Hoshizaki CRMF48, CRMR60W, CRMF48W, CRMR60, CRMR27WD Service Manual

...
Page 1
Service Manual
Commercial Series Refrigerated Kitchen Equipment
Models Undercounter Worktop Prep Table
hoshizakiamerica.com
Number: 73191 Issued: 9-29-2011 Revised: 5-1-2017
Page 2
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No service should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
Page 3
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this booklet carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this booklet for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Refrigeration Circuit Diagram ................................................................. 8
A. Construction .................................................................................................................. 8
B. Refrigeration Circuit Diagram ........................................................................................ 9
II. Sequence of Operation and Service Diagnosis ............................................................... 10
A1. Thermostat Control Sequence of Operation Flow Chart ............................................ 10
1. Undercounter and Work Top: Refrigerator .............................................................. 10
2. Prep Table ...............................................................................................................11
3. Undercounter and Work Top: Freezer .....................................................................11
A2. Thermistor/Control Module Sequence of Operation Flow Chart ............................... 12
1. Undercounter and Work Top: Refrigerator .............................................................. 12
2. Prep Table .............................................................................................................. 13
3. Undercounter and Work Top: Freezer .................................................................... 14
B1. Thermostat Control Service Diagnosis ...................................................................... 15
1. Undercounter and Worktop: Refrigerator ................................................................ 15
2. Prep Table .............................................................................................................. 16
3. Undercounter and Worktop: Freezer ...................................................................... 17
B2. Thermistor/Control Module Service Diagnosis .......................................................... 19
C. Defrost Timer Check ................................................................................................... 23
D. Control Module Check ................................................................................................. 24
E. Diagnostic Table .......................................................................................................... 26
III. Controls and Adjustments ............................................................................................... 28
A. Temperature Settings .................................................................................................. 28
B. Defrost ......................................................................................................................... 28
C. Safety Devices ............................................................................................................ 30
D. Perimeter and Mullion Heaters .................................................................................... 30
IV. Refrigeration Circuit and Component Service Information.............................................. 31
A. Refrigeration Circuit Service Information .................................................................... 31
B. Component Service Information .................................................................................. 33
C. Door Reversal ............................................................................................................. 34
D. Door/Drawer Location Reversal .................................................................................. 37
V. Preparing the Appliance for Periods of Non-Use ............................................................. 48
VI. Disposal .......................................................................................................................... 49
3
Page 4
VII. Technical Information ..................................................................................................... 50
A. Electrical and Refrigerant Data ................................................................................... 50
B. Wiring Diagrams .......................................................................................................... 51
1a. Undercounter and Worktop: Refrigerator; Cabinet Thermostat ............................ 51
1b. Undercounter and Worktop: Refrigerator; Cabinet Thermistor/Control Module .... 52
2a. Prep Table; Cabinet Thermostat (Without Defrost Heater) ................................... 53
2b. Prep Table; Cabinet Thermostat (With Defrost Heater) ........................................ 54
2c. Prep Table; Cabinet Thermistor/Control Module ................................................... 55
3a. Undercounter and Work Top: Freezer; Cabinet Thermostat ................................. 56
3b. Undercounter and Work Top: Freezer; Cabinet Thermistor/Control Module ......... 57
4
Page 5

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
This appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service this appliance.
• This appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• To reduce the risk of electric shock, do not touch the plug with damp hands.
• Unplug the appliance before servicing.
• This appliance requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing wiring, or component failure. This could lead to heat generation or re.
THIS APPLIANCE MUST BE GROUNDED. This appliance is equipped with a NEMA5-15 three-prong grounding plug hazards. It must be plugged into a properly grounded, independent 3-prong wall outlet. If the outlet is a 2-prong outlet, it is your personal responsibility to have a qualied electrician replace it with a properly grounded, independent 3-prong wall outlet. Do not remove the ground prong from the power cord and do not use an adapter plug. Failure to follow these instructions may result in death, electric shock, or re.
• Do not use an extension cord.
• Do not use an appliance with a damaged power cord. The power cord should not be altered, jerked, bundled, weighed down, pinched, or tangled. Such actions could result in electric shock or re. To unplug the appliance, be sure to pull the plug, not the cord, and do not jerk the cord.
to reduce the risk of potential shock
5
Page 6
WARNING, continued
• The GREEN ground wire in the factory-installed power cord is connected to the appliance. If it becomes necessary to remove or replace the power cord, be sure to connect the power cord's ground wire.
• Do not splash, pour, or spray water directly onto or into the appliance. This might cause short circuit, electric shock, corrosion, or failure.
• Do not make any alterations to the appliance. Alterations could result in electric shock, injury, re, or damage to the appliance.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
• Children should be properly supervised around this appliance.
• Do not climb, stand, or hang on the appliance or door or allow children or animals to do so. Do not climb into the appliance or allow children or animals to do so. Death or serious injury could occur or the appliance could be damaged.
• Be careful not to pinch ngers when opening and closing the doors or rail cover (prep table models). Be careful when opening and closing the doors or rail cover when children are in the area.
• Open and close the doors and rail cover (prep table models) with care. Opening the doors or rail cover too quickly or forcefully may cause injury or damage to the appliance or surrounding equipment.
• Do not use combustible spray or place volatile or ammable substances in or near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the equipment.
• Do not throw anything onto the shelves or load any single shelf with more than 120lb. (54.5 kg) of product. They might fall off and cause injury.
• This appliance is designed only for temporary storage of food. Employ sanitary methods. Use for any other purposes (for example, storage of chemicals or medical supplies such as vaccine and serum) could cause deterioration of stored items.
• Do not block air inlets or outlets, otherwise cooling performance may be reduced.
• Do not tightly pack the cabinet. Allow some space between items to ensure good air ow. Also allow space between items and interior surfaces.
• Do not put warm or hot foods in the cabinet. Let them cool rst, or they will raise the cabinet temperature and could deteriorate other foods in the cabinet or overload the appliance.
6
Page 7
WARNING, continued
• All foods should be wrapped in plastic lm or stored in sealed containers. Otherwise foods may dry up, pass their smells onto other foods, cause frost to develop, result in poor appliance performance, or increase the likelihood of cross-contamination. Certain dressings and food ingredients, if not stored in sealed containers, may accelerate corrosion of the evaporator, resulting in failure.
• Do not store items near air outlets. Otherwise, items may freeze up and crack or break causing a risk of injury or contamination of other food.
Additional Warnings for Prep Table Models
• The entire rail must always be covered by rail dividers and pans (1/6 size, up to 6"(15cm)deep). Otherwise, the appliance will not cool properly.
• Use only 1/6 size pans up to 6"(15cm) deep. Do not use damaged pans.
• Ingredients must be pre-chilled to 37°F (3°C) or less before placing in rail.
• Keep the rail cover closed when not actively preparing food.
• The rail is for keeping ingredients cool while preparing food. If not actively preparing food for a long period such as overnight, seal pans with plastic wrap in addition to closing the rail cover. Depending on conditions, the cabinet temperature setting may need to be adjusted to prevent items from freezing. Alternatively, seal ingredients and store them in a refrigerator or freezer.
NOTICE
• Protect the oor when moving the appliance to prevent damage to the oor.
• Keep ventilation openings, in the appliance enclosure or in the built-in structure, clear of obstruction. Do not place anything on top of the appliance in an undercounter installation. There must be at least 1.5" (4 cm) overhead clearance for proper ventilation. The factory-installed rear bumpers must be in place to ensure proper rear clearance. Blockage of airow could negatively affect performance and damage the appliance.
• Do not allow the appliance to bear any outside weight.
• To prevent deformation or cracks, do not spray insecticide onto the plastic parts or let them come into contact with oil.
• To avoid damage to the gasket, use only the door handle when opening and closing.
• To avoid damage to the top seal, do not lift the appliance by the top panel or remove the top panel.
Additional Notice for Prep Table and Mega Top Models
• Do not place anything on top of the rail hood or rail cover and do not lift the appliance by the rail hood or rail cover. The rail hood and rail cover are not designed to bear any outside weight.
• CRMR27-8(-12M) Auxiliary Code B-5 to C-7: Do not place anything on the air distribution table beneath the pans. The air distribution table is not a load-bearing surface.
7
Page 8

I. Construction and Refrigeration Circuit Diagram

A. Construction

Undercounter, Worktop, Prep Table
Common Parts
• Evaporator
• Evaporator Fan
• Evaporator Fan Shroud Nameplate
Thermometer
Door Gasket
Door
Cabinet Temperature Control Dial (Cabinet Thermostat/Thermistor) Verify Auxiliary Code in Parts List for Change
Power Cord
Prep Table
Specic Parts
Air Distribution Table Panels
CRMR27-8, CRMR27-12M Auxiliary Codes B-5 to C-7
Upper Front
Lower Front
Pans
Rail Dividers
Upper Rear
Lower Rear
Rail Hood
Defrost Timer: Prep Table and Freezer. Verify Auxiliary Code in Parts List for Change
Rear Panel
Control Module: Verify Auxiliary Code in Parts List for Change
Condenser
Condenser Fan Motor
Compressor
Model Shown: CRMF27
Model Shown: CRMR36-10
Rail Cover
Cutting Board
Model Shown: CRMR27-12M
8
Page 9

