Hoshizaki KM-650MAH, KM-650MRH, KM-650MWH User Manual

Page 1
Hoshizaki
“A Superior Degree
of Reliability”
www.hoshizaki.com
Models KM-650MAH KM-650MWH KM-650MRH
Modular Crescent Cuber
Hoshizaki America, Inc.
SERVICE MANUAL
Number: 73147 Issued: 12-12-2006
1
Page 2
IMPORTANT
Only qualified service technicians should attempt to service or maintain this unit. No such service or maintenance should be undertaken until the technician has thoroughly read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the unit.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, write or send an e-mail message to the HOSHIZAKI Technical Support Department for assistance.
HOSHIZAKI AMERICA, INC. 618 Highway 74 South Peachtree City, GA 30269
Attn: HOSHIZAKI Technical Support Department
Phone: 1-800-233-1940 Technical Service (770) 487-2331 Fax: 1-800-843-1056 (770) 487-3360 E-mail: techsupport@hoshizaki.com
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
2
Page 3
Please review this manual. It should be read carefully before the icemaker is serviced or maintenance operations are performed. Only qualified service technicians should service and maintain the icemaker. This manual should be made available to the technician prior to service or maintenance.
CONTENTS
I. Specifications ...................................................................................................................... 5
A. Icemaker ....................................................................................................................... 5
1. KM-650MAH (air-cooled) ......................................................................................... 5
2. KM-650MWH (water-cooled) ................................................................................... 6
3. KM-650MRH (remote air-cooled) ............................................................................ 7
B. Condensing Unit ............................................................................................................ 8
1. URC-5F ................................................................................................................... 8
II. General Information ......................................................................................................... 10
A. Construction ................................................................................................................ 10
1. KM-650MAH (air-cooled) .......................................................................................
2. KM-650MWH (water-cooled) ................................................................................. 11
3. KM-650MRH (remote air-cooled) .......................................................................... 12
B. Sequence of Operation ............................................................................................... 13
1. One Minute Fill Cycle ............................................................................................ 13
2. Initial Harvest Cycle .............................................................................................. 13
3. Freeze Cycle ......................................................................................................... 13
4. Pump-Out Cycle ................................................................................................... 13
5. Normal Harvest Cycle .......................................................................................... 13
C. Control Board .............................................................................................................. 15
1. Control Board Layout ............................................................................................. 16
2. Features ................................................................................................................ 17
a) Maximum Water Supply Period – 6 minutes ....................................................... 17
b) Harvest Backup Timer and Freeze Timer ........................................................... 17
c) High Temperature Safety .................................................................................... 17
d) Low Water Safety ............................................................................................... 17
e) High Voltage and Low Voltage Cut-outs ............................................................. 17
f) LED Lights and Audible Alarm Safeties ............................................................... 18
3. Controls and Adjustments ..................................................................................... 19
a) Default Dip Switch Settings ................................................................................ 19
b) Harvest Control – Thermistor ............................................................................. 19
c) Harvest Timer (dip switch 1 & 2) ......................................................................... 20
d) Pump-Out Timer (dip switch 3 & 4)..................................................................... 20
e) Pump-Out Frequency Control (dip switch 5 & 6) ................................................ 21
f) Freeze Timer (dip switch 9 & 10) ......................................................................... 21
g) Bin Control .......................................................................................................... 21
4. Control Board Check Procedure ............................................................................ 22
5. Control Board Replacement .................................................................................. 22
10
3
Page 4
III. Technical Information ...................................................................................................... 23
A. Water Circuit and Refrigeration Circuit ........................................................................ 23
1. KM-650MAH (air-cooled) .......................................................................................
2. KM-650MWH (water-cooled) ................................................................................. 24
3. KM-650MRH (remote air-cooled) .......................................................................... 25
B. Wiring Diagrams .......................................................................................................... 26
1. KM-650MAH (air-cooled) and KM-650MWH (water-cooled) .................................
2. KM-650MRH (remote air-cooled) ..........................................................................
C. Performance Data ....................................................................................................... 28
1. KM-650MAH (air-cooled) ....................................................................................... 28
2. KM-650MWH (water-cooled) ................................................................................. 29
3. KM-650MRH (remote air-cooled) .......................................................................... 30
IV. Service Diagnosis ........................................................................................................... 31
A. 10-Minute KM Diagnostic Procedure ......................................................................... 31
B. Diagnostic Charts ........................................................................................................ 32
1. No Ice Production .................................................................................................. 32
2. Evaporator is Frozen Up ........................................................................................ 36
3. Low Ice Production ................................................................................................ 37
4. Abnormal Ice ......................................................................................................... 37
5. Other ...................................................................................................................... 37
V. Removal and Replacement of Components .................................................................... 39
A. Service for Refrigerant Lines ...................................................................................... 39
1. Refrigerant Recovery ............................................................................................. 39
2. Evacuation and Recharge (R-404A) ...................................................................... 39
B. Brazing ........................................................................................................................ 40
C. Removal and Replacement of Compressor ................................................................ 40
D. Removal and Replacement of Drier ............................................................................ 41
E. Removal and Replacement of Expansion Valve .......................................................... 42
F. Removal and Replacement of Hot Gas Valve and Line Valve ..................................... 43
G. Removal and Replacement of Evaporator .................................................................. 44
H. Removal and Replacement of Water Regulating Valve - Water Cooled Model Only ... 44
I. Adjustment of Water Regulating Valve - Water-Cooled Model Only ............................. 45
J. Removal and Replacement of Headmaster (Condensing Pressure Regulator - C.P.R.)
- Remote Air-Cooled Model Only .............................................................................. 46
K. Removal and Replacement of Thermistor ................................................................... 47
L. Removal and Replacement of Fan Motor .................................................................... 47
M. Removal and Replacement of Inlet Water Valve ......................................................... 48
N. Removal and Replacement of Pump Motor ................................................................ 48
O. Removal and Replacement of Spray Tubes ................................................................ 49
VI. Cleaning and Maintenance Instructions ......................................................................... 50
A. Cleaning and Sanitizing Procedures ........................................................................... 50
1. Cleaning Procedure ...............................................................................................
2. Sanitizing Procedure - Following Cleaning Procedure ..........................................
B. Maintenance ................................................................................................................ 52
C. Preparing the Icemaker for Long Storage ................................................................... 53
23
26 27
51 52
4
Page 5
I. Specifications
SPECIFICATION NO. 06A019 ISSUED: 10/10/2006
ITEM: HOSHIZAKI MODULAR CRESCENT CUBER MODEL: KM-650MAH
AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 6.6 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *589 (267) 566 (257) 526 (238) Reference without *marks 80 572 (259) 537 (243) 490 (222)
90 566 (257) *512 (232) 467 (212)
100 555 (252) 501 (227) 426 (193) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 13.5 lbs. (6.1 kg) 720 pcs. APPROXIMATE STORAGE CAPACITY N/A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1240(5.8) 1100(4.5) WATER gal./24HR (gal./100 lbs.) 108(21.1) 257(43.7) EXTERIOR DIMENSIONS (WxDxH) 22" x 27-3/8" x 37-7/16" (560 x 695 x 950 mm) EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 169 lbs. (77 kg), Shipping 200 lbs. (91 kg) CONNECTIONS - ELECTRIC Permanent - Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT
3/8" OD Tube CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Thermostat COMPRESSOR Hermetic, Model RS55C2E-CAV CONDENSER Air-Cooled , Fin and tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R-404A, 1 lb. 8.7 oz. (700g) DESIGN PRESSURE High 467PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED N/A
-REQUIRED Ice Storage Bin OPERATING CONDITIONS VOLTAGE RANGE 187 - 253 V
AMBIENT TEMP. 45 -100° F WATER SUPPLY TEMP. 45 - 90° F WATER SUPPLY PRESSURE 10 - 113 PSIG

A. Icemaker

1. KM-650MAH (air-cooled)

Note: We reserve the right to make changes in specifications and design without prior
notice.
5
Page 6

2. KM-650MWH (water-cooled)

SPECIFICATION NO. 06A020 ISSUED: 10/10/2006
ITEM: HOSHIZAKI MODULAR CRESCENT CUBER MODEL: KM-650MWH
AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 5.3 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *680 (308) 675 (306) 626 (284) Reference without *marks 80 676 (307) 668 (303) 595 (270)
90 675 (306) *662 (300) 598 (271)
100 651 (295) 647 (294) 540 (245) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 14.8 lbs. (6.7 kg) 720 pcs. APPROXIMATE STORAGE CAPACITY N/A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1050(3.8) 1020(3.6) WATER gal./24HR (gal./100 lbs.) 149(22.5) 254(37.4) WATER COOLED CONDENSER 741(112) 408(60)
gal./24HR (gal./100 lbs.) EXTERIOR DIMENSIONS (WxDxH) 22" x 27-3/8" x 37-7/16" (560 x 695 x 950 mm) EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 169 lbs. (77 kg), Shipping 200 lbs. (91 kg) CONNECTIONS - ELECTRIC Permanent - Connection
- WATER SUPPLY Inlet 1/2" FPT Condenser Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT Condenser Outlet 3/8" FPT
3/8" OD Tube CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL Pressure Regulator BIN CONTROL SYSTEM Thermostat COMPRESSOR Hermetic, Model RS55C2E-CAV CONDENSER Water-cooled, Tube in tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R-404A, 1 lb. 5.7 oz. (615g) DESIGN PRESSURE High 427PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED N/A
-REQUIRED Ice Storage Bin OPERATING CONDITIONS VOLTAGE RANGE 187 - 253 V
AMBIENT TEMP. 45 -100° F WATER SUPPLY TEMP. 45 - 90° F WATER SUPPLY PRESSURE 10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior
notice.
6
Page 7

