Hoshizaki KM-201BAH, KM-201BWH, KM-260BWH, KM-260BAH User Manual

NO. F015-774 ISSUED: MAR. 18, 2009 REVISED: JUN. 17, 2011
HOSHIZAKI
SELF-CONTAINED
CRESCENT CUBER
MODEL
KM-201BAH
SERVICE MANUAL
IMPORTANT
Only qualified service technicians should install, service or maintain the product. No service or maintenance should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the equipment in accordance with this manual may adversely affect safety, performance, and warranty coverage.
Hoshizaki provides this manual primarily to assist qualifi ed service technicians in the maintenance and service of the product.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, write, or send an e-mail message to the Hoshizaki Technical Support Department for assistance.
HOSHIZAKI AMERICA, INC. 618 Highway 74 South Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department Phone: 1-800-233-1940 Technical Support
(770) 487-2331 Fax: 1-800-843-1056 (770) 487-3360 E-mail: techsupport@hoshizaki.com
Web Site: www.hoshizaki.com NOTE: To expedite assistance, all correspondence/communication MUST include the
following information: * Model Number * Serial Number * Complete and detailed explanation of the problem.
IMPORTANT
This manual should be read carefully before the icemaker is serviced or maintenance operations are performed. Only qualifi ed service technicians should install, service, and maintain the icemaker. Read the warnings contained in this booklet carefully as they give important information regarding safety. Please retain this booklet for any further reference that may be necessary.
CONTENTS
I. SPECIFICATIONS -------------------------------------------------------------------------------------1
1. SPECIFICATIONS ----------------------------------------------------------------------------------1 [a] KM-201BAH -------------------------------------------------------------------------------------1 [b] KM-260BAH -------------------------------------------------------------------------------------2 [c] KM-201BWH -------------------------------------------------------------------------------------3 [d] KM-260BWH ------------------------------------------------------------------------------------4
II. GENERAL INFORMATION -------------------------------------------------------------------------5
1. CONSTRUCTION ----------------------------------------------------------------------------------5 [a] KM-201BAH, KM-260BAH -------------------------------------------------------------------5 [b] KM-201BWH ------------------------------------------------------------------------------------6 [c] KM-260BWH -------------------------------------------------------------------------------------7 [d] ICEMAKING COMPARTMENT -------------------------------------------------------------8
2. SEQUENCE OF OPERATION ------------------------------------------------------------------9 [a] ONE MINUTE FILL CYCLE ------------------------------------------------------------------9 [b] INITIAL HARVEST CYCLE ------------------------------------------------------------------9 [c] FREEZE CYCLE -------------------------------------------------------------------------------9 [d] PUMP-OUT CYCLE ---------------------------------------------------------------------------9 [e] NORMAL HARVEST CYCLE ------------------------------------------------------------- 10 [f] SHUTDOWN ----------------------------------------------------------------------------------10
3. CONTROL BOARD ------------------------------------------------------------------------------12 [a] CONTROL BOARD LAYOUT -------------------------------------------------------------13 [b] FEATURES ------------------------------------------------------------------------------------14 [c] CONTROLS AND ADJUSTMENTS ------------------------------------------------------ 16 [d] CONTROL BOARD CHECK PROCEDURE-------------------------------------------21 [e] CONTROL BOARD REPLACEMENT ---------------------------------------------------22
4. THERMISTOR -------------------------------------------------------------------------------------22
5. BIN CONTROL ------------------------------------------------------------------------------------23 [a] EXPLANATION OF OPERATION --------------------------------------------------------23 [b] BIN CONTROL CHECK PROCEDURE ------------------------------------------------ 23
6. SWITCHES ---------------------------------------------------------------------------------------- 24 [a] CONTROL SWITCH -------------------------------------------------------------------------24 [b] SERVICE SWITCH -------------------------------------------------------------------------- 24
PAGE
III. TECHNICAL INFORMATION --------------------------------------------------------------------26
1. WATER CIRCUIT AND REFRIGERANT CIRCUIT --------------------------------------- 26
i
[a] KM-201BAH, KM-260BAH ----------------------------------------------------------------- 26 [b] KM-201BWH, KM-260BWH ---------------------------------------------------------------27
2. WIRING DIAGRAM ------------------------------------------------------------------------------28
3. TIMING CHART -----------------------------------------------------------------------------------29
[a] KM-201BAH -----------------------------------------------------------------------------------29 [b] KM-260BAH -----------------------------------------------------------------------------------30 [c] KM-201BWH -----------------------------------------------------------------------------------31 [d] KM-260BWH ---------------------------------------------------------------------------------- 32
4. PERFORMANCE DATA ------------------------------------------------------------------------- 33
[a] KM-201BAH -----------------------------------------------------------------------------------33 [b] KM-260BAH -----------------------------------------------------------------------------------34 [c] KM-201BWH -----------------------------------------------------------------------------------35 [d] KM-260BWH ---------------------------------------------------------------------------------- 36
IV. SERVICE DIAGNOSIS ---------------------------------------------------------------------------- 37
