Only qualied service technicians should install and service the appliance. To
obtain the name and phone number of your local Hoshizaki Certied Service
Representative, visit www.hoshizaki.com. No service should be undertaken until
the technician has thoroughly read this Service Manual. Failure to service and
maintain the appliance in accordance with this manual will adversely affect safety,
performance, component life, and warranty coverage. Proper installation is the
responsibility of the installer. Product failure or property damage due to improper
installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, send an e-mail message, or write to the Hoshizaki Technical
Support Department for assistance.
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read
the warnings and guidelines contained in this booklet carefully as they provide
essential information for the continued safe use, service, and maintenance of the
appliance. Retain this booklet for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Refrigeration Circuit Diagram ................................................................. 8
A. Construction .................................................................................................................. 8
B. Refrigeration Circuit Diagram ........................................................................................ 9
II. Sequence of Operation and Service Diagnosis ............................................................... 10
A1. Thermostat Control Sequence of Operation Flow Chart ............................................ 10
1. Undercounter and Work Top: Refrigerator .............................................................. 10
3a. Undercounter and Work Top: Freezer; Cabinet Thermostat ................................. 56
3b. Undercounter and Work Top: Freezer; Cabinet Thermistor/Control Module ......... 57
4
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICEIndicates a situation which could result in damage to the
appliance or property.
IMPORTANTIndicates important information about the use and care of the
appliance.
WARNING
This appliance should be destined only to the use for which it has been expressly
conceived. Any other use should be considered improper and therefore dangerous.
The manufacturer cannot be held responsible for injury or damage resulting from
improper, incorrect, and unreasonable use. Failure to service and maintain the
appliance in accordance with this manual will adversely affect safety, performance,
component life, and warranty coverage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic
precautions including the following:
• Only qualied service technicians should install and service this appliance.
• This appliance must be installed in accordance with applicable national, state, and
local codes and regulations.
• To reduce the risk of electric shock, do not touch the plug with damp hands.
• Unplug the appliance before servicing.
• This appliance requires an independent power supply of proper capacity. See
the nameplate for electrical specications. Failure to use an independent power
supply of proper capacity can result in a tripped breaker, blown fuse, damage to
existing wiring, or component failure. This could lead to heat generation or re.
• THIS APPLIANCE MUST BE GROUNDED.This appliance is equipped with a
NEMA5-15 three-prong grounding plug
hazards. It must be plugged into a properly grounded, independent 3-prong wall
outlet. If the outlet is a 2-prong outlet, it is your personal responsibility to have
a qualied electrician replace it with a properly grounded, independent 3-prong
wall outlet. Do not remove the ground prong from the power cord and do not use
an adapter plug. Failure to follow these instructions may result in death, electric
shock, or re.
• Do not use an extension cord.
• Do not use an appliance with a damaged power cord. The power cord should not
be altered, jerked, bundled, weighed down, pinched, or tangled. Such actions
could result in electric shock or re. To unplug the appliance, be sure to pull the
plug, not the cord, and do not jerk the cord.
to reduce the risk of potential shock
5
WARNING, continued
• The GREEN ground wire in the factory-installed power cord is connected to the
appliance. If it becomes necessary to remove or replace the power cord, be sure
to connect the power cord's ground wire.
• Do not splash, pour, or spray water directly onto or into the appliance. This might
cause short circuit, electric shock, corrosion, or failure.
• Do not make any alterations to the appliance. Alterations could result in electric
shock, injury, re, or damage to the appliance.
• This appliance is not intended for use by persons (including children) with reduced
physical, sensory, or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
• Children should be properly supervised around this appliance.
• Do not climb, stand, or hang on the appliance or door or allow children or animals
to do so. Do not climb into the appliance or allow children or animals to do so.
Death or serious injury could occur or the appliance could be damaged.
• Be careful not to pinch ngers when opening and closing the doors or rail cover
(prep table models). Be careful when opening and closing the doors or rail cover
when children are in the area.
• Open and close the doors and rail cover (prep table models) with care. Opening
the doors or rail cover too quickly or forcefully may cause injury or damage to the
appliance or surrounding equipment.
• Do not use combustible spray or place volatile or ammable substances in or near
the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance
could cause harm to individuals or damage to the equipment.
• Do not throw anything onto the shelves or load any single shelf with more than
120lb. (54.5 kg) of product. They might fall off and cause injury.
• This appliance is designed only for temporary storage of food. Employ sanitary
methods. Use for any other purposes (for example, storage of chemicals or
medical supplies such as vaccine and serum) could cause deterioration of stored
items.