B. Refrigeration Circuit Diagram

1. Refrigerator and Freezer
Condenser
High-Pressure Switch CRMR60 and CRMR72 Prep Table, CRMF48, and CRMF60
Capillary Tube
Thermostatic Expansion Valve
CRMF48(-W) Auxiliary Code: A-5 and B-5
Condenser Fan
Evaporator Fans (1, 2, or 3 depending on model)
Drier
Compressor
Evaporator
Cabinet Thermostat Bulb
Freezer and Prep Table Models: Defrost Heater, Defrost Safety Thermostat, and Defrost Thermistor
9
Page 10

II. Sequence of Operation and Service Diagnosis

The steps in the sequence are as outlined below. See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Approximate Default Temperature
Control Setting
Undercounter Worktop
Between 4 and 5 Refrigerator: 34°F (1°C)
Freezer: -5°F (-21°C)
Prep Table 6 34°F (1°C)

A1. Thermostat Control Sequence of Operation Flow Chart

1. Undercounter and Work Top: Refrigerator

Refrigerator Sequence Flow Chart
1. Startup/Cool Down
CTh above setpoint CTh cools to setpoint
CTh closed Comp energized ConFM energized EvapFM energized
Legend: Comp-compressor ConFM-condenser fan motor CTh-cabinet thermostat EvapFM-evaporator fan motor
CTh open EvapFM energized CRMR60 and CRMR72 Comp de-energized ConFM de-energized EvapFM de-energized CRMR27 and CRMR48
2. Cool Down Achieved
CTh in control
CTh above
Off cycle defrost between run cycles.
setpoint
10
Page 11

2. Prep Table

Prep Table/Mega Top Sequence Flow Chart
1. Startup
EvapFM energized
(without DH)
Legend: Comp-compressor ConFM-condenser fan motor CTh-cabinet thermistor DH-defrost heater DTh-defrost thermistor EvapFM-evaporator fan motor MH-mullion heater PH-perimeter heater
2. Cool Down
CTh above setpoint
CTh closed Comp energized ConFM energized EvapFM energized
(with DH)
3. Cool Down Achieved
CTh cools to setpoint
CTh in control
CTh open EvapFM energized Comp de-energized ConFM de-energized
4. Defrost
20 or 25 min. DT in
CTh above
8 or 6-hr. DT terminates 20 or 25-min. DT starts DH energized EvapFM energized (without DH) Comp de-energized ConFM de-energized EvapFM de-energized (with DH)
control
setpoint
8 or 6-hr. DT terminates 20 or 25-min. DT starts DH de-energized (if applicable)
CTh above
setpoint

3. Undercounter and Work Top: Freezer

Freezer Sequence Flow Chart
1. Startup/Cool Down
CTh above setpoint
CTh in control
CTh closed Comp energized ConFM energized EvapFM energized MH energized PH energized
Legend: Comp-compressor ConFM-condenser fan motor CTh-cabinet thermistor DH-defrost heater DTh-defrost thermistor EvapFM-evaporator fan motor MH-mullion heater PH-perimeter heater
2. Cool Down Achieved
CTh cools to setpoint
CTh open Comp de-energized ConFM de-energized EvapFM de-energized MH de-energized PH de-energized
3. Defrost
DT* in control
CTh above
setpoint
8 or 6-hr. DT terminates
20 or 25-min. DT starts DH energized Comp de-energized ConFM de-energized EvapFM de-energized MH de-energized PH de-energized
CTh above
setpoint
20 or 25-min. DT terminates 8 or 6-hr. DT starts DH de-energized
11
Page 12

A2. Thermistor/Control Module Sequence of Operation Flow Chart

1. Undercounter and Work Top: Refrigerator

Refrigerator Sequence Flow Chart
1. Startup/Cool Down
CTh above setpoint
*
2-min. Comp
Power on Red LED On (5 sec. Delay)
Legend: Comp-compressor ConFM-condenser fan motor CTh-cabinet thermistor EvapFM-evaporator fan motor
on timer starts
Green LED Flashes If Red LED ashes, check CTh
Comp energized ConFM energized EvapFM energized
2. Cool Down Achieved
CTh cools to setpoint
CTh in control
*
2-min. Comp off timer starts
Green LED Flashes If Red LED ashes, check CTh
Comp de-energized ConFM de-energized EvapFM de-energized
Note: Delays
*
a) 2-min. minimum Comp on timer starts when Comp energizes. b) 2-min. minimum Comp off timer starts when Comp de-energizes.
Off cycle defrost between run cycles
CTh above
setpoint
12
Page 13

2. Prep Table

°F (4.4°C).
achieved 44°F (6.7°C)
4. Defrost
3. Cool Down Achieved
Defrost:
time/temp. initiated
temp. terminated
DTh in control
*
2-min. Comp off
CTh cools to setpoint
CTh in control
setpoint CTh above
timer starts
DH de-energized
*
25-min. max. DT starts
ConFM de-energized
*
6-hr DT starts
After DOT Delay:
Comp energized
DH energized
Comp de-energized
ConFM de-energized
Evap. Temp.
reaches 44°F (6.7°C)
*
6-hr. DT terminates
5-min. min. DT starts
EvapFM energized
Comp de-energized
ConFM energized
EvapFM de-energized
*
After FDD
EvapFM energized
Prep Table Top Sequence Flow Chart
*
*
2-min. Comp on
2. Cool Down
CTh above setpoint
timer starts
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 25-min. maximum defrost time.
e) DOT (drip off time) 1-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 30-sec. EvapFM delay timer terminates or DTh reaches 40
Comp energized
ConFM energized
EvapFM energized
Note: Delays
g) If evaporator temperature raises above 50°F (10°C) during the cooling cycle, 6-hr. DT resets.
1. Startup
Red LED Off
Green LED Flashes
If Red LED Flashes,
check CTh or DTh
Power on
EvapFM energized
Red LED On
(5 sec. Delay)
13
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
Page 14

3. Undercounter and Work Top: Freezer

5. Defrost Termination
Defrost Termination:
Temp. achieved:
45°F (7°C) or 50°F (°10C)
DTh in control
Defrost
DH de-energized
Terminated
6-hr. or 8-hr. DT starts
*
After DOT Delay:
Comp energized
ConFM energized
MH energized
PH energized
*
After FDD
EvapFM energized
Defrost Initiation:
3. Defrost
Time/Temp achieved.
CTh warms
above
setpoint
6-hr. or 8-hr. DT terminates
Evap. temp. below 41°F (5°C)
6-hr. or 8-hr. DT terminates
Evap. temp. below 41°F (5°C)
5-min. min. DT starts
60-min. max. DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
Freezer Sequence Flow Chart
2. Cool Down Achieved
Achieved
2-min. Comp off
timer starts
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
Setpoint
*
CTh in control
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 1-hr. maximum defrost time.
e) DOT (drip off time) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 7-minute EvapFM delay timer terminates or DTh reaches 25°F (-4°C).
1. Startup/Cool Down
Red LED off
Green LED Flashes
If Red LED ashes,
check CTh or DTh
6-hr. or 8-hr. DT starts
2-min. Comp on
timer starts
Note: Delays
Comp energized
Power on
Red LED On
(5 sec. Delay)
ConFM energized
EvapFM energized
14
MH energized
PH energized
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
Page 15

B1. Thermostat Control Service Diagnosis

WARNING
• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Make sure all food zones are clean after the appliance is serviced.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation and proper voltage per nameplate.
See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Control Setting
Undercounter Worktop
Prep Table 6 34°F (1°C)
Between 4 and 5 Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
Note: When checking voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.

