Hoshizaki KM1340MWH, KM901MRH3, KM320MWH, KM515MAH, KM515MRH Service Manual

...
Service Manual
Models KM-320MAH, MWH KM-340MAH, MWH KM-515MAH, MWH, MRH KM-600MAH KM-650MAH, MWH, MRH KM-901MAH, MWH, MRH/3 KM-1100MAH, MWH, MRH KM-1340MAH, MWH, MRH/3 KM-1601MRH/3
hoshizakiamerica.com
Number: 73196 Issued: 4-29-2013 Revised: 9-21-2016
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No service should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
HOSHIZAKI AMERICA, INC. 618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 6
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 8
A. Construction .................................................................................................................. 8
1. Air-Cooled Models (MAH) ........................................................................................ 8
2. Water-Cooled Models (MWH) .................................................................................. 9
3. Remote Models (MRH/3) ....................................................................................... 10
B. Water/Refrigeration Circuit Diagram .............................................................................11
1. Air-Cooled Models (MAH) .......................................................................................11
2. Water-Cooled Models (MWH) ................................................................................ 12
3. Remote Models (MRH/3) ....................................................................................... 13
II. Sequence of Operation and Service Diagnosis ............................................................... 14
A. Sequence of Operation Flow Chart ............................................................................. 14
1. "E" and "G" Control Board without Harvest Pump Timer Operation ....................... 14
2. "G" Control Board with Harvest Pump Timer Operation ....................................... 16
B. Service Diagnosis ....................................................................................................... 17
1. "E" and "G" Control Board without Harvest Pump Timer Diagnosis ....................... 18
2. "G" Control Board with Harvest Pump Timer Diagnosis ........................................ 24
C. Control Board Check ................................................................................................... 30
D. Bin Control Check ....................................................................................................... 31
1. Thermostatic Bin Control Check ............................................................................ 31
2. Mechanical Bin Control Check and Cleaning ....................................................... 32
E. Float Switch Check and Cleaning ............................................................................... 34
1. Float Switch Check ................................................................................................ 34
2. Float Switch Cleaning ............................................................................................ 35
F. Thermistor Check ......................................................................................................... 36
G. Diagnostic Tables ........................................................................................................ 37
III. Controls and Adjustments ............................................................................................... 41
A. Control Board Layout .................................................................................................. 42
1. "E" Control Board .................................................................................................. 42
2. "G" Control Board ................................................................................................. 43
B. LED Lights and Audible Alarm Safeties ....................................................................... 44
1. "E" Control Board .................................................................................................. 44
2. "G" Control Board ................................................................................................. 45
C. Settings and Adjustments ............................................................................................ 46
1. Default Dip Switch Settings .................................................................................... 46
a) "E" and "G" Control Board without Harvest Pump Timer Operation .................. 46
b) "G" Control Board with Harvest Pump Timer Operation .................................... 46
2. Harvest Timer (S4 dip switch 1 & 2) ...................................................................... 46
3. Pump-Out Timer (S4 dip switch 3 & 4) .................................................................. 47
4. Pump-Out Frequency Control (S4 dip switch 5 & 6) .............................................. 48
3
5. Bin Control Selector or Harvest Pump Timer Operation (S4 dip switch 7) ............. 48
6. Factory Use (S4 dip switch 8) ................................................................................ 49
7. Freeze Timer (S4 dip switch 9 & 10) ....................................................................... 49
8. Float Switch Selector (S5 dip switch 1): "G" Control Board ................................... 50
9. Rell Counter (S5 dip switch 2 through 5): "G" Control Board ............................... 50
D. Control Switch ............................................................................................................. 50
IV. Refrigeration Circuit and Component Service Information.............................................. 51
A. Refrigeration Circuit Service Information .................................................................... 51
B. Component Service Information .................................................................................. 54
C. Water Regulating Valve Adjustment (water-cooled model) .......................................... 54
V. Maintenance .................................................................................................................... 55
VI. Preparing the Appliance for Periods of Non-Use ............................................................ 56
VII. Disposal ......................................................................................................................... 58
VIII. Technical Information .................................................................................................... 59
A. Specication and Performance Data Sheets ............................................................... 59
1. KM-320MAH........................................................................................................... 59
2. KM-320MWH ......................................................................................................... 60
3. KM-340MAH .......................................................................................................... 61
4. KM-340MWH ......................................................................................................... 62
5. KM-515MAH .......................................................................................................... 63
6. KM-515MWH ......................................................................................................... 64
7. KM-515MRH with URC-5F ..................................................................................... 65
8. KM-600MAH .......................................................................................................... 66
9. KM-650MAH .......................................................................................................... 67
10. KM-650MWH ....................................................................................................... 68
11. KM-650MRH with URC-5F ................................................................................... 69
12. KM-901MAH ........................................................................................................ 70
13. KM-901MWH ....................................................................................................... 71
14. KM-901MRH with URC-9F ................................................................................... 72
15. KM-901MRH3 with URC-9F ................................................................................. 73
16. KM-1100MAH ........................................................................................................74
17. KM-1100MWH ...................................................................................................... 75
18. KM-1100MRH....................................................................................................... 76
19. KM-1340MAH ...................................................................................................... 77
20. KM-1340MWH ..................................................................................................... 78
21. KM-1340MRH with URC-14F ............................................................................... 79
22. KM-1340MRH3 with URC-14F ............................................................................ 80
23. KM-1601MRH with URC-21F ............................................................................... 81
24. KM-1601MRH with URC-22F ............................................................................... 82
25. KM-1601MRH3 with URC-21F ............................................................................. 83
26. KM-1601MRH3 with URC-22F ............................................................................. 84
4
C. Wiring Diagrams ......................................................................................................... 85
1. Diagrams Without Harvest Pump Timer Relays ..................................................... 85
a) KM-320M_H, KM-515M_H, KM-600MAH ........................................................ 85
b) KM-650MAH (V-1 and earlier), KM-650MWH (V-1 and earlier),
KM-901MAH (B-0 and earlier), KM-901MWH (C-0 and earlier) ....................... 86
c) KM-650MRH (V-1 and earlier), KM-901MRH (C-0 and earlier) ........................ 87
d) KM-901MWH (D-1 and later), KM-901MRH (C-1 and later) ............................. 88
e) KM-1340MAH, KM-1340MWH ......................................................................... 89
f) KM-1340MRH .................................................................................................. 90
g) KM-1601MRH .................................................................................................. 91
h) KM-901MRH3, KM-1340MRH3, KM-1601MRH3 ............................................. 92
2. Diagrams With Harvest Pump Timer Relays .......................................................... 93
a) KM-340M_H ..................................................................................................... 93
b) KM-515MAH .................................................................................................... 94
c) KM-650MAH (V-2 to C-2), KM-650MWH (V-2 to C-2),
KM-901MAH (B-1 to C-2) ................................................................................. 95
d) KM-650MAH (D-1 and later), KM-650MWH (D-1 and later),
KM-901MAH (D-1 and later) ............................................................................. 96
e) KM-650MRH (V-2 to C-1) ................................................................................. 97
f) KM-650MRH (C-2 and later) ............................................................................. 98
g) KM-1100M_H ................................................................................................... 99
5