1. DIAGNOSTIC PROCEDURE ------------------------------------------------------------------37
2. NO ICE PRODUCTION -------------------------------------------------------------------------39
3. EVAPORATOR IS FROZEN UP --------------------------------------------------------------42
4. LOW ICE PRODUCTION -----------------------------------------------------------------------43
5. ABNORMAL ICE ----------------------------------------------------------------------------------43
6. OTHER ----------------------------------------------------------------------------------------------44
V. REMOVAL AND REPLACEMENT --------------------------------------------------------------45
1. SERVICE FOR REFRIGERANT LINES ---------------------------------------------------- 45
[a] SERVICE INFORMATION -----------------------------------------------------------------45 [b] REFRIGERANT RECOVERY ------------------------------------------------------------- 46 [c] EVACUATION AND RECHARGE (R-404A) -------------------------------------------46
2. BRAZING -------------------------------------------------------------------------------------------47
3. COMPRESSOR -----------------------------------------------------------------------------------48
4. DRIER -----------------------------------------------------------------------------------------------49
5. HOT GAS VALVE --------------------------------------------------------------------------------- 50
6. EXPANSION VALVE ----------------------------------------------------------------------------- 52
7. AIR-COOLED CONDENSER ------------------------------------------------------------------53
8. WATER-COOLED CONDENSER ------------------------------------------------------------54
9. FAN MOTOR (AIR-COOLED MODEL)------------------------------------------------------ 55
10. WATER REGULATING VALVE (WATER-COOLED MODEL) -------------------------56
11. ADJUSTMENT OF WATER REGULATING VALVE (WATER-COOLED MODEL) -------------------------------------------------------------------58
12. PUMP MOTOR------------------------------------------------------------------------------------59
13. WATER VALVE------------------------------------------------------------------------------------60
14. DRAIN VALVE, CLEANING VALVE ----------------------------------------------------------61
15. FLOAT SWITCH ---------------------------------------------------------------------------------- 62
16. BIN CONTROL SWITCH ----------------------------------------------------------------------- 63
17. THERMISTOR ------------------------------------------------------------------------------------64
18. CONTROL BOX ----------------------------------------------------------------------------------65 [a] POWER SWITCH ---------------------------------------------------------------------------- 66 [b] FUSE -------------------------------------------------------------------------------------------- 66
ii
[c] FUSE HOLDER ------------------------------------------------------------------------------- 66 [d] CONTROL BOARD -------------------------------------------------------------------------- 66 [e] POWER RELAY ------------------------------------------------------------------------------66 [f] CONTROL BOARD TRANSFORMER -------------------------------------------------- 67
19. WATER TANK -------------------------------------------------------------------------------------67
20. CUBE GUIDE -------------------------------------------------------------------------------------68
21. SEPARATOR -------------------------------------------------------------------------------------- 68
22. SPRAY TUBE, WATER SUPPLY PIPE, SPRAY GUIDE -------------------------------70
23. DOOR ----------------------------------------------------------------------------------------------- 71
VI. CLEANING AND MAINTENANCE INSTRUCTIONS --------------------------------------72
1. CLEANING -----------------------------------------------------------------------------------------72 [a] CLEANING PROCEDURE -----------------------------------------------------------------72 [b] SANITIZING PROCEDURE --------------------------------------------------------------- 73
2. MAINTENANCE ---------------------------------------------------------------------------------- 74 [a] EXTERIOR PANELS ------------------------------------------------------------------------74 [b] STORAGE BIN AND SCOOP ------------------------------------------------------------- 74 [c] AIR FILTER (AIR-COOLED MODEL) ---------------------------------------------------75 [d] CONDENSER (AIR-COOLED MODEL) ------------------------------------------------ 75
3. PREPARING THE ICEMAKER FOR LONG STORAGE --------------------------------75
iii
I. SPECIFICATIONS
1. SPECIFICATIONS
[a] KM-201BAH
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 6.1 A ( 5 Min. Freeze AT 104°F / WT 80°F) MAXIMUM FUSE SIZE N/A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *201 (91) 190 (86) 176 (80) Reference without *marks 80 193 (88) 177 (80) 162 (73)
90 190 (86) *165 (75) 150 (68)
100 187 (85) 161 (73) *136 (62) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 4.0lbs. (1.82 kg) 182pcs. APPROXIMATE STORAGE CAPACITY 80 lbs(36Kg). ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 510(7.5) 490(5.8) WATER gal./24HR (gal./100 lbs.) 36(22.0) 72(35.6) CEC/CEE TIER LEVEL 3 ENERGY STAR Yes EXTERIOR DIMENSIONS (WxDxH) 24" x 28" x 39" (612 x 712 x 990 mm)
Including 6" legs EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 137 lbs. (62 kg), Shipping 165 lbs. (75 kg) CONNECTIONS - ELECTRIC Cord Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Mechanical Level Switch with Delay COMPRESSOR Hermetic, Model NF7CLX CONDENSER Air-Cooled, Fin and tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R-404A, 12 oz. (340g) DESIGN PRESSURE High 467PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED Ice Scoop, 6" leg 4 pcs OPERATING CONDITIONS VOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 -100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG DRAWING NO. (DIMENSION) 372022
We reserve the right to make changes in specifications and design without prior notice.