3. KM-650MRH (remote air-cooled)

SPECIFICATION DATA NO. 06A021 ITEM: HOSHIZAKI MODULAR CRESCENT CUBER MODEL: KM-650MRH
AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 7.1 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *615 (279) 597 (271) 556 (252) Reference without *marks 80 601 (273) 574 (260) 523 (237)
90 597 (271) *554 (251) 506 (230)
100 583 (264) 543 (246) 462 (210) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 14.1 lbs. (6.4 kg ) 720 pcs. APPROXIMATE STORAGE CAPACITY N/A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1250(5.4) 1150(4.5) WATER gal./24HR (gal./100 lbs.) 111(20.0) 266(43.2) EXTERIOR DIMENSIONS (WxDxH) 22" x 27-3/8" x 37-7/16" (560 x 695 x 950 mm) EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 169 lbs. (77 kg), Shipping 200 lbs. (91 kg) CONNECTIONS - ELECTRIC Permanent - Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT
3/8" OD Tube CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Thermostat COMPRESSOR Hermetic, Model RS55C2E-CAV CONDENSER Air-cooled Remote, Condenser Unit URC-5F EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-5F
REFRIGERANT CHARGE R-404A, 5 lbs. 11 oz. (2580 g)
( Icemaker 3 lbs. 13 oz. Cond. Unit 1 lb. 14 oz. ) DESIGN PRESSURE High 467 PSIG, Low 230 PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED N/A
-REQUIRED Ice Storage Bin, Remote Condenser Unit OPERATING CONDITIONS VOLTAGE RANGE 187 - 253 V
AMBIENT TEMP. 45 -100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
ISSUED: 10/10/2006
Note: We reserve the right to make changes in specifications and design without prior
notice.
7
Page 8

B. Condensing Unit

1. URC-5F

24"
(610 mm.)
23-1/32"
(585 mm.)
18-1/8"
(460 mm.)
17-1/8"
(435 mm.)
14-9/16"
(370 mm.)
19-11/16"
(500 mm.)
18-1/8"
(460 mm.)
20-15/32"
(520 mm.)
21-15/16"
(557 mm.)
6/16" x 3/4" (10 mm. x 20 mm.)
4 x 2 (SLOTTED HOLES)
14-1/8"
(358 mm.)
14-15/16"
15-11/16"
(380 mm.)
(398 mm.)
17-7/8"
(454 mm.)
14-15/16"
(380 mm.)
2-1/2"
(63 mm.)
7/8" DIA. HOLE
(23 mm. DIA.)
6-5/16"
(160 mm.)
2-15/16"
(75 mm.)
8
Page 9
Specifications
SPECIFICATION NO. 06A022
ISSUED: 10/12/2006
ITEM: HOSHIZAKI REMOTE CONDENSER UNIT
MODEL URC-5F
BEGINNING SERIAL NO. ________________
ENDING SERIAL NO. ___________________
AC SUPPLY VOLTAGE 115/60/1 (Connection to Icemaker)
FAN MOTOR 115 V Total 1.3FLA 65W
EXTERIOR DIMENSIONS (WxDxH) 21-15/16" x 15-11/16" x 17-7/8" (557 x 398 x 454 mm)
DIMENSIONS INCLUDING LEGS (WxDxH) 24" x 18-1/8" x 32-13/16" (610 x 460 x 834 mm)
EXTERIOR FINISH Galvanized Steel
WEIGHT Net 61 lbs. ( 28 kg ) Shipping 68 lbs. ( 31 kg )
CONNECTIONS - ELECTRIC Permanent - Connection
- REFRIGERANT Discharge Line 1-1/16"-12 UNF Fitting (#10 AEROQUIP)
Liquid Line 5/8"-18 UNF Fitting (#6 AEROQUIP)
CONDENSER Air-cooled, Fin and tube type
FAN MOTOR PROTECTION Thermal Protection
REFRIGERANT CONTROL Condensing Pressure Regulator
REFRIGERANT CHARGE R-404A 1 lb. 14 oz. (850g)
DESIGN PRESSURE High 467 PSIG
OPERATING CONDITIONS VOLTAGE RANGE 104 ~ 127 V
AMBIENT TEMP. -20 ~ 122 °F
ACCESSORIES -SUPPLIED Leg 2 pcs
Hex. Head Bolt w/Washer 8 x 16 8 pcs
Hex. Nut 8 8 pcs
DRAWING NO. (DIMENSION) 441211
MODEL: URC-5F
Note: We reserve the right to make changes in specifications and design without prior
notice.
9
Page 10

II. General Information

A. Construction

1. KM-650MAH (air-cooled)

Spray Tubes
Water Supply Inlet
Condenser
Control Switch
Bin Control Thermostat
Expansion Valve
Float Switch
Water Pump
Control Box
Fan Motor
Hot Gas Valve
Drier
Compressor
10
Page 11

2. KM-650MWH (water-cooled)

Spray Tubes
Water Supply Inlet
Control Switch
Bin Control Thermostat
Expansion Valve
Float Switch
Water Pump
Water Regulator Valve
Control Box
Condenser
Drier
Hot Gas Valve
Compressor
11
Page 12

3. KM-650MRH (remote air-cooled)

Spray Tubes
Water Supply Inlet
Junction Box
Control Switch
Bin Control Thermostat
Expansion Valve
Float Switch
Water Pump
Control Box
Receiver Tank
Hot Gas Valve
Drier
Compressor
Liquid Line Valve
12
Page 13

B. Sequence of Operation

The steps in the sequence are as outlined below. When power is supplied, a 5 second delay occurs at startup. Note that the order of the LEDs from the outer edge of the board is 1, 4, 3, 2.

1. One Minute Fill Cycle

LED 4 is on. WV opens and the fill period begins. After 1 minute, the board checks for a closed F/S. If F/S is closed, the harvest cycle begins. If not, WV will remain energized through additional 1 minute cycles until water enters the sump and F/S closes. This serves as a low water safety to protect the water pump.

2. Initial Harvest Cycle

LEDs 1, 4, and 2 are on. WV remains open, Comp and FMR energize, HGV opens, and harvest begins. As the evaporator warms, the thermistor located on the suction line checks for a 48°F (9°C) temperature. When 48°F (9°C) is reached, a 3.9 kΩ signal turns the harvest over to the adjustable harvest timer which is factory set for normal conditions. The timer has settings of 60, 90, 120, and 180 seconds (dip switch 1 & 2). The water valve is open during harvest for a maximum of 6 minutes or the length of harvest, whichever is shorter. When the harvest timer completes its count down, the harvest cycle is complete and the freeze cycle starts. The minimum total time allowed by the board for a complete harvest cycle is 2 minutes.

3. Freeze Cycle

LED 1 is on. Comp and FMR continue to run, PM and FMS energize, LLV opens, HGV and WV close and the freeze cycle starts. For the first 5 minutes the control board will not accept a signal from F/S. This 5 minute minimum freeze acts as a short cycle protection. At the end of 5 minutes, F/S assumes control. As ice builds on the evaporator the water level in the sump lowers. The freeze continues until F/S opens and terminates ice production.

4. Pump-Out Cycle

LEDs 1, 3, and 2 are on. Comp and FMR continue to run, HGV opens, LLV closes, and FMS deenergizes. PM stops for 2 seconds and reverses, taking water from the bottom of the sump and forcing pressure against the check valve seat allowing water to go through the check valve and down the drain. At the same time water flows through the small tube to power flush the F/S. When the pump-out timer stops counting, the pump out is complete. Pump out always occurs on the 2nd harvest after startup. Then, depending on the control board setting, pump out occurs every cycle, or every 2nd, 5th or 10th cycle (dip switch 5 &
6).

5. Normal Harvest Cycle

LEDs 1, 4, and 2 are on. Comp and FMR continue to run, HGV remains open and WV opens. As the evaporator warms, the thermistor reaches 48°F (9°C). The control board then receives the thermistor's 3.9 kΩ signal and starts the harvest timer. The water valve is open during harvest for a maximum of 6 minutes or the length of harvest, whichever is shorter. When the harvest timer completes its count down, the harvest cycle is complete and the next freeze cycle starts. The unit continues to cycle through 3, 4 and 5 sequence until the bin control senses ice and shuts the unit down.
Legend: Comp–compressor; FMR–remote fan motor; FMS–self-contained fan motor;
F/S–float switch; HGV–hot gas valve; LLV–Liquid Line Valve; PM–pump motor; WV–inlet water valve
13
Page 14
Cycle
4. Pump-Out
F/S in
control
5 minute timer
in control
• Minimum freeze time: 5 minutes
• Maximum freeze time: freeze timer setting
Pump motor stops
for 2 sec. and then
Freeze cycle
operation turned
over to F/S
F/S closed
Comp continues
FMR continues
HGV de-energized
F/S Check
reverses for 10/20 sec.
each 1, 2, 5, or 10 cycles.
Comp continues
FMR continues
HGV energized
FMS de-energized
WV de-energized
PM energized
FMS energized
F/S open
1 to 3 minute timer
in control
Thermistor temp
reaches 48°F (9°C)
2. Harvest Cycle 3. Freeze Cycle
Thermistor in
• Maximum harvest time: 20 minutes
Fill Cycle
control
F/S closed
Initial startup always
begins here
Comp energized
HGV energized
F/S Check
WV Energized
"E" board will have
5 second delay
• Maximum inlet water valve time: 6 minutes
1. One Minute
KM-650MAH, KM-650MWH, KM-650MRH Sequence Flow Chart and Component Operation
Cycle Steps
(3.9 kΩ or less)
Harvest timer starts
FMR energized
WV continues
F/S open
If F/S is open, compressor stops and cycle returns to 1 minute fill
Components Energized when the Control Switch is in the WASH Position
The WASH position on the control switch is used when cleaning and sanitizing the unit. When in the WASH
position, power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer flow
Legend:
Comp - compressor
FMR - remote fan motor
FMS - self-contained fan motor
over the outside of the evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer
F/S - float switch
flow over both the outside and the inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not re-start
HGV - hot gas valve
when the control switch is placed in the ICE position.
PM - pump motor
WV - inlet water valve
14
Page 15