• Do not block air inlets or outlets, otherwise cooling performance may be reduced.
• Do not tightly pack the cabinet. Allow some space between items to ensure good
air ow. Also allow space between items and interior surfaces.
• Do not put warm or hot foods in the cabinet. Let them cool rst, or they will raise
the cabinet temperature and could deteriorate other foods in the cabinet or
overload the appliance.
6
WARNING, continued
• All foods should be wrapped in plastic lm or stored in sealed containers.
Otherwise foods may dry up, pass their smells onto other foods, cause frost
to develop, result in poor appliance performance, or increase the likelihood of
cross-contamination. Certain dressings and food ingredients, if not stored in
sealed containers, may accelerate corrosion of the evaporator, resulting in failure.
• Do not store items near air outlets. Otherwise, items may freeze up and crack or
break causing a risk of injury or contamination of other food.
Additional Warnings for Prep Table Models
• The entire rail must always be covered by rail dividers and pans (1/6 size, up to
6"(15cm)deep). Otherwise, the appliance will not cool properly.
• Use only 1/6 size pans up to 6"(15cm) deep. Do not use damaged pans.
• Ingredients must be pre-chilled to 37°F (3°C) or less before placing in rail.
• Keep the rail cover closed when not actively preparing food.
• The rail is for keeping ingredients cool while preparing food. If not actively
preparing food for a long period such as overnight, seal pans with plastic
wrap in addition to closing the rail cover. Depending on conditions, the cabinet
temperature setting may need to be adjusted to prevent items from freezing.
Alternatively, seal ingredients and store them in a refrigerator or freezer.
NOTICE
• Protect the oor when moving the appliance to prevent damage to the oor.
• Keep ventilation openings, in the appliance enclosure or in the built-in structure,
clear of obstruction. Do not place anything on top of the appliance in an
undercounter installation. There must be at least 1.5" (4 cm) overhead clearance
for proper ventilation. The factory-installed rear bumpers must be in place
to ensure proper rear clearance. Blockage of airow could negatively affect
performance and damage the appliance.
• Do not allow the appliance to bear any outside weight.
• To prevent deformation or cracks, do not spray insecticide onto the plastic parts or
let them come into contact with oil.
• To avoid damage to the gasket, use only the door handle when opening and
closing.
• To avoid damage to the top seal, do not lift the appliance by the top panel or
remove the top panel.
Additional Notice for Prep Table and Mega Top Models
• Do not place anything on top of the rail hood or rail cover and do not lift the
appliance by the rail hood or rail cover. The rail hood and rail cover are not
designed to bear any outside weight.
• CRMR27-8(-12M) Auxiliary Code B-5 to C-7: Do not place anything on the air
distribution table beneath the pans. The air distribution table is not a load-bearing
surface.
7
I. Construction and Refrigeration Circuit Diagram
A. Construction
Undercounter, Worktop, Prep Table
Common Parts
• Evaporator
• Evaporator Fan
• Evaporator Fan Shroud
Nameplate
Thermometer
Door Gasket
Door
Cabinet Temperature Control Dial
(Cabinet Thermostat/Thermistor)
Verify Auxiliary Code in Parts List
for Change
Power Cord
Prep Table
Specic Parts
Air Distribution Table Panels
CRMR27-8, CRMR27-12M
Auxiliary Codes B-5 to C-7
Upper Front
Lower Front
Pans
Rail Dividers
Upper Rear
Lower Rear
Rail Hood
Defrost Timer:
Prep Table and
Freezer.
Verify Auxiliary
Code in Parts List
for Change
Rear Panel
Control Module:
Verify Auxiliary Code in
Parts List for Change
Condenser
Condenser Fan Motor
Compressor
Model Shown: CRMF27
Model Shown: CRMR36-10
Rail Cover
Cutting Board
Model Shown: CRMR27-12M
8
B. Refrigeration Circuit Diagram
1. Refrigerator and Freezer
Condenser
High-Pressure Switch
CRMR60 and CRMR72 Prep Table,
CRMF48, and CRMF60
Capillary Tube
Thermostatic
Expansion Valve
CRMF48(-W)
Auxiliary Code: A-5 and B-5
Condenser Fan
Evaporator Fans
(1, 2, or 3 depending on model)
Drier
Compressor
Evaporator
Cabinet Thermostat Bulb
Freezer and Prep Table Models: Defrost Heater, Defrost Safety Thermostat, and Defrost Thermistor
9
II. Sequence of Operation and Service Diagnosis
The steps in the sequence are as outlined below.
