Only qualified service technicians should attempt to service or maintain this
icemaker. No service or maintenance should be undertaken until the technician
has thoroughly read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call or write to the HOSHIZAKI Technical Support Department for
assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: HOSHIZAKI Technical Support Department
Phone: 1-800-233-1940 Technical Service
(770) 487-2331
Fax: 1-800-843-1056
(770) 487-3360
Web Site: www.hoshizakiamerica.com
Note: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
2
Please review this manual. It should be read carefully before the icemaker is serviced or
maintenance operations are performed. Only qualified service technicians should service
and maintain the icemaker. This manual should be made available to the technician prior
to service or maintenance.
CONTENTS
I. Specification ...................................................................................................................... 5
AC SUPPLY VOLTAGE115/60/1
COMPRESSOR120 V9.4 RLA51 LRA
GEAR MOTOR120 V3 FLA1/4 HP
FAN MOTOR115 V0.85 FLA1/15 HP
OTHER120 V0.03 A
MAXIMUM FUSE SIZE20 A
MAX. HACR BREAKER (USA ONLY)20 A
MAX. CIRC. BREAKER (CANADA ONLY)20 A
MINIMUM CIRCUIT AMPACITY20 A
APPROXIMATE ICE PRODUCTIONAmbient
PER 24 HR.Temp.(°F)
lbs./day ( kg/day )70* 823 (373)786 (357)748 (339)
Reference without *marks80711 (323)677 (307)644 (292)
90613 (278) * 599 (272)555 (252)
100528 (239)502 (228) * 471 (214)
SHAPE OF ICEFlake
ICE QUALITYApprox. 70%, Ice (90/70°F, Conductivity 200 µs/cm)
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1131 (4.5)1089 (3.2)
POTABLE WATER72 (12)99 (12)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)22" x 27-3/8" x 25-15/16" (560 x 695 x 658mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 176 lbs. ( 80 kg ), Shipping 207 lbs. ( 94 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FP
- DRAINOutlet 3/4" FPT
ICE MAKING SYSTEMAuger type
HARVESTING SYSTEMDirect Driven Auger ( 1/4HP Gear Motor )
ICE MAKING W ATER CONTROLFloat Switch
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMMechanical Bin Control ( Proximity Sw. )
COMPRESSORHermetic , Model RS43-C2E-CAA
CONDENSERAir-cooled, Fin and Tube Type
EVAPORATORCopper Tube on Cylinde
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A,(800 g)
DESIGN PRESSUREHigh 427 PSIG, Low 230 PSIG
PC BOARD CIRCUIT PROTECTIONHigh Voltage Cut-off Relay
COMPRESSOR PROTECTIONAuto-reset Overload Protector
GEAR MOTOR PROTECTIONFuse (3A)
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pres sure Control Switch
LOW WATER PROTECTIONFloat Switch and Timer
ACCESSORIES - SUPPLIEDSpare Fuse
- REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
1lb 12oz
WATER TEMP. (°F)
50
7090
We reserve the right to make changes in specifications and design without prior notice.
5
F-801MWH
T
r
r
r
AC SUPPLY VOLTAGE115/60/1
COMPRESSOR120 V8.5 RLA51 LRA
GEAR MOTOR120 V3 FLA1/4 HP
OTHER120 V0.03 A
MAXIMUM FUSE SIZE20 A
MAX. HACR BREAKER (USA ONLY)20 A
MAX. CIRC. BREAKER (CANADA ONLY)20 A
MINIMUM CIRCUIT AMPACITY20 A
APPROXIMATE ICE PRODUCTIONAmbient
PER 24 HR.Temp.(°F)
lbs./day ( kg/day )70* 720 (327)693 (315)677 (307)
Reference without *marks80661 (300)646 (293)630 (286)
90616 (279) * 605 (274)587 (266)
100573 (260)560 (254) * 520 (236)
SHAPE OF ICEFlake
ICE QUALITYApprox. 70%, Ice (90/70°F, Conductivity 200 µs/c m)
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1078 (4.3)1076 (3.6)
POTABLE WATER72 (12)86 (12)
WATER-COOLED CONDENSER360 (60)219 (31)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)22" x 27-3/8" x 25-15/16" (560 x 695 x 658mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 176 lbs. ( 80 kg ), Shipping 207 lbs. ( 94 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPTCond. Inlet 1/2" FPT
- DRAINOutlet 3/4" FP
ICE MAKING SYSTEMAuger type
HARVESTING SYSTEMDirect Driven Auger ( 1/4HP Gear Motor )
ICE MAKING WA TER CONTROLFloat Switch
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMMechanical Bin Control ( Proximity Sw. )
COMPRESSORHermetic, Model RS43-C2E-CAA
CONDENSERWater-cooled, tube in tube type
EVAPORATORCopper Tube on Cylinde
REFRIGERANT CONTROLThermostatic Ex pansion Valve
REFRIGERANT CHARGER-404A,(470 g)
DESIGN PRESSUREHigh 427 PSIG, Low 230 PSIG
PC BOARD CIRCUIT P ROTECTIONHigh Voltage Cut-off Relay
COMPRESSOR PROTECTIONAuto-reset Overload Protecto
GEAR MOTOR PROTECTIONFuse (3A)
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LO W W A TER P RO TECTIO NFloat S wi tch and Tim e
ACCESSORIES - SUPPLIEDSpare Fuse
- REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
1lb 1oz
WATER TEMP. (°F)
50
7090
Cond. Outlet 3/8" FPT
We reserve the right to make changes in specifications and design without prior notice.