C. Control Board

• A HOSHIZAKI exclusive solid-state control is employed in KM-650MAH, KM-650MWH and KM-650MRH Modular Crescent Cubers.
• All models are pretested and factory-adjusted.
CAUTION
1. Fragile, handle very carefully.
2. A control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the unit when handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4 and K5, because the same connector is used for the thermistor and float switch. K4 is not connected.
5. Always replace the whole board assembly if it goes bad.
6. Do not short out power supply to test for voltage.
15
Page 16

1. Control Board Layout

Control Products "E" Control Board
Alarm Reset Switch
Backup Freeze Timer LED
Backup Harvest Timer LED
Alarm Buzzer
Dip Switch
Output Test Switch (used to test relays on board)
Connector K3 Harvest Control (thermistor)
Connector K4 Open (not connected)
Power LED (lights when power is supplied to the board)
Relay LEDs (4) (indicate which relays are energized as listed below)
LED 2 Hot Gas Valve (HGV) Self-Contained Fan Motor (FMS) (FMS off when LED on)
LED 3 Pump Motor (PM) (on at pump out only)
LED 4 Water Valve (WV)
LED 1 Compressor (Comp) Remote Fan Motor (FMR)
Transformer Connector
Microprocessor (board revision level indicated by last 2 digits on label)
Connector K5 Float Switch
Part Number
Connector K1
Pins #1 through #10 #1, 9 Magnetic Contactor #2 Hot Gas Valve #3 Line Valve Self-Contained Fan Motor (FMS) #4 Pump Motor (icemaking) #5 Pump Motor (drain) #6 Water Valve #7, 10 Power (line, bin control) #8 Open
Switch for "C" board and "ALPINE" board (service boards only)
Control Board
Part Number 2A1410-01 (factory); 2A1410-02 (service)
Type HOS-001A (Control Products - 10 Pin)
16
Page 17

2. Features

a) Maximum Water Supply Period – 6 minutes
Inlet water valve opening, in the harvest cycle, is limited by the harvest timer. The water valve cannot remain open longer than the maximum period. The water valve can close in less than six minutes if the harvest cycle is completed.
b) Harvest Backup Timer and Freeze Timer
The harvest backup timer shuts down the icemaker if, for two cycles in a row, the harvest cycle takes more than 20 minutes to complete. The control board will signal this problem using 2 beeps every 3 seconds. The freeze timer shuts down the icemaker if, for two cycles in a row, the freeze cycle takes longer than the time specified to complete. The control board will signal this problem using 3 beeps every 3 seconds. The time is factory set using dip switches 9 &
10. The reset button on the control board must be pressed with power on to reset either of these safeties.
c) High Temperature Safety
The temperature of the suction line in the refrigeration circuit is limited by the high temperature safety. This protects the unit from excessively high temperatures. If the evaporator temperature rises above 127 ± 7°F (53 ± 4°C), the thermistor operates the safety. This shuts down the circuit and the icemaker automatically stops. The control board will signal this problem using 1 beep every 3 seconds. The reset button on the control board must be pressed with power on to reset the safety.
d) Low Water Safety
If the pump motor is operated without water, the mechanical seal can fail. To prevent this type of failure, the control board checks the position of the float switch at the end of the initial one minute water fill cycle and at the end of each harvest cycle. If the float switch is in the up position (electrical circuit closed), the control board changes to the ice making cycle. If the float switch is in the down position (electrical circuit open), the control board changes to additional one minute water fill cycles until water enters the sump and the float switch closes. When the float switch closes, the control board changes to the ice making cycle. The unit will not start without adequate water in the sump. This serves as a low water safety to protect the pump motor from mechanical seal failure. For water-cooled model, if the water is shut off, the unit is protected by the high pressure switch.
e) High Voltage and Low Voltage Cut-outs
The maximum and minimum allowable supply voltages of this icemaker are limited by the high voltage and low voltage cut-outs. If miswiring (especially on single phase 3 wire models) causes excessive voltage (147Vac ±5% or more) on the control board, the high voltage cut-out shuts down the circuit in 3 seconds and the icemaker automatically stops. The control board will signal this problem using 7 beeps every 3 seconds. The icemaker also automatically stops in cases of insufficient voltage (92Vac ±5% or less). The control board will signal this problem using 6 beeps every 3 seconds. When the proper supply voltage is resumed, the icemaker automatically starts running again.
17
Page 18
f) LED Lights and Audible Alarm Safeties
The red LED indicates proper control voltage and will remain on unless a control voltage problem occurs. At startup a 5 second delay occurs while the board conducts an internal timer check. A short beep occurs when the power switch is turned OFF. The green LEDs 1 through 4 energize and sequence from initial startup as listed in the table below. Note that the order of the LEDs from the outer edge of the board is 1, 4, 3,
2. For more information, see "II.B. Sequence of Operation."
Sequence Step LED
1 Minute Fill Cycle Harvest Cycle 1, 4, and 2 WV, HGV,
Freeze Cycle 1 Comp, PM,
Reverse Pump Out 1, 3, and 2 Comp, HGV,
The built in safeties shut down the unit and have alarms as follows:
No. of Beeps
(every 3 sec.)
1 High Evaporator Temp.
2 Harvest Backup Timer
4 WV 60 seconds
Type of Alarm Notes
(temperature > 127°F) (53°C)
(harvest > 20 min. for two cycles in a row)
Energized
Components
Comp, FMR
FMR/FMS, LLV
PM, FMR
Min. Max. Avg.
2 minutes 20 minutes
5 minutes freeze timer
10 seconds 20 seconds factory setting
Check for harvest problem (stuck HGV or relay), hot water entering unit, stuck HM, or shorted thermistor.
Orange LED marked H TIMER lights up. Check for open thermistor, HGV not opening, TXV leaking by, low charge, or inefficient compressor.
Time LEDs are On
setting
3 to 5 minutes
30 to 35 minutes
3 Freeze Timer
(freeze > specified setting for two cycles in a row) Timer is factory set using dip switches 9 & 10
To manually reset the above safeties, press the alarm reset button with the power supply on.
6 Low Voltage
(92Vac ±5% or less)
7 High Voltage
(147Vac ±5% or more)
Legend: Comp–compressor; FMR–remote fan motor; FMS–self-contained fan motor; F/S–float switch; HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–Liquid Line Valve; PM–pump motor; TXV–thermostatic expansion valve; WV–inlet water valve
Yellow LED marked F TIMER lights up. Check for F/S stuck closed (up), WV leaking by, HGV leaking by, TXV not feeding properly, low charge, HM not bypassing, or inefficient compressor.
Red LED will turn off if voltage protection operates. The control voltage safeties automatically reset when voltage is corrected.
18
Page 19

3. Controls and Adjustments

a) Default Dip Switch Settings
The dip switch is factory-adjusted to the following positions:
Dip Switch No. 1 2 3 4 5 6 7 8 9 10
KM-650MAH OFF OFF OFF OFF ON ON OFF OFF OFF OFF
KM-650MWH OFF OFF OFF OFF ON ON OFF OFF OFF OFF
KM-650MRH OFF OFF OFF OFF ON ON OFF OFF ON OFF
Freeze Timer (9 & 10)
Normally in the OFF position.
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
b) Harvest Control – Thermistor
A thermistor (semiconductor) is used for a harvest control sensor. The resistance varies depending on the suction line temperatures. The thermistor detects the temperature of the evaporator outlet to start the harvest timer. No adjustment is required. If necessary, check for resistance between thermistor leads, and visually check the thermistor mounting, located on the suction line next to the evaporator outlet.
Temperature (°F) Temperature (°C)
Resistance (k)
0 -18 14.401 10 -12 10.613 32
0 6.000 50 10 3.871 70 21 2.474 90 32 1.633
Check a thermistor for resistance by using the following procedure:
1) Disconnect the connector K3 on the board.
2) Remove the thermistor. See "V.K. Removal and Replacement of Thermistor."
3) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 minutes.
4) Check for a resistance between thermistor leads. Normal reading is within 3.5 to 7 k. Replace the thermistor if it exceeds the normal reading.
19
Page 20
c) Harvest Timer (dip switch 1 & 2)
The harvest timer starts counting when the thermistor reads 48°F (9°C) at the evaporator outlet. No adjustment is required under normal use, as the harvest timer is adjusted to the suitable position. However, a setting longer than the factory setting may be advised in cases where the flush provided at harvest needs to be prolonged for extra cleaning. Before changing this setting, call the HOSHIZAKI Technical Support Department at 1-800-233-1940 for recommendations. Keep in mind that setting the harvest timer to a longer setting will decrease 24 hour production.
Dip Switch Setting Time
No. 1 No. 2
OFF OFF 60
ON OFF 90
OFF ON 120
ON ON 180
d) Pump-Out Timer (dip switch 3 & 4)
When a freeze cycle is completed, the pump motor stops, and the icemaker resumes operation in 2 seconds. Then, during cycles when a pump out is called for, the pump motor drains the water tank for the time determined by the pump-out timer. The pump­out timer also acts in place of the harvest timer during cycles with a pump out. The pump-out timer is factory-adjusted, and no adjustment is required.
(seconds)
Dip Switch Setting
No. 3 No. 4
OFF OFF 10 150
ON OFF 10 180
OFF ON 10 120
ON ON 20 180
T1: Time to drain the water tank T2: Harvest timer at pump out
Pump out always occurs on the 2nd harvest after startup. Then, depending on the pump­out frequency control setting (dip switch 5 & 6), pump out occurs every cycle, or every 2nd, 5th or 10th cycle.
Time (seconds)
T1
T2
20
Page 21
e) Pump-Out Frequency Control (dip switch 5 & 6)
The pump motor drains the water tank at the frequency set by the pump-out frequency control. The pump-out frequency control is factory-adjusted to drain the water tank every 10 cycles, and no adjustment is required. However, where water quality is bad and the icemaker needs a pump drain more often, the pump-out frequency can be adjusted as shown in the table below.
Dip Switch Setting
No. 5 No. 6
OFF OFF every cycle
ON OFF every 2 cycles
OFF ON every 5 cycles
ON ON every 10 cycles
f) Freeze Timer (dip switch 9 & 10)
Frequency
CAUTION
Adjust to proper specification, or the unit may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of freeze timer, machine initiates the harvest cycle. After 2 consecutive timer terminations, machine will shut down, possibly indicating a problem. The freeze timer is factory adjusted and no adjustment is required.
Dip Switch Setting Time
No. 9 No. 10
OFF OFF 60
(minutes)
OFF ON 50
ON OFF 70 ON ON 60
g) Bin Control
CAUTION
When the ambient temperature is below 45°F (7°C), the bin control thermostat operates to stop the icemaker even if the ice storage bin is empty. When the thermostat is set in the prohibited range, the icemaker operates continuously even if the ice storage bin is filled with ice. Setting in the prohibited range might cause severe damage to the icemaker resulting in failure.
No adjustment is required under normal use, as the bin control is factory-adjusted. Adjust it, if necessary, so that the icemaker stops automatically within 10 seconds after ice contacts the bin control thermostat bulb.
21
Page 22