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service this appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or severe damage to equipment.
• The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuses, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker could result in death or serious injury.
• Move the control switch to the "OFF" position and turn off the power supply before servicing. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
• To reduce the risk of electric shock, do not touch the control switch with damp hands.
• Do not make any alterations to the unit. Alterations could result in electric shock, injury, re, or damage to the unit.
• The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
6
WARNING, continued
• Children should be properly supervised around this appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.
Additional Warning for Remote Models
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and ground connection to the remote condenser unit are supplied from the icemaker. Failure to properly ground the remote condenser unit could result in death or serious injury.
• Move the icemaker control switch to the "OFF" position and turn off the power supply to the icemaker before servicing the remote condenser unit. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water damage.
• In areas where water damage is a concern, install in a contained area with a oor drain.
• Install the appliance in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the icemaker on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the icemaker for these occasions, follow the instructions in "VI. Preparing the Appliance for Periods of Non-Use."
• Do not place objects on top of the appliance.
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in the dispenser unit/ice storage bin.
7

I. Construction and Water/Refrigeration Circuit Diagram

A. Construction

1. Air-Cooled Models (MAH)

Thermostatic Expansion Valve
Spray Tubes
Inlet Water Valve
Thermostatic Bin Control
Cleaning Valve
Control Switch
Float Switch
Water Pump
Control Box
Water Supply Inlet
Hot Gas Valve
Condenser
Fan Motor
High-Pressure Switch
Drier
Liquid Line Valve KM-515MAH
Thermostatic Bin Control Bracket & Bulb Holder
Compressor
Mechanical Bin Control and Bracket
Model Shown: KM-515MAH
8

2. Water-Cooled Models (MWH)

Thermostatic Expansion Valve
Spray Tubes
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
High-Pressure Switch
Thermostatic Bin Control
Cleaning Valve
Control Switch
Float Switch
Water Pump
Compressor
Water Regulating Valve
Condenser
Control Box
Liquid Line Valve KM-320MWH and KM-515MWH
Drier
Thermostatic Bin Control Bracket & Bulb Holder
Mechanical Bin Control and Bracket
Model Shown: KM-515MWH
9

3. Remote Models (MRH/3)

Spray Tubes
Inlet Water Valve
Cleaning Valve
Control Switch
Thermostatic Expansion Valves
Water Supply Inlet
Hot Gas Valve
Junction Boxes
Thermostatic Bin Control
Float Switch
Water Pump
Compressor
Thermostatic Bin Control Bracket & Bulb Holder
Control Box
Receiver Tank
Drier
Liquid Line Valve
Mechanical Bin Control and Bracket
Model Shown: KM-901MRH
10

B. Water/Refrigeration Circuit Diagram

1. Air-Cooled Models (MAH)

Spray Tubes
Inlet Water Valve
Condenser
Drier
Water Supply
Float Switch
Drain
Water Tank
Evaporator
Thermistor
Water Pump
Pump Out
Freeze
Fan
Liquid Line Valve (KM-515MAH)
Heat Exchanger
Suction Line
Compressor
High-Pressure Switch
Strainer
Hot Gas Val ve
Discharge Line
Refrigeration Circuit
Water Circuit
Thermostatic Expansion Valve
Check Valve
11

2. Water-Cooled Models (MWH)

Spray Tubes
Inlet Water Valve
Water Regulating Valve
Condenser
Water Supply
Float Switch
Drain
Water Tank
Evaporator
Thermistor
Water Pump
Pump Out
Freeze
Liquid Line Valve (KM-320MWH and KM-515MWH)
Heat Exchanger
Suction Line
Compressor
Drier
High-Pressure Switch
Strainer
Hot Gas Val ve
Discharge Line
Refrigeration Circuit
Water Circuit
Thermostatic Expansion Valve
Check Valve
12