6
F-801MAH-C
T
r
r
r
AC SUPPLY VOLTAGE115/60/1
COMPRESSOR120 V9.4 RLA51 LRA
GEAR MOTOR120 V3 FLA1/4 HP
FAN MOTOR115 V0.85 FLA1/15 HP
OTHER120 V0.03 A
MAXIMUM FUSE SIZE20 A
MAX. HACR BREAKER (USA ONLY)20 A
MAX. CIRC. BREAKER (CANADA ONLY)20 A
MINIMUM CIRCUIT AMPACITY20 A
APPROXIMATE ICE PRODUCTIONAmbient
PER 24 HR.Temp.(°F)
lbs./day ( kg/day )70* 752 (341)728 (330)688 (312)
Reference without *marks80650 (295)614 (279)580 (263)
90548 (249) * 552 (250)490 (222)
100463 (210)437 (198) * 405 (184)
SHAPE OF ICECubelet
ICE QUALITYApprox. 80%, Ice (90/70°F, Conductivity 200 µs/c m)
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1169 (5.1)1110 (3.5)
POTABLE WATER66 (12)90 (12)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)22" x 27-3/8" x 25-15/16" (560 x 695 x 658mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 176 lbs. ( 80 kg ), Shipping 207 lbs. ( 94 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FP
ICE MAKING SYSTEMAuger type
HARVESTING SYSTEMDirect Driven Auger ( 1/4HP Gear Motor )
ICE MAKING WA TER CONTROLFloat Switch
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMMechanical Bin Control ( Proximity Sw. )
COMPRESSORHermetic, Model RS43-C2E-CAA
CONDENSERAir-cooled, Fin and Tube Type
EVAPORATORCopper Tube on Cylinde
REFRIGERANT CONTROLThermostatic Ex pansion Valve
REFRIGERANT CHARGER-404A,(800 g)
DESIGN PRESSUREHigh 427 PSIG, Low 230 PSIG
PC BOARD CIRCUIT P ROTECTIONHigh Voltage Cut-off Relay
COMPRESSOR PROTECTIONAuto-reset Overload Protecto
GEAR MOTOR PROTECTIONFuse (3A)
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LO W W A TER P RO TECTIO NFloat S wi tch and Tim e
ACCESSORIES - SUPPLIEDSpare Fuse
- REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
1lb 12oz
WATER TEMP. (°F)
50
7090
We reserve the right to make changes in specifications and design without prior notice.
7
F-801MWH-C
T
T
T
r
AC SUPPLY VOLTAGE115/60/1
COMPRESSOR120 V8.5 RLA51 LRA
GEAR MOTOR120 V3 FLA1/4 HP
OTHER120 V0.03 A
MAXIMUM FUSE SIZE20 A
MAX. HACR BREAKER (USA ONLY)20 A
MAX. CIRC. BREAKER (CANADA ONLY)20 A
MINIMUM CIRCUIT AMPACITY20 A
APPROXIMATE ICE PRODUCTIONAmbient
PER 24 HR.Temp.(°F)
lbs./day ( kg/day )70* 645 (293)620 (281)608 (276)
Reference without *marks80596 (270)585 (265)574 (260)
90563 (255) * 550 (249)541 (246)
100531 (241)521 (236) * 485 (220)
SHAPE OF ICECubelet
ICE QUALITYApprox. 80%, Ice (90/70°F, Conductivity 200 µs/cm)
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1075 (4.7)1083 (4.1)
POTABLE WATER66 (12)77 (12)
WATER-COOLED CONDENSER302 (55)199 (31)
gal./24HR (gal./100 lbs.)
EXTERIOR DIMENSIONS (WxDxH)22" x 27-3/8" x 25-15/16" (560 x 695 x 658mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 176 lbs. ( 80 kg ), Shipping 207 lbs. ( 94 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FP
- DRAINOutlet 3/4" FPTCond. Outlet 3/8" FP
ICE MAKING SYSTEMAuger type
HARVESTING SYSTEMDirect Driven Auger ( 1/4HP Gear Motor )
ICE MAKING W ATER CONTROLFloat Switch
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMMechanical Bin Control ( Proximity Sw. )
COMPRES SORHermetic , Model RS43-C2E-CAA
CONDENSERWater-cooled, tube in tube type
EVAPORATORCopper Tube on Cylinde
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A,(470 g)
DESIGN PRESSUREHigh 427 PSIG, Low 230 PSIG
PC BOARD CIRCUIT PROTECTIONHigh Voltage Cut-off Relay
COMPRESSOR PROTECTIONAuto-reset Overload Protector
GEAR MOTOR PROTECTIONFuse (3A)
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pres sure Control Switch
LOW WATER PROTECTIONFloat Switch and Timer
ACCESSORIES - SUPPLIEDSpare Fuse
- REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE 104 - 127 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
We reserve the right to make changes in specifications and design without prior notice.
1lb 1oz
WATER TEMP. (°F)
50
7090
Cond. Inlet 1/2" FP
8
II. General Information
1. Construction
F-801MAH/-C
Control Water Valve
Water Supply
Inlet
Bin Control
Ice Chute
Evaporator
Expansion
Valve
Flush Water
Valve
Control Box
Gear Motor
Junction Box
Condenser
Fan Motor
Compressor
Drier
9
F-801MWH/-C
Control Water Valve
Water Supply
Inlet
Bin Control
Ice Chute
Evaporator
Expansion
Valve
Flush Water
Valve
Control Box
Gear Motor
Junction Box
Water
Regulator
Compressor
Drier
10
2. Control Box Layout
)
F-801MAH/-C
CONNECTOR
PRESSURE
SWITCH
FLUSH
TIMER
GEAR
MOTOR
RELAY
CIRCUIT PROTECT
RELAY
GEAR MOTOR
PROTECT RELAY
WATER CONTROL
RELAY
FAN
MOTOR
CAP
STARTER
TRANSFORMER
FLUSH
GEAR
MOTOR
CAP.
FLUSH
SWITCH
ICE
POWER
SWITCH
START
CAPACITOR
RUN
CAPACITOR
CONTROL
TIMER
Note: The above component names are identical with the wiring label, but not with
the parts list.