4. Control Board Check Procedure

Before replacing a control board that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis.
1) Check the dip switch settings to assure that #3, 4, 7, 8, 9, & 10 are in the factory default position. On units with a slide-type output test switch, the output test switch (S3) should be OFF. Switches 1, 2, 5, & 6 are cleaning adjustments and the settings are flexible.
2) Turn the control switch to ICE and check for proper control voltage. If the red LED is ON, the control voltage is good. If the red LED is OFF, check the control transformer circuit.
3) Check the 115 volt input at the 10-pin connector. Check the brown wire at pin #10 to a white neutral wire for 115 volts. (Always choose a white neutral wire to establish a good neutral connection when checking voltages.) A jumper also feeds 115 volts into pin #7. If no voltage is present, check the 115 volt supply circuit.
4) The output test switch provides a relay sequence test. On units with a slide-type output test switch, move the control switch to the OFF position, move the output test switch to the ON position, then move the control switch to the ICE position. On units with a push­type output test switch, make sure the control switch is in the ICE position, then press the output test switch. The correct lighting sequence should be none, 2, 3, 4, 1, and 4, normal sequence every 5 seconds. Components (e.g., the compressor) will cycle during the test. Note that the order of the relays from the outer edge of the board is 1, 4, 3, 2. Note: If the LEDs light in a different sequence or the 5–second interval does not occur,
the control board is bad and should be replaced.
5) After checking the sequence, place the output test switch back in the OFF position on units with a slide-type switch. The output test switch must remain in the OFF position during normal operation. On units with a push-type output test switch, the unit automatically resumes normal operation after the test. The unit begins normal operation with the 1 minute fill cycle.

5. Control Board Replacement

The application switch located between relay X3 & X4 must be set to match the original board application. Place this switch in the ALP position if there is no white wire supplied to the K1 connector. If there is a white wire, place the switch in the C position. If this switch is placed in the wrong position either the compressor contactor will remain energized with the control switch OFF or the unit will not start. The dip switches should be adjusted to the factory default settings as outlined in this manual. Dip switch #8 must remain in the OFF position.
22
Page 23

III. Technical Information

A. Water Circuit and Refrigeration Circuit

1. KM-650MAH (air-cooled)

23
Page 24

2. KM-650MWH (water-cooled)

24
Page 25

3. KM-650MRH (remote air-cooled)

25
Page 26

B. Wiring Diagrams

1. KM-650MAH (air-cooled) and KM-650MWH (water-cooled)

*
* Pressure Switch
Air-Cooled Model Water-Cooled Model
Cut-out 412±21 PSIG 384±21 PSIG
0
Cut-in 327±21 PSIG 284±21 PSIG
0
12V
26
Page 27

2. KM-650MRH (remote air-cooled)

* Pressure Switch
Cut-out 412±21 PSIG
0
Cut-in 327±21 PSIG
*
12V
27
Page 28

C. Performance Data

PERFORMANCE DATA NO. 06A019 ISSUED: 10/10/2006
ITEM: HOSHIZAKI MODULAR CRESCENT CUBER
MODEL: KM-650MAH
70/21 589 267 566 257 526 238 80/27 572 259 537 243 490 222
90/32 566 257 512 232 467 212
lbs./day kg./day 100/38 555 252 501 227 426 193
70/21
80/27
90/32
watts 100/38
70/21 257 0.97 214 0.81 190 0.72
80/27 224 0.85 156 0.59 153 0.58
90/32 214 0.81 108 0.41 95 0.36
gal./day m3/day 100/38 163 0.62 105 0.40 84 0.32
70/21 80/27
90/32
min. 100/38
70/21
80/27 90/32
min. 100/38
70/21 225 15.8 246 17.3 270 19.0 80/27 241 17.0 275 19.3 295 20.7
90/32 246 17.3 298 21.0 320 22.5
PSIG kg/cm2G 100/38 249 17.5 303 21.3 341 24.0
70/21 53 3.7 55 3.9 58 4.1
80/27 54 3.8 57 4.0 61 4.3 90/32 55 3.9 59 4.2 63 4.4
PSIG kg/cm2G 100/38 56 3.9 60 4.2 67 4.7
2.0
TOTAL HEAT OF REJECTION FROM CONDENSER 10,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
SUCTION PRESSURE
HARVEST CYCLE TIME
HEAD PRESSURE
3.6
3.0
3.9 2.1
38
32
33
37
1170
1209
1261
1280
35 38
40
43
1138
1141
1195
1240
1245
1100
1131
1141
30
APPROXIMATE ICE PRODUCTION PER 24 HR.
APPROXIMATE ELECTRIC CONSUMPTION
APPROXIMATE WATER CONSUMPTION PER 24 HR.
FREEZING CYCLE TIME
WATER TEMP. (ºF/ºC)
AMBIENT TEMP.
(ºF/ºC)
50/10 70/21 90/32
31
32 35
2.2
4.6
3.1
3.9
3.0
2.2
4.1

1. KM-650MAH (air-cooled)

Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior notice.
28
Page 29
PERFORMANCE DATA NO. 06A020 ISSUED: 10/10/2006
ITEM: HOSHIZAKI MODULAR CRESCENT CUBER
MODEL: KM-650MWH
70/21 680 308 675 306 626 284 80/27 676 307 668 303 595 270
90/32 675 306 662 300 598 271
lbs./day kg./day 100/38 651 295 647 294 540 245
70/21
80/27
90/32
watts 100/38
70/21 662 2.51
729 2.76 1173 4.44
80/27 713 2.70 817 3.09 1457 5.52
90/32 729 2.76 890 3.37 1457 5.52
gal./day m3/day 100/38 980 3.71 1023 3.87 1977 7.49
70/21 80/27
90/32
min. 100/38
70/21
80/27 90/32
min. 100/38
70/21 231 16.2
231 16.2 238 16.7 80/27 231 16.2 231 16.2 242 17.0
90/32 231 16.2 231 16.2 240 16.9
PSIG kg/cm2G 100/38 235 16.5 233 16.4 249 17.5
70/21 50 3.5 51 3.6 53 3.7
80/27 51 3.6 54 3.8 54 3.8 90/32 51 3.6 56 3.9 56 4.0
PSIG kg/cm2G 100/38 51 3.6 56 3.9 57 4.0
TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] WATER FLOW FOR CONDENSER 77 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
2.1
TOTAL HEAT OF REJECTION FROM CONDENSER 10,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
SUCTION PRESSURE
HARVEST CYCLE TIME
HEAD PRESSURE
3.7
3.1
4.1 2.5
31
28
29
31
1036
1044
1055
1060
30 32
33
35
1028
1029
1040
1050
1051
1020
1027
1029
27
APPROXIMATE ICE PRODUCTION PER 24 HR.
APPROXIMATE ELECTRIC CONSUMPTION
APPROXIMATE WATER CONSUMPTION PER 24 HR.
FREEZING CYCLE TIME
WATER TEMP. (ºF/ºC)
AMBIENT TEMP.
(ºF/ºC)
50/10 70/21 90/32
28
28 30
2.7
4.7
3.4
4.1
3.4
2.8
4.3

2. KM-650MWH (water-cooled)

Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
2. We reserve the right to make changes in specifications and design without prior
should be used for reference only.
notice.
29
Page 30