3. Remote Models (MRH/3)

Spray Tubes
Inlet Water Valve
Condenser
Fan
Headmaster (C.P.R.)
Access Val ve
Water Supply
Cleaning Valve
Float Switch
Drain
Water Tank
Thermistor
Water Pump
Freeze Pump-Out
Receiver
Evaporator
Liquid Line Val ve
Heat Exchanger
Suction Line
Compressor
Drier
High-Pressure Switch
Strainer
Hot Gas Val ve
Check Valves (KM-901MRH)
Discharge Line
Refrigeration Circuit
Water Circuit
Thermostatic Expansion Val ve
Check Valve
13

II. Sequence of Operation and Service Diagnosis

A. Sequence of Operation Flow Chart

1. "E" and "G" Control Board without Harvest Pump Timer Operation

10th cycle
(except KM-515M_H)
(S4 dip switch 5 & 6)
2 sec., then reverses
for 10/20 sec. (S4 dip
• Factory set for every
4. Pump-Out Cycle
• Pump motor stops for
switch 3 & 4)
FS in control
Comp continues
FMR continues
FS opens or
freeze timer
terminates
HGV energized
WV energized (KM-320M_H S4 dip
switch 3 & 4)
PM de-energizes for 2 sec.,
then reverses for 10/20 sec.
FM de-energized
LLV de-energized
3. Freeze Cycle
2. Harvest Cycle
• Minimum freeze time: 5 min.
• Maximum freeze time: freeze
• Maximum inlet water valve time: 6 min.
• Maximum harvest time: 20 min.
timer setting
(S4 dip switch 9 & 10)
5-min. minimum
freeze timer in
1 to 3-min. harvest
timer in control
Thermistor in
control
control
(S4 dip switch 1 & 2)
FS closed
Comp continues
FS check
Thermistor temperature
FS closed
Comp energized
FS check
FMR continues
FM energized
LLV energized
PM energized
HGV de-energized
WV de-energized
FS open
reaches 48°F (9°C) (3.9 kΩ
or less). Harvest timer starts
(1 to 3 min.).
FMR energized
HGV energized
WV energized
FS open
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the icemaker. When in the "WASH" position,
power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the outside of the
evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer ow over both the outside and the inside
of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the icemaker will not restart when the
control switch is placed in the "ICE" position.
See next page.
Startup
WV energized
If FS is open, Comp stops and cycle returns to 1-min. ll.
Legend:
Comp–compressor
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
LLV –liquid line valve
PM–pump motor
WV–inlet water valve
Shutdown and Restart
1. 1-Minute
Fill Cycle
"E" and "G" Control Board Without Harvest Pump Timer Operation Flow Chart
Cycle
Steps
14
To 1. 1-Minute Fill Cycle
Icemaker starts at
"1. 1-Minute Fill Cycle."
3. Ice Level Lowered
MBC closed
(MBC actuator paddle disengaged)
Green "BC CLOSED" LED on
Yellow "BC OPEN" LED off
2. Icemaker Off
All components
de-energized.
To 1. 1-Minute Fill Cycle
Yellow "BC OPEN" LED continues. All
components de-energized.
"E" and "G" Control Board Without Harvest Pump Timer Operation Flow Chart, Continued
3. Ice Level Lowered
No ice touching
TBC bulb.
Icemaker starts at
"1. 1-Minute Fill Cycle."
TBC closed
2. Icemaker Off
All components
1. Bin Full
de-energized.
Within 10 sec.
after ice contacts
TBC bulb,
icemaker shuts
down.
TBC open
All components
de-energized
Ice contacts TBC bulb
1. Bin Full
Shutdown Delay:
Fill Cycle–15 sec. after activation.
Harvest Cycle–At the end of the harvest cycle, or up to 15 sec. into the
freeze cycle if activated at the end of the harvest cycle.
the 5-min. short cycle protection timer terminates.
Freeze Cycle–15 sec. after activation if activated at least 15 sec. before
Otherwise, at the end of the next harvest cycle.
MBC open (MBC actuator paddle engaged)
Green "BC CLOSED" LED off
Yellow "BC OPEN" LED on
Mechanical Bin Control Shutdown Sequence Flow Chart
Shutdown
TBC
Shutdown
Thermostatic Bin Control Shutdown Sequence Flow Chart
and Restart
Operation
and Restart
MBC Operation
15
Legend:
MBC–mechanical bin control
TBC–themostatic bin control