FUSE
FUSE
(GEAR MOTOR
11
F-801MWH/-C
CONNECTOR
PRESSURE
SWITCH
FLUSH
TIMER
GEAR
MOTOR
RELAY
CIRCUIT PROTECT
RELAY
GEAR MOTOR
PROTECT RELAY
WATER CONTROL
RELAY
STARTER
TRANSFORMER
GEAR
MOTOR
CAP.
FLUSH
ICE
FLUSH
SWITCH
POWER
SWITCH
START
CAPACITOR
RUN
CAPACITOR
CONTROL
TIMER
FUSE
FUSE
(GEAR MOTOR)
12
III. Technical Information
1. Water Circuit and Refrigeration Circuit
F-801MAH/-C
13
F-801MWH/-C
14
2. Wiring Diagrams
F-801MAH/-C, F-801MWH/-C
15
3. Sequence of Electrical Circuit
[a] When power switch is moved to “ON” position and flush switch to “ICE” position,
water starts to be supplied to reservoir.
16
[b] When reservoir has been filled, gear motor starts immediately.
17
[c] Compressor starts about 60 sec. after gear motor starts.
18
[d] Bin control operates, and about 6 sec. later, compressor and gear motor stop
simultaneously.
19
[e] Low water (except water-cooled model).
20
[f] Low water (water-cooled model), or dirty air filter (air-cooled model), pressure
switch to “OPEN”, compressor and gear motor operate intermittently.
21
[g] When flush switch is moved to “FLUSH” position, flush water valve opens and
flushes reservoir and evaporator.
22
[h] When flush timer operates (for 15 min. every 12 hours).
23
[i] When 208-230V are supplied to circuit protect relay, it protects the circuit from
miswiring. If the power supply is properly connected, the contact of circuit protect
relay does not move even when the coil is energized.
24
[j] When input voltage is too low, (less than 70%), gear motor fuse (1.5A) is blown
causing the compressor and gear motor to turn off immediately.
25
4. Timing Chart
1. CIRCUIT PROTECT
RELAY
2. WATER LEVEL
ON
OFF
UPPER
LOWER
BOTTOM
Miswiring. Circuit Protect Relay operates.)
Proper wiring. The unit starts.
BIN CONTROL
OFF ON
UPPER
3. FLOAT
SWITCH
LOWER
4. WATER CONTROL
RELAY
5. CONTROL WATER
VALV E
6. FLUSH TIMER
7. FLUSH SWITCH
8. FLUSH WATER
VALV E
9. BIN CONTROL
10. GEAR MOTOR
RELAY
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1 - 2
2 - 3
FLUSH
ICE
ON
OFF
ON
OFF
ON
OFF
1 sec
6 sec1 sec
11. GEAR MOTOR
12. FAN MOTOR
13. COMPRESSOR
14. PRESSURE
SWITCH
ON
OFF
ON
OFF
ON
OFF
ON
OFF
60 sec
60 sec
26
LOW WATER
FLUSH TIMER
1. CIRCUIT PROTECT
RELAY
2. WATER LEVEL
UPPER
3. FLOAT
SWITCH
LOWER
4. WATER CONTROL
RELAY
5. CONTROL WATER
VALV E
6. FLUSH TIMER
7. FLUSH SWITCH
ON
OFF
UPPER
LOWER
BOTTOM
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1 - 2
2 - 3
FLUSH
ICE
21 min every 12 hr
8. FLUSH WATER
VALV E
9. BIN CONTROL
10. GEAR MOTOR
RELAY
11. GEAR MOTOR
12. FAN MOTOR
13. COMPRESSOR
14. PRESSURE
SWITCH
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
150 sec
90 sec60 sec90 sec60 sec
1 sec
150 sec
1 sec
27
FLUSH
FLUSH SWITCHPRESSURE SWITCH
ICE
OFFON
1. CIRCUIT PROTECT
RELAY
2. WATER LEVEL
UPPER
3. FLOAT
SWITCH
LOWER
4. WATER CONTROL
RELAY
5. CONTROL WATER
VALV E
6. FLUSH TIMER
7. FLUSH SWITCH
ON
OFF
UPPER
LOWER
BOTTOM
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1 - 2
2 - 3
FLUSH
ICE
8. FLUSH WATER
VALV E
9. BIN CONTROL
10. GEAR MOTOR
RELAY
11. GEAR MOTOR
12. FAN MOTOR
13. COMPRESSOR
14. PRESSURE
SWITCH
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
150 sec
90 sec60 sec
1 sec
1 sec
60 sec
28
5. Performance Data
F-801MAH
APPROXIMATEAmbientWater Temp. (F)
ICE PRODUCTIONTemp. (F)
PER 24 HR.70* 823(373)786(357)748(339)
10042(3.0)43(3.0)*44(3.1)
WATER FLOW FOR CONDENSER15 gal/h (AT 90°F / WT 70°F)
PRESSURE DROP OF COOLING WATER LINELess than 7 PSIG
HEAT OF REJECTION FROM CONDENS ER
HEAT OF REJECTION FROM COMPRESSOR1050 BTU/h (AT 90°F / WT 70°F)
507090
5155 BTU/h (AT 90°F / WT 70°F)
Note: The data without *marks should be used for reference.
We reserve the right to make changes in specifications and design without prior notice.
30
F-801MAH-C
APPROXIMATEAmbientWater Temp. (F)
ICE PRODUCTIONTemp. (F)
PER 24 HR.70* 752(341)728(330)688(312)
10046(3.2)46(3.3)*47(3.3)
WATER FLOW FOR CONDENSER
PRESSURE DROP OF COOLING WATER LINE
HEAT OF REJECTION FROM CONDENS ER
HEAT OF REJECTION FROM COMPRESSOR1050 BTU/h (AT 90°F / WT 70°F)
507090
13 gal/h (AT 90°F / W T 70°F)
Less than 7 PSIG
5155 BTU/h (AT 90°F / WT 70°F)
Note: The data without *marks should be used for reference.
We reserve the right to make changes in specifications and design without prior notice.
