Only qualied service technicians should install and service the appliance. To
obtain the name and phone number of your local Hoshizaki Certied Service
Representative, visit www.hoshizaki.com. No service should be undertaken until
the technician has thoroughly read this Service Manual. Failure to service and
maintain the appliance in accordance with this manual will adversely affect safety,
performance, component life, and warranty coverage. Proper installation is the
responsibility of the installer. Product failure or property damage due to improper
installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service and maintenance of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, send an e-mail message, or write to the Hoshizaki Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
Page 3
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read
the warnings and guidelines contained in this manual carefully as they provide
essential information for the continued safe use, service, and maintenance of the
appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. General Information ............................................................................................................ 8
A. Construction .................................................................................................................. 8
B. Refrigeration Flow Chart ............................................................................................... 9
II. Sequence of Operation and Service Diagnosis ............................................................... 10
A. Sequence of Operation Flow Charts ........................................................................... 10
2. Power Supply Connection ...................................................................................... 45
VI. Preparing the Appliance for Periods of Non-Use ............................................................ 46
VII. Disposal ......................................................................................................................... 47
VIII. Technical Information .................................................................................................... 48
A. Electrical and Refrigerant Data ................................................................................... 48
B. Wiring Diagrams .......................................................................................................... 49
4
Page 5
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, or damage to the appliance or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICEIndicates a situation which could result in damage to the
appliance or property.
IMPORTANTIndicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly
conceived. Any other use should be considered improper and therefore dangerous.
The manufacturer cannot be held responsible for injury or damage resulting from
improper, incorrect, and unreasonable use. Failure to service and maintain the
appliance in accordance with this manual will adversely affect safety, performance,
component life, and warranty coverage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic
precautions including the following:
• Only qualied service technicians should install and service the appliance.
• The appliance must be installed in accordance with applicable national, state, and
local codes and regulations.
• The appliance requires an independent power supply of proper capacity. Seethe
nameplate for electrical specications. Failure to use an independent power
supply of proper capacity can result in a tripped breaker, blown fuse, or damage
to existing wiring. This could lead to heat generation or re.
• To reduce the risk of electric shock, do not touch the plug or power switch with
damp hands.
• Make sure the power switch is in the "OFF" position before plugging in or
unplugging the appliance to reduce the risk of electric shock.
• Before servicing, move the power switch to the "OFF" position. Unplug the
appliance from the electrical outlet.
For 115VAC Models
• THE APPLIANCE MUST BE GROUNDED:The appliance is equipped with a
NEMA5-15 three-prong grounding plug
hazards. It must be plugged into a properly grounded, independent 3-prong wall
outlet. If the outlet is a 2-prong outlet, it is your personal responsibility to have a
qualied electrician replace it with a properly grounded, independent 3-prong wall
outlet. Do not remove the ground prong from the plug and do not use an adapter
plug. Failure to follow these instructions may result in death, electric shock, or re.
to reduce the risk of potential shock
5
Page 6
For 208-230VAC Models
WARNING, continued
• THE APPLIANCE MUST BE GROUNDED:
NEMA L14-20 four-prong locking, grounding plug
shock hazards. It must be plugged into a properly grounded, independent 4-prong
wall outlet. If the outlet is a 3-prong outlet or a 4-prong non-locking outlet, it is your
personal responsibility to have a qualied electrician replace it with a properly
grounded, independent 4-prong locking wall outlet. Do not remove the ground
prong from the plug and do not use an adapter plug. After plugging in, twist the plug
clockwise to lock it into place. Failure to follow these instructions may result in death,
electric shock, or re.
For All Models
• The GREEN ground wire in the factory-installed power cord is connected to the
appliance. If it becomes necessary to remove or replace the power cord, be sure to
connect the power cord's ground wire.
• Do not use an extension cord.
• Do not use an appliance with a damaged power cord. The power cord should not
be altered, jerked, bundled, weighed down, pinched, or tangled. Such actions could
result in electric shock or re. To unplug the appliance, be sure to pull the plug, not
the cord, and do not jerk the cord. Before unplugging a 4-prong plug, rotate the plug
counter-clockwise to unlock it.
The appliance is equipped with a
to reduce the risk of potential
• Do not splash, pour, or spray water directly onto or into the appliance. This might
cause short circuit, electric shock, corrosion, or failure.
• Do not make any alterations to the appliance. Alterations could result in electric
shock, injury, re, or damage to the appliance.
• The appliance is not intended for use by persons (including children) with reduced
physical, sensory, or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or door or allow children or animals to
do so. Do not climb into the appliance or allow children or animals to do so. Death or
serious injury could occur or the appliance could be damaged.
• Be careful not to pinch ngers when opening and closing the door. Be careful when
opening and closing the door when children are in the area.
• Open and close the doors with care. Doors opened too quickly or forcefully may
cause injury or damage to the appliance or surrounding equipment.
• Do not use combustible spray or place volatile or ammable substances near the
appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance
could cause harm to individuals or damage to the appliance.
• Do not throw anything onto the shelves or load any single shelf with more than
120lb. (54.5 kg) of product. They might fall off and cause injury.
6
Page 7
WARNING, continued
• Do not place anything on top of the appliance. Foreign objects or moisture could
enter the appliance and result in electric shock or re.
• The appliance is designed only for temporary storage of food. Employ sanitary
methods. Use for any other purposes (for example, storage of chemicals or medical
supplies such as vaccine and serum) could cause deterioration of stored items.
• Do not block air inlets or outlets, otherwise cooling performance may be reduced.
• Do not tightly pack the cabinet. Allow some space between items to ensure good air
ow. Also allow space between items and interior surfaces.
• Do not put warm or hot foods in the cabinet. Let them cool rst, or they will raise the
cabinet temperature and could deteriorate other foods in the cabinet or overload the
appliance.
• All foods should be wrapped in plastic lm or stored in sealed containers. Otherwise
foods may dry up, pass their smells onto other foods, cause frost to develop, result
in poor appliance performance, or increase the likelihood of cross-contamination.
Certain dressings and food ingredients, if not stored in sealed containers, may
accelerate corrosion of the evaporator, resulting in failure.
• Do not store items near the air outlet. They might freeze up and crack or break
causing a risk of injury or contamination of other food.
NOTICE
• Protect the oor when moving the appliance to prevent damage to the oor.
• Keep ventilation openings, in the appliance enclosure or in the built-in structure,
clear of obstruction. Do not place anything on top of the appliance. Blockage of
airow could negatively affect performance and damage the appliance.
• To prevent deformation or cracks, do not spray insecticide onto the plastic parts or
let them come into contact with oil.
• To avoid damage to the gasket, use only the door handle when opening and closing.
7
Page 8
I. General Information
A. Construction
Condensate Pump
Control Box
Control Module
with Remote
Display Module
Power Cord
Reservoir and
Condensate Pump
Float Switch
Power Switch
Compressor
Display Module/
Control Module
with Integrated
Display
Light Switch
(glass door
models only)
Light
Door Switch
Thermostatic Expansion Valve
Condenser Fan Motor
Condenser
Front Panel
Door Lock
Door
• Evaporator
• Cabinet Thermistor
• Defrost Thermistor
• Evaporator Fan Shroud
Model Shown: CR1B-FS
8
Door Gasket
Page 9
B. Refrigeration Flow Chart
Condenser
Condenser Fan
High-Pressure Switch
Thermostatic
Expansion Valve
Condensate Pan
Drier
High-Side
Access Valve
Condensate Pump
Defrost Heater and
Defrost Thermostat
(freezer only)
Low-Side
Access
Valve
Evaporator Fans
(2 or 3 depending on model)
Condensate Pump Float Switch
Compressor
Defrost
Thermistor
Reservoir
Evaporator
Cabinet Thermistor
9
Page 10
II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Charts
1. Refrigerator
DTh warms to
5. Defrost Termination
4. Defrost
40°F (4.4°C)
DTh cools to
8.6°F(-13°C)
Comp energized
ConFM energized
EvapFM energized
MH energized
DTh in control
EvapFM energized
MH energized
Comp de-energized
ConFM de-energized
CTh warms
to 3°F (1.7°C)
above
setpoint
a) EvapFM de-energizes when door is opened on -FS models and
when upper door is opened on -HS models.
b) 2-min. minimum Comp on timer starts when Comp energizes.
c) 2-min. minimum Comp off timer starts when Comp de-energizes.
d) 20-min. minimum defrost time.
e) 1-hr. maximum defrost time.
f) 2-min. temperature display delay timer starts when defrost termination
temperature is met.
f) Temperature displayed during defrost.
Control Module with Integrated Display
2. Cool Down Achieved
CTh cools
to 3°F (1.7°C)
below setpoint.
Factory default
36°F (2°C)
2-min. Comp off
timer starts
EvapFM energized
MH energized
Comp de-energized
ConFM de-energized
Note:
Control Module with Remote Display Module
Refrigerator Sequence Flow Chart
1. Startup/Cool Down
Cycle Steps
3. Cool Down Restart
Slight
Delay at
Startup
CTh in control
2-min. Comp on
timer starts
Power On
Comp energized
EvapFM energized
ConFM energized
MH energized
EvapFM energized
MH energized
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
10
Page 11
2. Freezer
DTh warms to 59°F (15°C)
5. Defrost Termination
MH energized
PH energized
DH de-energized
DrH de-energized
Comp energized (after delay)
ConFM energized (after delay)
EvapFM energized (after delay)
DTh in control
DTh is at or below 32°F (0°C)
and 4-hr. cumulative Comp
4. Defrost
run timer terminates
CTh warms
to 3°F (1.7°C)
above setpoint
DH energized
DrH energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
Freezer Sequence Flow Chart
CTh cools to
3°F (1.7°C)
below setpoint.
