Hoshizaki IM-51BAE User Manual

Page 1
IM SERVICE TRAINING
1
Featuring the
IM-51BAE
80041 9/9/99
Page 2
All IM models have similar sequence of operation. This manual is designed as a generic IM Training manual.
A standard 120 volt power cord provides the electrical connection. The unit is designed to operate on a separate 15 amp circuit.
2
The water supply connection is ½”FIP and is located at the bottom right rear of the unit. A minimum 3/8” water line is required for proper operation.
The drain connection is ¾”MIP and is located on the left rear of the unit. Since the unit will likely be enclosed, it is recommended to use flexible supply and drain connections. This will allow easy removal if service is necessary. Access to the evaporator compartment is gained by removing the front and top covers.
Open the bin door and remove the front cover screws and drain pan thumbscrews. Lower the drain pan pipe into the drain hole.
Lift upward on the front panel and push backward to remove the top cover.
Page 3
This horizontal evaporator and water distribution system is unique to the IM series.
The ABS water plate sprays water up into the evaporator cells to form the square IM cube.
3
The moveable water pan assembly includes the water plate, reservoir pan, and pump motor assembly.
Tension springs connect two cam arms to the water plate assembly. An actuator motor rotates the cam arms to raise and lower the water pan during the ice making cycle.
Page 4
4
The front cam arm has a switch lever that operates the actuator toggle switch located above the pan assembly.
The actuator toggle switch controls the direction of rotation for the actuator motor and energizes the pump motor during the freeze cycle.
When the switch is in the right
position, the actuator motor rotates counter clock wise to lower the water pan assembly.
When the switch is in the left
position, the actuator motor turns clock wise to raise the water pan assembly.
The IM51 uses a mechanical proximity switch bin control assembly located in the bin area.
When ice fills the bin and pushes the control arm over, the activator magnet moves to the switch and closes the contacts.
The IM bin control closes the contacts to signal the control board to shut down the unit. This is different from the standard KM control, which opens the contacts to de-energize the unit.
Page 5
The louver has a flip down cover to access the control switch.
The switch has 3 positions.
ICE, OFF, & WASH.
The louver covers the compressor compartment. Remove the louver screws and lift the louver forward to access the condenser coil fan assembly and compressor.
5
For easy access during preventative maintenance or service, the inlet water valve is located in the front right hand corner of the compressor compartment.
Page 6
6
The control box is accessed from the rear of the unit. Remove the screws holding the pipe cover and the control box cover to reach the control board and other components.
A solid state board controls the IM operation. Several adjustments are included on the board. These adjustments are factory set for proper operation.
CONTROL SWITCH TO ICE.
INITIAL HARVEST CYCLE.
FREEZE CYCLE.
NORMAL HARVEST CYCLE.
FREEZE, HARVEST, FREEZE, HARVEST, FREEZE, HARVEST,
Later, we will cover the adjustments and discuss the proper settings.
Now, lets take a look at the basic IM sequence of operation. When the control switch is placed in ICE, the unit starts in the Initial Harvest cycle.
When power is supplied, the compressor, hot gas valve, and actuator motor energize. The compressor starts in harvest to reduce the starting load and increase compressor life. This will also clear any ice from the evaporator plate before the freeze cycle begins.
Page 7
The actuator motor turns counter clock wise to rotate the cam arms and lower the water pan away from the evaporator. When the water plate is completely down the switch lever moves the actuator toggle switch to the left. The board energizes the inlet water valve and condenser fan motor and de-energizes the hot gas valve.
Switching the actuator toggle switch to the left position also reverses the actuator motor. The motor now turns clock wise to raise the water plate upward.
7
When the plate reaches the evaporator, the cam arm switch lever moves the actuator toggle switch to the right position. This stops the actuator motor and sets up the circuit to lower the plate in the next harvest cycle. It also energizes the pump motor and the board de-energizes the inlet water valve. The Freeze Cycle now begins.
Page 8
The freeze cycle is controlled by a thermistor, which is mounted at the evaporator outlet. The pump is spraying water up into the evaporator cells to form the square IM cubes. The evaporator temperature lowers as the ice cubes form.
A thermistor temperature of –9.4°F signals the control board to begin harvest and energize the hot gas valve and actuator motor circuit. The actuator motor now turns counter clock wise to lower the water pan. The switch lever moves the actuator toggle switch to the left. This sets the actuator motor circuit to raise the water plate at the end of harvest. The board energizes the inlet water valve.
8
Unlike the initial harvest, the normal harvest is controlled by the thermistor. When the thermistor reaches 59°F, the control board de­energizes the hot gas valve and energizes the condenser fan motor. The actuator motor energizes to raise the plate. When the plate reaches the evaporator, the actuator toggle switch is moved back to the right. The board de-energizes the inlet water valve and the freeze cycle begins again. The average harvest cycle is about 3 minutes.
Page 9
The unit will continue through the freeze and harvest cycle until the bin control shuts down the refrigeration system.
When pushed over, the bin control has a 10-second delay before shut down occurs. An 85-second delay occurs at startup when the bin control is released.
Now let’s take a look at the control board adjustments. Remember that the adjustments are factory set to provide proper operation in normal operating conditions.
9
NO SEASONAL ADJUSTMENTS!
The board adjustments are made through variable resistors on the board. The cube control is marked VR5. This adjusts the thermistor
switching temperature of - 9.4°F and the length of the freeze cycle. The dimple size in the cube also changes. Adjusting to a larger dimple will result in a shorter freeze cycle and a smaller cube. A smaller dimple setting will result in a longer cycle and a larger cube. The factory setting is 5.