1. Undercounter and Worktop: Refrigerator

1) Unplug the appliance from the electrical outlet.
2) Remove the rear panel.
3) Plug the appliance back into the electrical outlet.
4) Startup/Cool Down–Temperature above setpoint. CTh closed. Comp, ConFM, and EvapFM energize. Diagnosis: Conrm that Comp, ConFM, and EvapFM energize. Ifnot, conrm that temperature is above setpoint and CTh is closed. Check both terminals of CTh (BK) or (BR) to a neutral (W) for 115VAC. If 115VAC is present on one terminal and not the other, replace CTh. If 115VAC is present on both terminals, Check voltage at Comp, external protector, and Comp terminals. Check Comp winding continuity. Check voltage on ConFM and EvapFM. Check ConFM and EvapFM winding continuity and check fan blades for binding.
If Comp, ConFM, and EvapFM are energized and the cabinet temperature does not
cool down, check for a restriction in the refrigeration circuit, low refrigerant charge, or inefficient Comp.5)
5) Cool Down Achieved–Temperature cools to setpoint. CThopens. Comp, ConFM, and EvapFM de-energize. Note: EvapFM continues on CRMR60 and CRMR72. Diagnosis: If temperature has cooled to setpoint and Comp and ConFM do not de-energize, check CTh continuity. If CTh defective, replace CTh. Note: EvapFM de-energizes with Comp on CRMR27 and CRMR48 and continues on CRMR60 and CRMR72.
15
Page 16

2. Prep Table

1) Unplug the appliance from the electrical outlet.
2) Remove the rear panel.
3) Plug the appliance back into the electrical outlet.
4) Startup/Cool Down–Temperature above setpoint. CTh closed. Comp, ConFM, and EvapFM energize. Diagnosis: Check that Comp, ConFM, and EvapFM energize. Ifnot, conrm that the appliance is not in a defrost cycle. DT is operating properly, temperature is above setpoint, and CTh is closed. Check voltage on DT. In cooling, 115VAC is present on both DT terminal #1 (BK) and DT terminal #4(BK) or (BR) to a neutral (W). If 115VAC is present on terminal #2 (R) to a neutral (W), advance DT out of defrost cycle or replace DT. Check both terminals of CTh (BK) or (BR) to a neutral (W) for 115VAC. If 115VAC is present on one terminal and not the other, replace CTh. If115VAC is present on both terminals, check for voltage at Comp, external protector, and Comp terminals. Check Comp winding continuity. Check voltage on ConFM and EvapFM. Check ConFM and EvapFM winding continuity and fan blades for binding. Note: CRMR60-xx and CRMR72-xx, also see "HPS Activation (CRMR60 and CRMR72 Prep Table)" below.
If Comp, ConFM, and EvapFM are energized and the cabinet temperature does not
cool down, check for a restriction in the refrigeration circuit, low refrigerant charge, or inefficient Comp.
HPS Activation (CRMR60 and CRMR72 Prep Table): Check continuity of HPS.
If open, allow time for system pressure to equalize and HPS to reset. If HPS does not reset, replace HPS and diagnose reason for HPS activation. Conrm ConFM is energized and fan blade turns freely. Check that the condenser coil is not clogged or restricted. Check that there are no restrictions in the refrigeration circuit (drier).
Conrm that the appliance location meets factory requirements:
• This appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C).
• The appliance should not be located next to ovens, grills, or other high heat producing equipment.
6) Cool Down Achieved–Temperature cools to setpoint. CTh opens. EvapFM continues. Comp and ConFM de-energize. Diagnosis: If cabinet temperature has cooled to setpoint and Comp and ConFM do not de-energize, check CTh continuity. If CTh defective, replace CTh.
7) Defrost–Defrost Initiation: DT terminates. EvapFM continues (auxiliary code C-5 and earlier). If CTh closed, Comp and ConFM de-energize. EvapFM de-energizes (auxiliary code C-6 and later) and DH energizes (CRMR48-xx aux. code C-7 and later. All others aux. code D-8 and later).
Defrost Termination: DT terminates. EvapFM continues (auxiliary code C-5 and earlier).
If CTh closed, Comp and ConFM energize. EvapFM energizes (auxiliary code C-6 and later) and DHde-energizes (CRMR48-xx aux. code C-7 and later. All others aux. code D-8 and later).
16
Page 17
Diagnosis: Defrost Initiation: Manually advance DT cam to terminate DT. Conrm
Comp and ConFM de-energize or remain de-energized and on auxiliary code C-6 and later, conrm EvapFM de-energizes. For CRMR48-xx aux. code C-7 and later and all other aux. code D-8 and later, conrm DH energizes. If not, replace DT.
Defrost Termination: Advance DT cam to terminate DT. If CTh closed, conrm Comp
and ConFM energize and on auxiliary code C-5 and earlier, conrm EvapFM energizes. For CRMR48-xx aux. code C-7 and later and all other aux. code D-8 and later, conrm DH de-energizes. If not, check DT voltage terminal #2(R) to a neutral (W). If115VAC is present, replace DT.

3. Undercounter and Worktop: Freezer

4) Startup/Cool Down–Temperature above setpoint. CTh closed. Comp, ConFM, EvapFM, PH, and MH energize. Diagnosis: Check that Comp, ConFM, EvapFM, PH, and MH energize. If not, conrm that the appliance is not in a defrost cycle, DT is operating properly, temperature is above setpoint, and CTh is closed. Check voltage onDT. In cooling, 115VAC is present on both DT terminal #1 (BK) and DT terminal #4 (BK) to a neutral (W). If 115VAC is present on terminal #2 (R) to a neutral (W), advance DT out of defrost cycle or replace DT. Check both terminals of CTh (BK) to a neutral (W) for 115VAC. If 115VAC is present on one terminal and not the other, replace CTh. If 115VAC is present on both terminals, check Comp, ConFM, and EvapFM. For CRMF48(-01)(-W)(-W01) and CRMF60(-W), also see "HPS Activation (CRMF48(-01) (-W)(-W01) and CRMF60(-W))" below.
Check voltage at Comp, external protector, and Comp terminals. Check Comp windings.
Check voltage on ConFM and EvapFM. Check ConFM and EvapFM windings. Check fan blades for binding.
If Comp, ConFM, and EvapFM are energized and the cabinet temperature does not
cool down, check for a restriction in the refrigeration circuit, low refrigerant charge, inefficient Comp, or defective TXV (CRMF48(-01)(-W)(-W01) auxiliary codes A-5 and B-5).
HPS Activation (CRMF48 and CRMF60): Check continuity of HPS. If open, allow time
for system pressure to equalize and HPS to reset. If HPS does not reset, replace HPS and diagnose reason for HPS activation. Conrm ConFM is energized and fan blade turns freely. Check that the condenser coil is not clogged or restricted. Check that there are no restrictions in the refrigeration circuit (drier, TXV (auxiliary codes A-5 and B-5)).
Conrm that the appliance location meets factory requirements:
• This appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C).
• The appliance should not be located next to ovens, grills, or other high heat producing equipment.
• A minimum of 1.5" (4 cm) overhead clearance should be provided for proper ventilation.
5) Cool Down Achieved–Temperature cools to setpoint. CTh opens. Comp, ConFM, EvapFM, PH, and MH de-energize. Diagnosis: If temperature has cooled to setpoint and Comp, ConFM, EvapFM, PH, and MH do not de-energize, check CTh continuity. IfCTh defective, replace CTh.
17
Page 18
6a) Defrost
Early DT's were designed with 8-hr. interval and 20-min. defrost cycle. Later DT's were designed with 6-hr. interval and 25-min. defrost cycle. Manual advance in and out of defrost by turning the defrost dial is quickest way to troubleshoot components.
Defrost Initiation: DT terminates. DH energizes. If CTh closed, Comp, ConFM, EvapFM, PH, and MH de-energize.
Defrost Termination: DT terminates. DH de-energizes. If CTh closed, Comp, ConFM,
EvapFM, PH, and MH energize.
Diagnosis: Defrost Initiation: Manually advance DT cam to terminate DT. Conrm DH
energizes and Comp, ConFM, EvapFM, PH, and MH de-energize. If not, replace DT. If Comp, ConFM, EvapFM, PH, and MH de-energize, check DH. Conrm DST is closed. If not, let DH cool, then recheck DST. If DST is still open, replace DST. Check DH amp draw and DH continuity.
Defrost Termination: Advance DT cam to terminate DT. If CTh closed, conrm Comp,
ConFM, EvapFM, PH, and MH energize. Conrm DH de-energizes. If not, check DT voltage terminal #2 (R) to a neutral (W). If 115VAC is present, replace DT.
7) PH and MH Diagnosis: Check that PH and MH energize. Check for 115VAC at PH and MH. If 115VAC is not present, check power supply. If 115VAC is present, check amp draw of PH and MH. If an amp reading is not present, check the continuity of PH and MH. If defective, replace PH or MH.
Legend: Comp–compressor; ConFM–condenser fan motor; CTh–cabinet thermostat;
DH–defrostheater; DST–defrost safety thermostat; DT–defrost timer; EvapFM–evaporator fan motor; HPS–high-pressure switch; MH–mullion heater; PH–perimeterheater; TXV–thermostatic expansion valve
18
Page 19