Factory default
-4°F (-20°C)
2-min. Comp off
CTh in control
2-min. Comp on
timer starts
timer starts
EvapFM energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
a) EvapFM de-energizes when door is opened on -FS models and when upper door is opened on -HS models.
b) 2-min. minimum Comp on timer starts when Comp energizes.
c) 2-min. minimum Comp off timer starts when Comp de-energizes.
d) 5-min. minimum defrost time.
e) 1-hr. maximum defrost time.
f) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met.
g) 8-minute EvapFM delay timer starts when defrost termination temperature is met (3-minute delay timer when defrost initiated manually).
h) 13-minute temperature display delay timer starts when defrost termination temperature is met.
g) 7-minute EvapFM delay timer starts when defrost termination temperature is met (3-minute delay timer when defrost initiated manually)
h) 18-minute temperature display delay timer starts when defrost termination temperature is met (15-minute delay timer when defrost
initiated manually).
Control Module with Integrated Display
Comp energized
ConFM energized
EvapFM energized
MH energized
PH energized
Note:
Control Module with Remote Display Module
2. Cool Down Achieved
1. Startup/Cool Down
3. Cool Down Restart
DTh reaches 32°F (0°C),
then 4-hr. cumulative
Comp run timer starts
Slight
Delay at
Startup
Power on
MH energized
PH energized
11
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DrH-drain heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
Page 12
B. Service Diagnosis
WARNING
• The appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Make sure all food zones are clean after the appliance is serviced.
NOTICE
• The appliance is not intended for outdoor use. Normal operating ambient
temperature must be within 45°F to 100°F (7°C to 38°C).
• The appliance must not be located next to ovens, grills, or other high heat
producing equipment.
• The appliance must not be located in a corrosive environment.
• The appliance must be a minimum of 4" (11 cm) from side walls.
• A minimum of 10" (25 cm) overhead clearance must be provided for proper
ventilation.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical
system and components. Before proceeding, check for correct installation and proper
voltage per nameplate. Always choose a neutral (W) to establish a good neutral
connection when checking high voltages. If the display is in alarm, see "III.D. Alarm
Safeties."
IMPORTANT
The maximum allowable voltage variation is ±10 percent of the nameplate rating.
115VAC is used as a reference voltage when checking voltage to components.
Voltage may vary depending on power supply.
12
Page 13
1. Factory Default Settings:
a) Temperature Settings: Refrigerator: 36°F (2°C); Freezer: -4°F (-20°C).
b) Temperature Display Scale: °F.
For further details, see "II.C. Control Module Check" or "III. Controls and Adjustments."
Note • When exposed to high temperatures, a high-temperature alarm "Hi" may occur
at startup. To silence the alarm, press and release the upper button. Alarm
automatically resets when temperature drops to an acceptable range.
• There is a minimum 2-min. Comp on time and 2-min. Comp off time.
1) Move the power switch to the "OFF" position.
2) Unplug the appliance from the electrical outlet.
3) Remove the control box cover.
4) Plug the appliance back into the electrical outlet.
5) Move the power switch to the "ON" position.
6) Conrm 115VAC at the power switch. On 3-section models, also conrm proper supply
voltage at the receptacle box (115VAC for refrigerator/208-230VAC for freezer).
Continue to the appropriate section:
"II.B.1a. Refrigerator-Control Module with Remote Display Module"
"II.B.1b. Refrigerator-Control Module with Integrated Display"
"II.B.2a. Freezer-Control Module with Remote Display Module"
"II.B.2b. Freezer-Control Module with Integrated Display"
13
Page 14
1a. Refrigerator-Control Module with Remote Display Module
7) Startup/Cool Down–EvapFM and MH energize. There is a slight delay, then Comp and
ConFM energize. Cabinet temperature appears on DM.
a) EvapFMDiagnosis: Conrm EvapFM energizes. If not, conrm doors are closed and
DS engaged. Next, check for 115VAC at DSR #8(LBU) to#7neutral(W). If 115VAC
is not present, check DS continuity. If DS is engaged and contacts are open, replace
DS. If 115VAC is present, check for 115VAC at DSR#4(DBU) to neutral (W). If
115VAC is not present, check for 115VAC at DSR#6 (BK) to neutral(W). If 115VAC
is present at DSR #6 (BK) to neutral (W) and not at DSR #4 (DBU) to neutral(W),
replace DSR. If 115VAC is present at DSR#4(DBU) to neutral (W), check EvapFM
blades for binding and EvapFM continuity.
b) MH Diagnosis: Conrm MH energizes. Check for 115VAC at MH. If 115VAC is not
present, conrm power supply and continuity of power switch. If 115VAC is present,
check amp draw of MH. If an amp reading is not present, check the continuity of
MH. If open, replace MH.
c) CM and DM Diagnosis: Cabinet temperature appears on DM. If not, check for
115VACat CM L3 (BK) to CM N5 neutral (W). If 115VAC is not present, check power
switch, power cord connections, and breaker/fuse. Conrm wiring connections are
secure for both CM L3 (BK) (power supply) and CMN5(W) (neutral). If 115VAC is
present and DM is off, conrm display cable connection is secure. If DM is still off,
replace CM and DM with HS kit.
d) Comp and ConFM Diagnosis: Conrm Comp and ConFM energize. If not, check for
115VAC at CM C1 (R) to neutral (W). If 115VAC is not present at
CM C1(R) to neutral (W), check CTh status. See "II.D.Thermistor Check." IfCTh
ohm reading is in proper range, replace CM and DM with HS kit. If 115VAC is
present at CMC1(R) to neutral (W), check continuity of HPS. If open, allow time
for HPS to reset. If HPS does not reset, see "e) HPS Activation" below. If HPS is
closed, check for 115VAC at CR #5 (GY) to CR #6 neutral (W). If115VAC is present,
check for 115VAC at CR #1 (R) to neutral (W). If 115VAC is not present, replace
CR. If 115VAC is present and ConFM is energized but Comp is not, check for
115VAC at Comp protector #14 to neutral (W). If 115VAC is not present, give time for
Comp protector to cool and reset. If Comp protector does not reset, replace Comp
protector. If 115VAC is present, check Comp start capacitor, start relay, and Comp
motor windings. If ConFM is not energized, check ConFM fan blades for binding and
motor winding continuity.
If Comp and ConFM are energized and the cabinet does not cool down, check for a
restriction in the refrigeration circuit, correct TXV operation, and correct refrigerant
charge.
e) HPS Activation: Conrm ConFM is energized and fan blade turns freely. Conrm
condenser coil is not clogged or restricted. Conrm there are no restrictions in the
refrigeration circuit (TXV and drier). Let refrigeration circuit pressures equalize.
IfHPS does not reset and pressures are equalized, replace HPS. If pressures are
not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction.
14
Page 15
8) Cool Down Achieved–CTh cools to 3°F (1.7°C) below setpoint. EvapFM and MH
continue. Comp and ConFM de-energize. Diagnosis: Conrm Comp and ConFM
de-energize. If not, and Comp and ConFM were energized longer than 2 min., check
CTh status. See "II.D. Thermistor Check." If CTh ohm reading is in range and Comp
and ConFM continue longer than 2 min., check for 115VAC at CM C1 (R) to neutral(W).
If115VAC is present, replace CM and DM with HS kit. If 115VAC is not present and
Comp and ConFM continue, check for 115VAC at CR #1 (R). If 115VAC is present,
replace CR.
9) Defrost–"dEF" is displayed during defrost. There is a 20-min. minimum defrost time,
a1-hr.maximum defrost time, and a 2 hr. minimum defrost interval.
1a) Temperature-Initiated: DTh cools to 8.6°F (-13°C). EvapFM and MH continue.
Comp and ConFM de-energize.
1b) Manually-Initiated: To initiate a manual defrost, press and hold the lower button
for 5seconds. "dEF" appears in the display. If energized, Comp and ConFM
de-energize.
2) Defrost Termination: DTh warms to 40°F (4.4°C). EvapFM and MH continue. Comp
and ConFM energize. 2-min. temperature display delay timer starts. 2 min. later,
cabinet temperature appears on DM.
Defrost Diagnosis:
a) Defrost Initiation: Has DTh cooled to 8.6°F (-13°C) or lower? Conrm DTh status.
See "II.D. Thermistor Check." If DTh is in proper range or manual defrost initiated,
conrm Comp and ConFM de-energize. If not, check for 115VAC at CM C1 (R) to
neutral (W). If 115VAC is present and DTh is within proper range, replace CM and
DM with HS kit. If there is no voltage at CMC1 (R) to neutral (W) and Comp and
ConFM do not de-energize, check for 115VAC at CR #1 (R) to neutral (W). If 115VAC
is present at CR l #1 (R) to neutral(W) and DTh is within proper range, replace CR.
b) Defrost Termination: Has DTh warmed to 40°F (4.4°C)? If not yet conrmed,
conrm DTh status. See "II.D. Thermistor Check." If DTh is in proper range, have
Comp and ConFM energized? If not, see "7d) Comp and ConFM Diagnosis"
above. 2-min. temperature delay timer terminates, temperature appears on display.
Iftemperature does not appear on display after 2-min., replace CM and DM with
HSkit.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
1b. Refrigerator-Control Module with Integrated Display
7) Startup/Cool Down–There is a slight delay, cabinet temperature appears on display.
Comp, ConFM, EvapFM, and MH energize.
a) EvapFMDiagnosis: Conrm EvapFM energizes. If not, conrm doors are closed and
DS engaged. Next, check for 115VAC at DSR #8 (LBU) to #7neutral(W). If115VAC
is not present, check DS continuity. If DS is engaged and contacts are open, replace
DS. If 115VAC is present, check for 115VAC at DSR #4(DBU) to neutral (W). If
115VAC is not present, check for 115VAC at DSR #6(BK) to neutral(W). If 115VAC
is present at DSR #6 (BK) to neutral (W) and not at DSR#4(DBU) to neutral (W),
replace DSR. If 115VAC is present at DSR #4 (DBU) to neutral (W), check EvapFM
blades for binding and EvapFM continuity.
b) MH Diagnosis: Conrm MH energizes. Check for 115VAC at MH. If 115VAC is not
present, conrm power supply and continuity of power switch. If 115VAC is present,
check amp draw of MH. If an amp reading is not present, check the continuity of
MH. If open, replace MH.
c) CM Diagnosis: Cabinet temperature appears on display. If not, check for 115VACat
CM L2 (BK) to CM N3 neutral (W). If 115VAC is not present, check power switch,
power cord connections, and breaker/fuse. Conrm wiring connections are secure
for both CM L2 (BK) (power supply) and CMN3(W) (neutral). If 115VAC is present
and display is off, replace CM.
d) Comp and ConFM Diagnosis: Conrm Comp and ConFM energize. Ifnot, check
for 115VAC at CM C1 (R) to neutral(W). If 115VAC is not present at CMC1(R) to
neutral (W), check CTh status. See "II.D.Thermistor Check." If CTh ohm reading
is in proper range, replace CM. If 115VAC is present at CM C1 (R) to neutral (W),
check continuity of HPS. If open, allow time for HPS to reset. If HPS does not reset,
see "e) HPS Activation" below. If HPS is closed, check for 115VAC at CR #5 (GY) to
CR#6neutral (W). If 115VAC is present, check for 115VAC at CR#1(R) to neutral
(W). If 115VAC is not present, replace CR. If 115VAC is present and ConFM is
energized but Comp is not, check for 115VAC at Comp protector#14to neutral (W).