2. "G" Control Board with Harvest Pump Timer Operation

10th cycle
(except KM-515M_H)
(S4 dip switch 5 & 6)
2 sec., then reverses
for 10/20 sec.
• Factory set for every
4. Pump-Out Cycle
• Pump motor stops for
(S4 dip switch 3 & 4)
FS in control
Comp continues
FM continues (KM-1100)
FMR continues
FS opens or
freeze timer
terminates
(KM-1100)
HGV energized
PM de-energizes for 2 sec.,
then reverses for 10/20 sec.
FM de-energized
LLV de-energized
3. Ice Level Lowered
Icemaker starts at
"1. 1-Minute Fill Cycle."
To 1 above
MBC closed
(MBC actuator paddle disengaged)
Green "BC CLOSED" LED on
Yellow "BC OPEN" LED off
3. Freeze Cycle
2. Harvest Cycle
• Minimum freeze time: 5 min.
• Maximum freeze time: freeze timer
• Maximum inlet water valve time: 6 min. or the length of
harvest minus 50 sec. (S4 dip switch 7), whichever is shorter.
setting (S4 dip switch 9 & 10)
• Maximum harvest time: 20 min.
5-min. minimum
freeze timer in
Harvest Pump
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Thermistor in
control
control
Timer
FS closed
50 sec.
FS closed
2. Icemaker Off
All components
de-energized.
Comp continues
FM continues
FMR continues
FM energized (except KM-1100)
LLV energized
PM energized
HGV de-energized
Yellow "BC OPEN" LED continues. All
FS check
FS open
PM energized
WV de-energized
Thermistor temperature reaches
48°F (9°C) (3.9 kΩ or less). Harvest
timer starts (1 to 3 min.).
Comp energized
FM energized (KM-1100)
FMR energized
HGV energized
WV energized
components de-energized.
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the icemaker. When in the "WASH" position, power is
supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the outside of the evaporator plate assembly.
With the cleaning valve open, the cleaner and sanitizer ow over both the outside and the inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the icemaker will not restart when the control switch is
placed in the "ICE" position.
freeze cycle if activated at the end of the harvest cycle.
Fill Cycle–15 sec. after activation.
"G" Control Board With Harvest Pump Timer Operation Sequence Flow Chart
FS open
1. 1-Minute
Cycle
Fill Cycle
Steps
FS check
WV energized
Startup
Shutdown Delay:
1. Bin Full
If FS is open, Comp stops and cycle returns to 1-min. ll.
Shutdown
and Restart
16
the 5-min. short cycle protection timer terminates.
Harvest Cycle–At the end of the harvest cycle, or up to 15 sec. into the
Freeze Cycle–15 sec. after activation if activated at least 15 sec. before
Otherwise, at the end of the next harvest cycle.
MBC open (MBC actuator paddle engaged)
Green "BC CLOSED" LED off
Yellow "BC OPEN" LED on
Legend:
Comp–compressor
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
LLV–liquid line valve
MBC–mechanical bin control
PM–pump motor
MBC Operation
WV–inlet water valve

B. Service Diagnosis

WARNING
• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Control switch in "OFF" position does not de-energize all loads Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Before servicing the appliance, move the control switch to the "OFF" position and turn off the power supply.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the appliance and dispenser unit/ice storage bin are clean after service.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation, proper voltage per nameplate, and adequate water supply. Check CB using the steps in "II.C. Control Board Check." Check dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip switch 1 through 5 ("G" CB) are in the factory default position. S4 dip switch 1, 2, 5, 6 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
Note: • When checking high voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
• On 208-230/60/1 models with main transformer and 208-230/60/3 models, the appliance neutral (W) is provided through the main transformer. To conrm a good neutral, check for 60VAC from white (W) neutral to ground (GND). If60VAC is present, neutral is good. If 60VAC is not present, check 208-230VAC main power supply to main transformer. If 208-230VAC is present, check main transformer continuity.
• When checking voltage from the CB K1 connector (10 pin connector), pull CBK1connector out slightly to allow room for multimeter test leads contact.
1) Turn off the power supply, then access the control box. Move the control switch to the "OFF" position. Clear any ice from BC.
2) Check that the 115VAC 10A fuse is good.
17

