Only qualified service technicians should attempt to service or maintain this icemaker.
No service or maintenance should be undertaken until the technician has thoroughly
read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call or write to the HOSHIZAKI Technical Support Depar tment for
assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: HOSHIZAKI Technical Support Department
Phone: 1-800-233-1940 Technical Service
(770) 487-2331
Fax:(770) 487-3360
NOTE: To expedite assistance, all correspondence/communication MUST include the following
information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
2
• Please review this manual. It should be read carefully before the icemaker is serviced or
maintenance operations performed. Only qualified service technicians should service and
maintain the icemaker. This manual should be made available to the technician prior to
service or maintenance.
CONTENTS
I. SPECIFICATIONS............................................................................................................ 5
AC SUP P LY VOLTAGE208-230/60/1 (3 wire wit h neut ral for 115V)
AM P E RA GE7.5 A ( 5 Mi n. Freeze A T 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs . /day ( k g/ day )70*600 (272)562 (255)514 (233)
Reference wi t hout * marks80571 (259)512 (232)466 (211)
90562 (255)* 470 (213)422 (191)
100554 (251)459 (208)378 (171)
SHAPE OF ICECresc ent Cube
ICE PRODUCTION PER CYCLE14.3 lbs. (6. 5 k g) 720 pc s.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs .)1332 (6.8)1250 (5.0)
WATER gal./ 24HR (gal./100 lbs. )157 (33.4)341 (56. 9)
EXTERIOR DIMENS IONS (WxDx H)22" x 27-1/ 2" x 37-1/2" (560 x 695 x 950 mm )
EXTERIOR FINISHSt ai nless Steel, Gal vanized Steel (Rear)
WEIGHTNet 154 lbs . ( 70 kg ), S hi ppi ng 185 lbs. (84 kg)
CONNECTIONS - ELE CTRICPermanent - Connec t i on
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
3/8" OD P i pe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAK ING W ATER CONTROLTimer Cont roll ed. Overfl ow P i pe
COOLING WA TE R CO NTROLN/A
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic , Model RS64C1E-CAV
CONDENSERAir-c ool ed, F i n and t ube t ype
EV A PORATORV ert i cal type, S t ai nl ess S teel and Copper
REFRIGERANT CONTROLThermos tatic Expansion V al ve
REFRIGERANT CHARGER-404A,1 lb. 7.6 oz. ( 670 g )
DESIGN PRE S SUREHigh 467 PS IG, Low 230 PSIG
P.C. BOA RD CIRCUIT PRO TE CTIONHigh V olta ge Cut-out ( Int er nal )
COMPRESSOR PROTECTIONAuto-reset Overload P rotector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW W ATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior notice.
5
2a. KM-630MWH Serial #L00001D - M20270B
AC SUPPLY VOLTAGE
AMPERAGE
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PE R 24 HR.Temp.(°F)5070
lbs . /day ( k g/ day )70*619 (281)596 (270)
Referenc e wit hout *marks80602 (273)566 (257)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE14.3 lbs. (6. 5 k g) 720 pc s.
APPROXIMATE STORAGE CAPACITYN/A
ELE CTRIC & WATER CONSUMP TION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1306 (5.7)1290 (5.0)
WATER gal./ 24HR (gal./100 lbs.)196 (36.3)335 (54.1)
WATER COOLED CONDENSER844 (156)458 (74)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENS IONS (W xDxH)22" x 27-1/ 2" x 37-1/2" (560 x 695 x 950 mm )
EXTERIOR FINISHSt ai nless Steel, G alvanized Steel (Rear)
WEIGHTNet 154 lbs . ( 70 kg ), Shipping 185 lbs . (84 kg)
CONNECTIONS - ELE CTRICPermanent - Connec t i on
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
CUBE CONTROL SYSTEMFloat Switc h
HARVESTING CONTROL SYSTE MHot Gas and Wat er, Thermistor and Timer
ICE MAK ING W ATER CONTROLTimer Cont roll ed. Overflow Pi pe
COOLING WA TE R CO NTROLN/A
BIN CO NTROL SYSTEMPro xim ity S witch wi th Del ay
COMPRE SSO RHermet ic, Mo de l RS64C1E-CA V
CONDENSERWater-cooled, Tube in tube t ype
EV A PORATORV ert i cal type, S tainles s St eel and Copper
REFRIGERA NT CONTROLThermostatic Ex pansion Valve
REFRIGERA NT CHARGER-404A,1 lb. 3 oz. ( 525 g )
DESIGN PRESSUREHigh 427 PSIG, Low 230 PSIG
P.C. BOA RD CIRCUIT PRO TE CTIONHi g h Vol tage Cut-out ( Int ern al )
COMPRE S SOR PROTECTIONA uto-reset Overload Protector ( Internal )
REF R IGERANT CIRCUIT PROTE CTIONAut o -re set High P re ss ur e Co ntrol Switch
LOW W ATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin
OP ERATING CON DITIONSVO LTA G E RANG E
208-230/60/1 (3 wire wit h neut ral for 115V)
6.5 A ( 5 M in. Freeze A T 104°F / WT 80°F)
15 A
15 A
90596 (270)*541 (245)
100589 (267)533 (242)
Condenser Inlet 1/ 2" F P T
Condenser Outl et 3/8" FP T
3/8" OD P i pe
AMBIENT TEMP.