If 115VAC is not present, give time for Comp protector to cool and reset. If Comp
protector does not reset, replace Comp protector. If115VAC is present, check Comp
start capacitor, start relay, and Comp motor windings. If ConFM is not energized,
check ConFM fan blades for binding and motor winding continuity.
If Comp and ConFM are energized and the cabinet does not cool down, check for a
restriction in the refrigeration circuit, correct TXV operation, and correct refrigerant
charge.
e) HPS Activation: Conrm ConFM is energized and fan blade turns freely.
Conrmcondenser coil is not clogged or restricted. Conrm there are no restrictions
in the refrigeration circuit (TXV and drier). Let refrigeration circuit pressures
equalize. IfHPS does not reset and pressures are equalized, replace HPS. If
pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit
restriction.
16
Page 17
8) Cool Down Achieved–CTh cools to 3°F (1.7°C) below setpoint. EvapFM and MH
continue. Comp and ConFM de-energize. Diagnosis: Conrm Comp and ConFM
de-energize. If not, and Comp and ConFM were energized longer than 2 min., check
CTh status. See "II.D. Thermistor Check." If CTh ohm reading is in range and Comp
and ConFM continue longer than 2 min., check for 115VAC at CM C1 (R) to neutral(W).
If 115VAC is present, replace CM. If 115VAC is not present and Comp and ConFM
continue, check for 115VAC at CR #1 (R). If 115VAC is present, replace CR.
9) Defrost–Cabinet temperature is displayed during defrost. There is a 20-min. minimum
defrost time, a 1-hr. maximum defrost time, and a 2-hr. minimum defrost interval.
1a) Time-Initiated: When 2-hr. cumulative Comp run timer terminates, defrost starts (off
cycle). EvapFM and MH continue. Comp and ConFM de-energize.
1b) Manually-Initiated: To initiate a manual defrost, press the manual defrost button
on display. Defrost icon turns on and, if energized, Comp and ConFM de-energize.
Cabinet temperature is displayed during defrost.
2) Defrost Termination: DTh warms to 40°F (4.4°C). EvapFM and MH continue. Comp
and ConFM energize.
Defrost Diagnosis:
a) Defrost Initiation: Has DTh cooled to 8.6°F (-13°C) or lower? Conrm DTh status.
See "II.D. Thermistor Check." If DTh is in proper range or manual defrost initiated,
conrm Comp and ConFM de-energize. If not, check for 115VAC at CM C1 (R) to
neutral (W). If 115VAC is present and DTh is within proper range, replace CM. If there
is no voltage at CMC1 (R) to neutral (W) and Comp and ConFM do not de-energize,
check for 115VAC at CR #1 (R) to neutral (W). If 115VAC is present at CR #1 (R) to
neutral(W) and DTh is within proper range, replace CR.
b) Defrost Termination: Has DTh warmed to 40°F (4.4°C)? If not yet conrmed,
conrm DTh status. See "II.D. Thermistor Check." If DTh is in proper range, have
Comp and ConFM energized? If not, see "7d) Comp and ConFM Diagnosis"above.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
2a. Freezer-Control Module with Remote Display Module
7) Startup/Cool Down–MH and PH energize. There is a slight delay, then Comp, ConFM,
and EvapFM energize. Cabinet temperature appears on DM. Once DTh cools to
32°F(0°C), 4-hr.Comp cumulative run timer starts.
a) MH and PH Diagnosis: Conrm MH and PH energize. Check for 115VAC at MH and
PH. If 115VAC is not present, conrm power supply and continuity of power switch.
If115VAC is present, check amp draw of MH and PH. If an amp reading is not
present, check continuity of MH or PH. If open, replace MH or PH.
b) CM and DM Diagnosis: Cabinet temperature appears on DM. If not, check for
115VACat CM L3 (BK) to CM N5 neutral (W). If 115VAC is not present, check power
switch, power cord connections, and breaker/fuse. Conrm wiring connections are
secure for both CM L3 (BK) (power supply) and CMN5(W) (neutral). If 115VAC is
present and DM is off, conrm display cable connection is secure. If DM is still off,
replace CM and DM with HS kit.
c) EvapFM Diagnosis: Conrm EvapFM energizes. If not, conrm doors are closed and
DS engaged. Next, check for 115VAC at DSR #8 (LBU) to #7neutral(W). If115VAC
is not present, check DS continuity. If DS is engaged and contacts are open, replace
DS. If 115VAC is present, check for 115VAC at CMF6 (BK) to neutral(W). If 115VAC
is not present, replace CM and DM with new HS kit. If115VAC is present, check for
115VAC at DSR #4(DBU) to neutral (W). If 115VAC is not present, check for 115VAC
at DSR #6 (BK) to neutral (W). If 115VAC is present at DSR #6 (BK) to neutral (W)
and not at DSR #4 (DBU) to neutral (W), replace DSR. If 115VAC is present at DSR
#4 (DBU) to neutral (W), check EvapFM blades for binding and EvapFM continuity.
d) Comp and ConFM Diagnosis: Conrm Comp and ConFM energize. Ifnot, check
for 115VAC at CM C1 (R) to neutral (W). If 115VAC is not present, check CTh
status. See "II.D.Thermistor Check." If CTh ohm reading is in proper range, replace
CM and DM with HS kit. If 115VAC is present at CM C1 (R) to neutral (W), check
continuity of HPS. If open, allow time for HPS to reset. If HPS does not reset,
see "e) HPS Activation" below. If HPS is closed, check for 115VAC at CR #5 (GY)
to CR#6neutral(W). If115VAC is present, check for 115VAC at CR#1 (R) to
neutral(W). If 115VAC is not present, replace CR. If 115VAC is present, and ConFM
is energized but Comp is not, check for 115VAC at Comp protector if external
(internal on 1-section, external on 2-section) to neutral (W). If 115VAC is not present,
give time for Comp protector to cool and reset. If Comp protector does not reset,
replace Comp protector. If115VAC is present, check run capacitor, start capacitor,
start relay, and Comp motor windings. If ConFM is not energized, check ConFM fan
blades for binding and motor winding continuity.
If Comp and ConFM are energized and the cabinet does not cool down, check for a
restriction in the refrigeration circuit, correct TXV operation, and correct refrigerant
charge.
e) HPS Activation: Conrm ConFM is energized and fan blade turns freely.
Conrmcondenser coil is not clogged or restricted. Conrm there are no restrictions
in the refrigeration circuit (TXV and drier). Let refrigeration circuit pressures
equalize. IfHPS does not reset and pressures are equalized, replace HPS. If
pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit
restriction.
18
Page 19
8) Cool Down Achieved–CTh cools to 3°F (1.7°C) below setpoint. EvapFM, MH, and
PH continue. Comp and ConFM de-energize. Diagnosis: Conrm Comp and ConFM
de-energize. If not, and Comp and ConFM were energized longer than 2 min., check
CTh status. See "II.D. Thermistor Check." If CTh ohm reading is in range and Comp
and ConFM continue longer than 2 min., check for 115VAC at CM C1 (R) to neutral
(W). If115VAC is present, replace CM and DM with HS kit. If 115VAC is not present and
Comp and ConFM continue, check for 115VAC at CR #1 (R) to neutral (W). If 115VAC is
present, replace CR.
9) Defrost–"dEF" is displayed during defrost. There is a 5-min. minimum defrost time and
a 1-hr.maximum defrost time.
1a) Temperature/Time-Initiated: DTh cools to 32°F (0°C), 4-hr. cumulative Comp run
timer starts. Once DTh is at or below 32°F (0°C) with 4-hr. cumulative Comp run
timer satised (Comp energized more than 4 hrs.), "dEF"appears on DM. MH and
PH continue. DH and DrH energize. Comp, ConFM, and EvapFM de-energize.
1b) Manually-Initiated: To initiate a manual defrost, press and hold the lower button
for 5seconds. "dEF" appears in the display. MH and PH continue. DH and DrH
temperature display delay timer starts.
(2) 3-min. Comp and EvapFM delay timers terminate, Comp, ConFM, and EvapFM
energize.
(3) 10 min. after that, 13-min. temperature display delay timer terminates and cabinet
temperature appears on DM.
19
Page 20
Defrost Diagnosis:
1a) Temperature/Time-Initiated: Has DTh cooled to 32°F (0°C) or lower? Before
proceeding, conrm DTh status. See "II.D. Thermistor Check." Has 4-hr. Comp
cumulative run timer satised?
(1) DM Diagnosis: Conrm "dEF" appears on DM. If not, replace CM and DM with
HS kit.
(2) DH and DrH Diagnosis: Conrm DH and DrH energize. If not, check for 115VAC
at CM H4 (BK) to neutral (W). If 115VAC is not present, replace CM and DM with
HS kit. If 115VAC is present, check DT continuity. If open, let cool and reset. If DT
does not close, replace DT. If DT is closed, check DH and DrH amp draw and
continuity.
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize. Ifnot,
check for 115VAC at CM C1 (R) to neutral(W). If 115VAC is present, replace CM
and DM with HS kit. If115VAC is not present and Comp and ConFM continue,
check CR#1 (R) to neutral. If 115VAC is present, replace CR.
(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
CM F6 (BK) to neutral (W). If 115VAC is present, replace CM and DM with HS kit.