1. "E" and "G" Control Board without Harvest Pump Timer Diagnosis

3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5-sec. delay occurs.
• "E" Control Board: CB red "POWER OK" LED turns on.
• "G" Control Board: CB red "POWER OK" LED and green "BC CLOSED" LEDturn on.
Note: • CB red "POWER" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.C. Control Board Check."
"G" CB with Thermostatic Bin Control: If yellow "BC OPEN" LED is on, check that CB red K4 connector has jumper 4A4883G01 properly connected.
• "G" CB with Mechanical Bin Control: If yellow "BC OPEN" LED is on (indicating a full bin), check MBC. See"II.D.2. Mechanical Bin Control Check and Cleaning."
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm closed TBC and
10A fuse is good. If TBC is open, remove ice from bulb and warm bulb in hand. IfTBC does not close, replace TBC. See "II.D.1. Thermostatic Bin Control Check." Check for 115VAC at control switch #1(BR) to neutral (W) then at control switch #2(P) to neutral (W). If 115VAC is present on #1 (BR) and not on #2(P), replace control switch. If 115VAC is present on control switch #2 (P), check for 115VAC at HPS (P) to neutral (W) then HPS (BK) to neutral (W). If115VAC is present at HPS (P) and not at HPS (BK), HPS is open. See HPS Diagnosis below. If 115VAC is present at HPS (BK), check for 10.5VAC at CB K2#1 red wire to CB K2 #2 red wire. If 10.5VAC is not present, check that the cleaning valve is closed and the interlock switch is closed. Next, check CT continuity. Ifopen replace CT.
b) HPS Diagnosis: Check that the condenser coil is not clogged or restricted. Let
refrigeration circuit pressures equalize. If HPS does not reset and pressures are equalized, replace HPS. If pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction. Check that there are no restrictions in the refrigeration circuit. Harvest Cycle: HGV, strainer, or check valve. Freeze Cycle: FM, FMR, TXV, HM, LLV, strainer, check valve, drier, and damaged line set or tting. Also conrm WRV opens in freeze cycle.
Conrm that the location meets installation requirements:
• The icemaker is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C).
• Allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required.
• The appliance should not be located in a corrosive environment.
18
4) 1-Minute Fill Cycle – LED 4 is on. WV energizes. After 1 min., CB checks for a closed FS. If FS is closed, harvest cycle begins. If harvest cycle begins (Comp, HGV, and FMR energize), continue to step 5. If FS is open, WV remains energized through additional 1-min. ll cycles until water enters the water tank and FS closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: Check that water enters the water tank. If not, check that the water supply line shut-off valve is open and screens or external lters are clear. Check for 115VAC at CB K1 #6(O) to neutral(W). If 115VAC is not present, replace CB. If 115VAC is present, and WV does not energize, check for 115VAC at WV. If 115VAC is present, check coil continuity. Ifopen, replace WV. If the water tank lls, but the appliance fails to start harvest (Comp energized), check for open FS. See "II.E. Float Switch Check and Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB.
5) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV continues. Comp, FMR, and HGV energize. CB monitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). The harvest timer has settings of 60, 90, 120, and 180sec. Thepump-out timer (S4dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump-out (S4 dip switch 5 & 6). WV remains energized during harvest for a maximum of 6min. or the length of harvest, whichever is shorter.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 or #9 (V) to neutral (W). If 115VAC is not present, check for 115VAC at CB K1 #7 or #10 (BR) to neutral (W). If115VAC is present at #7 or #10 (BR) and not at #1 or #9 (V), replace CB. If 115VAC is present, check for 115VAC at CR or MC solenoid. If 115VAC is present, conrm contacts are closed. If not, replace CR or MC. If CR or MC contacts are closed, check Comp external overload, Comp start and run capacitors, Comp start relay, and Comp motor winding.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W). If115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGV coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
Ifenergized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by.
19
e) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). Check discharge line temperature. For a thermistor check, see "II.F.Thermistor Check." If 1-min. ll cycle starts after harvest timer terminates, check that FS is clean and operating properly, see "II.E. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot, replace CB.
Note: The minimum total time allowed by CB for a complete harvest cycle is 2 min.
Maximum harvest time allowed is 20 min.
NOTICE! On models with "G" control board and no harvest pump timer relays, S4dip switch 7 must remain off. Otherwise, PM energizes in reverse direction the last 50 seconds of harvest and empties water from water tank.
6) Freeze Cycle – LED 1 is on. Comp and FMR continue. PM, FM, and LLVenergize. WV and HGV de-energize. Appliance is held in freeze by a 5-min. short cycle protection timer. After 5-min. timer terminates and FSopens, freeze cycle terminates.
a) Freeze Cycle Diagnosis: Conrm Comp and FMR continue. Conrm that
PM, FM, and LLV energize. Conrm WRV opens. Next, conrm WV and HGV de-energize. During the rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV and FM energize, TXV and HM operate correctly, WRV opens, Comp is efficient, and refrigerant charge is correct. See "VIII.A. Specication Sheet" and "VIII.B.Performance Data."
b) Comp and FMR Diagnosis: If Comp and FMR de-energize once freeze begins,
check that appliance has not shut off on HPS ("POWER OK" LED off). If so, check "3)b) HPS Diagnosis" above. If "POWER OK" LED is on, check for 115VAC at CB K1#1 (V) or #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on, replace CB. If 115VAC is present, check for 115VAC at CR or MC coil. If 115VAC is present, check CR or MC coil and contact continuity. Replace as needed. If CR or MC is ok, check Comp external overload, start relay, and start and run capacitors. Next, check Comp motor winding continuity. If Comp is energized but evaporator is not cooling, check for an inefficient Comp. See "VIII.B. Performance Data." If Comp is energized but FMR is not, check for 115VAC at the FMR junction box. If 115VAC is not present, check icemaker wiring connections. If 115VAC is present, check for voltage at condenser unit. If115VAC is not present, check eld wiring connections. If 115VAC is present, check FMR capacitor, motor winding, and fan blade for binding.
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to
neutral (W). If 115VAC is present after PM energizes, replace CB. If 115VAC is not present, replace WV (bypassing). If HGV did not de-energize, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present after PM energizes, replace CB. If115VAC is not present, replace HGV (bypassing).
20
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV. If PM
de-energizes once freeze begins, check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized, check for 115VAC at control switch #5 (R) to neutral (W). If 115VAC is present at CB K1 #4 (R) and not at control switch #5 (R), check control switch continuity between #5 (R) and #4 (R). Replace as needed. If 115VAC is present at control switch #5 (R) to neutral (W), check PM capacitor and motor winding continuity.
e) FM and LLV Diagnosis: If FM or LLV does not energize, check for 115VAC at CB
K1#3 (BK) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present: For FM, check capacitor, motor winding, and blade for binding. For LLV, check coil voltage and continuity.
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.B. Performance Data." Next, check HM operation. If refrigeration pressures are above HM setpoint and HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing between warm and cold conditions indicate a good TXV. If a 10 to 15pound swing is not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.B. Performance Data." If refrigerant pressures are correct and WRV does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve Adjustment (water-cooled models)."
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.E. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this manual. See "VIII.B. Performance Data."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during 1 min.
ll and harvest cycles. If not, check water supply lters, shut-off valve, WV screen. Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check that CV is not leaking by (water owing down the potable drain). If CV is leaking by, remove and clean CV, replace rubber seat and spring if necessary. If water tank is full, see "II.E. Float Switch Check and Cleaning" for erratic operating FS.
21
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the rst pump-out is dependent on CB. "E" CB rst pump-out is after the rst freeze cycle. "G" CB rst pump-out is determined by S4 dip switch 5 & 6. See the table below.
"E" & "G" Control Board Settings 1st Pump-Out
S4 Dip Switch Setting
No. 5 No. 6
OFF OFF Every cycle After 1st freeze cycle After 2nd freeze cycle
ON OFF Every 2 cycles After 3rd freeze cycle
OFF ON Every 5 cycles After 6th freeze cycle
ON ON Every 10 cycles After 11th freeze cycle
Pump-Out
Frequency
"E" Control Board "G" Control Board
Comp and FMR continue, HGV energizes. If S4dip switch 3 & 4 are set to 3 off and 4 on, LED 4 turns on and WV energizes. FM and LLVde-energize. PM stops for 2 sec., then reverses for 10/20 sec. depending on pump-out timer (S4 dip switch 3 & 4) setting. When the pump-out timer terminates, pump-out is complete. The pump-out frequency control (S4 dip switch 5 & 6) is factory set, and generally no adjustment is required. However, the pump-out frequency control can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. For details, see "III.C.4. Pump-Out Frequency Control (S4 dip switch 5 & 6)."
Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), disconnect CB black K5 connector (FS connector) after 5 min. of freeze. Check that PM stops and re-starts and water is owing down the drain through CV. If PM does not stop and re-start, check that CB LEDs 1, 3, and 2 are on. If not, replace CB. IfLEDs1,3, and 2 are on and PM does not energize, check for 115VAC at CB K1 #5 (DBU) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, make sure the drain line is not clogged and that CV is clean and operating properly.
Conrm FM and LLV de-energize. If FM or LLV is energized with LEDs 1, 3, and 2 on, replace CB.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5 above. Note: Appliance continues to cycle until TBC or MBC is satised or power is turned off.
The appliance always restarts at the 1-min. ll cycle.
22
9) Shutdown
a) Thermostatic Bin Control (TBC):
When the appliance is running, hold ice in contact with the thermostatic bulb. TBC switch opens within 10 sec., shutting down the appliance. TBC is factory set, and generally no adjustment is required. However, adjustment may be needed in some conditions, particularly at higher altitude locations.
NOTICE
• On "E" control boards, do not adjust S4 dip switch 7 out of the factory default position. This dip switch must be left in the factory default position or the appliance will not operate correctly.
• On "G" control boards, CB red K4 connector jumper (4A4883G01) must be in place. Diagnosis: See "II.D.1. Thermostatic Bin Control Check."
b) Mechanical Bin Control:
See "II.D.2. Mechanical Bin Control Check and Cleaning."
Legend: BC–bin control; CB–control board; Comp–compressor; CV–check valve;
FM–fan motor; FMR–fan motor-remote; FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; L LV –liquid line valve; MBC–mechanical bin control; PM–pump motor; TBC–thermostatic bin control; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water
valve
23