3. KM-650MRH (remote air-cooled)

PERFORMANCE DATA NO. 06A021 ISSUED: 10/10/2006
ITEM: HOSHIZAKI MODULAR CRESCENT CUBER
MODEL: KM-650MRH
70/21 615 279
597 271 556 252
80/27 601 273 574 260 523 237
90/32 597 271 554 251 506 230
lbs./day kg./day 100/38 583 264 543 246 462 210
70/21
80/27
90/32
watts 100/38
70/21 266 1.01
220 0.83 198 0.75
80/27 231 0.87 161 0.61 160 0.61
90/32 220 0.83 111 0.42 100 0.38
gal./day m3/day 100/38 169 0.64 108 0.41 91 0.34
70/21 80/27
90/32
min. 100/38
70/21
80/27 90/32
min. 100/38
70/21 214 15.1
233 16.4 254 17.8
80/27 229 16.1 258 18.2 275 19.4
90/32 233 16.4 279 19.6 298 21.0
PSIG kg/cm2G 100/38 235 16.6 283 19.9 315 22.2
70/21 51 3.6 53 3.8 56 4.0
80/27 53 3.7 56 3.9 59 4.1 90/32 53 3.8 58 4.1 61 4.3
PSIG kg/cm2G 100/38 54 3.8 59 4.2 64 4.5
TOTAL HEAT OF REJECTION FROM COMPRESSOR CONDENSER VOLUME
9400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
1600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] 40 CU. IN (URC-5F)
37
40
4.0
3.8
3.0
3.6
3.0
SUCTION PRESSURE
TOTAL HEAT OF REJECTION FROM CONDENSER
35
31
32
34
HARVEST CYCLE TIME
HEAD PRESSURE
2.0
4.6
1212
1247
1281
13101183
1179
1218
1250
1257
APPROXIMATE ICE PRODUCTION PER 24 HR.
APPROXIMATE ELECTRIC CONSUMPTION
APPROXIMATE WATER CONSUMPTION PER 24 HR.
FREEZING CYCLE TIME
33 36
WATER TEMP. (ºF/ºC)
AMBIENT TEMP.
(ºF/ºC)
50/10 70/21 90/32
1150
1172
1179
29
30
31 33
2.0
2.0
3.8
2.8
2.0
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior notice.
30
Page 31

IV. Service Diagnosis

A. 10-Minute KM Diagnostic Procedure

The 10 minute check out procedure is basically a sequence check which can be used at unit start-up or for system diagnosis. Using this check out procedure will allow you to diagnose electrical system and component failures in approximately 10 minutes under normal operating conditions of 70°F or warmer air and 50°F or warmer water temperatures. Before conducting a 10 minute checkout, check for correct installation, proper voltage per unit nameplate and adequate water supply. As you go through the procedure, check to assure the components energize and de-energize correctly. If not, those components and controls are suspect. Check for voltage at the 10-pin connector.
1) Turn power OFF and access the control box.
2) Turn power ON and place the control switch in ICE position. A 5 second delay occurs.
3) One Minute Fill Cycle – The inlet water valve is energized. After 1 minute, the control board checks the float switch. If the float switch is closed, the unit cycles to harvest. If closed, continue to step 4. If the float switch is open, the unit repeats the 1 minute fill cycle until water enters and the float switch closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: If the water valve does not open, check for no supply voltage at water valve terminals, bad coil, or plugged screen or external filter (no water flow). If unit fails to start harvest, check for open float switch or bad 1 minute timer in board.
4) Initial Harvest Cycle – Inlet water valve remains energized, contactor coil energizes to start the compressor (and fan motor on a remote condenser unit), and the hot gas valve energizes. The evaporator warms and the thermistor senses 48°F (9°C). The control board then receives the thermistor's 3.9 kΩ signal and turns operation of harvest over to the harvest timer. The timer completes counting (1 to 3 minutes). The unit then cycles to freeze. Diagnosis: Check if compressor is running, hot gas valve is open, water valve still open. Average harvest cycle at factory setting is 2 to 3 minutes. How long does initial harvest last? 1.5 minutes after initial harvest begins, touch the compressor discharge line. Is it hot? If not check refrigerant pressures and compressor operation. If it is hot, touch the inlet line to the evaporator. Is it hot? If it is hot and the freeze cycle is not starting, check the harvest timer adjustment, the thermistor for open circuit, the discharge line temperature, compressor efficiency, and if the hot gas valve is fully open.
5) Freeze Cycle – Compressor remains energized, pump motor, (line valve on remote condenser unit), and fan motor energize. The inlet water valve and hot gas valve de-energize. The unit is held in freeze by a 5 minute short cycle protection timer. After 5 minutes, the freeze cycle operation is transferred to the float switch for freeze termination. During the first 5 minutes of freeze, confirm that the evaporator temperature drops. After 7 minutes in freeze, remove the black float switch lead from the K5 connector. The unit should immediately switch to the pump-out cycle. Diagnosis: If the evaporator is not cold, check to see if the hot gas valve is still open or if the expansion valve is not opening properly, if the water valve is continuing to fill the reservoir, if there are improper unit pressures, an inoperative compressor, or an inoperative headmaster (C.P.R.) (remote condenser unit only). If the unit remains in
31
Page 32
freeze with the float switch removed, replace the board. Note: Normal freeze cycle will last 20 to 40 minutes depending on model and
conditions. Cycle times and pressures should follow performance data provided in this manual.
6) Pump-Out Cycle (10/20 second pump out) – the compressor remains energized, the hot gas valve energizes, the fan motor de-energizes, the pump motor stops for 2 seconds and starts in reverse rotation for 10/20 seconds. (This removes contaminants from the water reservoir through the check valve (drain valve) and down the drain and allows for a power flush of the float switch.) Check for clear tubing at the check valve housing and check the unit drain for water flow. Diagnosis: If the pump motor does not reverse, check the circuit and capacitor. If water does not pump out, remove the check valve (drain valve) housing and check/clean the valve assembly.
7) Normal Harvest Cycle – same as the initial harvest cycle – Return to step 4. Note: Unit continues to cycle until bin control is satisfied or power is switched OFF. (The
pump out cycle can be adjusted to occur every cycle, or every 2, 5, or 10 cycles. The factory default is every 10 cycles.) The unit always restarts at the 1 minute fill cycle.

B. Diagnostic Charts

1. No Ice Production

Problem Possible Cause Remedy
[1]
The icemaker will not start.
a)Power Supply 1. OFF position. 1. Move to ON position.
Loose connection. 2. Tighten.
2.
3. Bad contacts. 3. Check for continuity and replace.
4. Voltage too high or too
low.
b)Fuse (Inside fused
disconnect, if any)
c) Control Switch 1. OFF position. 1. Move to ICE position.
d)Bin Control Thermostat 1. Tripped with bin filled
1. Blown. 1. Check for short circuit and
2. Bad contacts. 2. Check for continuity and
with ice.
2. Ambient temperature
too cool.
3. Set too warm. 3. See "II.C.3. Controls
4. Check and get recommended voltage.
replace.
replace.
1. Remove ice.
2. Increase ambient temperature.
and Adjustments, g) Bin Control."
4. Bulb out of position. 4. Place in position.
5. Bad contacts. 5. Check for continuity and replace.
e)High Pressure Control 1. Bad contacts. 1. Check for continuity and
replace.
2. Dirty air filter or
condenser.
2. Clean.
32
Page 33
Problem Possible Cause Remedy
[1]
The icemaker will not start. (continued)
e)High Pressure Control
(continued)
3. Ambient or condenser water temperature too warm.
4. Refrigerant overcharged.
5. Fan not operating. (except water-cooled model)
3. Reduce temperature.
4. Recharge.
5. See chart 1.[6]
6. Refrigerant line or components plugged.
7. Condenser water pressure too low or off. (water-cooled model only)
f) Transformer 1. Coil winding opened
or shorted.
g)Wiring to Control Board 1. Loose connections or
open.
h)Thermistor 1. Leads shorted or
opened and high temperature or harvest backup timer safety operates. (1 beep or 2 beep alarm)
i) Hot Gas Valve 1. Continues to open
in freeze cycle and freeze timer safety operates. (3 beep alarm)
j) Water Supply Line 1. Water supply off and
water supply cycle does not finish.
2. Condenser water pressure too low or off and pressure control opens and closes frequently to finally operate high temperature safety. (1 beep alarm)
k) Inlet Water Valve 1. Mesh filter or orifice
gets clogged and water supply cycle does not finish.
Coil winding opened. 2. Replace.
2.
3. Wiring to water valve. 3. Check for loose
l) Control Board 1. Defective. 1. See "II.C.4. Control Board
6. Clean and replace drier.
7. Check and get recommended pressure.
1. Replace.
1. Check for continuity and replace.
1. See "II.C.3. Controls and Adjustments, b) Harvest Control."
1. Check for hot gas valve stuck open and replace.
1. Check and get recommended pressure.
2. Check and get recommended pressure.
1. Clean.
connection or open, and replace.
Check Procedure."
33
Page 34
Problem Possible Cause Remedy
[1]
The icemaker will not start. (continued)
Water continues to
[2]
be supplied, and the icemaker will not start.
[3] Compressor will
not start or stops operating.
m)Interlock Switch
(Cleaning Valve)
n)Wash Switch 1. WASH position. 1. Move to ICE position.
a)Float Switch 1. Connector
b)Control Board 1. Defective. 1. Replace.
a)Magnetic Contactor 1. Bad contacts. 1. Check for continuity and
b)Start Capacitor or Run
Capacitor
c) Internal Overload
Protector Open (check 1 through 3 to the right and d through f below)
1. OFF position. 1. Move to ON position.
Bad contacts. 2. Check for continuity and
2. replace.
2. Bad contacts. 2. Check and replace.
1. Place in position.
disconnected.
Leads opened or
2.
defective switch.
3. Float does not move
freely.
Coil winding opened. 2. Replace.
2.
1. Defective. 1. Replace.
1. Loose terminal. 1. Tighten or replace.
2. Voltage. 2. Check and correct.
3. Dirty condenser. 3. Clean.
2. Check and replace.
3. Clean or replace.
replace.
[4] Water continues to
be supplied in freeze cycle.
[5] No water comes from
spray tubes. Water pump will not start, or freeze cycle time is too short.
d)Starter 1. Bad contacts. 1. Check and replace.
2. Coil winding opened. 2. Replace.
e)Compressor 1. Wiring to compressor. 1. Check for loose
connection or open, and replace.
Defective. 2. Replace.
2.
3. Protector tripped. 3. Reduce temperature.
f) Control Board 1. No power to contactor. 1. See "II.C.4. Control Board
Check Procedure."
a)Inlet Water Valve 1. Diaphragm does not
close.
b)Control Board 1. Defective. 1. See "II.C.4. Control Board
a)Water Supply Line 1. Water pressure too
low and water level in water tank too low.
b)Inlet Water Valve 1. Dirty mesh filter or
orifice and water level in water tank too low.
c) Water System 1. Water leaks. 1. Check connections for
1. Check for water leaks with icemaker off.
Check Procedure."
1. Check and get recommended pressure.
1. Clean.
water leaks, and replace.
34
Page 35
Problem Possible Cause Remedy
[5] No water comes from
spray tubes. Water pump will not start, or freeze cycle time is too short. (continued)
[6] Fan motor will
not start, or is not operating.
[7] All components
run, but no ice is produced.
c) Water System
(continued)
d)Pump Motor 1. Motor winding opened. 1. Replace.
e)Control Board 1. Defective. 1. See "II.C.4. Control Board
a)Fan Motor 1. Motor winding opened. 1. Replace.
b)Control Board 1. Defective. 1. See "II.C.4. Control Board
a)Refrigerant 1. Undercharged. 1. Check for leaks and
b)Compressor 1. Defective valve. 1. Replace.
c) Hot Gas Valve 1. Continues to open in
d)Line Valve 1. Continues to close in
e)Inlet Water Valve 1. Water valve is wide
2. Clogged. 2. Clean.
3. Pump out check valve leaking by.
2. Bearing worn out. 2. Replace.
3. Wiring to pump motor. 3. Check for loose
4. Defective capacitor. 4. Replace.
5. Defective or bound impeller.
6. Mechanical seal worn out.
2. Bearing worn out. 2. Replace.
3. Wiring to fan motor. 3. Check for loose
4. Defective capacitor. 4. Replace.
5. Fan blade bound. 5. Check and replace.
Air or moisture
2. trapped.
freeze cycle.
freeze cycle.
open during freeze.
3. Check assembly and clean.
connection or open, and replace.
5. Replace and clean.
6. Check and replace.
Check Procedure."
connection or open, and replace.
Check Procedure."
recharge.
2. Replace drier and recharge.
1. Check and replace.
1. Check and replace.
1. Check for water leaks with icemaker off.
f) Headmaster (C.P.R.)
(Remote Unit)
g)Water Supply Line
(water-cooled model only)
h)Water Regulator
(water-cooled model only)
1. Not operating properly and liquid line temperature too warm.
1. Condenser water pressure too low or off and pressure control opens and closes frequently.
1. Set too high. 1. Adjust or replace. See
1. Replace headmaster.
1. Check and get recommended pressure.
"V.I. Adjustment of Water Regulating Valve."
35
Page 36