32
IV. Adjustment of Components
1. Adjustment of Water Regulating Valve (water-cooled model only)
The water regulating valve or also called “water regulator” is factory-adjusted. No adjustment
is required under normal use. Adjust the water regulator , if necessary, using the following
procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer to
check the condenser drain temperature.
2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge
shows 260 PSIG (R-404A models/-F type), or the thermometer reads 100 -104°F, in 5
minutes after the icemaking process starts. When the pressure exceeds 260 PSIG, or the
condenser drain temperature exceeds 104°F, rotate the adjustment screw counterclockwise.
3) Check that the pressure or the condenser drain temperature holds a stable setting.
Adjustment Screw
CW
CCW
Bottom View
CW - Higher
CCW - Lower
Adjustment Screw
33
2. Adjustment of Flake Size
To adjust the flake size, change the direction of the cutter head on the top of the auger,
according to the following procedures:
1) Remove the bolt and the cutter head.
FINE
2) The cutter head has two holes, one for fine flake
and the other for coarse flake size. The unit is
shipped from the factory in the fine flake
COARSE
position.
3) Place the cutter head so that the pin on the top of the auger fits into the selected hole.
4) Secure the cutter head by the bolt.
34
V. Service Diagnosis
1. No Ice Production
PROBLEMPOSSIBLE CAUSEREMEDY
[1] The icemaker will
not start.
[2] Water flow does not
stop, and the
icemaker will not
start
[3] Water has been
supplied, but the
icemaker will not
start.
a) Power Supply1. OFF position.1. Move to ON position.
b) Power Switch
c) Fuse (Control Box)1.Blown out.1. Check for short circuit
d) Circuit Protect Relay1.Miswiring.1. Check power supply
e) Flush Timer1. Flushing out.1. Wait for 15 minutes.
f)Flush Switch1. FLUSH position.1. Move to ICE position.
g) Transformer1. Coil winding opened.1.Replace.
h) Control Water Valve1. Coil winding opened.1.Replace.
i)Shut-off Valve1.Closed.1. Open.
j)Plug and Receptacle
a) Water Control Relay1.Contact fused.1. Replace.
b) Float Switch1. Bad contacts.1. Check for continuity
c) Flush Water Valve1.Valve seat clogged
d) Hoses1.Disconnected.1. Connect.
a) Water Control Relay1.Bad contacts.1.Check for continuity
b)
c) Gear Motor Relay1.Coil winding opened.1. Replace.
d) Control Timer
e) Gear Motor Protect
2. Loose connection.2. Tighten.
3. Bad contacts.3. Check for contintinuity
4. Blown fuse.4.Replace.
(Control Box)
(Control Box)
Bin Control1.Bad contacts.1.Check for continuity
(Printed Circuit
Board)
Relay
1. Off position.1. Move to ON position.
2. Bad contacts.2. Check for continuity
2. Bad contacts.2. Check for continuity
2. Bad contacts.2. Check for continuity
2. Water failure.2. Wait till water is
1. Disconnected.1. Connect.
2. Terminal out of Plug
or Receptacle.
2. Coil winding opened.2.Replace.
2. Float does not move
freely.
and water leaking.
2. Activator does not
move freely.
2. bad contacts.2. Check for continuity
1. Broken.1.Replace.
1. Coil winding opened.1.Replace.
2. Bad contacts.2. Check for continuity
and replace.
and replace.
and replace.
voltage and wire
properly.
and replace.
and replace.
supplied.
2. Insert Terminal back in
position
and replace.
2. Clean or replace.
1. Clean or replace
and replace.
and replace.
2. Clean Axle and its
corresponding holes
or replace Bin Control.
and replace.
and replace.
35
PROBLEMPOSSIBLE CAUSEREMEDY
[4] Water has been
supplied, Fan Motor
starts, but Gear
Motor and
Compressor will not
start.
[5] Gear Motor and
Compressor start
but operate
intermittently.
[6] Gear Motor starts,
but Compressor will
not start or operates
intermittently.
a) Gear Motor Fuse
(BUSSMAN GMD
1.5A)
b) Thermal Protector
(Gear Motor)
a) Pressure Switch1. Dirty Air Filter or
a) X2 Relay on Control
Timer
b) Starter1. Bad contacts.1. Check for continuity
c) Start Capacitor or
Run Capacitor
d) Compressor1. Loose connections.1. Tighten.
1. Blown Fuse.1.See "3. [3]." Find out
1. Bad contacts.1.Check for continuity
Condenser.
2. Ambient or
condenser water
temperature too
warm.
3. Condenser water
pressure too low or
off. (Water-cooled
model only)
4. Water Regulating
Valve set too high.
(Water-cooled model
only)
5. Fan not rotating.5. See "3. [1] a) Fan
6. Refrigerant
overcharged.
7. Refrigerant line or
components
plugged.
8. Bad contacts.8.Check for continuity
9. Loose connections.9. Tighten.
1. Bad contacts.1.Replace.Check for
2. Coil winding opened.2. Replace Timer.
2. Coil winding opened.2. Replace.
3. Loose Connections.3. Tighten.
1. Defective.1. Replace.
the cause and replace
the Fuse.
and replace.
1. Clean.
2. Get cooler.
3. Check and get
recommended
pressure.
4. Adjust it lower.
Motor."
6. Recharge.
7. Clean and replace
drier.
and replace.
continuity and replace.
and replace.
[7] Gear Motor and
Compressor start,
but no ice is
produced.
2. Motor winding
opened or grounded.
3. Motor Protector
tripped.
e) Power Supply1. Circuit Ampacity too
low.
a) Refrigerant Line1. Gas leaks.1. Check for leaks with a
2. refrigerant line
clogged.
2. Replace.
3. Find out the cause of
overheat or
overcurrent.
1. Install a larger-sized
conductor.
leak detector. Reweld
leak, replace drier and
charge with
refrigerant. The
amount of refrigerant
is marked on
Nameplate or Label.
2. Replace the clogged
component.