2. "G" Control Board with Harvest Pump Timer Diagnosis

3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5-sec. delay occurs. CB red "POWER OK" LED and green "BC CLOSED" LED turn on. If yellow "BC OPEN" LED is on (indicating a full bin), check MBC. Move ice away from MBC actuator paddle. If yellow "BC OPEN" LED stays on, see"II.D.2. Mechanical Bin Control (MBC) Check."
Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.C. Control Board Check."
• Conrm CB green "BC CLOSED" LED is on. If CB yellow "BC OPEN" LED is on, remove ice from BC. If no ice is around BC and yellow "BC OPEN" LED is on, see "II.D.2. Mechanical Bin Control (MBC) Check."
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm 10A fuse is good.
Check for 115VAC at control switch #1 (BR) to neutral (W) then at control switch #2(P) to neutral (W). If 115VAC is present on #1 (BR) and not on #2(P), replace control switch. If 115VAC is present on control switch #2 (P), check for 115VAC at HPS (P) to neutral (W) then HPS (BK) to neutral (W). If115VAC is present at HPS (P) and not at HPS (BK), HPS is open. See HPS Diagnosis below. If 115VAC is present at HPS (BK), check for 10.5VAC at CB K2#1 red wire to CB K2 #2 red wire. If 10.5VAC is not present, check that the cleaning valve is closed and the interlock switch is closed. Next, check CT continuity. If open, replace CT.
b) HPS Diagnosis: Check that the condenser coil is not clogged or restricted. Let
refrigeration circuit pressures equalize. If HPS does not reset and pressures are equalized, replace HPS. If pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction. Check that there are no restrictions in the refrigeration circuit. Harvest Cycle: HGV, strainer, or check valve. Freeze Cycle: FM, FMR, TXV, WRV, HM, LLV, strainer, check valve, drier, and damaged line set or tting.
Conrm that the location meets installation requirements:
• The appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C).
• Allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required.
• The appliance should not be located in a corrosive environment.
24
4) 1-Min. Fill Cycle – LED 4 is on. WV and X11 relay energize. After 1 min., CB checks for a closed FS. If FS is closed, the harvest cycle begins. If harvest cycle begins (Comp, HGV, FMR energized), continue to step 5a. If FS is open, WV remains energized through additional 1-min. ll cycles until water enters the water tank and FS closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: Check that water enters the water tank. If not, check that the water supply line shut-off valve is open and screens or external lters are clear. Check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, and WV does not energize, check for 115VAC at WV. If 115VAC is present, check coil continuity. Ifopen, replace WV. If the water tank lls, but the appliance fails to start harvest (Comp energized), check for open FS. See "II.E. Float Switch Check and Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB.
5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp,
FMR, HGV, and X10 relay energize. CBmonitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). The harvest timer has settings of 60, 90, 120, and 180 sec. The pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump-out (S4 dip switch 5 & 6). WV and X11 relay are energized during harvest for a maximum of 6 min. or the length of harvest minus 50sec., whichever is shorter. 50sec. before harvest terminates, PM energizes. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 or #9 (V) to neutral (W). If 115VAC is not present, check for 115VAC at CB K1 #7 or #10 (BR) to neutral (W). If115VAC is present at #7 or #10 (BR) and not at #1 or #9 (V), replace CB. If 115VAC is present, check for 115VAC at CR or MC solenoid. If 115VAC is present, conrm contacts are closed. If not, replace CR or MC. If CR or MC contacts are closed, check Comp external overload, Comp start and run capacitors, Comp start relay, and Comp motor winding. If Comp is energized and evaporator is not warming, check that HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to a neutral(W). If 115VAC is not present and LED 2 is on, replace CB. If115VAC is present, check coil voltage and continuity. Replace as needed. Conrm that LLV is de-energized and closed (not bypassing). If energized, replace CB. Ifde-energized and bypassing, replace LLV. Conrm WRV is not leaking by. If evaporator is warming, PM energizes for the last 50 sec. of harvest.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W). If115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGV coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing). If
energized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by.
25
5b) Harvest Pump Timer – LEDs 1, 3, and 2 are on. When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). 50 sec. before the harvest timer terminates, LED 3turns on and PM energizes. Comp, FMR, HGV, and X10 relay continue. LED 4 turns off, WV and X11 relay de-energize. Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it warmed to 48°F (9°C) or warmer? Conrm thermistor status. See "II.F. Thermistor Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does not energize 50 sec. before harvest terminates, replace CB. If WV continues, check for 115VAC at CB K1 #6 (O). If115VAC is present, and LED 4 is off, replace CB. If LED 3is on and PM is not energized, check for 115VAC at CB K1 #5(DBU). If115VAC is not present, replace CB. If 115VAC is present and PM is not energized, check for 115VAC at X10relay terminal #7 (Y) to neutral (W). If 115VAC is not present, check for 115VAC at X10 relay terminal #3 (P) to neutral (W) and X10 relay terminal #5 (Y) to neutral (W). If 115VAC is present on terminal #3(P) and not on terminal #5 (Y), replace X10 relay. If 115VAC is present on X10 relay terminal #7 (Y) and PM is not energized, check for 115VAC at X10 relay terminal #4 (R) to neutral (W) and terminal #6 (DBU) to neutral (W). If 115VAC is present on terminal #6(DBU) and not on terminal #4 (R), replace X10 relay. If 115VAC is present on X10relay terminal #4 (R), check control switch contact continuity between terminals #4(R) and #5(R). Ifcontacts are open, replace control switch. If contacts are closed and 115VAC is present between control switch terminal #5 (R) and neutral (W), check PM capacitor and motor winding continuity.
5c) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). Check discharge line temperature. For a thermistor check, see "II.F.Thermistor Check." If 1-min. ll cycle starts after harvest timer terminates, check that FS is clean and operating properly, see "II.E. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot, replace CB. Note: The minimum total time allowed by CB for a complete harvest cycle is 2 min.