WATER SUPPLY TEMP.
WATER SUPPLY PRESSURE
90
563 (256)
533 (242)
507 (230)
476 (216)
187 - 253 V
45 -100° F
45 - 90° F
10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior notice.
6
2b. KM-630MWH Serial #M20301E -
AC SUP P LY VOLTAGE208-230/60/1 (3 wire wit h neut ral for 115V)
AM P E RA GE6.5 A ( 5 Mi n. Freeze A T 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
APPROXIMATE ICE PRODUCTIONAmbientWA TER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs . /day ( k g/ day )70*621 (282)603 (273)563 (256)
Reference wi t hout * marks80607 (275)578 (262)532 (241)
90603 (273)* 558 (253)514 (233)
100590 (268)548 (248)473 (215)
SHAPE OF ICECresc ent Cube
ICE PRODUCTION PER CYCLE14.3 lbs. (6.5 kg) 720 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs .)1279 (5.5)1268 (4.9)
WATER gal./ 24HR (gal./100 lbs. )156 (27.9)299 (48.1)
WATER COOLED CONDENSER536 (96)354 (57)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENS IONS (W xDxH)22" x 27-1/ 2" x 37-1/2" (560 x 695 x 950 mm)
EXTERIOR FINISHSt ai nless Steel, Gal vanized Steel (Rear)
WEIGHTNet 154 lbs . ( 70 kg ), Shi ppi ng 185 lbs. (84 kg)
CONNECTIONS - ELE CTRICPermanent - Connec t i on
- WA TER S UPPLYInlet 1/2" FPTCondenser Inlet 1/2" FPT
- DRAINOutl et 3/ 4" FPTCondenser Outl et 3/8" FP T
3/8" OD P i pe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAK ING W ATER CONTROLTimer Controlled. O verfl ow P i pe
COOLING WA TE R CO NTROLPre ss ur e Re g ul a tor
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic , Model RS64C2E-CAV-219
CONDENSERWater-cooled, Tube in tube t ype
EV A PORATORV ert i cal type, S t ai nl ess S teel and Copper
REFRIGERANT CONTROLThermos tatic Ex pansion Valve
REFRIGERANT CHARGER-404A,1 lb. 4.3 oz. ( 575 g )
DESIGN PRE S SUREHigh 427 PSIG, Low 230 PSIG
P.C. BOA RD CIRCUIT PRO TE CTIONHi g h Voltage Cu t-out ( Inte rn al )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Int ernal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW W ATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPP LY P RE S SURE10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior notice.