36
2. Low Ice Production
PROBLEMPOSSIBLE CAUSEREMEDY
[1] Low ice productiona) Refrigerant Line1. Gas leaks.1. See "1. [5] a)
Refrigerant Line."
b) High-side Pressure
Too High
c) Expansion Valve
(not adjustable)
2. Refrigerant line
clogged.
3. Overcharged.3. Recharge.
1. Dirty Air Filter or
Condenser.
2. Ambient or
condenser water
temperature too
warm.
3. Condenser water
pressure too low or
off. [Water-cooled
model only]
4. Fan rotating too
slow.
5. Water Regulating
Valve clogged.
[Water-cooled model
only]
6. Condensing unit out
of order.
1. Low-side pressure
too low.
2. Low-side pressure
too high.
2. Replace the clogged
component.
1. Clean.
2. Get cooler.
3. Check and get
recommended
pressure.
4. See "3 [1] a) Fan
Motor."
5. Clean.
6. Check condensing
unit.
1. Replace.
2. See if Expansion
Valve Bulb is mounted
properly, and replace
the valve if necessary.
37
3. Other
PROBLEMPOSSIBLE CAUSEREMEDY
[1] Abnormal noisea) Fan Motor1. Bearing worn out.1. Replace.
2. Fan blade deformed. 2. Replace fan blade.
[2] Overflow from
Reservoir (Water
does not stop.)
[3] Gear Motor Fuse
blown frequently.
3. Fan blade does not
move freely.
b) Compressor1. Bearings worn out,
or cylinder valve
broken.
2. Mounting pad out of
position.
c) Refrigerant Lines1. Rub or touch lines or
other surfaces.
d) Gear Motor (Ice
Making)
e) Evaporator1. Too much pressure
a) Water Supply1. Water pressure too
b) Control Water Valve1. Diaphragm does not
c) Float Switch1. Bad contacts.1. Check for continuity
a) Power Supply
Voltage
b) Ice Making Unit1. Bearings or Auger
c) Bin Control1. Bad contacts.1. Check for continuity
1. Bearing or Gear
worn out / damaged.
loss.
2. Scale on inside wall
of Freezing Cylinder.
high.
close.
1. Too high or too low.1. Connect the unit to a
worn out.
2. Activator does not
move freely.
3. Replace.
1. Replace.
2. Reinstall.
1. Replace.
1. Replace.
1. Replace.
2. Remove Auger. Use
"SCALE AWAY" or
"LIME-A-WAY"
solution to clean
periodically. If the
water is found hard by
testing, install a
softener.
1. Install a pressure
Reducing Valve
1. Clean or replace.
and replace.
power supply of
proper voltage.
1. Replace Bearing or
Auger.
and replace.
2. Clean Axle and its
corresponding holes
or replace Bin Control.
38
VI. Removal and Replacement of Components
IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place
after the equipment is serviced.
IMPORTANT
1. The Polyolester (POE) oils used in R-404A units can absorb moisture
quickly. Therefore it is important to prevent moisture from entering the
system when replacing or servicing parts.
2. Always install a new filter drier every time the sealed refrigeration system
is opened.
3. Do not leave the system open for longer than 15 minutes when replacing
or servicing parts.
1. Service for Refrigerant Lines
[a] Refrigerant Recovery
The icemaker unit is provided with two refrigerant access valves - one on the low-side and
one on the high-side line. Using proper refrigerant practices recover the refrigerant from the
access valves and store it in an approved container. Do not discharge the refrigerant into
the atmosphere.
[b] Evacuation and Recharge [R-404A]
1) Attach charging hoses, a service manifold and a vacuum pump to the system. Be sure
to connect charging hoses to both high-side and low-side access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Never allow the oil in the vacuum pump to flow backward.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period
depends on pump capacity.
39
4) Close the low-side valve and high-side valve on the service manifold.
5) Disconnect the vacuum pump, and attach a refrigerant service cylinder to the highside line. Remember to loosen the connection, and purge the air from the hose. See
the nameplate for the required refrigerant charge. Hoshizaki recommends only virgin
refrigerant or reclaimed refrigerant which meets ARI Standard No. 700-88 be used.
6) A liquid charge is recommended for charging an R-404A system. Invert the service
cylinder. Open the high-side, service manifold valve.
7) Allow the system to charge with liquid until the pressures balance.
8) If necessary, add any remaining charge to the system through the low-side. Use a
throttling valve or liquid dispensing device to add the remaining liquid charge
through the low-side access port with the unit running.
9) Close the two refrigerant access valves, and disconnect the hoses and service
manifold.
10) Cap the access valves to prevent a possible leak.
2. Brazing
1. Refrigerant R-404A itself is not flammable at atmospheric pressure and
temperatures up to 176° F.
2. Refrigerant R-404A itself is not explosive or poisonous. However, when
exposed to high temperatures (open flames) R-404A can be decomposed
to form hydrofluoric acid and carbonyl fluoride both of which are
hazardous.
3. Always recover the refrigerant and store it in an approved container. Do
not discharge the refrigerant into the atmosphere.
4. Do not use silver alloy or copper alloy containing arsenic.
5. Do not use R-404A as a mixture with pressurized air for leak testing.
Refrigerant leaks can be detected by charging the unit with a little
refrigerant, raising the pressure with nitrogen and using an electronic leak
detector.
DANGER
40
3. Removal and Replacement of Compressor
IMPORTANT
Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repairs or replacement
have been made.
1) Turn off the power supply, and remove the panels.
2) Remove the terminal cover on the compressor, and disconnect the compressor wiring.
3) Recover the refrigerant and store it in an approved container, if required by an applicable
law.
4) Remove the discharge, suction and access pipes from the compressor using brazing
equipment.
WARNING
When repairing a refrigerant system, be careful not to let the burner flame
contact any electrical wires or insulation.
5) Remove the bolts and rubber grommets.
6) Slide and remove the compressor. Unpack the new compressor package. Install the new
compressor.
7) Attach the rubber grommets of the prior compressor.