See the table for default cabinet temperature control settings.
ModelDefault Cabinet Temperature
Approximate Default Temperature
Control Setting
Undercounter
Worktop
Between 4 and 5Refrigerator: 34°F (1°C)
Freezer: -5°F (-21°C)
Prep Table634°F (1°C)
A1. Thermostat Control Sequence of Operation Flow Chart
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermostat
EvapFM-evaporator fan motor
CTh open
EvapFM energized CRMR60 and CRMR72
Comp de-energized
ConFM de-energized
EvapFM de-energized CRMR27 and CRMR48
2. Cool Down Achieved
CTh in control
CTh above
Off cycle defrost
between run cycles.
setpoint
10
2. Prep Table
Prep Table/Mega Top Sequence Flow Chart
1. Startup
EvapFM energized
(without DH)
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
Off cycle defrost
between run cycles
CTh above
setpoint
12
2. Prep Table
°F (4.4°C).
achieved
44°F (6.7°C)
4. Defrost
3. Cool Down Achieved
Defrost:
time/temp. initiated
temp. terminated
DTh in control
*
2-min. Comp off
CTh cools to setpoint
CTh in control
setpoint
CTh above
timer starts
DH de-energized
*
25-min. max. DT starts
ConFM de-energized
*
6-hr DT starts
After DOT Delay:
Comp energized
DH energized
Comp de-energized
ConFM de-energized
Evap. Temp.
reaches 44°F (6.7°C)
*
6-hr. DT terminates
5-min. min. DT starts
EvapFM energized
Comp de-energized
ConFM energized
EvapFM de-energized
*
After FDD
EvapFM energized
Prep Table Top Sequence Flow Chart
*
*
2-min. Comp on
2. Cool Down
CTh above setpoint
timer starts
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 25-min. maximum defrost time.
e) DOT (drip off time) 1-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 30-sec. EvapFM delay timer terminates or DTh reaches 40
Comp energized
ConFM energized
EvapFM energized
Note: Delays
g) If evaporator temperature raises above 50°F (10°C) during the cooling cycle, 6-hr. DT resets.
1. Startup
Red LED Off
Green LED Flashes
If Red LED Flashes,
check CTh or DTh
Power on
EvapFM energized
Red LED On
(5 sec. Delay)
13
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
3. Undercounter and Work Top: Freezer
5. Defrost Termination
Defrost Termination:
Temp. achieved:
45°F (7°C) or 50°F (°10C)
DTh in control
Defrost
DH de-energized
Terminated
6-hr. or 8-hr. DT starts
*
After DOT Delay:
Comp energized
ConFM energized
MH energized
PH energized
*
After FDD
EvapFM energized
Defrost Initiation:
3. Defrost
Time/Temp achieved.
CTh warms
above
setpoint
6-hr. or 8-hr. DT terminates
Evap. temp. below 41°F (5°C)
6-hr. or 8-hr. DT terminates
Evap. temp. below 41°F (5°C)
5-min. min. DT starts
60-min. max. DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
Freezer Sequence Flow Chart
2. Cool Down Achieved
Achieved
2-min. Comp off
timer starts
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
Setpoint
*
CTh in control
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 1-hr. maximum defrost time.
e) DOT (drip off time) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 7-minute EvapFM delay timer terminates or DTh reaches 25°F (-4°C).
1. Startup/Cool Down
Red LED off
Green LED Flashes
If Red LED ashes,
check CTh or DTh
6-hr. or 8-hr. DT starts
2-min. Comp on
timer starts
Note: Delays
Comp energized
Power on
Red LED On
(5 sec. Delay)
ConFM energized
EvapFM energized
14
MH energized
PH energized
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
B1. Thermostat Control Service Diagnosis
WARNING
• The appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Make sure all food zones are clean after the appliance is serviced.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical
system and components. Before proceeding, check for correct installation and proper
voltage per nameplate.
See the table for default cabinet temperature control settings.
ModelDefault Cabinet Temperature
Control Setting
Undercounter
Worktop
Prep Table634°F (1°C)
Between 4 and 5Refrigerator: 34°F (1°C)
Approximate Default Temperature
Freezer: -5°F (-21°C)
Note: When checking voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
1. Undercounter and Worktop: Refrigerator
1) Unplug the appliance from the electrical outlet.
2) Remove the rear panel.