7
3. KM-630MRH
AC SUP P LY VOLTAGE208-230/60/1 (3 wire wit h neut ral for 115V)
AM P E RA GE6.5 A ( 5 Mi n. Freeze A T 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs . /day ( k g/ day )70*603 (274)573 (260)531 (241)
Reference wi t hout * marks80580 (263)532 (242)491 (223)
90573 (260)* 499 (226)457 (207)
100564 (256)489 (222)418 (190)
SHAPE OF ICECresc ent Cube
ICE PRODUCTION PER CYCLE14.3 lbs. (6.5 kg) 720 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs .)1414 (6.8)1332 (5.3)
WATER gal./ 24HR (gal./100 lbs. )166 (33.3)323 (53.6)
EXTERIOR DIMENS IONS (WxDx H)22" x 27-1/ 2" x 37-1/2" (560 x 695 x 950 mm)
EXTERIOR FINISHSt ai nless Steel, Gal vanized Steel (Rear)
WEIGHTNet 154 lbs . ( 70 kg ), Shi ppi ng 185 lbs. (84 kg)
CONNECTIONS - ELE CTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
3/8" OD P i pe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAK ING W ATER CONTROLTimer Cont roll ed. Overfl ow P i pe
COOLING WA TE R CO NTROLN/A
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic , Model RS64C1E-CAV
CONDENSERAir-c ool ed Remot e, Condenser Unit URC 6 F
EV A PORATORV ert i cal type, S t ai nl ess S teel and Copper
REFRIGERANT CONTROLThermos tatic Expansion V alve
Condensing P res sure Regulator on URC-6F
REFRIGERANT CHARGER-404A,4 lb. 4 oz. ( 1950 g )
( Icemak er 2 lbs. 6 oz . Cond. 1 lbs . 14 oz. )
DESIGN PRE S SUREHigh 467 PS IG, Low 230 PSIG
P.C. B O ARD CIRCUIT PROTE CTIONHi g h Voltage Cu t-out ( Inte rn al )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Int ernal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW W ATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
Note: We reserve the right to make changes in specifications and design without prior notice.
8
4. CONDENSER UNIT
URC-6F
24"
(610 mm.)
23-1/32"
(585 mm.)
18-1/8"
(460 mm.)
17-1/8"
(435 mm.)
14-9/16"
(370 mm.)
19-11/16"
(500 mm.)
18-1/8"
(460 mm.)
20-15/32"
(520 mm.)
21-15/16"
(557 mm.)
6/16" x 3/4" (10 mm. x 20 mm.)
4 x 2 (SLOTTED HOLES)
14-1/8"
(358 mm.)
14-15/16"
15-11/16"
(380 mm.)
(398 mm.)
17-7/8"
(454 mm.)
14-15/16"
(380 mm.)
2-1/2"
(63 mm.)
7/8" DIA. HOLE
(23 mm. DIA.)
6-5/16"
(160 mm.)
2-15/16"
(75 mm.)
9
MODEL: URC-6F
SPECIFICATIONS
EXTERIOR
DIMENSIONS (W x D x H)
REFRIGERANT CHARGE
WEIGHT
CONNECTIONS
REFRIGERANT
ELECTRICAL
CONDENSER
HEAD PRESSURE CONTROL
AMBIENT CONDITION
Galvanized Steel
21-15/16" x 15-11/16" x 17-7/8"
(557 x 398 x 453.8 mm.)
R404A1 lb. 2 oz. (505 g)
Net 61 lbs. (28 kg)
Shipping 68 lbs. (31 kg)
One Shot Couplings (Aeroquip)
Permanent Connection
Air-cooled
Condensing Pressure Regulator
Min. -20°F - Max. +122°F
(-29°C to +50°C)
Outdoor use
10
II. GENERAL INFORMATION
1. CONSTRUCTION
[a] KM-630MAH
Spray TubesWater Supply Inlet
Control Switch
Bin Control Thermostat
(except models with
Mechanical Bin Control)
Expansion ValveFan Motor
Compressor
Float Switch
Water Pump
Mechanical
Bin Control
(except models
with Thermostat)
Condenser
Hot Gas Valve
Condenser
Drier
Control Box
11
[b] KM-630MWH
Spray TubesWater Supply Inlet
Control Switch
Bin Control Thermostat
(except models with
Mechanical Bin Control)
Water Regulator
Expansion ValveHot Gas Valve
Compressor
Float SwitchDrier
Water PumpControl Box
Mechanical
Bin Control
(except models
with Thermostat)
12
[c] KM-630MRH
Spray TubesWater Supply Inlet
Control Switch
Bin Control Thermostat
(except models with
Mechanical Bin Control)
Expansion ValveReceiver Tank
Compressor
Junction Box
Float SwitchDrier
Water PumpHot Gas Valve
Line Valve
Control Box
Mechanical
Bin Control
(except models
with Thermostat)
13
2. CONTROLLER BOARD
[a] SOLID-STATE CONTROL
1) A HOSHIZAKI exclusive solid-state control is employed in Modular Crescent Cubers.