B2. Thermistor/Control Module Service Diagnosis

WARNING
• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Appliance is heavy. Use care when lifting or positioning. Work in pairs when needed to prevent injury or damage.
• Make sure all food zones are clean after the appliance is serviced.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation and proper voltage per nameplate.
See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Control Setting
Undercounter Worktop
Prep Table 6 34°F (1°C)
Between 4 and 5 Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation and proper voltage per nameplate. Conrm that the appliance location meets factory requirements:
• This appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 86°F (7°C to 30°C).
• The appliance should not be located next to ovens, grills, or other high heat producing equipment. Check CM using the steps in "II.C. Control Module Check."
Note: • When checking voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
• CM has high and low voltage protection. If off on either protection, no LED is visible and all components are off. High Voltage: 135VAC Low Voltage: 90VAC
• Solid red LED for 5 sec. at startup.
• Flashing green LED: Normal operation.
• Flashing red LED: check cabinet thermistor and defrost thermistor (if applicable).
• CM has a 2 min. minimum on time and 2 min. minimum off time for Comp.
1. Service Diagnosis: All Refrigerators, Prep Tables, and Freezers
1) Unplug the appliance from the electrical outlet.
2) Remove the rear panel.
19
Page 20
3) Plug the appliance back into the electrical outlet. If appliance was in defrost when power supply was disconnected, defrost is terminated and normal cooling cycle begins when power supply is reconnected.
4) Startup/Cool Down–There is a slight delay (solid red LED for 5 sec., then ashing green LED). Temperature above setpoint at CTh and if applicable, conrm appliance is not in a defrost cycle (PT and Freezers). Comp, CondFM, and EvapFM energize. 2-min. Comp on timer starts. Freezers: PH, and MH energize.
a) CTh Diagnosis: If CTh fails, a red LED ashes along with the green LED on the CM.
Conrm CTh is properly connected to CM. Check Ohm reading of CTh. Replace as needed.
b) TD Diagnosis: Conrm TD is set between 4 and 5. Check Ohm reading of TD.
Replace as needed.
c) CM Diagnosis: Conrm green LED is ashing. If not, check for 115VAC between
CM 2 (L) black (BK) wire and CM 3 white (W) neutral wire. If 115VAC is not present, check power cord connections and breaker/fuse. Conrm wiring connections are secure for both CM 2 (L) black (BK) (power supply) and CM 3 white (W) (neutral). If 115VAC is present and green LED is not ashing, replace CM.
d) Comp/CondFM Diagnosis: Check that Comp and ConFM energize. If not, conrm
that the temperature is above setpoint. Next, check for 115VAC at CM (C) 1 brown (BR) wire to neutral (W) wire. If 115VAC is not present, replace CM. If 115VAC is present, check HPS continuity (if applicable). See "f) HPS Activation" below. Comp: If 115VAC is present, check Comp external overload, start cap, start relay, and Comp motor windings. Replace as needed. CondFM: If 115VAC is present, check fan blade for binding, then check ConFM motor windings.
e) EvapFM Diagnosis: Check that EvapFM(s) energize. If not, check for 115VAC at
CM (F) 5 dark blue (DBU) wire to neutral (W) wire. If 115VAC is not present, replace CM. If 115VAC is present, check fan blades for binding, then check EvapFM motor windings.
f) HPS Activation (CRMR60 and CRMR72 Prep Table and Freezer Models):
Check continuity of HPS. If open, allow time for system pressure to equalize and HPS to reset. If HPS does not reset, replace HPS and diagnose reason for HPS activation. Conrm ConFM is energized and fan blade turns freely. Check that the condenser coil is not clogged or restricted. Check that there are no restrictions in the refrigeration circuit (drier).
g) PH and MH Diagnosis (Freezer only): PH and MH follow Comp operation. When
Comp is energized, PH and MH are energized. If 115VAC is present, check amp draw of PH and MH. If an amp reading is not present, check the continuity of PH and MH. If defective, replace PH or MH.
If Comp, ConFM, and EvapFM are energized and the cabinet does not cool down,
check for a restriction in the refrigeration circuit, low refrigerant charge, or inefficient Comp.
20
Page 21
5) Cool Down Achieved–Temperature cools to setpoint. Comp and ConFM de-energize. UC/WT Refrigerators and Freezers: EvapFM de-energizes. Prep Table: EvapFM continues. Diagnosis: If temperature setpoint achieved and Comp, ConFM, and EvapFM(except PT models) does not de-energize, check CTh and TD continuity. If CTh or TD is defective, replace. If CTh and TD are good and either the Comp, ConFM, and/or EvapFM (except PT models) continue, or if EvapFM on PT models de-energizes, replace CM.
6) Defrost–Manually initiated defrost, off cycle defrost, and time-initiated temperature-terminated heated defrost.
1a) Manually-Initiated (All): Turn the TD all the way to the right. Wait 1 to 3 sec. then
back to original setting. Defrost initiated. If defrost does not initiate, wait 1 to 2 min. and repeat process.
1b) Off Cycle-Initiated (UC/WT Refrigerators): Off cycle between cooling cycles.
CTh cools below TD setting. TD setting satised. Comp, CondFM, and EvapFM de-energize.
1c) Time-Initiated (Heated) (Prep Table and All Freezers): 6-hr. DT terminates.
(1) Prep Tables: Comp and ConFM de-energizes, EvapFM continues. DH energizes.
5-min. minimum DT starts and 25-min. maximum DT starts.
(2) Freezers: Comp, ConFM, PH, MH, and EvapFM de-energize. DH energizes.
5-min. minimum DT starts and 1-hr maximum DT starts.
Note: When DTh is above 50°F on Prep Tables or above 41°F on Freezers, defrost
will not initiate and 6-hr. DT resets and starts once DTh temperature cools below 50°F on Prep Tables and cools below 41°F on Freezers.
2a) Manually-Terminated: Turn the TD all the way to the right. Wait 1 to 3 sec. then
back to original setting. Defrost terminated. If DH continues or Comp does not energize, make several more attempts of manual termination.
2b) Off Cycle-Terminated: CTh warms above TD setting. Comp, CondFM, EvapFM
energize.
2c) Temperature-Terminated: DTh achieves termination temperature or backup DT
terminates.
(1) Prep Tables: 44
°F achieved or 25-min. backup DT terminates. DH de-energizes.
IfCTh calling for cooling, 1-min. Comp delay timer starts (drip time) and 90-sec. EvapFM delay timer starts. 1-min. Comp delay timer terminates. Comp and ConFM energize. 30 sec. later, 90-sec. EvapFM delay timer terminates and EvapFM energizes. Note: If DTh achieves 40°F before 90-sec. EvapFM delay timer terminates, 90-sec. EvapFM delay timer terminates and EvapFM energizes.
(2) Freezers: 45°F achieved or 1-hr. DT terminates. DH de-energizes. If CTh calling
for cooling, 3-min. Comp delay timer starts (drip time) and 7-min. EvapFM delay timer starts. 3-min. Comp delay timer terminates. Comp and ConFM energize. 4 min. later, 7-min. EvapFM delay timer terminates and EvapFM energizes. Note: If DTh achieves 25°F before 7-min. EvapFM delay timer terminates, 7-min. EvapFM delay timer terminates and EvapFM energizes.
21
Page 22
Defrost Diagnosis:
1) Manual-Initiation or Time-Initiation: TD rotated to max. position and back or 6-hr. or 80hr. DT terminates. After rotating TD several times and defrost still not activated, wait 1 to 2 min. and repeat process. Replace TD as needed.
(2) CM Diagnosis: Conrm DH energizes (if applicable) and Comp, ConFM, and
EvapFM (if applicable) de-energize. If not, replace CM.
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize. If not,
check for 115VAC at CM 1 (C) (BR) to neutral (W). If 115VAC is present, Check DTh continuity. Replace as needed. If DTh conrmed, replace CM.
(4) EvapFM (if applicable): Conrm EvapFM de-energizes. If not, check for 115VAC
at CM 5 (F) (DBU) to neutral (W). If 115VAC is present, conrm Comp and ConFM de-energized. Next, check DTh continuity. Replace as needed. If DTh conrmed, replace CM.
2) Off Cycle Defrost: Off cycle defrost. Has CTh warmed above temperature setpoint? If not, conrm CTh continuity. Replace as needed. If CTh conrmed, replace CM.
3) Heated Defrost Diagnosis: Initiation; Conrm Comp is energized, then manually initiate defrost. Rotate TD all the way to the right. Wait 1 to 5sec. then rotate back to original setting. Defrost initiated.
a) Prep Table: Check that Comp and ConFM de-energize. DH energizes.
EvapFMcontinues.
b) Freezer: Check that Comp, ConFM, PH, MH, and EvapFM de-energize.
DHenergizes.
(1) TD: If Comp and ConFM continue, wait 1 to 2 min. and make several more
attempts of manual initiation. Ifmanual initiation fails, replace TD. (2) CM: If TD conrmed and Comp and ConFM continue, replace CM. (3) DH: If Comp and ConFM de-energize, check that DH energizes. Check for
115VAC at CM 4 (H) (R) to CM 3 (N) (W). If 115VAC is not present, replace CM.
If115VAC is present, and DH is not energized, check for 115VAC at DTS black (B)
wire to any white (W) neutral wire. If 115VAC is not present, DTS is open. Let cool
and reset. If DTS does not reset (close), replace DTS. If 115VAC is present, check
continuity of DH. Replace as needed.
4) Heated Defrost Diagnosis: Termination; a) Prep Table
(1) DTh: DTh warms to 44°F (6.6°C). DH de-energizes. Conrm continuity of DTh. Replace as needed. If DTh is good and DH continues after DTh achieves 44°F (6.6°C), replace CM.
b) Freezer
(1) DTh: DTh warms to 45°F. (7°C) DH de-energizes. Conrm continuity of DTh. Replace as needed. If DTh is good and DH continues after DTh achieves 45°F (7°C), replace CM.
Legend: Comp–compressor; ConFM–condenser fan motor; CM–control module;
CTh–cabinet thermistor; TD–temperature dial; DH–defrostheater; DST–defrost safety thermostat; DT–defrost timer; DTh–defrost thermistor; EvapFM–evaporator fan motor; HPS–high-pressure switch; MH–mullion heater; PH–perimeterheater
22
Page 23

