Only qualied service technicians should install, service, and maintain the
unit. No service or maintenance should be undertaken until the technician
has thoroughly read this Service Manual. Failure to service and maintain
the equipment in accordance with this manual may adversely affect safety,
performance, component life, and warranty coverage.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service and maintenance of the unit.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write, or send an e-mail message to the Hoshizaki Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number __________________________
• Serial Number __________________________
• Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the unit is serviced or maintenance
operations are performed. Only qualied service technicians should install,
service, and maintain the unit. Read the warnings contained in this booklet
carefully as they give important information regarding safety. Please retain this
booklet for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Specications ...................................................................................................................... 6
A. Nameplate Ratings ........................................................................................................ 6
B. Dimensions ................................................................................................................... 6
1. Refrigerated Volume and Shelf Space ..................................................................... 6
2. One Section/Two Section ........................................................................................ 7
II. General Information ........................................................................................................... 8
A. Construction .................................................................................................................. 8
1. One Section ............................................................................................................. 8
2. Two Section ............................................................................................................. 9
B. Sequence of Operation ............................................................................................... 10
1. Sequence Cycles and Shutdown ........................................................................... 10
a) Refrigerator ...................................................................................................... 10
b) Freezer ..............................................................................................................11
3. Evacuation and Recharge ..................................................................................... 34
B. Removal and Replacement of Compressor ................................................................. 36
C. Removal and Replacement of Evaporator................................................................... 37
D. Removal and Replacement of Condenser................................................................... 39
E. Removal and Replacement of Expansion Valve (2-Section Freezer) .......................... 40
F. Removal and Replacement of Evaporator Fan Motor .................................................. 41
G. Removal and Replacement of Condenser Fan Motor ................................................. 41
H. Removal and Replacement of Control Module ............................................................ 42
I. Removal and Replacement of Thermistors ................................................................... 43
J. Removal and Replacement of Condensate Pump ....................................................... 45
K. Removal and Replacement of Door Gasket ................................................................ 46
L. Door Re-Hinging .......................................................................................................... 46
VI. Cleaning Instructions ...................................................................................................... 46
4
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, or damage to the unit.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
CAUTION Indicates a situation which could result in damage to the unit.
IMPORTANT Indicates important information about the use and care of the
unit.
WARNING
This unit should be destined only to the use for which it has been expressly
conceived. Any other use should be considered improper and therefore
dangerous. The manufacturer cannot be held responsible for eventual damage
caused by improper, incorrect, and unreasonable use.
To reduce the risk of death, electric shock, serious injury, or re, follow
basic precautions including the following:
• This unit requires an independent power supply. See the nameplate for proper
voltage and breaker/fuse size. Failure to use a proper breaker or fuse can
result in a tripped breaker, blown fuse, or damage to existing wiring. This
could lead to heat generation or re.
• THIS UNIT MUST BE GROUNDED:This unit is equipped with a 3-prong
grounding plug to reduce the risk of potential shock hazards. It must be
plugged into a properly grounded, independent 3-prong wall outlet. If the
outlet is a 2-prong outlet, it is your personal responsibility to have a qualied
electrician replace it with a properly grounded, independent 3-prong wall
outlet. Do not remove the ground prong from the power cord and do not use
an adapter plug.
• Do not use an extension cord.
• Make sure the power switch is in the "OFF" position before plugging in or
unplugging the unit to reduce the risk of electric shock.
• Do not use a unit with a damaged power cord. The power cord should not be
altered, jerked, bundled, weighed down, pinched, or tangled. Such actions
could result in electric shock or re. To unplug the unit, be sure to pull the
plug, not the cord, and do not jerk the cord.
• To reduce the risk of electric shock, do not touch the plug or power switch with
damp hands.
• This unit should be disassembled or repaired only by qualied service
personnel to reduce the risk of electric shock, injury, or re.
• Do not make any alterations to the unit. Alterations could result in electric
shock, injury, re, or damage to the unit.
See the nameplate for electrical and refrigeration specications. The nameplate is located
on the inner right side wall of the cabinet behind the front panel.
Note: We reserve the right to make changes in specications and design without prior
notice.
B. Dimensions
1. Refrigerated Volume and Shelf Space
Total Refrigerated
Model
C_1A-FS/HS2011.5
C_2A-FS/HS4524.6
Volume ft
3
Total Shelf Space
2
ft
Note: We reserve the right to make changes in specications and design without prior
notice.
6
2. One Section/Two Section
Unit: mm (in.)