1
[b] KM-260BAH
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 7.6 A ( 5 Min. Freeze AT 104°F / WT 80°F) MAXIMUM FUSE SIZE N/A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *263 (119) 245 (111) 227 (103) Reference without *marks 80 249 (113) 220 (100) 207 (94)
90 245 (111) *200 (91) 185 (84)
100 244 (111) 196 (89) *171 (78) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 5.0.lbs. (2.26kg) 238 pcs. APPROXIMATE STORAGE CAPACITY 100 lbs(45Kg). ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 630(7.6) 590(5.4) WATER gal./24HR (gal./100 lbs.) 41(20.3) 78(29.7) CEC/CEE TIER LEVEL 3 ENERGY STAR Yes EXTERIOR DIMENSIONS (WxDxH) 30" x 28" x 39" (762 x 712 x 990 mm)
Including 6" legs EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 154 lbs. (70 kg), Shipping 187 lbs. (85 kg) CONNECTIONS - ELECTRIC Cord Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Mechanical Level Switch with Delay COMPRESSOR Hermetic, Model SC10CL CONDENSER Air-Cooled, Fin and tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R-404A 12.7oz (360g) DESIGN PRESSURE High 467PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED Ice Scoop, 6" leg 4 pcs OPERATING CONDITIONS VOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 -100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG DRAWING NO. (DIMENSION) 372021
We reserve the right to make changes in specifications and design without prior notice.
2
[c] KM-201BWH
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 5.5 A ( 5 Min. Freeze AT 104°F / WT 80°F) MAXIMUM FUSE SIZE N/A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *215 (98) 205 (93) 192 (87) Reference without *marks 80 207 (94) 192 (87) 180 (82)
90 205 (93) *181 (82) 168 (76)
100 203 (92) 178 (81) *157 (71) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 4.0lbs. (1.82 kg) 182pcs. APPROXIMATE STORAGE CAPACITY 80 lbs(36Kg). ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 470(6.17) 460(5.08) WATER gal./24HR (gal./100 lbs.) 43(24.0) 55(25.6) COND.WATER gal./24HR (gal./100 lbs) 226(141.3) 119(55.6) CEC/CEE TIER LEVEL 3 EXTERIOR DIMENSIONS (WxDxH) 24" x 28" x 39" (612 x 712 x 990 mm)
Including 6" legs EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 137 lbs. (62 kg), Shipping 165 lbs. (75 kg) CONNECTIONS - ELECTRIC Cord Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT CONDENSER WATER Inlet 1/2" FPT
Outlet 1/2" FPT CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Mechanical Level Switch with Delay COMPRESSOR Hermetic, Model NF7CLX CONDENSER Water-Cooled, Tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R-404A, 9.9 oz. (280g) DESIGN PRESSURE High 467PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED Ice Scoop, 6" leg 4 pcs OPERATING CONDITIONS VOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 -100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG DRAWING NO. (DIMENSION) 373568S01
We reserve the right to make changes in specifications and design without prior notice.
3
[d] KM-260BWH
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 7.5 A ( 5 Min. Freeze AT 104°F / WT 80°F) MAXIMUM FUSE SIZE N/A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *268 (122) 259 (117) 242 (110) Reference without *marks 80 261 (118) 247 (112) 228 (103)
90 259 (117) *237 (108) 218 (99)
100 254 (115) 233 (106) *201 (91) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 5.0.lbs. (2.26kg) 238 pcs. APPROXIMATE STORAGE CAPACITY 100 lbs(45Kg). ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 630(6.37) 620(5.59) WATER gal./24HR (gal./100 lbs.) 62(26.3) 77(28.7) COND.WATER gal./24HR (gal./100 lbs) 285(120.6) 151(56.2) CEC/CEE TIER LEVEL 3 EXTERIOR DIMENSIONS (WxDxH) 30" x 28" x 39" (762 x 712 x 990 mm)
Including 6" legs EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 154 lbs. (70 kg), Shipping 187 lbs. (85 kg) CONNECTIONS - ELECTRIC Cord Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT CONDENSER WATER Inlet 1/2" FPT
Outlet 1/2" FPT CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Mechanical Level Switch with Delay COMPRESSOR Hermetic, Model SC10CL CONDENSER Water-Cooled, Tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R-404A 12.7oz (360g) DESIGN PRESSURE High 467PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED Ice Scoop, 6" leg 4 pcs OPERATING CONDITIONS VOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 -100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG DRAWING NO. (DIMENSION) 373569S01
We reserve the right to make changes in specifications and design without prior notice.