C. Defrost Timer Check

The defrost timer (DT) starts once the appliance in plugged into the electrical outlet. There are 2 possible interval and defrost cycle times: 8-hr./20min. and 6-hr./25min.
1. Defrost Timer
Before replacing a DT that does not show a visible defect and that you suspect is bad, conduct the folowing check procedure. This procedure will help you verify your diagnosis. Always choose a neutral (W) to establish a good power supply and neutral connection to DT: 115VAC at DT 1 (BK) to DT 3 (W).
2. Normal Operation
DT 8-hr. or 6-hr. interval timer starts. DT switch (internal) closed between DT 1 (BK) and DT 4 (BK or BR) and open between DT 1 (BK) and DT 2 (R). Once DT terminates DT switch (internal) opens. DT switch (internal) opens between DT4 (BK or BR) and DT1(BK) and closes between DT 1 (BK) and DT 2 (R). Diagnosis: In normal operation, Comp, ConFM, and EvapFM energized, check for 115VAC between DT1(BK) and neutral (W). Next, check for 115VAC at DT4 (BK or BR) and neutral (W). If 115VAC is not present between DT4 (BK or BR) and neutral (W) (Comp, ConFM, and EvapFM de-energized), check for 115VAC between DT 2 (R) and neutral (W). If 115VAC is not present between DT4 (BK or BR) and neutral (W) or between DT 2 (R) and neutral (W), DT switch (internal) defective. Replace DT. If 115VAC is present between DT4 (BK or BR) and neutral (W) (Comp, ConFM, and EvapFM energized), advance the cam dial on DT until it clicks (defrost initiated). Comp, ConFM, and EvapFM de-energize. If not, replace DT. Next, check for 115VAC between DT 2 (R) and neutral (W). If 115VAC is not present, replace DT. Off Cycle Defrost: If 115VAC is present, off cycle defrost initiated and 20-min. or 25-min. DT starts. After 20-min. or 25-min. defrost cycle terminates, Comp, ConFM, and EvapFM energize. If not, replace DT. Heated Defrost: If 115VAC is present, DH energized and 20-min. or 25-min. DT starts. Once DST achieves termination temperature, DH de-energized. After 20-min. or 25-min. defrost cycle terminates, Comp, ConFM, and EvapFM energize. If not, replace DT.
Legend: Comp–compressor; ConFM–condenser fan motor; CM–control module;
CTh–cabinet thermistor; TD–temperature dial; DH–defrostheater; DST–defrost safety thermostat; DT–defrost timer; DTh–defrost thermistor; EvapFM–evaporator fan motor; HPS–high-pressure switch; MH–mullion heater; PH–perimeterheater
23
Page 24

D. Control Module Check

1. Control Module
Before replacing a CM that does not show a visible defect and that you suspect is bad, conduct the following check procedure. This procedure will help you verify your diagnosis. Always choose a neutral (W) to establish a good power supply and neutral connection to CM: 115VAC at CM 2 (L) (BR)
2. Startup/Cool Down
At startup, CM displays a solid red LED for 5 sed. After 5 sec. CM turns red LED off and begins ashing a green LED. This is normal operation. If a red LED ashes (fault code), check CTh or DTh for continuity and good connection to CM.
1) Check all wiring connections.
2) Be sure the power supply is connected to the electrical outlet.
3) Conrm the CTh and DTh are properly connected (no red LED ashing). A Red LED turns on for 5 sec. at startup. After 5 sec. the red LED turns off and a green LED starts ashing. This is normal operation. If the red LED starts ashing, check CTh and DTh continuity. Replace as needed.
4) Check that Comp, ConFM, and EvapFM energize (PH and MH on freezers). If not check CTh status. If CTh ohm reading is in proper range, Comp and ConFM and PH and MH (freezers); check for 115VAC at CM 1 (C) (BR) to neutral (W). If 115VAC is not present, replace CM. If 115VAC is present and Comp energized and ConFM did not, check ConFM blades for binding and motor winding continuity. If PH or MH (freezers) does not energize, check continuity, replace as needed. EvapFM; Check for 115VAC at CM 5 (F) (DBU) to neutral (W). If 115VAC is not present, replace CM. If115VAC is present, check EvapFM blades for binding and motor winding continuity.
3. Defrost initiation
5) Manual Defrost Check: Turn the TD all the way to the right. Wait 1 to 3 sec. then back to original setting. Defrost initiated. If Comp and ConFM continue, wait 1 to 2 min. and repeat process of manual initiation. If Comp remains energized, replace CM.
6) Conrm Comp, ConFM, EvapFM (UC/WT refrigerator and freezer), PH and MH (freezers) de-energize. If not, for Comp, ConFM and PH and MH (freezers), check for 115VAC at CM 1 (C) (BR) to neutral (W) and for EvapFM (if applicable) CM 5 (F) (DBU) to neutral (W). If 115VAC is present, replace CM. Note: EvapFM continues on Prep Table models.
7) Heated Defrost: Conrm DH energizes. Check for 115VAC at CM 4 (H) (R) to neutral (W). If 115VAC is not present, replace CM.
4. Defrost Termination
8) Check that all components restart after defrost termination.
a) UC/WT Refrigerator: CTh above setpoint. Cool cycle starts. Comp, ConFM, and
EvapFM energize.
24
Page 25
b) Prep Table: DTh warms to 44°F (6.6°C). DH de-energizes. Conrm continuity of
DTh. Replace as needed. If DTh is good and DH continues after DTh achieves 44°F (6.6°C), replace CM.
c) Freezer: DTh warms to 45°F (7°C) or 50°F (10°C). DH de-energizes. Conrm
continuity of DTh. Replace as needed. If DTh is good and DH continues after DTh achieves 45°F (7°C) or 50°F (10°C), replace CM.
Legend: Comp–compressor; ConFM–condenser fan motor; CM–control module;
CTh–cabinet thermistor; DH–defrost heater; DTh–defrost thermistor; EvapFM–evaporator fan motors, MH–mullion heater; PH–perimeter heater
25
Page 26

E. Diagnostic Table

Before consulting the diagnostic tables, check the following:
• Check the cabinet temperature control setting. See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Control Setting
Undercounter Worktop
Prep Table 6 34°F (1°C)
Between 4 and 5 Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
• Make sure the doors are not left open or opened too often and that they are sealing properly.
• On prep tables, pans and rail dividers must be in place. Otherwise, the rail will not cool properly.
• Make sure product is not blocking airow and that the cabinet is not overloaded with warm or hot product. Product should be allowed to cool before putting in the appliance. On prep tables, only load ingredients that have been pre-chilled to 37°F (3°C) or less.
• Check for correct installation and proper voltage per appliance nameplate. This appliance is not intended for outdoor use. Normal operating ambient temperature: – Undercounter and Worktop 45°F to 100°F (7°C to 38°C) – Prep Table 45°F to 86°F (7°C to 30°C)
• The appliance should not be located next to ovens, grills, or other high heat producing equipment. A minimum of 1.5" (38 mm) overhead clearance is required for proper ventilation.
1. Appliance Not Cooling
Appliance Not Cooling - Possible Cause
Power Supply
1.
Power Supply Cord and Plug
2.
Wiring
3.
Cabinet Thermostat or Cabinet
4.
Thermistor Cabinet Temperature Dial
5.
Defrost Timer or Control Module
6.
(if applicable)
Evaporator Fan Motor
7.
Condenser Fan Motor
8.
Unplugged, blown fuse, or tripped or defective circuit breaker.
a)
Loose connection.
b)
Not within specications.
c)
Loose connection.
a)
Defective.
b)
Loose connection or open.
a)
Faulty.
b)
Loose, disconnected, or defective.
a)
Loose, disconnected, or defective.
a)
Defrost timer defective. If applicable.
a)
Control module in alarm (red LED ashing). If applicable.
b)
Control module defective. If applicable.
c)
Defective.
a)
Fan blade binding.
b)
Defective.
a)
Fan blade binding.
b)
26
Page 27
Appliance Not Cooling - Possible Cause
Compressor External Protector
9.
a) b) c) d) e)
f)
Compressor
10.
Condenser
11.
Evaporator
12.
Refrigerant/Refrigerant Lines
13.
a) a) a) a) b)
High-Pressure Switch
10. (if applicable)
a)
b)
c)
d)
e)
f)
Thermostatic Expansion Valve
11.
(not adjustable) CRMF48(-01)(-W)(-W01) (auxiliary codes A-5 and B-5)
a)
Dirty condenser.
Condenser fan motor not operating.
Defective.
Start relay defective.
Low charge.
Start capacitor (if applicable) defective.
Defective.
Dirty.
Dirty or frozen up.
Gas leak.
Refrigerant lines or components restricted.
Dirty condenser.
Ambient temperature too warm.
Condenser fan motor not operating.
Refrigerant overcharge.
Refrigerant lines or components restricted.
Bad contacts.
Defective.
2. Evaporator is Frozen Up
Evaporator is Frozen Up - Possible Cause
Evaporator
1.
Evaporator Fan Motor
2.
Refrigerant Charge
3.
Defrost Heater (if applicable)
4.
Defrost Timer or Control Module
5.
(if applicable) Defrost Safety Thermostat Open
6.
(if applicable) Thermostatic Expansion Valve
7.
(not adjustable) CRMF48(-01)(-W)(-W01) (auxiliary codes A-5 and B-5)
Dirty.
a)
Defective.
a)
Fan blade binding.
b)
Low.
a)
Defective.
a)
Defective.
a)
Defective.
a)
Defective.
a)
3. Defrost Fails to Initiate or Terminate
Defrost Fails to Initiate or Terminate - Possible Cause
Defrost Thermistor (if applicable)
1.
Defrost Timer or Control Module
2.
(if applicable) Defrost Heater (if applicable)
3.
Defective.
a)
Defective.
a)
Defective
a)
27
Page 28