2) A Printed Circuit Board (hereafter called “Controller Board”) includes a stable and high
quality control system.
3) All models are pretested and factory-adjusted.
[b] CONTROLLER BOARD
CAUTION
1. Fragile, handle very carefully.
2. A controller board contains integrated circuits, which are susceptible to
failure due to static discharge. It is especially important to touch the metal
part of the unit when handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to
prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4 and K5,
because the same connector is used for the Thermistor (white), Float Switch
(black), and Mechanical Bin Control (red).
(For machines with thermostat, there is no connection on K4.)
5. Always replace the whole board assembly when it goes bad.
6. Do not short out power supply to test for voltage.
PART NUMBERTYPE
2A1410-01 HOS-001A (Control Products)
Features of Control Products “E” Controller Board
1) Maximum Water Supply Period - 6 minutes
Water Solenoid Valve opening, in the Defrost (Harvest) Cycle, is limited by the defrost
timer. The Water Valve cannot remain open longer than the
maximum period. The Water Valve can close in less than six minutes if the defrost cycle is
completed.
14
2) Defrost Timer
The defrost cycle starts when the Float Switch opens and completes the freeze cycle.
But the Defrost Timer does not start counting until the Thermistor senses 48°F at the
Evaporator outlet. The period from the end of the freeze cycle up to the point of the
Thermistor's sensing varies depending on the ambient and water temperatures.
3) High Temperature Safety - 127 ± 7°F
The temperature of the suction line in the refrigerant circuit is limited by the High
Temperature Safety.
During the defrost cycle the Evaporator temperature rises. The Thermistor senses
48°F and starts the Defrost Timer. After the Defrost Timer counts down to zero,
the normal freeze cycle begins. If the Evaporator temperature continues to rise,
the Thermistor will sense the rise in temperature and at 127 ± 7°F the Thermistor
operates the High Temperature Safety.
This High Temperature Safety shuts down the circuit and the icemaker automatically
stops.
This High Temperature Safety protects the unit from excessive temperature. The Control
Board will Beep every 3 seconds. The white Reset Button on the Control Board must be
pressed with power on to reset the Safety.
4) Low Water Safety
If the Pump Motor is operated without water, the mechanical seal can fail. To prevent this
type of failure, the Controller Board checks the position of the Float Switch at the end of
the initial one minute water fill cycle and at the end of each defrost cycle.
If the Float Switch is in the up position (electrical circuit closed), the Controller Board
changes to the ice making cycle. If the Float Switch is in the down position (electrical
circuit open), the Controller Board changes to a one minute water fill cycle before starting
the ice making cycle. This method allows for a Low Water Safety shut down to protect the
Water Pump from mechanical seal failure.
For water-cooled model, if the water is shut off, the unit is protected by the High Pressure
Switch.
5) High Voltage Cutout
The maximum allowable supply voltage of this icemaker is limited by the High Voltage Cutout.
If miswiring (especially on single phase 3 wire models) causes excessive voltage on the
Controller Board, the High Voltage Cutout shuts down the circuit in 3 seconds and the
icemaker automatically stops. When the proper supply voltage is resumed, the icemaker
automatically starts running again. The Control Board will signal this problem using 7 Beeps
every 3 seconds.
6) LED Lights and Audible Alarm Safeties
The red LED indicates proper control voltage and will remain on unless a control voltage
problem occurs. At startup a 5 second delay occurs while the board conducts an internal
timer check. A short beep occurs when the power switch is turned ON or OFF.
15
The green LED’s 1-4 represent the corresponding relays and energize and sequence 5
seconds from initial start-up as follows:
Sequence StepLED’s on Length:Min.Max.Avg.
1 Minute Fill CycleLED460 sec.
Harvest CycleLED1, 4, & 22 min.20 min.3-5 min.
Freeze CycleLED15 min.60 min.30-35 min.
Reverse Pump OutLED1, 3, & 210 sec.20 sec.Factory set.
{LED 1 – Comp; LED 2 - HGV/CFM; LED 3 – PM; LED 4 - WV}
The built in safeties shut down the unit and have alarms as follows:
1 beep every 3 sec. = High Evaporator Temperature >127 ° F.
Check for defrost problem (stuck HGV or relay), hot water entering unit, stuck
headmaster, or shorted thermistor.