1b) Manually-Initiated: After pressing the lower button for 5 sec., check the following:
(1) CM and DM Diagnosis: Conrm "dEF" appears on DM. If not, replace CM and
DM with HS kit.
(2) DH and DrH Diagnosis: Conrm DH and DrH energize. If not, check for 115VAC
at CM H4 (BK) to neutral (W). If 115VAC is not present, replace CM and DM with
HS kit. If115VAC is present, check DT continuity. If open, let cool and reset. If DT
does not close, replace DT. If DT is closed, check DH and DrH amp draw and
continuity.
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize.
If not, check for 115VAC at CM C1 (R) to neutral (W). If 115VAC is present,
replace CM and DM with HS kit. If 115VAC is not present and Comp and ConFM
continue, check CR#1(R) to neutral (W). If 115VAC is present, replace CR.
(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
CM F6 (BK) to neutral (W). If 115VAC is present, replace CM and DM with HS kit.
2a) Temperature/Time Initiated Defrost-Termination: Has DTh warmed to 59°F
(15°C)? If not yet conrmed, conrm DTh status. See "II.D. Thermistor Check." If
DTh is in proper range, DHde-energizes and 3 delay timers start. If DTh has not
warmed to 59°F (15°C), check DT and DH continuity. Next, check DH amp draw.
(1) 3-min. Comp delay timer terminates: 3 min. after DH de-energizes, conrm
Comp and ConFM energize. If not, conrm cabinet temperature is warm enough
for Comp and ConFM operation. Next, check for 115VAC at CM C1 (R) to
neutral(W). If 115VAC is not present, check CTh status. See "II.D.Thermistor
Check." If CTh ohm reading is in proper range, replace CM and DM with HS kit.
If 115VAC is present, check for 115VAC at CR #4 (BK) to neutral (W) and
CR#1(R) to neutral (W). If 115VAC is present at CR #4 (BK) to neutral (W) but
not at CR #1 (R) to neutral (W), replace CR. If 115VAC is present at CR #1 (R)
and Comp or ConFM are not energized, check Comp start components, Comp
protector (internal on 1-section, external on 2-section), and Comp motor winding
continuity. If ConFM is not energized, check ConFM fan blades for binding and
motor winding continuity.
20
Page 21
(2) 8-min. EvapFM delay timer terminates: 5min. after Comp and ConFM
energize, conrm EvapFM energizes. Ifnot, conrm doors are closed and DS
engaged. Next, check for 115VAC at CMF6(BK) to neutral (W). If 115VAC is not
present, replace CM and DM with HSkit. If 115VAC is present, check for 115VAC
at DSR #4 (DBU) to neutral (W).
If 115VAC is not present, check for 115VAC at DSR #6 (BK) to neutral (W).
If 115VAC is present on DSR #6 (BK) to neutral (W) and not on DSR #4 (DBU) to
neutral (W), replace DSR. If 115VAC is present on DSR #4 (DBU) to neutral (W)
and EvapFM is not energized, check EvapFM blades for binding and EvapFM
continuity.
(3) 13-min. temperature display delay timer terminates: 5 min. after EvapFM
energizes, "dEF" is replaced by cabinet temperature on display. If not, replace
CM and DM with HSkit.
2b) Manually Initiated Defrost-Termination: Has DTh warmed to 59°F (15°C)? If not
yet conrmed, conrm DTh status. See "II.D. Thermistor Check." If DTh is in proper
range, DHde-energizes and 3 delay timers start. If DTh has not warmed to 59°F
(1) 3-min. Comp/ConFM and EvapFM delay timers terminate: 3 min. after DH
de-energizes, conrm Comp, ConFM, and EvapFM energize. If Comp and
ConFM do not energize, conrm cabinet temperature is warm enough for Comp
and ConFM operation.
Comp and ConFM: Check for 115VAC at CM C1 (R) to neutral(W). If 115VAC
is not present, check CTh status. See "II.D.Thermistor Check." If CTh ohm
reading is in proper range, replace CM and DM with HS kit. If 115VAC is present,
check for 115VAC at CR #4 (BK) to neutral (W) and CR#1(R) to neutral (W).
If115VAC is present at CR #4 (BK) to neutral (W) but not at CR #1 (R) to neutral
(W), replace CR. If 115VAC is present at CR #1 (R) and Comp or ConFM are not
energized, check Comp start components, Comp protector (internal on 1-section,
external on 2-section), and Comp motor winding continuity. If ConFM is not
energized, check ConFM fan blades for binding and motor winding continuity.
EvapFM: Conrm EvapFM energizes. Ifnot, conrm doors are closed and DS
engaged. Next, check for 115VAC at CMF6(BK) to neutral (W). If 115VAC is not
present, replace CM and DM with HSkit. If 115VAC is present, check for 115VAC
at DSR #4 (DBU) to neutral (W). If 115VAC is not present, check for 115VAC at
DSR #6 (BK) to neutral (W). If 115VAC is present on DSR #6 (BK) to neutral (W)
and not on DSR #4 (DBU) to neutral (W), replace DSR. If 115VAC is present
on DSR #4 (DBU) to neutral (W) and EvapFM is not energized, check EvapFM
blades for binding and EvapFM continuity.
(2) 13-min. temperature display delay timer terminates: 10 min. after Comp,
ConFM, and EvapFM energize, "dEF" is replaced by cabinet temperature on
display. If not, replace CM and DM with HSkit.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
2b. Freezer-Control Module with Integrated Display
7) Startup/Cool Down– MH and PH energize. There is a slight delay, then Comp, ConFM,
and EvapFM energize. Cabinet temperature appears on display. Once DTh cools to
32°F (0°C), 4-hr.Comp cumulative run timer starts.
a) MH and PH Diagnosis: Conrm MH and PH energize. Check for 115VAC at MH and
PH. If 115VAC is not present, conrm power supply and continuity of power switch.
If 115VAC is present, check amp draw of MH and PH. If an amp reading is not
present, check continuity of MH or PH. If open, replace MH or PH.
b) CM Diagnosis: Cabinet temperature appears on display. If not, check for 115VAC
at CM L2 (BK) to CM N3 neutral (W). If 115VAC is not present, conrm wiring
connections are secure on CM L2 (BK) (power supply) and CM N3 (W) (neutral).
If115VAC is present and display is off, replace CM.
c) EvapFM Diagnosis: Conrm EvapFM energizes. If not, conrm doors are closed
and DS engaged. Next, check for 115VAC at DSR #8 (LBU) to DSR#7neutral (W).
If 115VAC is not present, check DS continuity. If DS is engaged and contacts are
open, replace DS. If 115VAC is present, check for 115VAC at CM F5(Y) to neutral
(W). If 115VAC is not present, replace CM. If115VAC is present, check for 115VAC
at DSR #4 (DBU) to neutral (W). If115VAC is not present, check for 115VAC at DSR
#6 (Y) to neutral (W). If115VAC is present at DSR #6 (Y) to neutral (W) and not at
DSR #4 (DBU) to neutral (W), replace DSR. If 115VAC is present at DSR#4(DBU)
to neutral (W), check EvapFM blades for binding and EvapFM continuity.
d) Comp and ConFM Diagnosis: Conrm Comp and ConFM energize. If not, check for
115VAC at CM C1 (R) to neutral (W). If 115VAC is not present, check CTh status.
See "II.D.Thermistor Check." If CTh ohm reading is in proper range, replace CM. If
115VAC is present at CM C1 (R) to neutral (W), check continuity of HPS. Ifopen,
allow time for HPS to reset. If HPS does not reset, see "e) HPS Activation" below.
If HPS is closed, check for 115VAC at CR #5 (GY) to CR #6 neutral(W). If115VAC
is present, check for 115VAC at CR #1 (R) to neutral(W). If115VAC is not present,
replace CR. If115VAC is present and ConFM is energized but Comp is not,
check for 115VAC at Comp protector if external (internal on 1-section, external on
2-section) to neutral (W). If 115VAC is not present, give time for Comp protector to
cool and reset. If Comp protector does not reset, replace Comp protector. If115VAC
is present, check run capacitor, start capacitor, start relay, and Comp motor
windings. If ConFM is not energized, check ConFM fan blades for binding and motor
winding continuity.
If Comp and ConFM are energized and the cabinet does not cool down, check for a
restriction in the refrigeration circuit, correct TXV operation, and correct refrigerant
charge.
e) HPS Activation: Conrm ConFM is energized and fan blade turns freely. Conrm
condenser coil is not clogged or restricted. Conrm there are no restrictions in the
refrigeration circuit (TXV and drier). Let refrigeration circuit pressures equalize.
IfHPS does not reset and pressures are equalized, replace HPS. If pressures are
not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction.
22
Page 23
8) Cool Down Achieved–CTh cools to 3°F (1.7°C) below setpoint. EvapFM, MH, and
PH continue. Comp and ConFM de-energize. Diagnosis: Conrm Comp and ConFM
de-energize. If not, and Comp and ConFM were energized longer than 2 min., check
CTh status. See "II.D. Thermistor Check." If CTh ohm reading is in proper range and
Comp and ConFM continue longer than 2 min., check for 115VAC at CM C1 (R) to
neutral (W). If115VAC is present, replace CM. If 115VAC is not present and Comp and
ConFM continue, check CR#1(R) to neutral (W). If 115VAC is present, replace CR.
9) Defrost–The defrost icon turns on and "dEF" is displayed during defrost. There is a
5-min. minimum defrost time and a 1-hr.maximum defrost time.
1a) Temperature/Time-Initiated: DTh cools to 32°F (0°C), 4-hr. cumulative Comp
run timer starts. Once DTh is at or below 32°F (0°C) with 4-hr. cumulative Comp
run timer satised (Comp energized more than 4 hrs.), defrosticon turns on and
"dEF"is displayed. MHand PH continue. DH and DrH energize. If on, Comp and
EvapFM icons turn off. Comp, ConFM, and EvapFM de-energize.
1b) Manually-Initiated: To initiate a manual defrost, press the manual defrost button
on display. Comp and EvapFM icons turn off. Defrost icon turns on and "dEF" is
displayed. MHand PH continue. DH and DrH energize, Comp and EvapFM icons
and PH continue. EvapFM icon turns on and EvapFM energizes. Note that the
7-min. EvapFM delay time is a maximum; if the defrost thermistor cools to 25°F
(-3.9°C) before the 7-min. EvapFM delay timer terminates, EvapFM icon turns on
and EvapFM energizes.