LEG
HEIGHT
CASTER
HEIGHT
DOOR
POSITION
STAY OPEN
(DS)
DOOR SWING
HEIGHT
(DHU/DHL)
DOOR OPENING
(DH)
HEIGHT
DOOR OPENING
1.13
153 28.6
6.02
4
101.6
132.5
659
25.94
713.3 / 710.3
28.08 / 27.96
59.59
1513.6
DHLDHU
DWDW
DH
579
(DW)
WIDTH
DOOR OPENING
DEPTH
INTERIOR
HEIGHT
INTERIOR
579
WIDTH
INTERIOR
EXTERIOR
DEPTH (D)
EXTERIOR
HEIGHT (H)
698.5
EXTERIOR
WIDTH (W)
22.80
711.2
1513.6
22.80
852.9
1920.5
27.5
593.7
28
59.59
1277.5
33.58
75.61
1397
23.37
D
DS
50.30
W
H
55
MODELS
COMMERCIAL
1 SEC
COMMERCIAL
2 SEC
7
II. General Information
A. Construction
1. One Section
Compressor
Condensate Pump
Condenser Fan Motor
Control Box Cover
Power Cord
Reservoir
Cover
Reservoir
Control Box
Float Switch
Float
Switch
Bracket
Control Module
Power Switch
Display Module
Door Lock
Light
Condenser
Air Filter
Front Panel
Door Switch
Door
• Evaporator
• Cabinet Thermistor
• Defrost Thermistor
• Evaporator Fan Shroud
Model Shown: CR1A-FS
Models
CR1A-FS/HS and CF1A-FS/HS
8
Door Gasket
2. Two Section
Condensate Pump
Power Cord
Float Switch
Bracket
Reservoir Cover
Display Module
Door Switch
Control Box Cover
Control Box
Float Switch
Reservoir
Compressor
Control Module
Power Switch
Thermostatic Expansion Valve (CF2A-FS/HS)
Condenser Fan Motor
Condenser
Air Filter
Front Panel
Door Switch
Door Lock
Light
• Evaporator
• Cabinet Thermistor
• Defrost Thermistor
• Evaporator Fan Shroud
Model Shown: CF2A-HS
Models
CR2A-FS/HS and CF2A-FS/HS
9
Door
Door Latch
Door Gasket
B. Sequence of Operation
1. Sequence Cycles and Shutdown
The steps in the sequence are as outlined below.
Note: 1. There is a slight delay at startup.
2. There is a 2-minute minimum Comp on time and a 2-minute minimum Comp off
time.
3. EvapFM de-energizes when door is opened on FS and when upper door is
opened on HS.
4. A oat-switch controlled condensate pump (located on top of the unit) is used to
pump evaporator condensation to the condensate pan.
5. On freezers, EvapFM is de-energized during defrost.
a) Refrigerator
1. Startup/Cool Down
EvapFM, MH, and PH energize. There is a slight delay before cabinet temperature
appears on DMand Comp and ConFM energize.
2. Cool Down Achieved
CM monitors cooling of the cabinet via CTh. CTh cools to 3°F (1.7°C) below setpoint.
EvapFM, MH, and PH continue. Comp and ConFM de-energize.
3. Cool Down Restart
CTh warms to 3°F (1.7°C) above setpoint. EvapFM, MH, and PH continue. Comp and
ConFM energize.
4. Defrost
"dEF" is displayed during defrost. There is a 20-minute minimum defrost time and a
1-hour maximum defrost time.
a) Temperature Initiation: When DThcools to 8.6°F (-13°C) defrost begins. EvapFM, MH,
and PH continue. Comp and ConFM de-energize.
b) Manual Initiation: Manual defrost may be initiated by pressing and holding the lower
button until "dEF" appears on DM. EvapFM, MH, and PH continue. Comp and ConFM
de-energize.
c) Termination: DTh warms to 40°F (4.4°C). EvapFM, MH, and PH continue. Comp and
ConFM energize, 2-minute temperature display delay timer starts.
2-minute temperature display delay timer terminates and temperature display returns
to DM.
Note: There is a 2-hour minimum defrost interval.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
MH and PH energize. There is a slight delay before cabinet temperature appears on DM
and Comp, ConFM, and EvapFM energize.
2. Cool Down Achieved
CM monitors cooling of the cabinet via CTh. CTh cools to 3°F (1.7°C) below setpoint.
EvapFM, MH, and PH continue. Comp and ConFM de-energize.