2. Evaporator is Frozen Up

Problem Possible Cause Remedy
Freeze cycle time is
[1]
too long.
[2]All ice formed on
evaporator does not fall into bin in harvest cycle.
a)Float Switch 1. Leads short-circuit or
defective switch.
2. Float does not move freely.
b)Inlet Water Valve 1. Diaphragm does not
close.
c) Control Board 1. Defective. 1. See "II.C.4. Control Board
a)Evaporator 1. Scaled up. 1. Clean.
b)Water Supply Line 1. Water pressure too
low.
c) Water Filter System 1. Dirty/Restricted 1. Replace filter.
d)Inlet Water Valve 1. Dirty mesh filter or
orifice.
2. Diaphragm does not close.
e) Ambient and/or water
temperature.
f) Line Valve 1. Continues to open in
1. Too cool. 1. Increase temperature.
harvest cycle.
1. Check and replace.
2. Clean or replace.
1. Check for water leaks with icemaker off.
Check Procedure."
1. Check and get recommended pressure.
1. Clean.
2. Check for water leaks with icemaker off.
1. Check operation in harvest cycle and replace.
g)Thermistor 1. Out of position or
loose attachment.
h)Control Board 1. Harvest timer is set
too short.
Defective. 2. See "II.C.4. Control Board
2.
[3]Other a)Spray Tubes 1. Clogged. 1. Clean
Out of position. 2. Place in position.
2.
b)Water System 1. Dirty. 1. Clean.
c) Refrigerant 1. Undercharged. 1. Check for leaks and
d)Expansion Valve 1. Bulb out of position or
loose attachment.
2. Defective. 2. Replace.
e)Hot Gas Valve 1. Coil winding opened. 1. Replace.
Plunger does not
2. move.
3. Wiring to hot gas valve.
f) Ice Cube Guide 1. Out of position and ice
trapped.
1. See "V.I. Removal and Replacement of Thermistor."
1. Adjust longer, referring to "II.C.3. Controls and Adjustments, c) Harvest Timer.
Check Procedure."
recharge.
1. Place in position.
2. Replace.
3. Check for loose connection or open, and replace.
1. Place in position.
36
Page 37
Problem Possible Cause Remedy
[3]Other (continued) g) Water Supply Line 1. Too small; requires
3/8" OD line dedicated per machine.
h)Water Filter 1. Flow rate too small. 1. Replace with filter that has
1. Increase water line size.
larger flow rate.

3. Low Ice Production

Problem Possible Cause Remedy
[1] Freeze cycle time is
long.
[2] Harvest cycle time is
long.
a) See chart 1.[3] and check dirty air filter or condenser, ambient or water
temperature, water pressure, condenser water regulating valve (water-cooled model), and refrigerant charge.
b) See chart 2.[1] and check float switch, inlet water valve and control board.
c) Check pump, hot gas valve, headmaster (C.P.R.) (remote air-cooled model),
expansion valve, refrigeration check valve, and compressor.
a) See chart 2.[2] and check control board, thermistor, evaporator, ambient and/or
water temperature, water supply line, inlet water valve, line valve, and gas valve.

4. Abnormal Ice

Problem Possible Cause Remedy
[1] Small cubes. a) Ice Cube Guide 1. Out of position.
Circulated water falls into bin.
b) See chart 1.[5] and check water supply line, inlet water valve, water system,
pump motor, and control board.
c) Pump Out Check Valve 1. Dirty. 1. Clean.
1. Place in position.
Cloudy or irregular
[2]
cubes.
a) See chart 2.[1] and 2.[3], and check float switch, inlet water valve, control
board, spray tubes, water system, refrigerant charge, and expansion valve.
b) Spray Guide 1. Dirty. 1. Clean.
c) Water Quality 1. High hardness or
contains impurities.
1. Install a water softener or filter.

5. Other

Problem Possible Cause Remedy
[1] Icemaker will not stop
when bin is filled with ice.
[2] Abnormal noise. a)Pump Motor 1. Bearings worn out. 1. Replace
a) Bin Control Thermostat 1. Set too cold. 1. Adjust warmer.
2. Defective. 2. Replace
b) Fan Motor 1. Bearings worn out. 1. Replace
2. Fan blade deformed. 2. Replace fan blade.
3. Fan blade does not move freely.
c) Compressor 1. Bearings worn out or
cylinder valve broken.
3. Replace.
1. Replace.
37
Page 38
Problem Possible Cause Remedy
[2] Abnormal noise.
(continued)
c) Compressor
(continued)
2. Mounting pad out of position.
2. Reinstall.
[3] Ice in storage bin
often melts.
d) Refrigerant Lines 1. Rub or touch other
lines or surfaces.
a) Drain Line(s) 1. Plugged. 1. Clean.
b) Icemaker and Bin 1. Drains not run
separately.
c) Ice Cube Guide 1. Out of position.
Circulated water falls into bin.
1. Replace.
1. Separate the drain lines.
1. Place in position.
38
Page 39

V. Removal and Replacement of Components

IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place after the equipment is serviced.
IMPORTANT
1. The Polyol Ester (POE) oils used in R-404A units can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts.
2. Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.
3. Do not leave the system open for longer than 15 minutes when replacing or servicing parts.

A. Service for Refrigerant Lines

1. Refrigerant Recovery

The icemaker unit is provided with refrigerant access valves. Using proper refrigerant practices recover the refrigerant from the access valves and store it in an approved container. Do not discharge the refrigerant into the atmosphere.

2. Evacuation and Recharge (R-404A)

1) Attach service manifold hoses and a vacuum pump to the system. Be sure to connect charging hoses to both high and low-side access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Never allow the oil in the vacuum pump to flow backward.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity.
4) Close the low-side valve and high-side valve on the service manifold.
5) Disconnect the vacuum pump and attach a refrigerant service cylinder to the high-side line. Remember to loosen the connection and purge the air from the hose. For air-cooled and water-cooled models, see the nameplate for the required refrigerant charge. For remote air-cooled models, see the charge label in the machine compartment. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard No. 700-88 be used.
39
Page 40
6) A liquid charge is recommended for charging an R-404A system. Invert the service cylinder and place it on scales. Open the high-side, service manifold valve.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side. Use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side access port with the unit running.
9) Close the two refrigerant access valves, and disconnect the service manifold hoses.
10) Cap the access valves to prevent a possible leak.