III. Controls and Adjustments

A. Temperature Settings

1. Temperature Reading
A thermometer with both °F and °C scales is mounted in the cabinet. See Fig. 1.
2. Cabinet Temperature
The appliance features a cabinet temperature control dial (TD). The warmest setting is 1and the coldest setting is 7. See the table for default cabinet temperature control settings.
Model Default Cabinet Temperature
Control Setting
Undercounter Worktop
Prep Table 6 34°F (1°C)
Between 4 and 5 Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
Fig. 1
Warmer Colder
Cabinet Temperature Control Dial

B. Defrost

There are 2 types of defrost: Off Cycle Defrost and Heated Defrost.
Manual Initiation (All Models): Turn the TD all the way to the right. Wait 3 sec. then
back to original setting. Defrost initiated.
Automatic Initiation: 8-hr. or 6hr. Defrost timer terminates. Manual Termination: Turn the TD all the way to the right. Wait 3 sec. then back to
original setting. Defrost terminated. Automatic Termination: Cabinet temperature above setpoint, or defrost thermistor above termination temperature, or back defrost timer terminates.
Thermometer
1. Undercounter and Worktop Refrigerators
Off-cycle defrost between run cycles.
28
Page 29
2. Prep Table and Freezer
Time-Initiated Defrost Cycle: 20-min. or 25-min. defrost cycle once every 8 or 6 hrs. (25/8 or 20/6). Defrost cycle initiation and termination are controlled by the defrost timer or control module and defrost thermistor.
Prep Table Refrigerators: The evaporator fan motor remains energized and all other components de-energize during the defrost cycle.
Freezers: The defrost heater energizes and all other components de-energize during the defrost cycle. There is an in-line defrost safety thermostat.
a) Defrost Timer Defrost: To initiate a manual defrost cycle follow the steps below.
1) Make sure the appliance is unplugged, then remove the rear panel. See Fig. 2.
Defrost Timer Cam
2) Rotate the defrost timer cam clockwise until it clicks. When the appliance is plugged in it will start a 20-min. or 25-min. defrost
Fig. 2
cycle. To bypass the defrost cycle and start at the beginning of an 8-hr. or 6 hr. interval, rotate the defrost timer cam clockwise until
nd
it clicks a 2
time.
Rear Panel
3) Replace the rear panel in its correct position.
4) Plug the appliance into the electrical outlet.
b) Control Module with Defrost Thermistor Defrost: To initiate a manual defrost cycle follow the steps below.
1) Rotate TD all the way to the right. Wait 1 to 5sec. then rotate back to original setting. Defrost initiated. See Fig. 3.
2) Repeat step 1 to terminate defrost.
Fig.3
29
Page 30

C. Safety Devices

1. Compressor External or Internal Protector (All Models)
If combined temperature/amperage value is above the limit specied by the compressor manufacturer, the compressor protector operates independently to turn off the compressor. The compressor protector de-energizes the compressor until the temperature/amperage value returns to an acceptable level.
2. High-Pressure Switch
If pressure on the high-side of the appliance exceeds Hoshizaki specications, the high-pressure switch activates and interrupts the compressor circuit, de-energizing the compressor until the pressure returns to an acceptable level. If the condenser fan motor is operating and the compressor is off, it is most likely that the compressor protector opened. If both the compressor and condenser fan motor are off, it is most likely the appliance is off or the high-pressure switch has opened.

D. Perimeter and Mullion Heaters

Freezers are equipped with perimeter and mullion heaters. If condensation occurs, check continuity of heaters.
30
Page 31

IV. Refrigeration Circuit and Component Service Information

WARNING
• This appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• To reduce the risk of electric shock, do not touch the plug with damp hands.
• Unplug the appliance from the electrical outlet before servicing.
• Make sure all food zones in the appliance are clean after the appliance is serviced.

A. Refrigeration Circuit Service Information

WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-134a as a mixture with pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 minutes when replacing or servicing parts. The Polyol Ester (POE) oils used in R-134a appliances can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
No refrigerant access valves are provided on this appliance. Using proper refrigerant practices, utilize a temporary tap-line valve on the high side to recover the refrigerant. Store the refrigerant in an approved container. Do not discharge the refrigerant into the atmosphere. After recovery is complete, replace the tap-line valve with a proper, permanent access valve.
31
Page 32
2. Brazing
WARNING
• R-134a itself is not ammable at atmospheric pressure and temperatures up to 212°F (100°C).
• R-134a itself is not explosive or poisonous. However, when exposed to high temperatures (open ames), R-134a can be decomposed to form hydrouoric acid and carbonyl uoride both of which are hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-134a as a mixture with pressurized air for leak testing.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-134a as a mixture with pressurized air for leak testing.
3. Evacuation and Recharge (R-134a)
1) Attach a vacuum pump to the system. Be sure the high-side charging hose is connected to the eld-installed high-side access valve.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump, then open the high-side valve on the gauge manifold. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity.
4) Close the high-side valve on the gauge manifold.
32
Page 33
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. See the nameplate for the required refrigerant charge. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets the requirements of ARI Standard 700 (latest edition) be used.
6) A liquid charge is recommended when charging an R-134a system. Place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) Close the high-side valve on the gauge manifold, then close the refrigerant access valve (if applicable). Disconnect the gauge manifold hose.
9) Cap the access valve to prevent a possible leak.

B. Component Service Information

NOTICE
When replacing a component listed below, see the notes to help ensure proper operation.
Component Notes
Compressor Install a new start relay and compressor external protector. WARNING! To reduce the
risk of electric shock, be sure to reconnect the compressor's ground wire.
Thermostatic Expansion Valve CRMF48(-01) (-W)(-W01) (auxiliary codes A-5 and B-5)
• Attach the thermostatic expansion valve bulb to the suction line in the same location as the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder.
33
Page 34