Maximum harvest time allowed is 20 min.
NOTICE! S4 dip switch 7 must remain on. Otherwise, PM will not energize during the last 50 sec. of harvest.
26
6) Freeze Cycle – LED 1 is on. Comp, FMR, and PM continue. FM and LLV energize. HGV and X10 relay de-energize. Appliance is held in freeze by a 5-min. short cycle protection timer. After 5-min. timer terminates and FS opens, freeze cycle terminates. Note: PM power supply switches from CBK1 #5(DBU) in harvest to K1 #4 (R) in freeze.
a) Freeze Cycle Diagnosis: Conrm Comp, FMR, and PM continue. Conrm that
FM and LLV energize. Conrm WRV opens. Next, conrm HGV and X10 relay de-energize. During the rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV and FM energize, TXV and HM operate correctly, WRV opens, Comp is efficient, and refrigerant charge is correct. See "VIII.A. Specication Sheet" and "VIII.B.Performance Data."
b) Comp and FMR Diagnosis: If Comp and FMR de-energize once freeze begins,
check that appliance has not shut off on HPS ("POWER OK" LED off). If so, check "3)b) HPS Diagnosis" above. If "POWER OK" LED is on, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on, replace CB. If 115VAC is present, check for 115VAC at CR or MC coil. If 115VAC is present, check CR or MC coil and contact continuity. Replace as needed. If CR or MC is okay, check Comp start relay and start and run capacitors. Next, check Comp motor winding continuity. If Comp is energized but evaporator is not cooling, check for an inefficient Comp. See "VIII.B. Performance Data." If Comp is energized but FMR is not, check for 115VAC at the FMR junction box. If 115VAC is not present, check icemaker wiring connections. If 115VAC is present, check for voltage at condenser unit. If115VAC is not present, check eld wiring connections. If 115VAC is present, check FMR capacitor, motor winding, and fan blade for binding.
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to
neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB. If 115VAC is not present, replace WV (bypassing). If HGV did not de-energize at the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present 50 sec. after PM energizes, replace CB. If 115VAC is not present, replace HGV (bypassing).
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV. If PM
de-energizes once freeze begins, check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized, check for 115VAC at control switch #5 (R) to neutral (W). If 115VAC is present at CB K1 #4 (R) and not at control switch #5 (R), check control switch continuity between #5 (R) and #4 (R). Replace as needed. If 115VAC is present at control switch #5 (R) to neutral (W), check PM capacitor and motor winding continuity.
e) FM and LLV Diagnosis: If FM or LLV does not energize, check for 115VAC at CB
K1#3 (BK) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present: For FM, check capacitor, motor winding, and blade for binding. For LLV, check coil voltage and continuity.
27
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.B. Performance Data." Next, check HM operation. If refrigeration pressures are above HM setpoint and HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.B. Performance Data." If refrigerant pressures are correct and WRV does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve Adjustment (water-cooled models)."
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.E. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this manual. See "VIII.B. Performance Data."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during 1 min.
ll and harvest cycles. If not, check water supply lters, shut-off valve, WV screen. Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check that CV is not leaking by (water owing down the potable drain). If CV is leaking by, remove and clean CV, replace rubber seat and spring if necessary. If water tank is full, see "II.E. Float Switch Check and Cleaning." for erratic operating FS.
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the rst pump-out is determined by S4 dip switch 5& 6. See the table below.
"G" Control Board Settings
S4 Dip Switch Setting
No. 5 No. 6
OFF OFF Every cycle After 2nd freeze cycle
ON OFF Every 2 cycles After 3rd freeze cycle
OFF ON Every 5 cycles After 6th freeze cycle
ON ON Every 10 cycles After 11th freeze cycle
Pump-Out
Frequency
"G" Control Board
Comp and FMR continue, HGV energizes. If S4dip switch 3 & 4 are set to 3 off and 4 on, LED 4 turns on and WV and X11 relay energize, energizing X10relay.
NOTICE!S4dip switch 3 & 4 must not be set to 3 off and 4 on. Otherwise, PM will rotate in freeze cycle direction instead of pump-out direction. FM and LLV
de-energize. PM stops for 2 sec., then reverses for 10/20 sec. depending on pump-out timer (S4dip switch 3 & 4) setting. When the pump-out timer terminates, pump-out
28
is complete. The pump-out frequency control (S4 dip switch 5 & 6) is factory set, and generally no adjustment is required. However, the pump-out frequency control can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. For details, see "III.C.4. Pump-Out Frequency Control (S4 dip switch 5 & 6)."
Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after 5min. of freeze disconnect CB black K5 connector (FS connector). Check that PM stops and re-starts and that PM rotation is correct (water owing down the drain through CV). If PM does not stop and re-start, check that CB LEDs 1, 3, and 2 are on. If not, replace CB. IfLEDs1,3, and 2 are on and PM does not energize, check for 115VAC at CB K1 #5 (DBU) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, check that X10 relay is de-energized. If not, check X11 relay status. If X11 relay is energized, replace CB. If X11 relay is de-energized and X10 relay is energized, replace X11 relay (contacts sticking). If X10 relay is de-energized, check for 115VAC at terminal #6 (DBU) to neutral (W) and terminal #2 (DBU) to neutral (W). If 115VAC is present on terminal #6 (DBU) and not on terminal #2 (DBU), replace X10 relay. If PM is energized and rotating in pump-out rotation, make sure the drain line is not clogged and that CV is clean and operating properly.
Conrm FM and LLV de-energize. If FM or LLV are energized with LEDs 1, 3, and 2 on, replace CB.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above.
Note: Appliance continues to cycle until MBC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
9) Shutdown
Mechanical Bin Control:
See "II.D.2. Mechanical Bin Control Check."
Legend: BC–bin control; CB–control board; Comp–compressor; CV–check valve;
FM–fan motor; FMR–fan motor remote; FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; L LV –liquid line valve; MBC–mechanical bin control; PM–pump motor; TXV–thermostatic expansion
valve; WRV–water regulating Valve; WV–inlet water valve
29