3. Cool Down Restart
CTh warms to 2°F (1.1°C) above setpoint. EvapFM, MH, and PH continue. Comp and
ConFM energize.
4. Defrost
"dEF" is displayed during defrost. There is a 5-minute minimum defrost time and a 1-hour
maximum defrost time.
a) Temperature/Time Initiation: DTh cools to 32°F (0°C), then a 4-hour cumulative Comp
run timer starts. Once 4-hour cumulative Comp run timer terminates and DThis at or
below 32°F (0°C), defrost begins. DH energizes, MH and PH continue, Comp, ConFM,
and EvapFM de-energize.
b) Manual Initiation: Manual defrost may be initiated by pressing and holding the lower
button until "dEF" appears on DM. MH and PH continue. DH energizes, Comp, ConFM,
and EvapFM de-energize.
c) Termination
(1) After Temperature/Time Initiation: DTh warms to 59°F (15°C). 3-minute Comp delay
timer starts, 8-minute EvapFM delay timer starts, and 13-minute temperature display
delay timer starts. MH and PH continue, DHde-energizes.
3-minute Comp delay timer terminates. Comp and ConFM energize. 5 minutes later,
8-minute EvapFM delay timer terminates and EvapFM energizes. 5 minutes after
EvapFM energizes, 13-minute temperature display delay timer terminates and cabinet
temperature returns to DM.
(2) After Manual Initiation: DTh warms to 59°F (15°C). MH and PH continue, DH
de-energizes. 3-minute Comp/EvapFM delay timer starts, 13-minute temperature
a) EvapFM de-energizes when door is opened on FS and when
upper door is opened on HS.
b) 2-minute minimum Comp on timer starts when Comp energizes.
c) 2-minute minimum Comp off timer starts when Comp de-energizes.
d) 2-minute temperature display delay timer starts when defrost
termination temperature is met.
e) 20-minute minimum defrost time.
f) 1-hour maximum defrost time.
CTh cools
to 3°F (1.7°C)
below setpoint.
Factory default
2. Cool Down Achieved
36°F (2°C)
2-min. Comp off
timer starts
EvapFM energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
Refrigerator Sequence Flow Chart
3. Cool Down Restart
1. Startup/Cool Down
Slight
Delay at
Startup
CTh in control
2-min. Comp on
timer starts
Power on
Comp energized
EvapFM energized
ConFM energized
MH energized
EvapFM energized
PH energized
MH energized
PH energized
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
12
b) Freezer
DTh warms to 59°F (15°C)
5. Defrost Termination
3-min. Comp delay timer starts
(EvapFM starts with Comp on manual
13-minute temperature display
(except on manual defrost restarts)
delay timer starts
DTh in control
MH energized
PH energized
DH de-energized
defrost restart)
8-min. EvapFM delay timer starts
DTh is at or below 32°F (0°C)
and 4-hour cumulative Comp
4. Defrost
run timer terminates
CTh warms
to 2°F (1.1°C)
above setpoint
DH energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
Freezer Sequence Flow Chart
CTh cools to
3°F (1.7°C)
below setpoint.
Factory default
-4°F (-20°C)
2-min. Comp off
CTh in control
2-min. Comp on
timer starts
timer starts
EvapFM energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
Note:
a) EvapFM de-energizes when door is opened on FS and when upper door is opened on HS.
b) 2-minute minimum Comp on timer starts when Comp energizes.
c) 2-minute minimum Comp off timer starts when Comp de-energizes.
d) 3-minute Comp delay timer starts when defrost termination temperature is met.
e) 8-minute EvapFM delay timer starts when defrost termination temperature is met.
f) 13-minute temperature display delay timer starts when defrost termination temperature is met.
g) 5-minute minimum defrost time.
h) 1-hour maximum defrost time.
Comp energized
ConFM energized
EvapFM energized
MH energized
PH energized
2. Cool Down Achieved
1. Startup/Cool Down
3. Cool Down Restart
DTh reaches 32°F (0°C),
then 4-hour cumulative
Comp run timer starts
Slight
Delay at
Startup
Power on
13
MH energized
PH energized
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
C. Display Module
When the power switch is moved to the "ON" position there is a slight delay, then the
current cabinet temperature is displayed. From the display module, the cabinet setpoint
and temperature display scale can be changed. For further details, see "II.C.2. Controls
and Adjustments."
1. Display Module Layout
Display Module
To Control Module
Display Cable
LED Display
Upper and Lower
Buttons
Fig. 1
14
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.