3) Plug the appliance back into the electrical outlet.
4) Startup/Cool Down–Temperature above setpoint. CTh closed. Comp, ConFM, and
EvapFM energize. Diagnosis: Conrm that Comp, ConFM, and EvapFM energize.
Ifnot, conrm that temperature is above setpoint and CTh is closed. Check both
terminals of CTh (BK) or (BR) to a neutral (W) for 115VAC. If 115VAC is present on
one terminal and not the other, replace CTh. If 115VAC is present on both terminals,
Check voltage at Comp, external protector, and Comp terminals. Check Comp winding
continuity. Check voltage on ConFM and EvapFM. Check ConFM and EvapFM winding
continuity and check fan blades for binding.
If Comp, ConFM, and EvapFM are energized and the cabinet temperature does not
cool down, check for a restriction in the refrigeration circuit, low refrigerant charge, or
inefficient Comp.5)
5) Cool Down Achieved–Temperature cools to setpoint. CThopens. Comp, ConFM, and
EvapFM de-energize. Note: EvapFM continues on CRMR60 and CRMR72.
Diagnosis: If temperature has cooled to setpoint and Comp and ConFM do not
de-energize, check CTh continuity. If CTh defective, replace CTh.
Note: EvapFM de-energizes with Comp on CRMR27 and CRMR48 and continues on
CRMR60 and CRMR72.
15
2. Prep Table
1) Unplug the appliance from the electrical outlet.
2) Remove the rear panel.
3) Plug the appliance back into the electrical outlet.
4) Startup/Cool Down–Temperature above setpoint. CTh closed. Comp, ConFM, and
EvapFM energize. Diagnosis: Check that Comp, ConFM, and EvapFM energize.
Ifnot, conrm that the appliance is not in a defrost cycle. DT is operating properly,
temperature is above setpoint, and CTh is closed. Check voltage on DT. In cooling,
115VAC is present on both DT terminal #1 (BK) and DT terminal #4(BK) or (BR) to a
neutral (W). If 115VAC is present on terminal #2 (R) to a neutral (W), advance DT out
of defrost cycle or replace DT. Check both terminals of CTh (BK) or (BR) to a neutral
(W) for 115VAC. If 115VAC is present on one terminal and not the other, replace CTh.
If115VAC is present on both terminals, check for voltage at Comp, external protector,
and Comp terminals. Check Comp winding continuity. Check voltage on ConFM and
EvapFM. Check ConFM and EvapFM winding continuity and fan blades for binding.
Note: CRMR60-xx and CRMR72-xx, also see "HPS Activation (CRMR60 and CRMR72
Prep Table)" below.
If Comp, ConFM, and EvapFM are energized and the cabinet temperature does not
cool down, check for a restriction in the refrigeration circuit, low refrigerant charge, or
inefficient Comp.
HPS Activation (CRMR60 and CRMR72 Prep Table): Check continuity of HPS.
If open, allow time for system pressure to equalize and HPS to reset. If HPS does
not reset, replace HPS and diagnose reason for HPS activation. Conrm ConFM is
energized and fan blade turns freely. Check that the condenser coil is not clogged or
restricted. Check that there are no restrictions in the refrigeration circuit (drier).
Conrm that the appliance location meets factory requirements:
• This appliance is not intended for outdoor use. Normal operating ambient temperature
should be within 45°F to 100°F (7°C to 38°C).
• The appliance should not be located next to ovens, grills, or other high heat producing
equipment.
6) Cool Down Achieved–Temperature cools to setpoint. CTh opens. EvapFM continues.
Comp and ConFM de-energize. Diagnosis: If cabinet temperature has cooled to
setpoint and Comp and ConFM do not de-energize, check CTh continuity. If CTh
defective, replace CTh.
7) Defrost–Defrost Initiation: DT terminates. EvapFM continues (auxiliary code C-5 and
earlier). If CTh closed, Comp and ConFM de-energize. EvapFM de-energizes (auxiliary
code C-6 and later) and DH energizes (CRMR48-xx aux. code C-7 and later. All others
aux. code D-8 and later).
If CTh closed, Comp and ConFM energize. EvapFM energizes (auxiliary code C-6
and later) and DHde-energizes (CRMR48-xx aux. code C-7 and later. All others aux.
code D-8 and later).
Comp and ConFM de-energize or remain de-energized and on auxiliary code C-6
and later, conrm EvapFM de-energizes. For CRMR48-xx aux. code C-7 and later
and all other aux. code D-8 and later, conrm DH energizes. If not, replace DT.