8) Sandpaper the discharge, suction and access pipes.
9) Place the compressor in position, and secure it using the bolts.
10) Remove plugs from the discharge, suction and access pipes.
11) Braze the access, suction and discharge lines (Do not change this order), while purging
with nitrogen gas flowing at the pressure of 3 - 4 PSIG.
12) Install the new drier.
13) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
41
14) Evacuate the system, and charge it with refrigerant. For the air-cooled and water-cooled
models, see the nameplate for the required refrigerant charge and type. For the remote aircooled models, see the label on the control box.
15) Connect the terminals to the compressor, and replace the terminal cover in its correct
position.
16) Replace the panels in their correct position, and turn on the power supply.
4. Removal and Replacement of Drier
IMPORTANT
Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repairs or replacement
have been made.
1) Turn off the power supply, and remove the panels.
2) Recover the refrigerant and store it in an approved container, if required by an applicable
law.
3) Remove the drier using brazing equipment.
4) Install the new drier with the arrow on the drier in the direction of the refrigerant flow. Use
nitrogen gas at the pressure of 3 - 4 PSIG when brazing the tubings.
5) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
6) Evacuate the system, and charge it with refrigerant. For the air-cooled and water-cooled
models, see the nameplate for the required refrigerant charge and type. For the remote
air-cooled models, see the label on the control box.
7) Replace the panels in their correct position, and turn on the power supply.
42
5. Removal and Replacement of Expansion Valve
IMPORTANT
Sometimes moisture in the refrigerant circuit exceeds the drier capacity and
freezes up at the expansion valve. Always install a new drier every time the
sealed refrigeration system is opened. Do not replace the drier until after all
other repairs or replacement have been made.
1) Turn off the power supply, and remove the panels.
2) Recover the refrigerant and store it in an approved container, if required by an applicable
law.
3) Remove the expansion valve bulb at the evaporator outlet.
4) Remove the expansion valve cover, and remove the expansion valve using brazing
equipment.
5) Braze the new expansion valve with nitrogen gas flowing at the pressure of 3 - 4 PSIG.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve from
overheating. Do not braze with the valve body exceeding 250°F.
6) Install the new drier.
7) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
8) Evacuate the system. Charge it with refrigerant. For the air-cooled and water-cooled
models, see the nameplate for the required refrigerant charge and type. For the remote
air-cooled models, see the label on the control box.
9) Attach the bulb to the suction line. Be sure to secure the bulb using a band and to insulate
it.
10) Place the new set of expansion valve covers in position.
11) Replace the panels in their correct position, and turn on the power supply.
43
6. Removal and Replacement of Water Regulating Valve
(water-cooled model only)
IMPORTANT
Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repairs or replacement
have been made.
1) Turn off the power supply, remove the panels and close the water supply line shut-off
valve.
2) Recover the refrigerant and store it in an approved container.
3) Disconnect the capillary tube using brazing equipment.
4) Disconnect the flare-connections of the valve.
5) Remove the screws and the valve from the bracket.
6) Install the new valve, and braze the capillary tube.
7) Install the new drier.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Connect the flare-connections.
10) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge and type.
11) Open the water supply line shut-off valve, and turn on the power supply.
12) Check for water leaks.
13) See “IV. 1. Adjustment of Water Regulating Valve.” If necessary, adjust the valve.
14) Replace the panels in their correct position.
44
7. Removal and Replacement of Evaporator Assembly
1) Turn off the power supply.
2) Remove the panels.
3) Move the flush switch to the "FLUSH" position.
4) Turn on the power supply and drain out all water from the water line.
5) Turn off the power supply.
6) Remove the strap connecting the spout to the chute assembly.
7) Remove the three thumbscrews and take off the spout from the evaporator.
Cutter
8) Remove the bolt and lift off the cutter.
9) Remove the rubber O-ring and the nylon ring at the top of the evaporator.
Extruding Head
10) Remove the four socket head cap screws and lift off the extruding head.
11) Replace the bearing inside the extruding head, if it exceeds the wear tolerance of 0.02"
or is scratched.
Note: Replacing the bearing requires a bearing press adaptor. If it is not available,
replace the whole extruding head.
Auger
12) Lift off the auger. If the area in contact with the bearing is worn out or the blade scratched,
replace the auger.
Evaporator
Note: Skip the following steps 13) through 15) when the evaporator does not need
replacement.
45
13) Recover the refrigerant and store it in an approved container, if required by an applicable
law.
IMPORTANT
Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repairs or replacement
have been made.
14) Remove the bulb of the expansion valve.
15) Disconnect the brazing-connections of the expansion valve and the copper tube -low
side from the evaporator, using brazing equipment.
16) Remove the two truss head machine screws and the strap securing the evaporator.
17) Disconnect the three hoses from the evaporator.
18) Remove the four socket head cap screws securing the evaporator with the bearinglower.
19) Lift off the evaporator.
Bearing-Lower and Mechanical Seal
20) The mechanical seal consists of two parts. One moves along with the auger, and the
other is fixed on the bearing-lower. If the contact surfaces of these two parts are worn or
scratched, the mechanical seal may cause water leaks and should be replaced.
21) Remove the O-ring on the bearing-lower.
22) Remove the four bolts and the bearing-lower from the gear motor. Replace the bearing
inside the bearing-lower, if it exceeds the wear tolerance of 0.02" or is scratched.
Note: Replacing the bearing requires a bearing press adaptor. If it is not available,
replace the whole bearing-lower.
Gear Motor
23) Remove the coupling-spline on the gear motor shaft.
24) Remove the barrier on the top of the gear motor.
25) Remove the three socket head cap screws securing the gear motor.
46
26) Assemble the removed parts in the reverse order of the above procedure.
WARNING
Be careful not to scratch the surface of the O-ring, or it may cause water leaks.
Handle the mechanical seal with care not to scratch nor to contaminate its
contact surface.
27) When replacing the evaporator;
(a) Braze the new evaporator with nitrogen gas flowing at the pressure of 3 - 4 PSIG.