4
II. GENERAL INFORMATION
1. CONSTRUCTION
[a] KM-201BAH, KM-260BAH
Top Panel
Side Panel (L)
Front Cover Rear Panel Door
Air Filter
Louver
Leg
Side Panel (R) Power Supply Cord
Top Cover Hot Gas Valve Thermistor Drain Valve Evaporator Condenser Fan Motor Cleaning Valve Separator Compressor
Water Tank Water Valve
Expansion Float Switch Valve Overow Pipe Drier Pump Motor
Control Switch Service Switch
Control Box
Front View Rear View
Bin Control Switch
With Tank Removed
5
[b] KM-201BWH
Top Panel
Side Panel (L) Front Cover Rear Panel
Door
Side Panel (R)
Louver Power Supply Cord
Leg
Top Cover Drain Valve Hot Gas Valve
Cleaning Valve Thermistor
Water Regulator Evaporator Condenser
Separator Compressor
Water Tank Water Valve
Expansion Valve Float Switch
Overfl ow Pipe
Drier
Control Switch Service Switch Control Box
Front View Rear View
Bin Control Switch
With Tank Removed
6
[c] KM-260BWH
Top Panel
Front Cover
Side Panel (L) Rear Panel
Door
Side Panel (R)
Louver Power Supply Cord
Leg
Top Cover Drain Valve Hot Gas Valve Thermistor
Cleaning Valve Water Regulator Evaporator Condenser Separator
Water Tank Compressor Expansion Valve Water Valve
Overfl ow Pipe Drier
Control Switch Float Switch Service Switch Control Box
Front View Rear View
Bin Control Switch
With Tank Removed
7
[d] ICEMAKING COMPARTMENT
Spray Tube
Evaporator
Water Supply Pipe
Separator
Cube Guide
Water Tank
Overfl ow Pipe
Drain Valve
Cleaning Valve Separator
Water Valve
Pump Motor
Float Switch
8
2. SEQUENCE OF OPERATION
The steps in the sequence are as outlined below. When power is supplied, a 5 second delay occurs at startup. Note that the order of the LEDs from the outer edge of the board is 5, 6, 8, 9, 4, 7.
[a] ONE MINUTE FILL CYCLE
LED 8 is on. WV opens and the fi ll period begins. After 1 minute, the board checks for a closed F/S. If F/S is closed, the harvest cycle begins. If not, WV will remain energized through additional 1 minute cycles until water enters the sump and F/S closes. This serves as a low water safety to protect the pump motor.
[b] INITIAL HARVEST CYCLE
LEDs 5, 6, and 8 are on. WV remains open, Comp energizes, HGV opens, and harvest begins. As the evaporator warms, the thermistor located on the suction line checks for a 48°F (9°C) temperature. When 48°F (9°C) is reached, a 3.9 k signal turns the harvest over to the adjustable harvest timer which is factory set for normal conditions. The timer has settings of 60, 90, 120, and 180 seconds (S1 dip switch 1 & 2). When the harvest timer completes its count down, the harvest cycle is complete and the freeze cycle starts. The minimum total time allowed by the board for a complete harvest cycle is 2 minutes. WV is open during harvest for a maximum of 6 minutes or the length of harvest minus 0, 10, 30, or 50 seconds (adjustable by S1 dip switch 7 & 8), whichever is shorter. LED 8 goes off when WV closes. PM energizes and runs for the last 0, 10, 30, or 50 seconds of harvest depending on S1 dip switch 7 & 8 setting. LED 7 comes on when PM energizes. At the end of harvest, the control board checks the position of F/S and proceeds to the freeze cycle if it is closed or calls for a 1-minute fi ll if it is open.
[c] FREEZE CYCLE
LEDs 5 & 7 are on. Comp continues to run, PM and FMS energize, HGV closes and the freeze cycle starts. For the fi rst 5 minutes after the thermistor temperature reaches 36°F (2°C), the control board will not accept a signal from F/S. This minimum freeze period acts as a short cycle protection. At the end of this period, F/S assumes control. As the evaporator cools, the thermistor located on the suction line checks the temperature and PM stops (see “III. 3. TIMING CHART” for details). This is to prevent slushing. As ice builds on the evaporator the water level in the sump lowers. The freeze continues until F/S opens and terminates ice production.