Defrost Termination: Advance DT cam to terminate DT. If CTh closed, conrm Comp
and ConFM energize and on auxiliary code C-5 and earlier, conrm EvapFM
energizes. For CRMR48-xx aux. code C-7 and later and all other aux. code D-8 and
later, conrm DH de-energizes. If not, check DT voltage terminal #2(R) to a neutral
(W). If115VAC is present, replace DT.
3. Undercounter and Worktop: Freezer
4) Startup/Cool Down–Temperature above setpoint. CTh closed. Comp, ConFM,
EvapFM, PH, and MH energize. Diagnosis: Check that Comp, ConFM, EvapFM,
PH, and MH energize. If not, conrm that the appliance is not in a defrost cycle, DT is
operating properly, temperature is above setpoint, and CTh is closed. Check voltage
onDT. In cooling, 115VAC is present on both DT terminal #1 (BK) and DT terminal
#4 (BK) to a neutral (W). If 115VAC is present on terminal #2 (R) to a neutral (W),
advance DT out of defrost cycle or replace DT. Check both terminals of CTh (BK) to a
neutral (W) for 115VAC. If 115VAC is present on one terminal and not the other, replace
CTh. If 115VAC is present on both terminals, check Comp, ConFM, and EvapFM. For
CRMF48(-01)(-W)(-W01) and CRMF60(-W), also see "HPS Activation (CRMF48(-01)
(-W)(-W01) and CRMF60(-W))" below.
Check voltage at Comp, external protector, and Comp terminals. Check Comp windings.
Check voltage on ConFM and EvapFM. Check ConFM and EvapFM windings. Check
fan blades for binding.
If Comp, ConFM, and EvapFM are energized and the cabinet temperature does not
cool down, check for a restriction in the refrigeration circuit, low refrigerant charge,
inefficient Comp, or defective TXV (CRMF48(-01)(-W)(-W01) auxiliary codes A-5 and
B-5).
HPS Activation (CRMF48 and CRMF60): Check continuity of HPS. If open, allow time
for system pressure to equalize and HPS to reset. If HPS does not reset, replace HPS
and diagnose reason for HPS activation. Conrm ConFM is energized and fan blade
turns freely. Check that the condenser coil is not clogged or restricted. Check that there
are no restrictions in the refrigeration circuit (drier, TXV (auxiliary codes A-5 and B-5)).
Conrm that the appliance location meets factory requirements:
• This appliance is not intended for outdoor use. Normal operating ambient temperature
should be within 45°F to 100°F (7°C to 38°C).
• The appliance should not be located next to ovens, grills, or other high heat producing
equipment.
• A minimum of 1.5" (4 cm) overhead clearance should be provided for proper
ventilation.
5) Cool Down Achieved–Temperature cools to setpoint. CTh opens. Comp, ConFM,
EvapFM, PH, and MH de-energize. Diagnosis: If temperature has cooled to setpoint
and Comp, ConFM, EvapFM, PH, and MH do not de-energize, check CTh continuity.
IfCTh defective, replace CTh.
17
6a) Defrost
Early DT's were designed with 8-hr. interval and 20-min. defrost cycle.
Later DT's were designed with 6-hr. interval and 25-min. defrost cycle.
Manual advance in and out of defrost by turning the defrost dial is quickest way to
troubleshoot components.
Defrost Initiation: DT terminates. DH energizes. If CTh closed, Comp, ConFM,
EvapFM, PH, and MH de-energize.
energizes and Comp, ConFM, EvapFM, PH, and MH de-energize. If not, replace
DT. If Comp, ConFM, EvapFM, PH, and MH de-energize, check DH. Conrm DST is
closed. If not, let DH cool, then recheck DST. If DST is still open, replace DST. Check
DH amp draw and DH continuity.
Defrost Termination: Advance DT cam to terminate DT. If CTh closed, conrm Comp,
ConFM, EvapFM, PH, and MH energize. Conrm DH de-energizes. If not, check DT
voltage terminal #2 (R) to a neutral (W). If 115VAC is present, replace DT.
7) PH and MH Diagnosis: Check that PH and MH energize. Check for 115VAC at PH and
MH. If 115VAC is not present, check power supply. If 115VAC is present, check amp
draw of PH and MH. If an amp reading is not present, check the continuity of PH and
MH. If defective, replace PH or MH.
Legend: Comp–compressor; ConFM–condenser fan motor; CTh–cabinet thermostat;