2 beeps every 3 sec. = Defrost Back Up Timer. Defrost >20 minutes.
Orange LED marked 20 MIN energizes.
Check for open thermistor, HGV not opening, TXV leaking by, low charge, or inefficient
compressor.
3 beeps every 3 sec. = Freeze Back Up Timer. Freeze > 60 minutes.
Yellow LED marked 60 MIN energizes.
Check for F/S stuck closed (up), WV leaking by, HGV leaking by, TXV not feeding
properly, low charge, or inefficient compressor.
4 beeps every 3 sec. = Short Circuit between the K4 connection on
Machines
with
mechanical
bin control
ONLY
the control board and the bin control relay. Check connections and
replace wire harness if necessary.
5 beeps every 3 sec. = Open Circuit between the K4 connection
on the control board and the bin control relay. Check connections and
replace wire harness if necessary.
To manually reset the above safeties, depress white alarm reset button with the power
supply ON.
6 beeps every 3 sec. = Low Voltage. Voltage is 92 Vac or less.
7 beeps every 3 sec. = High Voltage. Control voltage > 147 Vac ±5%.
The red LED will de-energize if voltage protection operates.
The voltage safety automatically resets when voltage is corrected.
The Output Test switch “S3” provides a relay sequence test. With power OFF, place S3
ON and switch power to ICE. The correct lighting sequence should be none, 2, 3, 4, 1, & 4,
normal sequence every 5 seconds. S3 should remain in the “OFF” position for normal
operation.
16
The application switch located between relay X3 & X4 must be set to match the original
board application. Place this switch in the ALP position if there is no white wire supplied
to the K1 connector. If there is a white wire, place the switch in the C position. If this
switch is placed in the wrong position, either the compressor contactor will remain energized with the control switch OFF, or the unit will not start.
The dip switches should be adjusted per the adjustment chart published in the Tech
Specs book. Number 8 must remain in the OFF position.
(Control Products HOS-001A Board)
17
[c] SEQUENCE
1st Cycle
1. Unit energized and Control Switch to “ICE”
position. Water supply cycle starts.
2. After 1 minute,
Defrost cycle starts.
3. Thermistor reads 48° F.
Defrost Timer starts counting.
5. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
IMPORTANT
Water Valve
opening is limited
to 6 minutes.
&
4. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if Defrost Timer does not stop counting.
18
2nd Cycle and after with pump drain
IMPORTANT
Freeze cycle time is limited to 60 minutes even
if Float Switch does not open.
1. Float Switch opens and signals to complete
freeze cycle.
Drain timer starts counting.
&
2. Drain timer stops counting.
Pump drain is completed
3. Thermistor reads 48° F.
Defrost Timer starts
counting.
IMPORTANT
Water Valve
opening is limited to 6
minutes.
5. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
4. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if Defrost Timer does not stop counting.
19
2nd Cycle and after with no pump drain
IMPORTANT
Freeze cycle time is limited to 60 minutes even
if Float Switch does not open.
1. Float Switch opens and signals to complete
freeze cycle.
&
2. Thermistor reads 48° F.
Defrost Timer starts counting.
IMPORTANT
Water Valve
opening is limited to 6
minutes.
4. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
3. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if Defrost Timer does not stop counting.
20
[d] CONTROLS AND ADJUSTMENTS
The Dip Switch is factory-adjusted to the following positions:
Used for adjustment of the Defrost Timer.
The Defrost Timer starts counting when the Thermistor reads a certain temperature
at the Evaporator outlet.
Switch Nos. 3 and 4:
Used for adjustment of the Drain Timer.
When a freeze cycle is completed, the Pump Motor stops, and the icemaker
resumes operation in 2 seconds. Then the Pump Motor drains the Water Tank
for the time determined by the Drain Timer. The Drain Timer also determines the
time to restrain completion of a defrost cycle, i.e. the minimum defrost time.
Switch Nos. 5 and 6:
Used for adjustment of the Drain Counter.
The Pump Motor drains the Water Tank at the frequency determined by the Drain
Counter.
Switch No. 7:
Used only on models with mechanical bin control. Dip Switch should be set “ON”.
(Models with bin thermostat, Switch No. 7 should be set in the “OFF” position.)
Switch No. 8:
Used only for checking the Controller Board. Usually set in OFF position.
21