[d] PUMP-OUT CYCLE
LEDs 4, 5, 6, and 7 are on. Comp continues to run, HGV opens, FMS de-energizes. PM stops for 2 seconds, DV energizes, then restarts to take water from the sump and force it through DV and down the drain. When the drain timer stops counting, the drain is complete. The drain timer has settings of 10 and 20 seconds (S1 dip switch 3 & 4). Pump-out cycle always occurs on the 2nd harvest after startup. Then, depending on
9
the control board setting, pump-out cycle occurs every cycle, or every 2nd, 5th, or 10th cycle (S1 dip switch 5 & 6).
[e] NORMAL HARVEST CYCLE
LEDs 5, 6, and 8 are on. Comp continues to run, HGV remains open and WV opens. As the evaporator warms, the thermistor reaches 48°F (9°C). The control board then receives the thermistor's 3.9 k signal and starts the harvest timer. WV is open during harvest for a maximum of 6 minutes or the length of harvest minus 0, 10, 30, or 50 seconds (adjustable by S1 dip switch 7 & 8), whichever is shorter. LED 8 goes off when WV closes. PM energizes and runs for the last 0, 10, 30, or 50 seconds of harvest depending on S1 dip switch 7 & 8 setting. LED 7 comes on when PM energizes. At the end of harvest, the control board checks the position of F/S and proceeds to the freeze cycle if it is closed or calls for a 1-minute fi ll if it is open. The unit continues to cycle through [c], [d], and [e] sequence until the bin control is activated and shuts the unit down. When the bin control is activated, the “POWER OK” LED fl ashes.
[f] SHUTDOWN
When BC is activated (BC open), the “POWER OK” LED flashes. There is a delay before the shutdown sequence begins. The delay varies depending on the cycle the icemaker is in at the time of activation. For details, see the table below.
Cycle at Bin Control Activation Delay Before Shutdown Sequence Begins
Fill Cycle 15 seconds Harvest Cycle 15 seconds after the next freeze cycle starts Freeze Cycle 15 seconds if BC is activated between the beginning of
freeze and termination of the 5-minute short cycle protection timer (timer starts when the thermistor temperature drops to 36°F (2°C) (5.5 k or more)). After this time, the unit will not shut down until the next harvest cycle is complete.
After the delay, all components de-energize. DV energizes after 2 seconds. PM energizes after 2 seconds. PM takes water from the tank and forces it through DV and down the drain. The water tank drains for a maximum of 5 minutes or until F/S opens. DV and PM (if applicable) then de-energize. When BC closes again calling for ice, the unit starts at the 1-minute fi ll cycle. There is a 90-second minimum off time before the icemaker can restart.
Legend: BC–bin control; Comp–compressor; DV–drain valve; FMS–self-contained fan
motor; F/Sfl oat switch; HGV–hot gas valve; PM–pump motor; WV–inlet water
valve
10
extended periods of time over the outside surface of the evaporator.
and sanitizer over both the insde and outside surfaces of the evaporator.
DRAIN Power is supplied to the pump and drain valve. This drains the water tank.
CIRCULATE Power is supplied to the pump only. This operation can be used to circulate cleaner for
Components Energized when the Control Switch is in the “SERVICE” Position
When in the “SERVICE” position, the control switch supplies power to the service switch and the machine
is in service mode. The service switch has three positions: “DRAIN”, “CIRCULATE”, and “WASH”. See the
information below for details of each function.
WASH Power is supplied to the pump and cleaning valve. This operation is used to circulate cleaner
11
3. CONTROL BOARD
* A HOSHIZAKI exclusive solid-state control is employed in crescent cubers.
* All models are pretested and factory-adjusted.
CAUTION
1. Fragile, handle very carefully.
2. A control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the unit before handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to prevent damage to the board.
4. Do not change wiring and connections.
5. Always replace the whole board assembly if it goes bad.
6. Do not short out the power supply to test for voltage.
12
[a] CONTROL BOARD LAYOUT
r3FMBZ-&%T
JOEJDBUFXIJDI SFMBZTBSFFOFSHJ[FE BTMJTUFECFMPX
r-&%93FMBZ
$PNQSFTTPS$PNQ 'BO.PUPS3FNPUF '.3
r-&%93FMBZ
)PU(BT7BMWF)(7 'BO.PUPS'.
(FM off when LED on)
-JRVJE-JOF7BMWF--7 '.BOE--7PGGXIFO
-&%PO
r-&%93FMBZ
*OMFU8BUFS7BMWF87 87POVOJUTXJUI JOMFUXBUFSWBMWFT
r-&%93FMBZ
*OMFU8BUFS7BMWF 87POVOJUTXJUI JOMFUXBUFSWBMWFT
r-&%93FMBZ
%SBJO7BMWF%7
r-&%93FMBZ
1VNQ.PUPS1.