(b) Replace the drier.
(c) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
(d) Evacuate the system. Charge it with refrigerant. For the air-cooled and water-cooled
models, see the nameplate for required refrigerant charge and type. For the remote
air-cooled models, see the label on the control box.
28) Move the flush switch to the "ICE" position.
29) Replace the panels in their correct position.
30) Turn on the power supply.
47
Rubber O-ring
Nylon Ring
Bolt
Washer
Auger
Mechanical
Seal
O-ring
Bearing
- Lower
Cutter
Extruding
Head
Washer
Socket Head
Cap Screw
Evaporator
Bolt
Washer
Coupling
- Spline
Washer
Socket Head
Cap Screw
Barrier
Gear Motor
48
8. Removal and Replacement of Fan Motor
1) Turn off the power supply and remove the panels.
2) Remove the wire connectors from the fan motor leads.
3) Remove the fan motor bracket and fan motor.
4) Install the new fan motor.
5) Replace the fan motor bracket and the wire connectors.
6) Replace the panels in their correct position, and turn on the power supply.
9. Removal and Replacement of Control Water Valve
1) Turn off the power supply, remove the panels and close the water supply line shut-off
valve.
2) Disconnect the terminals from the control water valve.
3) Loosen the fitting nut on the control water valve inlets, and remove the control water
valve. Do not lose the packings inside the fitting nut.
4) Remove the water supply hose from the control water valve.
5) Install the new control water valve.
6) Assemble the removed parts in the reverse order of the above procedure.
7) Open the water supply line shut-off valve.
8) Check for water leaks.
9) Replace the panels in their correct position, and turn on the power supply.
49
10. Removal and Replacement of Flush Water Valve
1) Turn off the power supply, remove the panels and close the water supply line shut-off
valve.
2) Remove the clamp and disconnect the hose from the flush water valve.
Note: Water may still remain inside the evaporator. Be sure to drain the water into the
drain pan.
3) Disconnect the terminals from the flush water valve.
4) Remove the flush water valve from the bracket.
5) Remove the drain pipe from the flush water valve.
6) Connect the drain pipe to the new flush water valve, and place the valve in position.
7) Connect the hose to the flush water valve and secure it with the clamp.
8) Pour water into the reservoir, and check for water leaks on the flush water valve.
9) Open the water supply line shut-off valve, and turn on the power supply.
10) Move the flush switch to the "ICE" position.
11) Check for water leaks.
12) Move the flush switch to the "FLUSH" position, and make sure water is flushing.
13) Move the flush switch to the "ICE" position.
14) Replace the panels in their correct position.
50
VII. Cleaning and Maintenance
IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place after
any maintenance or cleaning is done to the equipment.
1. Preparing the Icemaker for Long Storage
WARNING
When shutting off the icemaker for an extended time, drain out all water from the
water line and remove the ice from the storage bin. The storage bin should be
cleaned and dried. Drain the icemaker to prevent damage to the water supply
line at sub-freezing temperatures, using air or carbon dioxide. Shut off the
icemaker until the proper ambient temperature is resumed.
[Air-Cooled and Remote Air-Cooled Models]
1) Run the icemaker with the water supply line shut-off valve closed.
2) Open the drain valve and blow out the water inlet line by using air pressure.
3) Turn off the power supply.
4) Remove the front panel.
5) Move the flush switch on the control box to the
“FLUSH” position.
6) Turn on the power supply, and then drain out all
water from the water line.
7) Turn off the power supply.
8) Turn off the power switch on the control box.
Air or CO2
9) Replace the front panel in its correct position.
Shut-off Valve
Drain Valve
10) Close the drain valve.
11) Remove all ice from the storage bin, and clean the bin.
51
[Water-Cooled Models]
1) Turn off the power supply and wait for 3 minutes.
2) Turn on the power supply and wait for 20 seconds.
3) Close the water supply line shut-off valve.
4) Open the drain valve and quickly blow the water supply line from the drain valve to drain
water in the condenser.
5) Follow the above steps 3) through 11) in [Air-Cooled and Remote Air-Cooled Models].
2. Cleaning and Sanitizing Instructions
WARNING
1. HOSHIZAKI recommends cleaning this unit at least once a year. More
frequent cleaning, however, may be required in some existing water
conditions.
2. To prevent injury to individuals and damage to the icemaker, do not use
ammonia type cleaners.
3. Always wear liquid-proof gloves to prevent the cleaning and sanitizing
solutions from coming into contact with skin.
[a] Cleaning Solution
Dilute 4.8 fl. oz. (142 ml) of recommended cleaner Hoshizaki “Scale Away” or
“LIME-A-WAY” (Economics Laboratory, Inc.) with 0.8 gallons (3 l) of warm water. This is a
minimum amount. Make more solution if necessary.
IMPORTANT
For safety and maximum effectiveness, use the solution immediately after
dilution.
52
[b] Cleaning Procedure
The cleaning process will remove lime deposits from the water system.
1) Remove the front panel and top panel, then turn off the power supply.
2) Close the water supply line shut-off valve.
3) Remove all ice from the storage bin.
4) Move the flush switch to the “FLUSH” position.
5) Turn on the power supply and drain out all water from the water line.
6) Turn off the power supply.
7) Remove the strap connecting the spout to the chute assembly.
8) Remove the thumbscrews securing the spout and lift it off.
9) Pour the cleaning solution over the extruding head until the evaporator assembly and the
reservoir are filled and the solution starts to overflow into the drain pan.
Note: If there is excess scale on the extruding head, fill the evaporator assembly and
reservoir as described above, then use a clamp on the reservoir hose between the
reservoir and evaporator assembly to block flow. Pour additional cleaning fluid
over the extruding head until the evaporator assembly is completely full.
10) Replace the spout and strap in their correct positions.
11) Allow the icemaker to sit for about 10 minutes before operation. If you placed a clamp on
the reservoir hose in step 9, remove it before operation.