(4) 11-min. later, 18-min. temperature display delay timer terminates. "dEF" is
replaced by cabinet temperature.
2b) Manually Initiated Defrost-Termination:
(1) DTh warms to 59°F (15°C). Defrost icon, "dEF," MH, and PH continue. DH and
DrH de-energize. 3-min. Comp, ConFM, and EvapFM delay timer starts, and
15-min. temperature display delay timer starts.
(2) 3-min. Comp, ConFM, and EvapFM delay timer terminates. "dEF," MH, and PH
continue. Defrost icon turns off, Comp and EvapFM icons turn on, and Comp,
ConFM, and EvapFM energize.
(3) 12-min. later, 15 min. temperature display timer terminates. "dEF" is replaced by
cabinet temperature.
23
Page 24
Defrost Diagnosis:
1a) Temperature/Time-Initiation: Has DTh cooled to 32°F (0°C) or lower? Before
proceeding, conrm DTh status. See "II.D. Thermistor Check." Has 4-hr. Comp
cumulative run timer satised?
(1) CM Diagnosis: Conrm defrost icon turns on, "dEF" is displayed, and Comp and
EvapFM icons turn off. If not, replaceCM.
(2) DH and DrH Diagnosis: Conrm DH and DrH energize. If not, check for 115VAC
at CM H4 (O) to neutral (W). If 115VAC is not present, replace CM. If115VAC is
present, check DT continuity. If open, let cool and reset. If DT does not close,
replace DT. If DT is closed, check DH and DrH amp draw and continuity.
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize.
If not, check for 115VAC at CM C1 (R) to neutral (W). If 115VAC is present,
replace CM. If 115VAC is not present and Comp and ConFM continue, check
CR#1(R) to neutral (W). If 115VAC is present, replace CR.
(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
CM F5 (Y) to neutral (W). If 115VAC is present, replace CM.
1b) Manual-Initiation: After pressing the manual defrost button, check the following:
(1) CM Diagnosis: Conrm Comp and EvapFM icons turn off, defrost icon turns on,
and "dEF" is displayed. If not, replace CM.
(2) DH and DrH Diagnosis: Conrm DH and DrH energize. If not, check for 115VAC
at CM H4 (O) to neutral (W). If 115VAC is not present, replace CM. If115VAC is
present, check DT continuity. If open, let cool and reset. If DT does not close,
replace DT. If DT is closed, check DH and DrH amp draw and continuity.
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize.
If not, check for 115VAC at CM C1 (R) to neutral (W). If 115VAC is present,
replace CM. If 115VAC is not present and Comp and ConFM continue, check
CR#1(R) to neutral (W). If 115VAC is present, replace CR.
(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
CM F5 (Y) to neutral (W). If 115VAC is present, replace CM.
2a) Temperature/Time Initiated Defrost-Termination: Has DTh warmed to 59°F
(15°C)? If not yet conrmed, conrm DTh status. See "II.D. Thermistor Check." If
DTh is in proper range, DHde-energizes and 3 delay timers start. If DTh has not
warmed to 59°F (15°C), check DT and DH continuity. Next, check DH amp draw.
(1) 3-min. Comp delay timer terminates: 3 min. after DH de-energizes, conrm
defrost icon turns off, Comp icon turns on, and Comp and ConFM energize.
If not, conrm cabinet temperature is warm enough for Comp and ConFM
operation. Next, check for 115VAC at CM C1 (R) to neutral(W). If 115VAC is not
present, check CTh status. See "II.D.Thermistor Check." If CTh ohm reading is in
proper range, replace CM. If 115VAC is present, check for 115VAC at CR #4(BK)
to neutral (W) and CR#1(R) to neutral (W). If 115VAC is present at CR #4 (BK)
to neutral (W) but not at CR #1(R) to neutral (W), replace CR. If 115VAC is
present at CR #1 (R) and Comp or ConFM are not energized, check Comp start
components, Comp protector (internal on 1-section, external on 2-section), and
Comp motor winding continuity. If ConFM is not energized, check ConFM fan
blades for binding and motor winding continuity.
24
Page 25
(2) 7-min. EvapFM delay timer terminates: (note that the 7-min. EvapFM delay time
is a maximum; if the defrost thermistor cools to 25°F (-3.9°C) before the 7-min.
EvapFM delay timer terminates, EvapFM icon turns on and EvapFM energizes):
4min. after Comp and ConFM energize, conrm EvapFM icon turns on and
EvapFM energizes. If not, conrm doors are closed and DS engaged. Next,
check for 115VAC at CMF5 (Y) to neutral (W). If 115VAC is not present, replace
CM.
If 115VAC is present, checkfor 115VAC at DSR#4(DBU) to neutral(W).
If115VAC is not present, check for 115VAC at DSR#6(BK) to neutral (W).
If115VAC is present on DSR #6 (BK) to neutral (W)and not on DSR #4(DBU) to
neutral (W), replace DSR. If 115VAC is present on DSR #4 (DBU) to neutral (W)
and EvapFM is not energized, check EvapFM blades for binding and EvapFM
continuity.
(3) 18-min. temperature display delay timer terminates: 11 min. after EvapFM
energizes, "dEF" is replaced by cabinet temperature on display. If not, replace
CM.
2b) Manually Initiated Defrost-Termination: Has DTh warmed to 59°F (15°C)? If not
yet conrmed, conrm DTh status. See "II.D. Thermistor Check." If DTh is in proper
range, DHde-energizes and 2 delay timers start. If DTh has not warmed to 59°F
(1) 3-min. Comp/ConFM and EvapFM delay timers terminate: 3 min. after DH
de-energizes, conrm defrost icon turns off, Comp and EvapFM icons turn on,
and Comp, ConFM, and EvapFM energize. If not, conrm cabinet temperature is
warm enough for Comp and ConFM operation.
Comp and ConFM: Check for 115VAC at CM C1 (R) to neutral(W). If 115VAC is
not present, check CTh status. See "II.D.Thermistor Check." If CTh ohm reading
is in proper range, replace CM. If 115VAC is present, check for 115VAC at CR
#4(BK) to neutral (W) and CR#1(R) to neutral (W). If 115VAC is present at CR
#4 (BK) to neutral (W) but not at CR #1(R) to neutral (W), replace CR. If 115VAC
is present at CR #1 (R) and Comp or ConFM are not energized, check Comp
start components, Comp protector (internal on 1-section, external on 2-section),
and Comp motor winding continuity. If ConFM is not energized, check ConFM
fan blades for binding and motor winding continuity.
EvapFM: Conrm EvapFM icon turns on and EvapFM energizes. If not, conrm
doors are closed and DS engaged. Next, check for 115VAC at CMF5 (Y) to
neutral (W). If 115VAC is not present, replace CM. If 115VAC is present, checkfor
115VAC at DSR#4(DBU) to neutral(W). If115VAC is not present, check for
115VAC at DSR#6(BK) to neutral (W). If115VAC is present on DSR #6 (BK) to
neutral (W) and not on DSR #4(DBU) to neutral (W), replace DSR. If 115VAC is
present on DSR #4 (DBU) to neutral (W) and EvapFM is not energized, check
EvapFM blades for binding and EvapFM continuity.
(2) 15-min. temperature display delay timer terminates: 12 min. after Comp,
ConFM, and EvapFM energize, "dEF" is replaced by cabinet temperature on
display. If not, replace CM.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
Before replacing CM that does not show a visible defect and that you suspect is
bad, conduct the following check procedure. This procedure will help you verify your
diagnosis. Always choose a neutral (W) to establish a good neutral connection when
checking high voltages. Also, conrm there is a good power supply and neutral
connection to CM: 115VAC at CM L3(BK) to neutral CM N5 (W).
Alarm Reset: To silence an alarm, press and release the upper or lower button with
power on. For alarm information, see "III.D. Alarm Safeties."
NOTICE! When replacing the display module or control module on appliances with
a control module with remote display module, a conversion kit must be ordered:
Refrigerator: HS-5079; Freezer: HS-5078.
Startup/Cool Down
1) Check all wiring connections. Conrm DM cable, CTh, and DTh are properly connected.
2) Move the power switch to the "ON" position.
3) Check for 115VAC at CM L3 (BK) to CM N5 neutral (W). If 115VAC is not present, check
power supply, wiring connections, and power switch continuity.
4) Check that the cabinet temperature is displayed on DM. If not and DM cable is
connected, replace DM and CM with HS kit.
5) Freezer: Check that EvapFM is energized. Make sure doors are closed and DS
engaged. Next, check for 115VAC at CM F6 (BK) to neutral (W). If 115VAC is not
present, replace DM and CM with HS kit.
6) Check that Comp and ConFM energize. If not, check CTh status. See "II.D.Thermistor
Check." If CTh ohm reading is in proper range, check for 115VAC at CM C1 (R) to
neutral (W). If 115VAC is not present, replace DM and CM with HS kit.
Defrost
7) Manual Defrost Check: Press and hold the lower button until "dEF" appears on DM.
8) Conrm Comp, ConFM, and EvapFM (freezer) de-energize. Check for 115VAC at CM
C1 (R) to neutral (W) for Comp and ConFM, then at CM F6 (BK) (freezer) to neutral (W)
for EvapFM. If "dEF" is displayed and 115VAC is present, replace DM and CM with HS
kit.
9) Freezer: Conrm DH energizes. Check for 115VAC at CM H4 (BK) to neutral (W).
If "dEF" is displayed and 115VAC is not present, replace DM and CM with HS kit.
26
Page 27
10) Check that the components restart after defrost termination.
Before replacing CM that does not show a visible defect and that you suspect is
bad, conduct the following check procedure. This procedure will help you verify your
diagnosis. Always choose a neutral (W) to establish a good neutral connection when
checking high voltages. Also, conrm there is a good power supply and neutral
connection to CM: 115VAC at CM L2 (BK) to CM N3 (W).
Alarm Reset: To silence the alarm, press and release the up button with power on.
Foralarm information, see "III.D. Alarm Safeties."