)$POUSPM#PBSE
r,$POOFDUPS
5SBOTGPSNFS
r,$POOFDUPS
Power Relay
.BHOFUJD$POUBDUPS
r108&30,-&%
-JHIUTXIFOQPXFSJT TVQQMJFEUPUIFCPBSE 'MBTIFTXIFOCJO DPOUSPMJTBDUJWBUFE
r,$POOFDUPS
1JOT 'BO.PUPS'. -JRVJE-JOF7BMWF--7 )PU(BT7BMWF 1VNQ.PUPS *OMFU8BUFS7BMWF 0QFO %SBJO7BMWF
r,$POOFDUPS
0QFO
r,$POOFDUPS
1JOT 'MPBU4XJUDI 0QFO #JO$POUSPM 5IFSNJTUPS 0QFO
r4%JQ4XJUDI
r4%JQ4XJUDI
Control Board
Auxiliary Code V0 or Earlier V1 or Later Part Number P00013-02 P01771-02 Type HKM2006V003
13
r"MBSN#V[[FS
r0651655&45#VUUPO
VTFEUPUFTUSFMBZTPO DPOUSPMCPBSE
r"-"3.3&4&5#VUUPO
[b] FEATURES
a) Maximum Water Supply Period - 6 minutes
The inlet water valve will be open during harvest for 6 minutes or the length of harvest minus 0, 10, 30, or 50 seconds (adjustable by S1 dip switch 7 & 8), whichever is shorter.
b) Harvest Backup Timer and Freeze Timer
The harvest backup timer shuts down the icemaker if, for two cycles in a row, the harvest cycle takes more than 20 minutes to complete. The control board will signal this problem using 2 beeps every 3 seconds. The freeze timer shuts down the icemaker if, for two cycles in a row, the freeze cycle takes longer than the time specified to complete. The control board will signal this problem using 3 beeps every 3 seconds. The time is factory set using S1 dip switch 9 &
10. The alarm reset button on the control board must be pressed with power on to reset either of these safeties.
c) High Temperature Safety
The temperature of the suction line in the refrigeration circuit is limited by the high temperature safety. This protects the unit from excessively high temperatures. If the evaporator temperature rises above 127°F (53°C) ± 7°F (4°C), the thermistor operates the safety. This shuts down the circuit and the icemaker automatically stops. The control board will signal this problem using 1 beep every 3 seconds. The alarm reset button on the control board must be pressed with power on to reset the safety.
d) Low Water Safety
The control board checks the position of the fl oat switch at the end of the initial one minute water fi ll cycle and at the end of each harvest cycle. If the float switch is in the up position (electrical circuit closed), the control board changes to the next cycle. If the fl oat switch is in the down position (electrical circuit open), the control board changes to additional one minute water fi ll cycles until water enters the sump and the fl oat switch closes. When the fl oat switch closes, the control board changes to the next cycle. The unit will not start without adequate water in the sump. This serves as a low water safety to protect the water pump. For water-cooled model, if the condenser water supply is shut off, the unit is protected by the high-pressure switch.
e) High Voltage and Low Voltage Cut-outs
The maximum and minimum allowable supply voltages of this icemaker are limited by the high voltage and low voltage cut-outs. If miswiring (especially on single phase 3 wire models) causes excessive voltage (147Vac ± 5% or more) on the control board, the high voltage cut-out shuts down the circuit in 3
14
seconds and the icemaker automatically stops. The control board will signal this problem using 7 beeps every 3 seconds. The icemaker also automatically stops in cases of insuffi cient voltage (92Vac ± 5% or less). The control board will signal this problem using 6 beeps every 3 seconds. When the proper supply voltage is resumed, the icemaker automatically starts running again.
f) LED Lights and Audible Alarm Safeties
The control board includes LED indicator lights, audible alarm safeties, and an output test feature. The “POWER OK” LED indicates control voltage and will remain on unless a control voltage problem occurs. The “POWER OK” LED fl ashes continuously when the bin is full and DV energizes for a maximum of 5 minutes to drain the water tank. At startup, a 5 second delay occurs to stabilize the circuit. LEDs 4 through 8 energize and sequence from initial startup as listed in the table below. Note that the order of the LEDs from the outer edge of the board is 5, 6, 8, 9, 4, 7. For more information, see “2. SEQUENCE OF OPERATION”.
Sequence Step LED
1 Minute Fill Cycle 8 WV 60 seconds
Harvest Cycle 5, 6, 8
Last 0, 10, 30, or 50 seconds (adjustable by dip switch) of harvest, WV de-energizes and PM energizes (LEDs 5, 6, and 7 are on)
Freeze Cycle 5, 7
Pump-Out Cycle 5, 6, 4, 7
Energized
Components
WV, HGV, Comp
Comp, PM, FMS Comp, HGV, DV, PM
Min. Max. Avg.
