the piercing valves.
11) Remove the piercing valves. Cut the process tubes to remove the piercing valve holes then braze the process tubes closed. Note: Be sure there is no refrigerant leak before brazing.
12) Use a combustible gas leak detector or soap bubbles to check for leaks again.
13) Place red sleeves over the process tubes.
14) Plug the appliance back into the electrical outlet.
30
Page 31

B. Component Service Information

NOTICE
When replacing a component listed below, see the notes to help ensure proper operation.
Component Notes Compressor Install a new start relay and compressor external protector. WARNING! To reduce the
risk of electric shock, be sure to reconnect the compressor's ground wire.
Thermostatic Expansion Valve
• Attach the thermostatic expansion valve bulb to the suction line in the same location as the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder.
31
Page 32

V. Preparing the Appliance for Periods of Non-Use

When shutting down the appliance for periods of non-use, follow the instructions below.
WARNING
Prevent the doors from closing to reduce the risk of children getting trapped.
NOTICE
Clean the cabinet interior, door gaskets, and shelves.
1) Before shutting down the appliance, move the stored food into another refrigerator or freezer.
2) Unplug the appliance. WARNING! To reduce the risk of electric shock, do not touch
the plug with damp hands.
32
Page 33

VI. Disposal

DANGER
Risk of Fire or Explosion Flammable Refrigerant Used
• Follow handling instructions carefully in compliance with U.S. government regulations.
• Do not puncture refrigerant tubing. Risk of re or explosion due to puncture of refrigerant tubing; follow handling instructions carefully.
• Dispose of properly in accordance with federal or local regulations.
Risque De Feu Ou D'Explosion Le Frigorigène Est Inammable
• Suivre attentivement les instructions de manipulation conformément à la réglementation gouvernementale.
• Ne pas perforer la tubulure contenant le frigorigène. Risque de feu ou d'explosion si la tubulure contenant le frigorigène est perforée; suivre les instructions de manutention avec soin.
• Éliminer conformément aux règlements fédéraux ou locaux.
WARNING
When preparing the appliance for disposal, remove the doors/drawers to reduce the risk of children getting trapped. Leave any shelves in place so that children may not easily climb inside.
The appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certied service personnel.
33
Page 34

VII. Technical Information

A. Electrical and Refrigerant Data

Design
Pressure
AC Supply
Model (includes drawer models)
U/WR27A(-xxx) UR27A-GLP01 2.9 U/WF27A(-xx)
UF27A-GLP01 2.0 SR27A-(xxxxx) 115/60/1 2.4 360 190 2.3 U/WR36A(-xx) 115/60/1 2.4 360 190 2.3
SR36A(-xxx) 115/60/1 2.7 360 190 2.1 U/WR48A(-01) U/WR48A-D2(-D4) 2.8 UR48A-GLP01 115/60/1 2.7 360 190 2.6 U/WF48A(-xx) U/WF48A-D4 3.0 SR48A-(xxxxx) 115/60/1 2.5 360 190 2.9 U/WR60A(-01) U/WR60A(-Dx) 3.3 U/WF60A(-xx) 115/60/1 5.6 360 190 3.9 SR60A-(xxxxx) 115/60/1 5.9 360 190 3.1 U/WR72A(-01) U/WR72A(-D6) 3.5 SR72A-(xxxxx) 115/60/1 6.3 360 190 3.4
Voltage Amperes
115/60/1
115/60/1
115/60/1
115/60/1 5.9 360 190
115/60/1
115/60/1
2.5
2.5
2.6
3.1
2.9
(PSIG) Refrigerant (oz.)
HIGH LOW R290
360 190 2.3
360 190 2.1UF27A-LP 2.3
360 190 3.0
360 190 2.8
360 190 3.9
3.2
See the nameplate for electrical and refrigeration specications. The nameplate is located inside the cabinet. We reserve the right to make changes in specications and design without prior notice.
Legend: U/WR–undercounter/worktop refrigerator; SR–prep table; U/WF–undercounter/worktop freezer
34
Page 35

B. Wiring Diagrams

1. Undercounter and Worktop: Refrigerator

35
Page 36

2. Prep Table

°F±5°F (49°C±3°C)
120
** Defrost Thermostat
Cut-Out
°F±5°F (21°C±3°C)
70
Cut-In
**
*
* High-Pressure Switch
Cut-Out 300±10 PSIG
Cut-In 190±20 PSIG
36
Page 37

3. Undercounter and Work Top: Freezer

**
°F±5°F (49°C±3°C)
*
** Defrost Thermostat
°F±5°F (21°C±3°C)
70
120
Cut-Out
Cut-In
* High-Pressure Switch
Cut-Out 360±30 PSIG
Cut-In 249±10 PSIG
37