Startup/Cool Down
1) Check all wiring connections. Conrm the CTh and DTh are properly connected.
2) Move the power switch to the "ON" position.
3) Check for 115VAC at CM L2 (BK) to CM N3 neutral (W). If 115VAC is not present, check
power supply, wire connections, and power switch.
4) Check that cabinet temperature is displayed. If not, replace CM.
5) Freezer: Check that EvapFM is energized. Make sure doors are closed and DS
engaged. Next, check for 115VAC at CM F5 (Y) to neutral. If 115VAC is not present,
replace CM.
6) Check that Comp and ConFM energize. If not, check CTh status. See "II.D.Thermistor
Check." If CTh ohm reading is in proper range, check for 115VAC at CM C1 (R) to
neutral (W). If 115VAC is not present, replace CM.
Defrost
7) Manual Defrost Check: Press the manual defrost button briey. If on, Comp and
EvapFM icons turn off. Defrosticon turns on and "dEF" is displayed.
8) Conrm Comp, ConFM, and EvapFM (freezer) de-energize. Check for 115VAC at CM
C1 (R) to neutral (W) for Comp and ConFM, then at CM F5 (Y) (freezer) to neutral (W)
for EvapFM. If"dEF" is displayed and 115VAC is present, replace CM.
9) Freezer: Conrm DH energizes. Check for 115VAC at CM H4 (O) to neutral (W). If"dEF"
is displayed and 115VAC is not present, replace CM.
27
Page 28
10) Check that the components restart after defrost termination.
Refrigerator: DTh reaches 40°F (4.4°C), Comp and ConFM (CM C1 (R)) energize. If
not, check DTh status. See "II.D.Thermistor Check." If DTh ohm reading is in proper
range, and Comp and ConFM do not energize, replace CM.
Freezer: DTh reaches 59°F (15°C). 3-min. later, Comp and ConFM (CM C1 (R)) and
EvapFM (CM F5 (Y)) energize. If not, check DTh status. See "II.D.Thermistor Check." If
DTh ohm reading is in proper range, and Comp, ConFM, or EvapFM do not energize,
replaceCM. 12min. after Comp, ConFM, and EvapFM energize, cabinet temperature
appears on CM. If components fail to start, replace CM.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
The cabinet thermistor is used for cabinet temperature control and the defrost thermistor
is used for defrost cycle initiation and termination. Thermistor resistance varies
depending on temperature. The control module monitors the thermistors to control
system operation. No adjustment is required.
In the event the cabinet thermistor reading is out of range (E1 alarm), the compressor
operates on a xed time basis of 5-min. on and 5-min. off.
In the event the refrigerator defrost thermistor reading is out of range (E2alarm), defrost
initiation occurs every 4-hr. of cumulative compressor run time and terminates on
20-min. minimum defrost timer.
In the event the freezer defrost thermistor reading is out of range (E2 alarm), defrost
initiation occurs every 4-hr. of cumulative compressor run time and terminates based on
cabinet thermistor temperature.
To check thermistor resistance, follow the steps below.
1) Move the power switch to the "OFF" position, then unplug the appliance.
2) Remove the control box cover.
3) Disconnect and remove the thermistor in question.
4) Immerse the thermistor sensor portion in a glass containing ice and water for 2 to 3 min.
5) Check the resistance between the wires at the thermistor connector. Normal reading is
within 16.0 to 16.7 kΩ. If outside the normal reading, replace the thermistor.
6) Reconnect and replace the thermistor in its correct position. See "IV.B. Important Notes
for Component Replacement."
7) Plug the appliance back in. Move the power switch to the "ON" position.
28
Page 29
E. Diagnostic Tables
Check for correct appliance installation per the instruction manual and proper voltage per
appliance nameplate.
1. Not Cooling
Not Cooling - Possible Cause
Power Supply
1.
Cord and Plug
2.
On three-section model, check
receptacle box cord and plug and
one-section and two-section cords
and plugs.
Power Switch (control box)
3.
Wiring
4.
Control Module
5.
See "III.D. Alarm Safeties" and "II.C.
Control Module Check."
Door Switch
6.
Door Switch Relay
7.
Evaporator Fan Motor
8.
High-Pressure Switch
9.
Compressor Relay
10.
Compressor Protector
11.
Compressor
12.
Condenser
13.
Evaporator
14.
See "2. Evaporator Frozen Up."
Refrigerant/Refrigerant Lines
15.
Unplugged, off, blown fuse, tripped or defective circuit breaker. On
a)
three-section receptacle box, only top receptacles have power.
Loose connection.
b)
Not within specications.
c)
Loose connection.
a)
Defective.
b)
"OFF" position.
a)
Defective.
b)
Loose connection.
a)
Faulty.
b)
In alarm or "- - -" shown on display module on models with remote display
a)
module.
Defective.
b)
Not engaged.
a)
Defective.
b)
Loose connection.
a)
Defective.
b)
Defective.
a)
Dirty condenser.
a)
Ambient temperature too warm.
b)
Condenser fan motor not operating.
c)
Refrigerant overcharge.
d)
Refrigerant lines or components restricted.
e)
Defective.
f)
Defective.
a)
Dirty condenser.
a)
Condenser fan motor not operating.
b)
Compressor capacitor or start relay defective.
c)
Defective.
d)
Defective.
a)
Dirty.
a)
Clogged or frozen.
a)
Refrigerant leak.
a)
Refrigerant lines restricted.
b)
29
Page 30
2. Evaporator Frozen Up
Evaporator Frozen Up - Possible Cause
Evaporator
1.
Evaporator Fan Motor
2.
Defrost Thermistor
3.
Control Module
4.
5. Compressor Relaya) Defective.
Refrigerant Charge/Refrigerant
6.
Lines
Defrost Heater (freezer)
7.
Defrost Thermostat Open (freezer)
8.
Dirty.
a)
Fan blades binding.
a)
Defective.
b)
Out of position or defective.
a)
Defective.
a)
Low.
a)
Component restriction (TXV, cap tube, drier).
b)
Defective.
a)
Defective.
a)
3a. Defrost: Control Module with Remote Display Module
Refrigerator Defrost Fails to Initiate - Possible Cause
1. Defrost Thermistor (Conrm
DTh status. See "II.D. Thermistor
Check.")
2. Control Modulea) Defective.
Refrigerator Defrost Fails to Terminate - Possible Cause
1. Defrost Thermistor (Conrm
DTh status. See "II.D. Thermistor
Check.")
2. Compressor Relaya) Defective.
3. Control Modulea) Defrost thermistor connection loose.
a) Defrost initiation temperature 8.6°F (-13°C) not achieved. See "1. Not
Cooling."
b) Out of position or defective.
a) Defrost termination temperature 40°F (4.4°C) not achieved.
b) Defective.
b) Defective.
Freezer Defrost Fails to Initiate - Possible Cause
Defrost Thermistor (Conrm
1.
DTh status. See "II.D. Thermistor
Check.")
Compressor 4-hr. cumulative run
2.
timer not satised.
Control Module
3.
Freezer Defrost Fails to Terminate - Possible Cause
Defrost Thermistor (Conrm
1.
DTh status. See "II.D. Thermistor
Check.")
Defrost Heater
2.
Compressor Relay
3.
Control Module
4.
Defrost initiation temperature 32°F (0°C) not achieved. See "1. Not
a)
Cooling."
Out of position or defective.
b)
Check compressor operation. See "1. Not Cooling."
a)
Defective.
a)
Defrost termination temperature 59°F (15°C) not achieved.
a)
Defrost thermistor connection loose.
b)
Defrost thermostat defective.
a)
Defective.
b)
Defective.
a)
Defective.
a)
30
Page 31
3b. Defrost: Control Module with Integrated Display
Refrigerator Defrost Fails to Initiate - Possible Cause
1. Defrost Thermistor (Conrm
DTh status. See "II.D. Thermistor
Check.")
2. Compressor Relaya) Defective.
3. Control Modulea) Defective.
Refrigerator Defrost Fails to Terminate - Possible Cause
1. Defrost Thermistor (Conrm
DTh status. See "II.D. Thermistor
Check.")
2. Compressor Relaya) Defective.
3. Control Modulea) Defrost thermistor connection loose.
Freezer Defrost Fails to Initiate - Possible Cause
Defrost Thermistor (Conrm
1.
DTh status. See "II.D. Thermistor
Check.")
Compressor 4-hr. cumulative run
2.
timer not satised.
Control Module
3.
Freezer Defrost Fails to Terminate - Possible Cause
Defrost Thermistor (Conrm
1.
DTh status. See "II.D. Thermistor
Check.")
Defrost Heater
2.
Compressor Relay
3.
Control Module
4.
a) Defrost initiation temperature 8.6°F (-13°C) not achieved. See "1. Not
Cooling."
b) Out of position or defective.
a) Defrost termination temperature 40°F (4.4°C) not achieved.
b) Defective.
b) Defective.
Defrost initiation temperature 32°F (0°C) not achieved. See "1. Not
a)
Cooling."
Out of position or defective.
b)
Check compressor operation. See "1. Not Cooling."
a)
Defective.
a)
Defrost termination temperature 59°F (15°C) not achieved.
a)
Defrost thermistor connection loose.
b)
Defrost thermostat defective.
a)
Defective.
b)
Defective.
a)
Defective.
a)
31
Page 32
III. Controls and Adjustments
A. Control and Display Modules
When the power switch is moved to the "ON" position there is a slight delay, then the
current cabinet temperature is displayed. From the display module, the cabinet setpoint
and temperature display scale can be changed.
Note: When exposed to high temperatures, a high-temperature alarm "Hi" may occur at
start-up. To silence the alarm, press and release the upper button. Alarm clears
once temperature is within factory parameters. For details, see"III.D.Alarm
Safeties."
1. Control Module with Remote Display Module
a) Remote Display Module Layout
Display Module
To Control Module
Display Cable
LED Display
Upper and Lower
Buttons
Fig. 2
32
Page 33
b) Control Module with Remote Display Module Connections
All models are pretested and factory set
.
NOTICE
• The control module is fragile, handle very carefully.
• Do not change wiring and connections. Never misconnect terminals.
• Do not short out power supply to test for voltage.