2 minutes 20 minutes 3 to 5 minutes
5 minutes
10 seconds 20 seconds
Time LEDs are On
freeze timer setting
25 to 30 minutes
factory default setting
The built in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
1
High Evaporator Temp. (temperature > 127
Type of Alarm Notes
Check for harvest problem (stuck HGV or
°F (53°C))
relay), hot water entering unit, stuck HM, or shorted thermistor.
Harvest Backup Timer
2
(harvest > 20 min. for two cycles in a row) Freeze Timer (freeze > specifi ed setting for
3
two cycles in a row) Timer is factory set using S1
Check for open thermistor, HGV not opening, TXV leaking by, low charge, ineffi cient Comp, or WRV leaking by. Check for a fl oat switch stuck closed (up), WV leaking by, HGV leaking by, PM not pumping, TXV not feeding properly, low charge, or ineffi cient Comp.
dip switch 9 & 10
To reset the above safeties, press the
ALARM RESET button with the power supply
on.
15
6
7
Legend:
Low Voltage (92Vac
± 5% or less)
High Voltage (147Vac
± 5% or more)
Comp–compressor; DV–drain valve; FMS–self-contained fan motor; HGV–hot
POWER OK LED will turn off if voltage
protection operates. The control voltage safeties automaticlly reset when voltage is corrected.
gas valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve
[c] CONTROLS AND ADJUSTMENTS
CAUTION
Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage.
a) Default Dip Switch Settings
The dip switch is factory-adjusted to the following positions:
Control
Board
P00013-02
P01771-02
Control Board
P00013-02
P01771-02
Program Ver.
(Auxiliary Code)
2.5 or earlier
(V-0 or earlier)
3.2
(V-1 or later)
Program Ver.
(Auxiliary Code)
2.5 or earlier
(V-0 or earlier)
3.2
(V-1 or later)
S1 Dip
Switch No. KM-201BAH OFF OFF OFF OFF ON ON OFF ON OFF ON KM-260BAH OFF OFF OFF OFF ON ON ON OFF OFF ON
KM-201BWH OFF OFF OFF OFF ON ON OFF ON ON OFF KM-260BWH ON OFF OFF OFF ON ON ON OFF OFF ON
KM-201BAH OFF OFF OFF OFF ON ON OFF ON OFF ON KM-260BAH OFF OFF OFF OFF ON ON ON OFF OFF ON
KM-201BWH OFF OFF OFF OFF ON ON OFF ON ON OFF KM-260BWH OFF OFF OFF OFF ON ON ON OFF ON OFF
S2 Dip Switch No. 1 2 3 4 5 6
12345678910
KM-201BAH ON OFF OFF OFF OFF ON
KM-260BAH ON OFF OFF OFF OFF ON KM-201BWH ON OFF OFF OFF ON OFF KM-260BWH ON OFF OFF OFF ON OFF
KM-201BAH ON OFF OFF OFF OFF OFF
KM-260BAH ON OFF OFF OFF OFF OFF KM-201BWH ON OFF OFF OFF OFF OFF KM-260BWH ON OFF OFF OFF OFF OFF
Do not adjust the S2 dip switch. These must be left in the factory default position, or the unit will not operate properly.
16
S1 Dip Switch S2 Dip Switch
Freeze Timer (9 & 10)
Anti-Slush Control (5 & 6)
Water Saver Timer (7 & 8)
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
* Functions of S2 dip switch nos. 2
through 6 depend on program version.
Refi ll Counter (3 & 4)
Float Switch Selector (2)
Pump-Out/Drain Selector (1)
Fig. 1 Fig. 2
b) Harvest Timer (S1 dip switch 1 & 2)
Used for adjustment of the harvest timer. The harvest timer starts counting when the thermistor reads a certain temperature at the evaporator outlet.
Dip Switch Setting No. 1 No. 2
OFF OFF 60
ON OFF 90
OFF ON 120
ON ON 180
Time
(seconds)
c) Pump-Out Timer (S1 dip switch 3 & 4)
Once every ten freeze cycles, the drain valve opens to drain the water tank for the time determined by the pump-out timer. These switches also determine the time to delay completion of a defrost cycle, i.e. the minimum defrost time. Do not change this setting, or the unit will not operate properly or produce high quality ice.
Dip Switch Setting Time (seconds) No. 3 No. 4 T1 T2
OFF OFF 10 120
ON OFF 10 180
OFF ON 20 120
ON ON 20 180
T1: Time to drain the water tank T2: Harvest timer at pump-out
17
Pump-out cycle always occurs on the 2nd harvest after startup. Then, depending on the pump-out frequency control setting (S1 dip switch 5 & 6), pump-out cycle occurs every cycle, or every 2nd, 5th, or 10th cycle.
d) Pump-Out Frequency Control (S1 dip switch 5 & 6)
The water tank drains at the frequency set by the pump-out frequency control. The pump-out frequency control is factory-adjusted to drain the water tank every 10 cycles, and no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted as shown in the table below.