Page 10
The maximum freeze timer is VR3. This timer will automatically switch the unit to the harvest cycle if the freeze cycle last longer than the setting time. The factory setting is 45 minutes.
The defrost control VR2 will adjust the time period between ice-drop and actuator motor restart during harvest. The factory setting is 4. This setting represents approximately 40 seconds. VR2 would be adjusted longer if the unit is operating in a cooler ambient temperature.
10
The control board includes a push­button reset. Pressing this button will initiate a harvest cycle anytime the control switch is in ICE position.
Page 11
A red Service Indicator LED is also included on the control board. This LED will either light continually or flash to indicate a service fault. A fault diagnosis chart in the service manual will help the technician determine the actual problem.
See chart next page.
Preventative maintenance for the IM is simple. Follow these steps to allow the unit to operate efficiently.
1. Clean the mesh air filter twice
monthly to ensure good airflow.
2. Clean the condenser once a year
using a brush or vacuum.
3. Check and clean the inlet water
valve screen as needed to assure proper water flow.
4. Clean and sanitize the water
distribution system annually using the recommended cleaner.
5. Wipe down the exterior using a
soft cloth and neutral cleaner.
11
Cleaning tips:
A detailed cleaning label is
located under the top cover. More detailed instructions are included in the customers Instruction Manual or in the product Service Manual.
Always follow the cleaning
instructions and use the recommended ice machine cleaner.
Use the cleaning brush shipped
with the unit to clean tight places.
Page 12
FAULT DIAGNOSIS
Only
Actuator
Replace
Replace
Replace
Defective Defective
Check the status of the Service lamp on the Controller Board (LED-5) by removing the Control Box Cover.
Lamp ON Water Plate closed This tends to indicate the Back-up Timer has stopped machine operation during the
freeze cycle. High ambient and water temperature are an obvious cause. But check out each component that could result in an extended freezing time (See guide below).
Lamp ON – Water Plate open
The Timer has stopped the machine because if an excessive defrost time. See the guide below to check out the probable cause.
Lamp flashing ON/OFF
If on the first cycle, check out the Cam operation and/or Toggle Switch. If the machine has been in service for some time, the Controller Board may be at fault.
REMEMBER: Hoshizaki controllers are very reliable. They also control every component’s Operation. So if a component malfunctions, the controller will respond.
Do not replace controllers in an attempt to shorten the diagnosis process and not before carefully checking the actual fault and possible cause.
12
When the icemaker stops, the Controller Board Interlock indicator shows possible faults.
PATTERN
1.
INTERLOCK INDICATOR
Flashing
WATER TANK POSITION
First Cycle
O
POSSIBLE CAUSE REMEDY
1
2
3
4
Toggle Switch Lever bent
Can Arm (A) Broken
Cam Arm
Actuator Motor
Controller Board
Actuator Toggle Switch
Replace
Page 13
13
Clogged Air Filter Clean or Replace
Replace
Check for leak
Replace Replace
Water leak from Valve
Gas leak from Hot Valve
Fan Motor Gas leak
Compressor
Hot Gas Solenoid will not open
Replace
Check
Compressor
Replace
Replace
Replace
Replace
Actuator
Cam Pin
Replace
Arm (A)
Defective Cube Replace
Harvest
Defective Actuator
PATTERN
2
INTERLOCK
INDICATOR
WATER TANK POSITION
Freeze Cycle
POSSIBLE CAUSE REMEDY
1
2 0V
Leak
3
and/or Condenser
Water Solenoid
Gas Solenoid
Replace
Hot Gas leak
4
stopped
5 Gas
6
stopped
Comp. Start Capacitor
3
Cycle
1
115v
2 Gas
3
Valve closed and
Gas leak
stopped
for leak
Comp. Start Capacitor
4
OR
1
Lever
2
3
Toggle Switch
Can Arm (A) Broken
Cam Arm
Motor
Actuator Toggle Swt.
4
Actuator motor Pin
5
Control Thermistor
damaged
Cam Pin and Cam
Page 14
WIRING DIAGRAM IM-51BAE
14
Page 15
IM SERIES REVIEW QUIZ
Choose the best answer for each question below.
1. The IM control board is located in the rear or the unit.
True False
2. The IM unit uses a thermostatic bin control.
True False
3. The bin control switch must OPEN or Close to shut the unit down.
4. The IM series uses R-404A or R-134A refrigerant.
5. To raise the water pan assembly the actuator toggle switch must be in the RIGHT or LEFT position.
15
6. With the actuator toggle switch in the left position, the actuator motor turns CLOCKWISE or COUNTER CLOCKWISE.
7. Adjusting the cube control or dimple adjustment changes which temperature
setting? - 9.4ºF or 59ºF.
8. The maximum freeze timer on the control board is factory set at 60 MINUTES or 45 MINUTES.
9. The black push button reset is included on the control board for
HARVEST INITIATION or SAFETY RESET.
10. The control transformer used in the IM series units is a 12VOLT or 24 VOLT output.
NOTE: Quiz answers are at the bottom of next page.
Page 16
NOTES:
16
Quiz answers:
1.True, 2. False, 3. Close, 4. R-134A, 5. Left, 6. CW, 7. – 9.4ºF, 8. 45 min., 9. Harvest initiation, 10. 24 volt