C. Control Board Check

Before replacing CB that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB
while CB is beeping. WARNING!Risk of electric shock. Care should be taken not to touch live terminals. Once reset, the icemaker starts at the 1-minute ll cycle. For audible alarm information, see "III.B. LED Lights and Audible Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip
switch 1 through 5 ("G" CB) are in the factory default position. S4 dip switch 1, 2, 5,6 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, control
voltage is good, continue to step 3. If the "POWER OK" LED is off, check CT secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary circuit has proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage, check CT primary circuit. Check
for 115VAC at CB K1 connector pin #10 (BR) to neutral (W) for 115VAC. Always choose a white (W) neutral wire to establish a good neutral connection when checking voltages. For additional checks, see "II.G.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control
switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct lighting sequence, see the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. Components (e.g., compressor) cycle during the test.
Control
Board
"E" 2, 3, 4, 1
"G" 1, 4, 3, 2
Correct LED
Lighting Sequence
Following the test, the icemaker begins operation at the 1-minute ll cycle for both "E" and "G" control boards. If the LEDs do not light as described above, replace CB.
4) To verify voltage output from CB to the components, slide the CB K1 connector out far
enough to allow multimeter lead contact. With the icemaker in the cycle to be tested, check output voltage from the corresponding pin on CB K1 connector to a neutral (Wwire). If output voltage is not found and the appropriate LED is on, replace CB.
Legend: CB–control board; CT–control transformer
30
Loading...
+ 69 hidden pages