Dip Switch Setting No. 5 No. 6
OFF OFF every cycle
ON OFF every 2 cycles
OFF ON every 5 cycles
ON ON every 10 cycles
e) Harvest Pump Timer (S1 dip switch 7 & 8)
The harvest pump timer allows the water valve to close and the pump motor to circulate water in the tank during the fi nal part of harvest. The water valve is open during harvest for a maximum of 6 minutes or the length of harvest minus 0, 10, 30, or 50 seconds (determined by the harvest pump timer setting), whichever is shorter. When the water valve closes, the pump motor energizes and runs for the time determined by the harvest pump timer setting. The harvest pump timer is factory-adjusted, and no adjustment is required.
Dip Switch Setting No. 7 No. 8
OFF OFF 0
ON OFF 10
OFF ON 30
ON ON 50
Frequency
Time
(seconds)
f) Freeze Timer (S1 dip switch 9 & 10)
CAUTION
Adjust to proper specifi cation, or the unit may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of freeze timer, machine initiates the harvest cycle. After 2 consecutive timer terminations, machine will shut down, possibly indicating a problem.
18
The freeze timer is factory adjusted, and no adjustment is required.
Dip Switch Setting No. 9 No. 10
ON OFF 50 OFF OFF 60 OFF ON 70
ON ON 100
g) Pump-Out Pump Motor Delay (S2 dip switch 1)
The pump-out pump motor delay determines whether or not the pump motor de­energizes for 2 seconds before restarting at the beginning of a drain cycle. The pump-out pump motor delay is factory adjusted, and no adjustment is required.
S2 Dip Switch Setting
No. 1
OFF 0
ON 2
Control Board P00013-02
Time
(minutes)
Delay
(seconds)
h) Refi ll Counter (S2 dip switch 2, 3, & 4) [Program Ver. 2.5 or earlier]
Do not adjust. These must be left in the factory default position or the unit will not operate properly. The KM-201BAH/BWH and KM-260BAH/BWH do not refi ll.
i) Anti-Slush Control (S2 dip switch 5 & 6) [Program Ver. 2.5 or earlier]
Do not adjust. These must be left in the factory default position or the unit will not operate properly. The anti-slush control (Ver. 1.0, Ver. 2.0) helps prevent slushing during the freeze cycle on small icemakers. It is deactivated on the KM-201BAH and KM-260BAH. When activated (Ver. 1.0), the thermistor located on the suction line checks for a 34°F (1°C) temperature as the evaporator cools. When 34°F (1°C) is reached, a 5.9 k signal causes the control board to de-energize the pump motor for 10 seconds. When activated (Ver. 2.0), the thermistor located on the suction line checks for a 50°F (10°C) temperature as the evaporator cools. When 50°F (10°C) is reached, a 3.9 k signal causes the control board to de-energize the pump motor for 10 seconds and energize it for 50 seconds repeatedly. When 34°F (1°C) is reached, a 5.9 k signal causes the control board to de-energize the pump motor for 10 seconds, energize it for 50 seconds, de-energize it again for 10 seconds, then energize it continuously.
19
S2 Dip Switch Setting
No. 5 No. 6
OFF OFF Activated (Ver. 1.0)
ON OFF Activated (Ver. 2.0)
OFF ON Deactivated
ON ON Deactivated
Control Board P01771-02
j) Harvest Promotion Control (S2 dip switch 2) [Program Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate properly. When activated, this control promotes harvest of ice on the evaporator that is hard to remove. If the harvest cycle exceeds 6 minutes, the pump motor starts to operate for a maximum of 3 minutes.
Anti-Slush Control
S2 Dip Switch Setting
No. 2
OFF Activated
ON Deactivated
k) Refi ll Counter (S2 dip switch 3) [Program Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate properly. The KM-201BAH/BWH and KM-260BAH/BWH do not refi ll.
l) Harvest Completion Detection Control (S2 dip switch 4) [Program Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate properly. It is deactivated on the KM-201BAH/BWH and KM-260BAH/BWH. When activated, this control determines whether ice remains on the evaporator at the end of a harvest cycle and at the beginning of a freeze cycle. If ice drops and activates the bin control switch in the last 10 seconds of a harvest cycle, the control determines that ice still remains on the evaporator and extends the harvest cycle for 30 seconds. If the bin control switch is activated at the beginning of a freeze cycle, the control determines that ice still remains on the evaporator and starts a harvest cycle after the minimum freeze cycle time has passed.
Harvest Promotion
Control
S2 Dip Switch Setting
No. 4
OFF Deactivated
ON Activated
Harvest Completion
Detection Control
20
Loading...