12) Move the flush switch to the “ICE” position, then turn on the power supply. Replace the
top panel and front panel in their correct positions. Make ice using the solution until the
icemaker stops making ice.
13) Remove the front panel.
14) Move the flush switch to the “FLUSH” position to drain the remainder of the solution.
15) After the solution is drained, move the flush switch to the “ICE” position.
16) Replace the front panel in its correct position.
17) Open the water supply line shut-off valve and supply water to the reservoir.
18) When the gear motor starts, remove the front panel and turn off the power supply.
19) Drain out all water from the water line. See 4) through 6).
53
[c] Sanitizing Solution
Dilute 2.5 fl. oz. (74 ml or 5 tbs) of IMS-II Sanitizer or a 5.25% sodium hypochlorite solution
(chlorine bleach) with 5 gallons (19 l) of warm water.
IMPORTANT
For safety and maximum effectiveness, use the solution immediately after
dilution.
[d] Sanitizing Procedure - Initial
The sanitizing process will sanitize the icemaker.
1) Close the water supply line shut-off valve.
2) Remove the strap connecting the spout to the chute assembly.
3) Remove the thumbscrews securing the spout and lift it off. Remove the rubber O-ring and
nylon O-ring at the top of the cylinder and also remove the packing between the spout
and the chute.
4) Pour the sanitizing solution over the extruding head until the evaporator assembly and
the reservoir are filled and the solution starts to overflow into the drain pan.
5) Remove the two thumbscrews securing the proximity switch to the chute assembly.
6) Remove the chute assembly from the icemaker.
7) Remove the packing at the bottom of the ice chute.
8) Remove the three ties and the chute insulation.
9) Remove the six wing nuts and two baffles.
10) Remove the two thumbscrews, the plate and the packing from the top of the ice chute,
then remove the bin control assembly by sliding it slightly toward the chute opening and
lifting it off.
11) Disassemble the bin control assembly by removing the two snap pins, shaft and
actuator.
12) Soak the removed parts in .25 gallons (1 l) of sanitizing solution for 10 minutes then
wipe them down.
13) Rinse the parts thoroughly.
If the solution is left on these parts, they will rust.
IMPORTANT
54
14) Replace all parts in their correct positions.
IMPORTANT
When installing the baffles, make sure that the bent surface (the one without the
studs) faces the actuator so that the bent surface can guide the ice to the center
of the actuator.
15) Move the flush switch to the “ICE” position, then turn on the power supply. Replace the
top panel and front panel in their correct positions. Make ice using the solution until the
icemaker stops making ice.
[e] Sanitizing Procedure - Final
1) Remove the front panel and top panel, then turn off the power supply.
2) Move the flush switch to the “FLUSH” position.
3) Turn on the power supply and drain out all water from the water line.
4) Turn off the power supply.
5) Remove the strap connecting the spout to the chute assembly.
6) Remove the thumbscrews securing the spout and lift it off.
7) Pour the sanitizing solution over the extruding head until the evaporator assembly and
the reservoir are filled and the solution starts to overflow into the drain pan.
8) Replace the spout and strap in their correct positions.
9) Allow the icemaker to sit for about 10 minutes before operation.
10) Move the flush switch to the “ICE” position, then turn on the power supply. Replace the
top panel and front panel in their correct positions. Make ice using the solution until the
icemaker stops making ice.
11) Remove the front panel.
12) Move the flush switch to the “FLUSH” position to drain the remainder of the solution.
13) After the solution is drained, move the flush switch to the “ICE” position.
14) Replace the front panel in its correct position.
15) Open the water supply line shut-off valve and supply water to the reservoir.
55
16) When the gear motor starts, remove the front panel and turn off the power supply.
17) Drain out all water from the water line. See 2) and 3).
18) Move the flush switch to the “ICE” position and run the icemaker.
19) Turn off the power supply after 30 minutes.
20) Pour warm water into the storage bin to melt all ice, and then clean the bin liner with the
solution.
21) Flush out any solution from the storage bin.
22) Turn on the power supply and start the automatic icemaking process.
IMPORTANT
1. After cleaning, do not use ice made from the sanitizing solution. Be careful
not to leave any solution in the storage bin.
2. Follow carefully any instructions provided with the bottles of cleaning or
sanitizing solution.
3. Never run the icemaker when the reservoir is empty.
56
3. Maintenance
1. This icemaker must be maintained individually, referring to the instruction
manual and labels provided with the icemaker.
2. To have the optimum performance of this icemaker, the following
consumable parts need periodical inspection, maintenance and
replacement:
These parts should be inspected at least once a year or every 10,000 hours
of operation. Their service life, however, depends on water quality and
environment. More frequent inspection and maintenance are recommended.
IMPORTANT
Extruding Head
Housing
Gear Motor
Auger
Mechanical Seal
Consult with your local distributor about inspection and maintenance
service. To obtain the name and phone number of your local distributor, call
Hoshizaki Technical Support at 1-800-233-1940.
1) Stainless Steel Exterior
To prevent corrosion, wipe the exterior occasionally with a clean and soft cloth. Use
a damp cloth containing a neutral cleaner to wipe off oil or dirt build up.
2) Storage Bin and Scoop
* Wash your hands before removing ice. Use the plastic scoop provided (bin
accessory).
* The storage bin is for ice use only. Do not store anything else in the bin.
* Keep the scoop clean. Clean using a neutral cleaner and rinse thoroughly.
* Clean the bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
57
3) Air Filter (air-cooled model only)
A plastic mesh air filter removes dirt or dust from the air, and keeps the condenser
from getting clogged. As the filter gets clogged, the icemaker’s performance will be
reduced. Check the filter at least twice a month. When clogged, use warm water and
a neutral cleaner to wash the filter.
4) Condenser (except water-cooled model)
Check the condenser once a year, and clean if required by using a brush or vacuum
cleaner. More frequent cleaning may be required depending on the location of the
icemaker.
58
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.