Refrigerator Control Module
To Display Module
Display Cable
Defrost Thermistor
Cabinet Thermistor
Freezer Control Module
To Display Module
Display Cable
Defrost Thermistor
Cabinet Thermistor
N5 Neutral (W)
L3 Power Supply (BK)
C1 Compressor (R)
Fig. 3
33
F6 Evaporator Fan
Motor (BK)
N5 Neutral (W)
H4 Defrost Heater (BK)
L3 Power Supply (BK)
C1 Compressor (R)
Page 34
2. Control Module with Integrated Display
All models are pretested and factory set
.
NOTICE
• The control module is fragile, handle very carefully.
• Do not change wiring and connections. Never misconnect terminals.
• Do not short out power supply to test for voltage.
a) Display Icons
Control Module Icons
IconMeaning
Compressor
Compressor running.
Defrost
Appliance is in defrost cycle. See "II.B. Service Diagnosis" for details.
Evaporator Fan Motor (Icon is Applicable to Freezers Only)
Evaporator fan motor is running. Evaporator fan motor de-energizes when door is open and
when appliance is in defrost.
Alarm
Appliance is in alarm. See "III.D. Alarm Safeties" for details.
b) Display Layout
Manual
Defrost
Button
Compressor Icon
SC
SC
Button
Defrost
Icon
ECO
Evaporator Fan
Motor Icon
°C
°F
Alarm
Icon
Up
Button
V
V
Down
Button
Front
Panel
34
Page 35
c) Control Module with Integrated Display Connections
Cabinet Thermistor
Defrost Thermistor
Cabinet ThermistorDefrost Thermistor
C1 Compressor (R)
L2 Power Supply (BK)
N3 Neutral (W)
F5 Evaporator Fan Motor (Y)
(Freezer)
H4 Defrost Heater (O)
(Freezer)
35
Page 36
B. Temperature
The temperature default scale is °F, but it can be changed to read °C. To change,
see "III.B.3. Changing the Temperature Display Scale (°F or °C)" below.
1. Default Settings
a) Temperature Setting: Refrigerator: 36°F (2°C).
Freezer: -4°F (-20°C).
b) Temperature Display Scale: °F.
Note: CM with remote DM: Pressing the upper and lower button at the same time for
5 sec. (or until "- - -" appears on the display module), turns the compressor,
condenser fan motor, and evaporator fan motor (freezer) off. To turn the appliance
on again, press the upper and lower button together for 5 sec. until the cabinet
temperature appears on the display module. NOTICE! The three dashes must
be cleared, otherwise the compressor will not run and product will be lost.
2. Temperature Setpoint
The temperature setpoint is the value for the average cabinet temperature. The
temperature differential for the compressor to turn on and off is ±3°F (±1.7°C) of the
temperature setpoint. For example, for a refrigerator temperature setpoint of 36°F (2°C),
the compressor comes on at 39°F (3.7°C), and the compressor goes off at 33°F (0.3°C).
If necessary, adjust the temperature setpoint as follows:
1) Press and hold the upper or lower button briey, then release. The current temperature
setpoint ashes.
2) Press the upper or lower button until the desired value is displayed. After a few sec.,
the display returns to the current cabinet temperature and the temperature setpoint is
saved.
• For refrigerators, the temperature setpoint is adjustable between 34°F and 52°F
(1°Cand 11°C). Factory default is 36°F (2°C).
• For freezers, the temperature setpoint is adjustable between -15°F and +12°F
(-26°Cand -11°C). Factory default is -4°F (-20°C).
Note: Do not adjust the temperature setpoint outside of the factory-specied range.
Adjustment outside of this range may prevent the appliance from operating
correctly.
3. Changing the Temperature Display Scale (°F or °C)
a) Control Module with Remote Display Module
To change the temperature display scale, follow the steps below.
1) Press the upper button for 5 sec. The current setting is displayed.
2) Press the upper button to change the scale. After a few sec., the display returns to the
current cabinet temperature and the setting is saved. The factory default is °F.
36
Page 37
b) Control Module with Integrated Display
EHE
To change the temperature display scale, follow the steps below.
1) Press and hold both the up and down buttons for 5 sec. "PAS" appears briey in the
display, then "000" appears.
2) Press the up button to change the display to "001".
3) Press the SC button. "
"diS" is displayed.
4) Press the SC button. "CFu" appears in the display. Press the SC button again. The
current temperature display scale setting appears.
5) Press the up or down button to change the temperature display scale.
6) Press the SC button to save the setting. Wait 1 min. or press the manual defrost button
twice to return to the temperature display.
" appears in the display. Press the up or down button until
C. Defrost
1. Control Module with Remote Display Module
To initiate a manual defrost, press and hold the lower button for 5sec. "dEF" appears
in the display.
2. Control Module with Integrated Display
To initiate a manual defrost, press the manual defrost button briey. The defrost icon
and "dEF" appear in the display.
37
Page 38
D. Alarm Safeties
Alarm signals are designed to protect the appliance and food product. These alarms
give information or warnings in the event the appliance is operating out of acceptable
parameters. Should one of the alarms occur, follow the instructions in the table below
to address the alarm. The alarm code ashes once every second with audible alarm. To
silence the alarm, press and release the upper button.
1. Control Module with Remote Display Module
Alarm Signals
Alarm Code ProblemCorrective Action/Reset Details
Cabinet Thermistor Malfunction Alarm
E1
E2
UHi
ULo
Hi
Cabinet thermistor has failed.
Defrost Thermistor Malfunction Alarm
Defrost thermistor has failed.
High-Voltage Alarm (135VAC
more)
Low-Voltage Alarm (96VAC
High-Temperature Alarm
Note: When power is turned on, a
high-temperature alarm may occur.
Refrigerator: Cabinet temperature has
exceeded the setpoint temperature by
10°F (5.6°C) for more than 2 hr.
±5% or
±5% or less)
Cabinet thermistor disconnected, shorted, or open.
Check connection and continuity. Reconnect or
replace as needed.
Unit cycles 5-min. on, 5-min. off.
Defrost thermistor disconnected, shorted, or open.
Check connection and continuity. Reconnect or
replace as needed.
Unit cycles on and off with cabinet thermistor.
The compressor de-energizes if voltage protection
operates. The voltage safeties automatically reset
when voltage is corrected.
First try obvious corrections such as closing doors
and cleaning the condenser.
Automatically resets when temperature returns to
normal.
Lo
E13
"– – –"
Freezer: Cabinet temperature has
exceeded the setpoint temperature by
27°F (15°C) for more than 2 hr.
Low-Temperature Alarm
Refrigerator & Freezer: Cabinet
temperature has remained below the
setpoint temperature by 8°F (4.4°C) for
more than 2 hr.
Communication Error Alarm
Communication between the control
module and the display module has been
interrupted or disconnected.
Compressor OffUnit (compressor) off.
Automatically resets when temperature returns to
normal.
Check the connections at the control module
and the display module. If connections are good,
the control module and display module must be
replaced.
The unit operates on a set 5-min. on, 5-min. off cycle
until communication is restored.
Press and hold the upper and lower buttons until the
temperature appears on the display.
38
Page 39
2. Control Module with Integrated Display
Alarm Signals
Alarm Code ProblemCorrective Action/Reset Details
E01
E02
Hi
Lo
Cabinet Thermistor Malfunction Alarm
Cabinet thermistor has failed.
Defrost Thermistor Malfunction Alarm
Defrost thermistor has failed.
High Temperature Alarm
Refrigerator: Cabinet temperature has
remained above 57°F (13.9°C) for more
than 2hr.
Freezer: Cabinet temperature has
remained above 26°F (-3.3°C) for more
than 2hr.
Low Temperature Alarm
Refrigerator: Cabinet temperature has
remained below 26°F (-3.3°C) for more
than 2hr.
Freezer: Cabinet temperature has
remained below -23°F (-30.6°C) for more
than 2hr.
Beeps for 10 sec., then silent for 50 sec.. To silence
the alarm, press and release the up button.
Appliance cycles 5 min. on, 5 min. off.
Beeps for 10 sec., then silent for 50 sec. To silence
the alarm, press and release the up button.
Appliance cycles on and off with cabinet thermistor.
Beeps for 10 sec., then silent for 50 sec. To silence
the alarm and clear "Hi" from the display, press and
release the up button. The alarm icon stays on.
Automatically resets when temperature returns to
normal.
Beeps for 10 sec., then silent for 50 sec. To silence
the alarm and clear "Lo" from the display, press and
release the up button. The alarm icon stays on.
Automatically resets when temperature returns to
normal.
39
Page 40
E. Safety Devices
1. Compressor External or Internal Protector
If combined temperature/amperage value is above the limit specied by the compressor
manufacturer, the compressor external or internal protector operates independently to
turn off the compressor. The compressor external or internal protector de-energizes the
compressor until the temperature/amperage value returns to an acceptable level.
• If the condenser fan motor is operating and the compressor is off, it is most likely that
the compressor external or internal protector opened. If both the compressor and
condenser fan motor are off, it is most likely the appliance is off or the high-pressure
switch has opened. For further details, see "II.B. Service Diagnosis."
• On refrigerators, the compressor external protector is integrated with the start relay.
On 1-section freezers, the compressor protector is an internal protector. On 2-section
freezers, the compressor protector is an external protector.
2. Short-Cycle Protection
There is a 2-min. minimum off-time and on-time for the compressor.
Note: Time may vary with compressor protector or high-pressure switch activation.
3. High-Pressure Switch
If pressure on the high-side of the appliance exceeds Hoshizaki specications, the
high-pressure switch activates and interrupts the compressor circuit, de-energizing the
compressor until the pressure returns to an acceptable level.
F. Mullion/Perimeter Heater
Refrigerators and freezers with mullions are equipped with mullion heaters. Freezers are
also equipped with perimeter heaters. The heaters are energized as soon as the power
switch is turned on.
40
Page 41
IV. Replacement of Components
WARNING
• The appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Move the power switch to the "OFF" position, then unplug the appliance from the
electrical outlet before servicing.
• Make sure all food zones in the appliance are clean after the appliance is
serviced.
A. Service for Refrigerant Lines
WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certied service personnel.
• Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-134a or R-404A as a
mixture with pressurized air for leak testing.
NOTICE
• Do not leave the system open for longer than 15 min. when replacing or servicing
parts. The Polyol Ester (POE) oils used in R-134a and R-404A appliances
can absorb moisture quickly. Therefore it is important to prevent moisture from
entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The appliance is provided with refrigerant access valves. Using proper refrigerant
practices recover the refrigerant from the access valves and store it in an approved
container. Do not discharge the refrigerant into the atmosphere.
41
Page 42
2. Brazing
WARNING
• R-134a and R-404A themselves are not ammable at atmospheric pressure and
temperatures up to 176°F (80°C).
• R-134a and R-404A themselves are not explosive or poisonous. However,
when exposed to high temperatures (open ames), R-134a and R-404A can be
decomposed to form hydrouoric acid and carbonyl uoride both of which are
hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace
of refrigerant to the system (if using an electronic leak detector), and then raise
the pressure using nitrogen gas (140PSIG). Do not use R-134a or R-404A as a
mixture with pressurized air for leak testing.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). Do not use R-134a or R-404A as a mixture
with pressurized air for leak testing.
3. Evacuation and Recharge
1) Attach a vacuum pump to the system. Be sure the charging hoses are connected to both
high and low-side access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the
vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends
on pump capacity.
4) Close the low-side valve and high-side valve on the gauge manifold.
42
Page 43
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a
refrigerant service cylinder. Remember to loosen the connection and purge the air from
the hose. See the nameplate for the required refrigerant charge. Hoshizaki recommends
only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest
edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation)
and optional when charging an R-134a system. Place the service cylinder on the
scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder,
then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid
dispensing device to add the remaining liquid charge through the low-side
access valve with the appliance running.
9) Close gauge manifold valves and disconnect the hoses.
10) Cap the access valves to prevent a possible leak.
43
Page 44
B. Important Notes for Component Replacement
NOTICE
• When replacing a component listed below, see the notes to help ensure proper
operation.
• When replacing a control module or display module on an appliance with a control
module with remote display module, an HS conversion kit is required.
Refrigerator: HS-5079; Freezer: HS-5078
ComponentNotes
CompressorInstall a new start relay, start capacitor, and compressor protector (compressor protector
is integrated with the start relay on refrigerators; internal on 1-section freezers; external on
2-section freezers).
Compressor,
Evaporator
Fan Motor,
Condenser Fan
Motor
Expansion Valve • Attach the expansion valve bulb to the suction line in the same location as the previous
Defrost
Thermistor
Control Module
w/Remote
Display
WARNING! To reduce the risk of electric shock, be sure to reconnect the
component's ground wire.
bulb.
• Secure the bulb with the clamp and holder, then insulate it.
After working with or around the defrost thermistor on a freezer, make sure the defrost
thermistor wire is not touching the defrost heater.
If three dashes (- - -) appear on the display module when energized, the compressor and
display module are off. To turn the compressor and display module on, press and hold the
upper and lower buttons until the temperature appears on the display. NOTICE! The three
dashes must be cleared, otherwise the compressor will not run and product will be
lost.
C. Door Reversal
The appliance is provided with a cabinet design which, after being delivered to the
installation location, permits changing of the door swing from left to right or right to left.
To change the door swing, an HS kit from your local Hoshizaki distributor is required. See
the table below. NOTICE! Improper installation of the HS kit may result in the doors not closing completely and/or the gaskets not sealing correctly. For further details,
contact your local Hoshizaki distributor or Hoshizaki Technical Support at
1-800-233-1940.
Door TypeConvertHS Kit Number
Full Glass
Full Solid, Half Solid
Right Hinge to Left HingeHS-5045
Left Hinge to Right HingeHS-5046
Right Hinge to Left HingeHS-3725
Left Hinge to Right HingeHS-3726
44
Page 45
V. Maintenance
WARNING
• Move the power switch to the "OFF" position and unplug the appliance before
performing maintenance to prevent electric shock or injury by moving parts. To
reduce the risk of electric shock, do not touch the power switch or plug with damp
hands.
• Before performing maintenance, move all foods into another clean refrigerator or
freezer.
1. Condenser
Check the condenser once a year and use a brush or vacuum cleaner to clean the
condenser as required.
2. Power Supply Connection
If a plug, power cord, or receptacle (three-section models) is damaged, replace it. Be
sure to connect the ground wire.
45
Page 46
VI. Preparing the Appliance for Periods of Non-Use
WARNING
• When preparing the appliance for long storage, prevent the doors from closing to
reduce the risk of children getting trapped.
• To reduce the risk of electric shock, do not touch the attachment plug or power
switch with damp hands.
• When shutting down the appliance for more than one week, move the power
switch to the "OFF" position and unplug the appliance.
• Do not plug in/unplug the appliance to start/stop operation. Make sure the power
switch is in the "OFF" position before plugging in or unplugging the appliance to
reduce the risk of electric shock.
1) Before shutting down the appliance, move the stored food into another refrigerator or
freezer.
2) Reach over the front panel and move the power switch to the "OFF" position. The
appliance will shut down.
3) Unplug the appliance.
IMPORTANT
When preparing the appliance for long storage, clean the cabinet interior, door
gaskets, and shelves.
46
Page 47
VII. Disposal
WARNING
When preparing the appliance for disposal, remove the door to reduce the risk of
children getting trapped. Leave the shelves in place so that children may not easily
climb inside.
The appliance contains refrigerant and must be disposed of in accordance with
applicable national, state, and local codes and regulations. Refrigerant must be
recovered by properly certied service personnel.
See the nameplate for electrical and refrigerant data. The nameplate is located inside the
cabinet.
We reserve the right to make changes in specications and design without prior notice.
(PSIG)Refrigerant (oz.)
HIGHLOW134a404A
1-Section
11
2-Section
12
-
1-Section
8
2-Section
17
48
Page 49
B. Wiring Diagrams
1a. CR1B-FG Auxiliary Code A-5 to B-5(A)
Control Module with
Remote Display Module
*
* High-Pressure Switch
Cut-out270±10 PSIG
Cut-in190±20 PSIG
49
Page 50
1b. CR1B-FG Auxiliary Code B-5(B) and Later
Control Module with
Integrated Display
*
* High-Pressure Switch
Cut-out300±10 PSIG
Cut-in190±20 PSIG
50
Page 51
2a. CR1B-FS/HS, CR3B-FS/HS Auxiliary Code V-5 to B-5(A)
Control Module with
Remote Display Module
*
* High-Pressure Switch
Cut-out270±10 PSIG
Cut-in190±20 PSIG
51
Page 52
2b. CR1B-FS/HS, CR3B-FS/HS Auxiliary Code B-5(B) and Later
Control Module with
Integrated Display
*
* High-Pressure Switch
Cut-out300±10 PSIG
Cut-in190±20 PSIG
52
Page 53
3a. CR2B-FG Auxiliary Code A-5
Control Module with
Remote Display Module
*
* High-Pressure Switch
Cut-out270±10 PSIG
Cut-in190±20 PSIG
53
Page 54
3b. CR2B-FG Auxiliary Code B-6 and Later
Control Module with
Integrated Display
*
* High-Pressure Switch
Cut-out300±10 PSIG
Cut-in190±20 PSIG
54
Page 55
4a. CR2B-FS and CR3B-FS Auxiliary Code V-5 to B-5(B)
CR2B-HS Auxiliary Code A-5 to B-5(A),
CR3B-HS Auxiliary Code A-5 to B-5(C)
Control Module with
Remote Display Module
*
* High-Pressure Switch
Cut-out270±10 PSIG
Cut-in190±20 PSIG
55
Page 56
4b. CR2B-FS and CR3B-FS Auxiliary Code B-5(C) and Later,
CR2B-HS Auxiliary Code A-5 to B-5(B) and Later,
CR3B-HS Auxiliary Code B-5(D) and Later
Control Module with
Integrated Display
*
* High-Pressure Switch
Cut-out300±10 PSIG
Cut-in190±20 PSIG
56
Page 57
5a. CF1B-FG Auxiliary Code B-5(C) and Earlier
Control Module with
Remote Display Module
**
*
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
°F±5°F (49°C±3°C)
120
°F±5°F (21°C±3°C)
70
57
Page 58
5b. CF1B-FG Auxiliary Code B-5(D) and Later
Control Module with
Integrated Display
**
*
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
°F±5°F (49°C±3°C)
120
°F±5°F (21°C±3°C)
70
58
Page 59
6a. CF1B-FS and CF3B-FS (one section side) Auxiliary Code A-5 to B-5(B),
CF1B-HS Auxiliary Code A-5 to B-5(A),
CF3B-HS (one section side) Auxiliary Code B-6 and Later
Control Module with
Remote Display Module
A-5 (G)
**
and later
*
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
°F±5°F (49°C±3°C)
120
°F±5°F (21°C±3°C)
70
59
Page 60
6b. CF1B-FS and CF3B-FS (one section side) Auxiliary Code A-5 to B-5(B),
CF1B-HS Auxiliary Code A-5 to B-5(A),
CF3B-HS (one section side) Auxiliary Code B-6 and Later
Control Module with
Integrated Display
**
*
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
°F±5°F (49°C±3°C)
120
°F±5°F (21°C±3°C)
70
60
Page 61
7a. CF2B-FS and CF3B-FS (two section side) Auxiliary Code A-5 to B-5(A),
CF2B-HS Auxiliary Code A-5 to B-5
Control Module with
Remote Display Module
*
A-5 (G)
and later
**
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
°F±5°F (49°C±3°C)
120
°F±5°F (21°C±3°C)
70
61
Page 62
7b. CF2B-FS and CF3B-FS (two section side) Auxiliary Code B-5(B) and Later,
CF2B-HS and CF3B-HS (two section side) Auxiliary Code B-6 and Later
Control Module with
Integrated Display
*
**
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
°F±5°F (49°C±3°C)
120
°F±5°F (21°C±3°C)
70
62
Page 63
8. CR3B-FS/HS Receptacle Box Connection
Note: Only the top receptacles have power.
9. CF3B-FS/HS Receptacle Box Connection
Note: Only the top receptacles have power.
63
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.