C. Door Reversal

This appliance is provided with a cabinet design which, after being delivered to the installation location, permits changing of the door swing from left to right or right to left. To change the door swing, follow the steps below. Example shows change from right hinged to left hinged.
WARNING
• Wear eye protection when reversing the doors.
• Keep ngers away from edge of upper hinge bracket. Spring cartridge can cause the upper hinge bracket to move suddenly with extreme force.
Door and Lower Hinge Removal and Relocation
1) Remove all items from the appliance. Make sure the appliance is unplugged from the electrical outlet. Move the appliance out for ease of access then lock the casters.
2) With the door closed, loosen, but do not remove, the upper hinge bracket outer screw. See Fig. 4. Next, open the door to the fully open position and remove the upper hinge bracket inner screw. See Fig. 5.
3) Slide the upper hinge bracket out from under the outer screw and remove the door.
WARNING! Keep away from upper hinge bracket. Upper hinge bracket may spring closed.
4) Replace the upper hinge bracket inner screw in its original position and tighten, then tighten the upper hinge bracket outer screw.
Upper Hinge Bracket
WARNING! Upper hinge bracket may spring closed
Upper Hinge Bracket
Upper Hinge Bracket Outer Screw
Door Closed
Fig. 4
Upper Hinge Bracket Inner Screw
Door Fully Open
Fig. 5
5) Remove the lower hinge bracket. See Fig. 6. Be sure to leave the thrust washer in place.
6) Clear the foam from the lower hinge bracket mounting holes prior to securing lower hinge bracket in its new location. Install the lower hinge bracket in its new location. Besure the lower hinge bracket is pushed all the way in and the thrustwasher is in its original position.
Thrust Washer
Lower Hinge Bracket Mounting Holes
Lower Hinge Bracket
Thrust Washer
Lower Hinge Bracket
Bolts
Fig. 6
34
Bolts
Page 35
Upper Hinge Bracket Removal and Spring Cartridge Relocation
7) While preventing the upper hinge bracket from rotating, remove the upper hinge bracket from the spring cartridge. See Fig. 7. Note which side of the upper hinge bracket is facing up.
8) Remove the ller cap, ller screws, and spring cartridge. See Fig. 16. Leave the thrust washers in place on the spring cartridge. NOTICE! Spring cartridge may be difficult to remove. Be careful not to damage the nish. See Fig. 8.
Upper Hinge Bracket
Screw
Washer
Door
Filler Screws
Filler Cap
Door
Screws
Thrust Washers
Spring Cartridge
Fig. 7
Fig. 8
9) Clear foam from the spring cartridge hole to allow for spring cartridge installation. See Fig. 9. Install the spring cartridge in its new location. Reinstall the ller cap and ller screws on the opposite side of the door.
Screws
Spring Cartridge
Spring Cartridge Hole
Filler Screws
Door
Filler Cap
Fig. 9
Lower Door Prep and Upper Hinge Bracket Relocation
10) Remove the ller cap and nylon bearing from the bottom of the door. SeeFig.10. Reinstall on the opposite side.
11) Make sure the thrust washers are in place on the spring cartridge, then ip the upper hinge bracket over from its original position and install onto the spring cartridge in the door open position. See Fig. 11. The upper hinge bracket should be positioned as
Filler Cap
shown.
Fig. 10
Upper Hinge Bracket Outer Screw Slot
Nylon Bearing
Screw
Washer
Upper Hinge Bracket Inner Screw Hole
Upper Hinge Bracket
Thrust Washers
Inside of Door
Fig. 11
35
Page 36
Door Installation
12) Remove the black plastic ller cap located from the hole above where the spring cartridge screw will line up. Note: The black plastic ller cap is not reusable.
13) Remove the upper hinge bracket screws from the new location and apply Loctite Threadlocker Blue 242 or 243 to the threads. Next, start the upper hinge bracket outer screw into the appliance. Rotate a few threads into the appliance; do not tighten thescrew. See Fig. 12.
Upper Hinge Bracket Outer Screw
Black Plastic Filler Cap
Upper Hinge Bracket Inner Screw
Upper Hinge Bracket Outer Screw
Fig. 12
14) Be sure the lower hinge bracket thrust washer is in place, then place the door on the lower hinge bracket in the fully open position. Slide the door upper hinge bracket outer slot onto the upper hinge bracket outer screw. See Fig. 13.
15) Install the upper hinge bracket inner screw and tighten.
Upper Hinge Bracket
Upper Hinge Bracket
Outer Screw
Upper Hinge Bracket Outer Screw
Upper Hinge Bracket
WARNING! Upper hinge bracket may spring closed
Door Fully Open
Lower Hinge Bracket
Thrust Washer
Fig. 13
36
Upper Hinge Bracket Inner Screw
Door Fully Open
Page 37
16) Close the door and tighten the upper hinge bracket outer screw. See Fig. 14.
Upper Hinge Bracket Outer Screw
Upper Hinge Bracket
Door Fully Closed
Fig. 14
17) Check the door operation to assure it opens and closes properly. Note: Hold door at 45°angle from closed position and release. Door should close on its own. If not, adjust hinge bracket.
18) Unlock the casters and move the appliance back into its original position. Lock the casters once in position, then plug the appliance back into the electrical outlet. Allow the appliance to cool down prior to putting product back in.

D. Door/Drawer Location Reversal

The appliance is provided with a cabinet design which, after being delivered to the installation location, permits changing of the drawer and door locations. To change the drawer and door locations, follow the steps below. Example shows CRMR48-D2.
WARNING
• Wear proper PPE (personal protection equipment) when executing these procedures (safety glasses and gloves).
• Keep ngers away from edge of upper hinge bracket. Spring cartridge can cause the upper hinge bracket to move suddenly with extreme force.
Drawer and Drawer Frame Removal
1) Remove all items from the appliance. Make sure the appliance is unplugged from the electrical outlet. Move the appliance out for ease of access then lock the casters. See Fig. 15.
Model Shown: CRMR48-D2
Casters
Fig. 15
37
Page 38
2) Remove the drawers. Pull the drawer out to its fully extended position. Open the safety clips (one on each side) by sliding them forward, then rotating them up. See Fig. 16. Lift up on the handle slightly, then pull to disengage the drawer. Be sure to support the rear and front of the drawer while removing it. WARNING! Be sure to close the safety
clips when reinstalling the drawer.
Safety Clip
Closed
Safety Clip
Open
Safety Clips
Drawer Slides
Upper Drawer
Lower Drawer
Fig. 16
3) Remove the 4 horizontal mullion screws, then cut the horizontal mullion silicone loose and remove the horizontal mullion. See Fig. 17.
Horizontal Mullion Screws
Horizontal Mullion Silicone
Horizontal Mullion Silicone
Horizontal Mullion
Fig. 17
38
Page 39
4) Remove the hex-bolts from the 2 right (front and rear) and 2 left (front and rear) brackets (2 hex-bolts per bracket), then remove the right and left drawer frames. See Fig. 18.
Right Drawer Frame
Right Rear Hex-Bolts
Right Front Hex-Bolts
Left Rear Bracket
Left Drawer Frame
Right Rear Bracket
Right Front Bracket
Right Drawer Frame
Right Rear Bracket
Right Front Bracket
Left Drawer Frame
Left Front Bracket
Fig. 18
Left Rear Bracket
Left Rear Hex-Bolts
Left Front Hex-Bolts
Left Drawer Frame
Left Front Bracket
Left Rear Bracket
Left Front Bracket
Right Drawer Frame
Right Front Bracket
Right Rear Bracket
39
Page 40
Pilaster and Inner Brackets Relocation
5) Remove the shelf from the door section, then remove the pilasters. See Fig. 19.
Right Side Pilasters
Vertical Mullion
Shelf
Center Rear Drawer Frame Bracket
Center Rear Pilaster
Vertical Mullion Pilaster
Fig. 19
6) Remove the center rear drawer frame bracket and the ller screw. See Fig. 20. Slide the center rear drawer frame bracket over to the new location and secure it. Place the ller screw in the former center rear drawer frame bracket hole.
New Center Rear Drawer Frame Bracket Location
Center Rear Drawer Frame Bracket
Filler Screw
Filler Screw
Center Rear Drawer Frame Bracket
Fig. 20
7) Remove the vertical mullion bracket. Rotate 180 degrees and mount it in the vertical mullion right mounting holes. See Fig. 21.
Vertical Mullion Bracket Rotation
Vertical Mullion Left Mounting Holes
Vertical Mullion Bracket
Vertical Mullion
Vertical Mullion Bracket
Fig. 21
Vertical Mullion Bracket
Vertical Mullion Right Mounting Holes
Vertical Mullion
40
Page 41
8) Place and secure the pilasters and shelf support clips in their new location. See Fig. 22. Replace the shelf.
Center Rear Pilaster
Left Side Pilasters
Vertical Mullion Pilaster
Vertical Mullion
Center Rear Drawer Frame Bracket
Vertical Mullion Bracket
Fig. 22
Door Relocation
9) With the door closed, loosen, but do not remove, the upper hinge bracket outer screw. See Fig. 23. Next, open the door to the fully open position and remove the upper hinge bracket inner screw. See Fig. 24.
10) Slide the upper hinge bracket out from under the outer screw and remove the door.
WARNING! Keep away from upper hinge bracket. Upper hinge bracket may spring closed.
11) Replace the upper hinge bracket inner screw in its original position and tighten, then tighten the upper hinge bracket outer screw.
Upper Hinge Bracket
Fig. 24
Upper Hinge Bracket
Upper Hinge Bracket Outer Screw
Door Closed
Fig. 23
WARNING! Upper hinge bracket may spring closed
Upper Hinge Bracket Inner Screw
Door Fully Open
41
Page 42
12) Remove the lower hinge bracket. See Fig. 25. Be sure to leave the thrust washer in place.
13) Install the lower hinge bracket in its new location. Be sure the lower hinge bracket is pushed all the way in and the thrust washer is in its original position.
Lower Hinge
Thrust Washer
Bracket Mounting Holes
Lower Hinge Bracket
Thrust Washer
Lower Hinge Bracket
Bolts
Fig. 25
Bolts
14) Remove the black plastic ller cap located from the hole above where the spring cartridge screw will line up. Note: The black plastic ller cap is not reusable.
15) Remove the upper hinge bracket screws from the new location and apply Loctite Threadlocker Blue 242 or 243 to the threads. Next, start the upper hinge bracket outer screw into the appliance. Rotate a few threads into the appliance; do not tighten thescrew. See Fig. 26.
Upper Hinge
Upper Hinge Bracket Outer Screw
Upper Hinge Bracket Inner Screw
Black Plastic Filler Cap
Bracket Outer Screw
Fig. 26
16) Be sure the lower hinge bracket thrust washer is in place, then place the door on the lower hinge bracket in the fully open position. Slide the door upper hinge bracket outer slot onto the upper hinge bracket outer screw. See Fig. 27.
17) Install the upper hinge bracket inner screw and tighten.
Upper Hinge Bracket
Upper Hinge Bracket Outer Screw
Thrust Washer
Lower Hinge Bracket
WARNING! Upper hinge bracket may spring closed
Upper Hinge Bracket Inner Screw
Door Fully Open
Door Fully Open
Fig. 27
42
Upper Hinge Bracket
Upper Hinge Bracket Outer Screw
Page 43
18) Close the door and tighten the upper hinge bracket outer screw. See Fig. 28.
Upper Hinge Bracket
Door Fully Closed
Upper Hinge Bracket Outer Screw
Fig. 28
19) Check the door operation to assure it opens and closes properly. Note: Hold door at 45°angle from closed position and release. Door should close on its own. If not, adjust hinge bracket.
Drawer Relocation
Left Drawer Frame Relocation
20) Place the left rear bracket in place on the center rear drawer frame bracket with hex-bolts removed in step4. Leave loose, do not tighten at this time. See Fig. 36.
21) Place the left front bracket in place on the vertical mullion bracket with the hex-bolts removed in step 4. See Fig. 29. Leave loose, do not tighten at this time.
Fig. 29
Center Rear Drawer Frame Bracket
Left Rear Bracket
Hex-Bolts
Center Rear Drawer Frame Bracket
Left Rear Bracket
Vertical Mullion
Vertical Mullion Bracket
Left Front Bracket
43
Vertical Mullion
Vertical Mullion Bracket
Left Front Bracket
Page 44
22) Place the left drawer frame in the appliance and align under the left rear bracket and tighten, then align under the left front bracket and tighten. See Fig. 30.
Note: Be sure the left drawer frame is under both the left rear bracket lip and left front
bracket lip.
Left Rear Bracket Lip
Left Drawer Frame
Left Front Bracket Lip
Fig. 30
Right Drawer Frame Relocation
23) Place the right rear bracket in place on the right side panel with the hex-bolts removed in step4. Leave loose, do not tighten at this time. See Fig. 31.
24) Place the right front bracket in place on the right side panel with the hex-bolts removed in step4. Leave loose, do not tighten at this time. See Fig. 31.
Hex-Bolts
Right Rear Bracket
Right Front Bracket
Vertical Mullion
Fig. 31
44
Right Rear Bracket
Right Front Bracket
Vertical Mullion
Page 45
25) Place the right drawer frame in the appliance and align under the right rear bracket and tighten, then align under the right front bracket and tighten. See Fig. 32.
Note: Be sure the right drawer frame is under both the right rear bracket lip and right
front bracket lip.
Right Rear Bracket Lip
Right Front Bracket Lip
Right Drawer Frame
Fig. 32
45
Page 46
Horizontal Mullion Replacement
26) Place the horizontal mullion in its correct position and secure with screws removed in step3.
27) Place a bead of food grade silicone down the 2 outside vertical gaps between the mullion and appliance. See Fig. 33.
Model Shown: CRMR48-D2
Silicone Location for Horizontal Mullion
Fig. 33
Horizontal Mullion
Silicone Location for Horizontal Mullion
46
Page 47
28) Place the lower drawer in the lower drawer slides and the upper drawer in the upper drawer slides. See Fig. 34. WARNING! Be sure to close the safety clips when
reinstalling the drawer.
29) Make sure all gaskets are making good contact. Using a ashlight, check that there are no openings around all gaskets.
30) Unlock the casters and move the appliance back into its original position. Lock the casters once in position, then plug the appliance back into the electrical outlet. Allow the appliance to cool down prior to loading it with food products.
Model Shown: CRMR48-D2
Fig. 34
47
Page 48