B. Brazing

DANGER
1. Refrigerant R-404A itself is not flammable at atmospheric pressure and temperatures up to 176°F (80°C).
2. Refrigerant R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open flames) R-404A can be decomposed to form hydrofluoric acid and carbonyl fluoride both of which are hazardous.
3. Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
4. Do not use silver alloy or copper alloy containing arsenic.
5. Do not use R-404A as a mixture with pressurized air for leak testing. Refrigerant leaks can be detected by charging the unit with a little refrigerant, raising the pressure with nitrogen and using an electronic leak detector.
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If it is necessary to braxe inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.

C. Removal and Replacement of Compressor

IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.
Note: When replacing a compressor with a defective winding, be sure to install the
new start capacitor and start relay supplied with the replacement compressor. Due to the ability of the POE oil in the compressor to absorb moisture quickly, the compressor must not be opened more than 15 minutes for replacement or service. Do not mix lubricants of different compressors even if both are charged with R-404A, except when they use the same lubricant.
1) Turn off the power supply.
40
Page 41
2) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the terminal cover on the compressor and disconnect the compressor wiring.
5) Remove the hold-down bolts, washers and rubber grommets.
6) Remove the discharge and suction pipes.
7) Remove the compressor. Unpack the new compressor package.
8) Attach the rubber grommets of the prior compressor.
9) Place the compressor in position and secure it using the bolts and washers.
10) Remove the drier, then place the new drier in position.
11) Remove the plugs from the suction, discharge and process pipes.
12) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
13) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
14) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled models, see the nameplate for the required refrigerant charge. For remote air-cooled models, see the charge label in the machine compartment.
15) Connect the terminals and replace the terminal cover in its correct position.
16) Replace the panels in their correct positions.
17) Turn on the power supply.

D. Removal and Replacement of Drier

IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.
1) Turn off the power supply.
2) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the drier, then place the new drier in position. Install the new drier with the arrow on the drier in the direction of the refrigerant flow.
5) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
6) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
7) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled models, see the nameplate for the required refrigerant charge. For remote air-cooled models, see the charge label in the machine compartment.
8) Replace the panels in their correct positions.
9) Turn on the power supply.
41
Page 42

E. Removal and Replacement of Expansion Valve

IMPORTANT
Sometimes moisture in the refrigeration circuit exceeds the drier capacity and freezes up at the expansion valve. Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.
1) Turn off the power supply.
2) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the insulation and the expansion valve bulb on the suction line.
5) Remove the expansion valve cover and disconnect the expansion valve. Place the new expansion valve in position.
6) Remove the drier, then place the new drier in position.
7) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve from overheating. Do not braze with the valve body exceeding 250°F (121°C).
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled models, see the nameplate for the required refrigerant charge. For remote air-cooled models, see the charge label in the machine compartment.
10) Attach the expansion valve bulb to the suction line in the same location as the previous bulb. The bulb should be at the 12 o'clock position on the tube. Be sure to secure the bulb with the clamp and holder and to insulate it.
11) Place the expansion valve cover in position.
12) Replace the panels in their correct positions.
13) Turn on the power supply.
42
Page 43

F. Removal and Replacement of Hot Gas Valve and Line Valve

IMPORTANT
1. Always use a copper tube of the same diameter and length when replacing the hot gas lines; otherwise the performance may be reduced.
2. Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement has been made.
3. Always replace the strainer when replacing the hot gas valve.
1) Turn off the power supply.
2) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the screw and the solenoid.
5) Disconnect the hot gas valve or line valve. Remove the strainer.
6) Place the new valve and strainer in position.
7) Remove the drier, then place the new drier in position.
8) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
CAUTION
Always protect the valve body by using a damp cloth to prevent the valve from overheating. Do not braze with the valve body exceeding 250°F (121°C).
9) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
10) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled models, see the nameplate for the required refrigerant charge. For remote air-cooled models, see the charge label in the machine compartment.
11) Cut the leads of the solenoid allowing enough lead length to reconnect using closed end connectors.
12) Connect the new solenoid leads.
13) Attach the solenoid to the valve body and secure it with a screw.
14) Replace the panels in their correct positions.
15) Turn on the power supply.
43
Page 44

G. Removal and Replacement of Evaporator

IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repairs or replacement have been made.
1) Turn off the power supply.
2) Remove the panels and the top insulation over the evaporator.
3) Recover the refrigerant and store it in an approved container.
4) Remove the spray tubes and the insulations at the "U" shaped notch where the refrigeration tubings pass through the molded chassis.
5) Disconnect the evaporator tubing.
6) Remove the pop rivets securing the evaporator, lift out the evaporator.
7) Install the new evaporator.
8) Remove the drier, then place the new drier in position.
9) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
10) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
11) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled models, see the nameplate for the required refrigerant charge. For remote air-cooled models, see the charge label in the machine compartment.
12) Replace the removed parts in the reverse order of which they were removed.
13) Replace the top insulation and the panels in their correct positions.
14) Turn on the power supply.
H. Removal and Replacement of Water Regulating Valve -
Water Cooled Model Only
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.
1) Turn off the power supply.
2) Close the water supply line shut-off valve.
3) Remove the panels.
4) Recover the refrigerant and store it in an approved container.
5) Disconnect the capillary tube at the condenser outlet.
6) Disconnect the flare-connections of the valve.
44
Page 45
7) Remove the screws and the valve from the bracket.
8) Install the new valve.
9) Remove the drier, then place the new drier in position.
10) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
11) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
12) Evacuate the system, and charge it with refrigerant. See the nameplate for the required refrigerant charge.
13) Connect the flare-connections.
14) Open the water supply line shut-off valve.
15) Check for water leaks.
16) Replace the panels in their correct positions.
17) Turn on the power supply.

I. Adjustment of Water Regulating Valve - Water-Cooled Model Only

The water regulating valve (also called "water regulator") is factory-adjusted. No adjustment is required under normal use. Adjust the water regulator, if necessary, using the following procedures.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure gauge to the high-side line of the system.
2) Five minutes after a freeze cycle starts, confirm that the thermometer reads 104°F to 115°F (40°C to 46°C). If it does not, rotate the adjustment screw by using a flat blade screwdriver until the temperature is in the proper range. See Fig. 1. Next, check that the reference pressure is in the range indicated in the Head Pressure table in the Performance Data section. If it is not in the proper range, verify the refrigerant charge.
3) Check that the condenser drain temperature is stable.
Adjustment Screw
CW – Higher CCW – Lower
Top View
Fig. 1
45
Page 46
J. Removal and Replacement of Headmaster (Condensing Pressure
Regulator - C.P.R.) - Remote Air-Cooled Model Only
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.
1) Turn off the power supply.
2) Remove the panels from the remote condenser unit.
3) Recover the refrigerant and store it in an approved container.
4) Before heating, break off the stub on the dome to release the dome charge.
5) Disconnect the headmaster.
6) Place the new headmaster in position.
7) Remove the drier, then place the new drier in position.
8) Braze all fittings with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
CAUTION
Always protect the headmaster body by using a damp cloth to prevent it from overheating. Do not braze with the headmaster body exceeding 250°F (121°C).
9) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
10) Evacuate the system and charge it with refrigerant. See the charge label in the machine compartment for the required refrigerant charge.
11) Replace the panels in their correct positions.
12) Turn on the power supply.
46
Page 47

K. Removal and Replacement of Thermistor

IMPORTANT
1. Fragile, handle very carefully.
2. Always use a recommended sealant (High Thermal Conductive Type), Model KE4560RTV manufactured by SHINETSU SILICONE, Part Code 60Y000­11, or Part Code 4A0683-01 equivalent.
3. Always use a recommended foam insulation (Non-absorbent Type) or equivalent.
4. Do not shorten or cut the thermistor leads when installing.
1) Turn off the power supply.
2) Remove the panels.
3) Remove the control box cover.
4) Disconnect the thermistor leads from the K3 connector on the control board.
5) Remove the plastic cable ties, foam insulation, thermistor holder and thermistor. See Fig. 2.
Thermistor Lead Cable Tie
6) Scrape away the old sealant on the thermistor holder and the suction pipe.
Foam Insulation Thermistor Holder
Fig. 2
7) Wipe off moisture or condensation on the suction pipe.
8) Smoothly apply recommended sealant (KE4560RTV, Part Code 60Y000-11 or 4A0683-01) to the thermistor holder concave.
9) Attach the new thermistor to the suction pipe in the same position as the previous thermistor. Be very careful to prevent damage to the leads. Secure it using the thermistor holder and recommended foam insulation.
10) Secure the insulation using the plastic cable ties.
11) Connect the thermistor leads through the bushing of the control box to the K3 connector on the control board. Note: Do not cut the leads of the thermistor while installing it.
12) Replace the control box cover and the panels in their correct positions.
13) Turn on the power supply.

L. Removal and Replacement of Fan Motor

Note: When replacing a fan motor with defective winding, it is recommended that a new
capacitor be installed.
1) Turn off the power supply.
2) Remove the panels.
47
Page 48
3) Remove the junction box cover from the remote condenser unit (remote air-cooled model).
4) Remove the closed end connectors from the fan motor leads.
5) Remove the fan motor bracket and fan motor.
6) Install the new fan motor and replace the removed parts in the reverse order of which they were removed.
7) Replace the panels in their correct positions.
8) Replace the junction box cover in its correct position (remote air-cooled model).
9) Turn on the power supply.

M. Removal and Replacement of Inlet Water Valve

1) Turn off the power supply.
2) Close the water supply line shut-off valve.
3) Remove the front panel.
4) Remove the valve outlet tubing by releasing the clamp.
5) Loosen the fitting nut. Be careful not to lose the washer.
6) Disconnect the terminals from the water valve.
7) Remove bracket and valve from the unit.
8) Remove the valve from the bracket. Attach new valve to the bracket, then install the valve.
9) Replace the removed parts in the reverse order of which they were removed. Make sure the washer is in place in the fitting nut.
10) Open the water supply line shut-off valve.
11) Turn on the power supply.
12) Check for leaks.
13) Replace the front panel in its correct position.

N. Removal and Replacement of Pump Motor

1) Turn off the power supply.
2) Remove the front panel.
3) Remove the base cover.
4) Drain the water tank by removing one end of the pump tubing. See Fig. 3.
5) Replace the removed parts in their correct positions.
6) Disconnect the pump suction and discharge hoses.
7) Remove the closed end connectors from the pump motor leads.
8) Remove the screw attaching the pump motor assembly to the base, then remove the pump motor assembly.
48
Fig. 3
Page 49
9) Remove the screw attaching the pump motor to the pump motor bracket.
10) Remove the screws attaching the pump housing to the pump motor. Remove the housing and check the impeller.
11) If the impeller is defective, install a new impeller.
12) Install the new motor or new parts, and replace the removed parts in the reverse order of which they were removed.
13) Turn on the power supply and check for leaks.
14) Replace the base cover in its correct position.
15) Replace the front panel in its correct position.

O. Removal and Replacement of Spray Tubes

1) Turn off the power supply.
2) Remove the front panel and the insulation panel.
3) Remove the rubber hoses from the spray tubes (water supply pipe).
4) Release the clamps and disconnect the rubber hoses.
5) Remove the spray tubes.
6) Install the new spray tubes, and replace the removed parts in the reverse order of which they were removed.
7) Replace the panels in their correct positions.
8) Turn on the power supply.
49
Page 50

VI. Cleaning and Maintenance Instructions

IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place after any maintenance or cleaning is done to the equipment.

A. Cleaning and Sanitizing Procedures

WARNING
1. HOSHIZAKI recommends cleaning this unit at least once a year. More frequent cleaning, however, may be required in some existing water conditions.
2. To prevent injury to individuals and damage to the icemaker, do not use ammonia type cleaners.
3. Always wear liquid-proof gloves to prevent the cleaning and sanitizing solutions from coming into contact with skin.
IMPORTANT
1. The cleaning valve is used to allow solution flow to the inside of the evaporator during the cleaning and sanitizing operation. It should be closed for all icemaking operation. The compressor will not operate unless this valve is completely closed.
2. To open the cleaning valve, the valve handle should be parallel to the valve body. To close the valve, the valve handle should be at a right angle to the valve body.
50
Page 51

1. Cleaning Procedure

1) Dilute approximately 16 fl. oz. of the recommended cleaner Hoshizaki "Scale Away" or "LIME-A-WAY" (Economics Laboratory, Inc.) with 3 gal. (11 l) of water.
2) Remove all ice from the evaporator and the storage bin. Note: To remove cubes on the evaporator, turn off the power supply and turn it on
after 3 minutes. The harvest cycle starts and the cubes will be removed from the evaporator.
3) Turn off the power supply.
4) Remove the front panel and the base cover, and then remove the insulation panel by lifting up the panel slightly and pulling it towards you.
5) Remove one end of the pump tubing (see Fig. 4). Drain the water tank. Replace the pump tubing in its correct position.
6) In bad or severe water conditions, clean the float switch assembly as described below. Otherwise, continue to step 7.
a. Remove the float switch assembly from the mounting bracket and remove the
rubber boot from the bottom of the assembly.
b. Remove the retainer rod from the bottom of the float switch assembly, then remove
the float. Be careful not to bend the retainer rod excessively when removing it.
c. Wipe down the float switch assembly's housing, shaft, float, and retainer rod with
cleaning solution. Wipe the inside of the rubber boot with cleaning solution.
d. Reassemble the float switch assembly and replace it and the rubber boot in their
correct positions.
Fig. 4
7) Pour the cleaning solution into the water tank.
8) Fully open the cleaning valve on the left side wall of the machine compartment.
9) Move the control switch on the control box to the "WASH" position.
10) Replace the insulation panel and the front panel in their correct positions.
11) Turn on the power supply and start the washing process.
12) Turn off the power supply after 30 minutes.
13) Remove the front panel.
14) Remove one end of the pump tubing. Drain the water tank. Replace the pump tubing in its correct position.
15) Move the control switch to the "ICE" position.
16) Close the cleaning valve. Note: The icemaker will not operate unless the cleaning valve is completely closed.
17) Replace the front panel in its correct position.
18) Turn on the power supply to fill the water tank with water.
19) Turn off the power supply after 3 minutes.
51
Page 52
20) Remove the front panel and fully open the cleaning valve.
21) Move the control switch to the "WASH" position.
22) Replace the front panel in its correct position.
23) Turn on the power supply to rinse off the cleaning solution.
24) Turn off the power supply after 5 minutes.
25) Remove the front panel.
26) Remove one end of the pump tubing. Drain the water tank. Replace the pump tubing in its correct position.
27) Repeat steps 15 through 26 three more times to rinse thoroughly. Note: If you do not sanitize the icemaker, go to step 10 in "2. Sanitizing Procedure."

2. Sanitizing Procedure - Following Cleaning Procedure

1) Dilute a 5.25% sodium hypochlorite solution (chlorine bleach) with water (add 1.5 fl. oz. of sanitizer to 3 gal. of water).
2) Remove the insulation panel.
3) Pour the sanitizing solution into the water tank.
4) Replace the insulation panel and the front panel in their correct positions. Note: Make sure that the control switch is in the "WASH" position and the cleaning valve
is open.
5) Turn on the power supply, and start the sanitizing process.
6) Turn off the power supply after 15 minutes.
7) Remove the front panel.
8) Remove one end of the pump tubing. Drain the water tank. Replace the pump tubing in its correct position.
9) Repeat steps 15 through 26 in "1. Cleaning Procedure" two times to rinse thoroughly.
10) Close the cleaning valve.
11) Move the control switch to the "ICE" position.
12) Replace the front panel and the base cover in their correct positions.
13) Clean the storage bin with water.
14) Turn on the power supply, and start the automatic icemaking process.

B. Maintenance

IMPORTANT
This icemaker must be maintained individually, referring to the instruction manual and labels provided with the icemaker.
1. Stainless Steel Exterior
To prevent corrosion, wipe the exterior occasionally with a clean and soft cloth. Use a
52
Page 53
damp cloth containing a neutral cleaner to wipe off oil or dirt build up.
2. Storage Bin and Scoop
• Wash your hands before removing ice. Use the plastic scoop provided (bin accessory).
• The storage bin is for ice use only. Do not store anything else in the bin.
• Keep the scoop clean. Clean it by using a neutral cleaner and rinse thoroughly.
• Clean the bin liner by using a neutral cleaner. Rinse thoroughly after cleaning.
3. Air Filters (air-cooled models only)
The plastic mesh air filters located behind the louvers remove dirt or dust from the air, and keep the condenser from getting clogged. As the filters get clogged, the icemaker’s performance will be reduced. Check the filters at least twice a month. When they are clogged, use warm water and a neutral cleaner to wash the filters.
4. Condenser (air-cooled and remote air-cooled models only)
Check the condenser once a year, and clean if required by using a brush or vacuum cleaner. More frequent cleaning may be required depending on the location of the icemaker or condenser unit.

C. Preparing the Icemaker for Long Storage

WARNING
When shutting off the icemaker for an extended time, drain out all water from the water tank and remove the ice from the storage bin. The storage bin should be cleaned and dried. Drain the icemaker to prevent damage to the water supply line at subfreezing temperatures, using air or carbon dioxide. Shut off the icemaker until the proper ambient temperature is resumed.
When the icemaker is not used for two or three days, it is sufficient to only move the control switch to the "OFF" position, unless the icemaker will be at subfreezing temperatures.
1. On water-cooled model only, first remove the water from the water-cooled condenser:
1) Remove the front panel.
2) Move the control switch on the control box to the "OFF" position.
3) Wait 3 minutes.
4) Move the control switch to the "ICE" position.
5) Allow 5 minutes for the icemaker to fill with water and the water pump to start operating.
6) Close the water-cooled condenser water supply line shut-off valve.
7) Open the drain valve for the water-cooled condenser water supply line.
8) Allow the line to drain by gravity.
9) Quickly attach compressed air or carbon dioxide supply to the condenser water line drain valve.
53
Page 54
10) Blow the water-cooled condenser out, using compressed air or carbon dioxide until water stops coming out.
2. Drain the potable water supply line:
1) Remove the front panel.
2) Move the control switch on the control box to the "OFF" position.
3) Wait 3 minutes.
4) Close the potable water supply line shut-off valve and open the potable water supply line drain valve.
5) Allow the line to drain by gravity.
6) Attach compressed air or carbon dioxide supply to the potable water line drain valve.
7) Move the control switch to the "ICE" position.
8) Blow the potable water line out using compressed air or carbon dioxide.
3. Drain the potable water tank:
1) Turn off the power supply.
2) Move the control switch to the "OFF" position.
3) Remove the front panel and the base cover, and then remove the insulation panel by lifting up the panel slightly and pulling it towards you.
5) Remove one end of the pump tubing (see Fig. 5). Drain the water tank. Replace the pump tubing in its correct position.
5) Remove all ice from the storage bin, and clean the storage bin.
7) Replace the front panel in its correct position.
8) Close the drain valve.
Fig. 5
54
Loading...