V. Preparing the Appliance for Periods of Non-Use

When shutting down the appliance for periods of non-use, follow the instructions below.
WARNING
Prevent the doors from closing to reduce the risk of children getting trapped.
NOTICE
Clean the cabinet interior, door gaskets, and shelves.
1) Before shutting down the appliance, move the stored food into another refrigerator or freezer.
2) Unplug the appliance. WARNING! To reduce the risk of electric shock, do not touch
the plug with damp hands.
48
Page 49

VI. Disposal

When disposing of the appliance, follow the instructions below.
WARNING
Remove the door to reduce the risk of children getting trapped. Leave the shelves in place so that children may not easily climb inside.
This appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certied service personnel.
49
Page 50

VII. Technical Information

A. Electrical and Refrigerant Data

Design
Pressure
AC Supply
Model (includes drawer models)
CRMR27 Undercounter, Worktop, and Prep Table 115/60/1 2.6 290 120 5.6 CRMF27 Undercounter and Worktop 115/60/1 3.4 310 120 5.0 CRMR36 Undercounter, Worktop, Prep Table, and Mega
To p CRMR48 Undercounter and Worktop 115/60/1 2.6 240 120 6.5 CRMR48 Prep Table and Mega Top 115/60/1 2.6 290 120 6.5 CRMF48 Undercounter and Worktop F-7 and Earlier CRMF48 Undercounter and Worktop G05 and Later 4.7 360 140 7 CRMR60 Undercounter and Worktop 115/60/1 4.2 290 120 8 CRMR60 Prep Table and Mega Top F-7 and Earlier CRMR60 Prep Table and Mega Top F-8 and Later and
Models Converted with SP-5227 Kit CRMF60 Undercounter and Worktop F-7 and Earlier CRMF60 Undercounter and Worktop G-5 and Later 9.5 360 140 9.5 CRMR72 Undercounter and Worktop 115/60/1 4.2 290 120 8 CRMR72 Prep Table and Mega Top F-7 and Earlier CRMR72 Prep Table and Mega Top F-8 and Later and
Models Converted with SP-5227 Kit
Voltage Amperes
115/60/1 2.9 290 120 5.6
115/60/1
115/60/1 6 360 140
115/60/1
115/60/1 6 360 140
6 360 140 9.2
6 360 140 10.6
(PSIG)
HIGH LOW 134a
Refrigerant
(oz.)
10.3
10.4
9.5
12
See the nameplate for electrical and refrigeration specications. The nameplate is located inside the cabinet. We reserve the right to make changes in specications and design without prior notice.
50
Page 51

B. Wiring Diagrams

1a. Undercounter and Worktop: Refrigerator; Cabinet Thermostat

CRMR27 and CRMR48:
Auxiliary Code C-6 and Later
CRMR27: DBU
for auxiliary code
A-5(K) and earlier
51
Page 52

1b. Undercounter and Worktop: Refrigerator; Cabinet Thermistor/Control Module

52
Page 53

2a. Prep Table; Cabinet Thermostat (Without Defrost Heater)

* High-Pressure Switch
Cut-Out 300±10 PSIG
Cut-In 190±20 PSIG
*
53
Page 54

2b. Prep Table; Cabinet Thermostat (With Defrost Heater)

*
**
°F±5°F (49°C±3°C)
°F±5°F (21°C±3°C)
70
120
* Defrost Thermostat
Cut-Out
Cut-In
54
* High-Pressure Switch
Cut-Out 300±10 PSIG
Cut-In 190±20 PSIG
Page 55

2c. Prep Table; Cabinet Thermistor/Control Module

*
**
** High-Pressure Switch
Cut-Out 300±10 PSIG
Cut-In 190±20 PSIG
°F±5°F (49°C±3°C)
°F±5°F (21°C±3°C)
70
120
55
* Defrost Thermostat
Cut-Out
Cut-In
Page 56

3a. Undercounter and Work Top: Freezer; Cabinet Thermostat

DBU for auxiliary code A-5(K) and earlier
*
**
°F±5°F (49°C±3°C)
°F±5°F (21°C±3°C)
70
120
56
** High-Pressure Switch
Cut-Out 300±10 PSIG
Cut-In 190±20 PSIG
* Defrost Thermostat
Cut-Out
Cut-In
Page 57

3b. Undercounter and Work Top: Freezer; Cabinet Thermistor/Control Module

*
**
°F±5°F (49°C±3°C)
120
°F±5°F (21°C±3°C)
70
57
* Defrost Thermostat
Cut-Out
Cut-In
** High-Pressure Switch
Cut-Out 300±10 PSIG
Cut-In 190±20 PSIG
Loading...