VNT6200H1000
A3 ERV/HRV VNT5070H1000 or VNT5070E1000
B Heat/Energy Recovery Core
C Filter (2)
D1 Round Duct Collars (4) [VNT5150, VNT5200,
VNT6150, VNT6200]
D2 Oval Duct Collars (VNT5070)
E Installation Kit
F Wall Mount Bracket (VNT5070)
G Optional controls (sold seperately)
Control Options (Sold separately)
G1 - Prestige IAQ Kit
G2 - DG115 IAQ control
G3 - Dehumidistat H8908D
G4 - T10 Pro Smart
G5 - 20/40/60 Minute Boost Control
G6 - W8150 Ventilation Control
G7 - Vent Boost Remote
G8 - VisionPRO WiFi
Contenu
A1 VRE/VRC VNT5150H1000, VNT5150E1000 ou
VNT6150H1000
A2 VRE/VRC VNT5200H1000, VNT5200E1000 ou
VNT6200H1000
A3 ERV/HRV VNT5070H1000 ou VNT5070E1000
B Noyau de récupération de chaleur et d’énergie
C Filtre (2)
D1 Colliers de conduit ronds (4) (VNT5150, VNT5200, VNT6150,
VNT6200)
D2 Colliers de conduit ovales (VNT5070)
E Nécessaire d’installation (flexible inclus avec le 5150 et le 5200)
F Support de montage mural (VNT5070)
G Commandes en option (vendues séparément)
Commandes en option (vendues séparément)
G1 - Nécessaire Prestige IAQ
G2 - Régulateur numérique DG115 IAQ
G3 - Déshumidistat H8908D
G4 - T10 Pro Smart
G5 - Minuteur de ventilation à haute vitesse (20, 40 ou 60 minutes)
G6 - Régulateur de ventilation W8150
G7 - Commande à distance de surventilation
G8 - VisionPRO WiFi
Tools Required (not supplied)
• Aluminum foil tape (UL1818)
• Standard screwdriver
• Crescent wrench
• Hex driver (1/4 in.)
Accessories (not included)
• 6 in. Dia. insulated duct (VNT5150, VNT5200,
VNT6150, VNT6200)
• 6 in. Dia. duct (VNT5150, VNT5200, VNT6150,
VNT6200)
• Two 6 in. Dia. weather hoods (VNT5150,
VNT5200, VNT6150, VNT6200)
• 5 in. Dia. insulated flex duct (VNT5070)
• 5 in. Dia. flex duct (VNT5070)
• 6 in. Dia. matrix hood, 50063805009 (VNT5070)*
* 6 in. to 5 in. reducer required
Warning: Installation must be performed by a
qualified service technician and must comply
with local codes.
Remove power to the device before installing or
servicing the device.
Failure to connect the device according to these
instructions may result in damage to the device
or the controls.
Outils nécessaires (non fournis)
• Ruban d’aluminium (UL1818)
• Tournevis standard
• Clé à molette
• Tournevis à tête hexagonale (1/4 po)
Accessoires (non inclus)
• Conduit isolé de 6 po de diamètre (VNT5150, VNT5200,
VNT6150, VNT6200)
• Conduit de 6 po de diamètre (VNT5150, VNT5200, VNT6150,
VNT6200)
• Hottes anti-intempéries de 6 po (VNT5150, VNT5200,
VNT6150, VNT6200)
• Conduit flexible isolé de 5 po de dia. (VNT5070)
• Conduit flexible de 5 po de dia. (VNT5070)
• Hotte à matrice de 6 po de dia. (VNT5070)*
* Réducteur de 6 po à 5 po requis
Avertissement : L’installation doit être effectuée par un
technicien qualifié et être conforme aux règlements locaux.
Débranchez l’appareil avant de l’installer ou d’en effectuer
l’entretien.
Un branchement de l’appareil non conforme aux présentes
instructions pourrait entraîner des dommages à l’appareil
lui-même ou aux commandes.
INSTALLATION INSTRUCTIONS BEGIN ON PAGE 1
INSTRUCTIONS POUR L’INSTALLATION COMMENCENT À LA
page 44.
• Prior to installing, serious consideration must be taken to ensure this ventilation system
will operate properly if integrated to any other type of mechanical system, i.e. a forced
air system, or an air handling unit. To ensure proper operation and compatibility of
both systems, it is required that the unit’s airflows (intake and exhaust) be balanced, by
following the procedures found in this manual
• Install the unit with space to access the front panel controls and the side access panel
for maintenance and service.
• To ensure quiet operation, do not place the device directly on the structural supports of
the home.
• The product is for residential applications only. Must be installed in accordance with all
national and local regulations, building and safety codes
NEED HELP? For assistance with this product please visit http://www.resideo.com
?
or call Customer Care toll-free at 18004681502.
The ERV/HRV Balanced Ventilation System provides
improved indoor air quality through its high performance
and efficiency.
Benefits
• Ventilation with sensible heat recovery (ERV and HRV)
• Ventilation with latent heat recovery (ERV only)
• Simplified mounting (hanging)
• Optional hanging with included straps.
• Removable duct collars for easy ducting to the unit
• Intuitive balancing via two variable speed motors and
a speed control
• Fits in tight spaces (VNT5070)
CAUTION: Electrical shock and fire hazard. Can cause personal and equipment damage.
• Before servicing or cleaning the system, always remove the power cord from the AC
wall outlet.
• Wear protective clothing and safety glasses when installing ventilator and working
with sheet metal.
• To reduce the hazards of electric shock or fire, do not perform any service to the
system other than those stated in the operating manual instructions.
• To reduce the risk of electric shock, this ventilation system comes equipped with a
3-prong plug-in. This plug will fit in a polarized outlet only one way.
• Do not use ventilation system for outdoor application.
• Do not pull or twist power cord when disconnecting it from the ventilation system.
Grasp the plug firmly, not the cord.
• Do not modify the power plug in any way; if modified, risk of electric shock, fire, or even
damage to the unit may occur.
• Do not use the ventilation system for removal of flammable fumes, gases or connect
directly to any appliances.
• Use a 120 VAC outlet only.
• Do not use an extension cord.
• Do not obstruct or cover the air intake or air outlet of the ventilation system.
• Do not modify, repair or disassemble this system. These tasks are to be performed by
authorized serviced personnel only. Fire, electrical shock and/or bodily injury may
occur if these warnings are not followed.
• To prevent injuries, do not operate the ventilation system, while servicing or
maintaining. There are impeller wheels turning at a very high speed that must fully
stop rotating prior to accessing the inside of the unit.
• Always assess how the operation of the ventilation system may interact with vented
combustion equipment (i.e. Gas Furnace, Oil Furnace, Combustion, Appliances, etc.)
• Ensure unit is properly installed and suspended to prevent falling or dropping injuries.
2
ERV/HRV Ventilation Systems 69-2480EF—19
Determining Your Ventilation Needs
How much fresh air do you need?
Good air quality is based in part on the capacity of the home’s ventilation system. Usually, the unit’s capacity
is measured in CFM (Cubic Feet per Minute) or L/s (Liters per second) of fresh air being distributed in the
living space. Use the ASHRAE 62.2 Ventilation Standard, the Room Count Calculation Method, or the Air
Change Per Hour (ACH) Method to determine your ventilation needs.
TOTAL cubic feet X 0.35 per hour = total cubic feet per hour
Take total and divide by 60 to get cubic feet per minute (CFM)
Example: A 25 ft. x 40 ft. (1,000 sq. ft.) house with basement
1,000 sq. ft. x 8 ft. high x 2 (1st floor + basement) = 16,000 cu. ft.
16,000 cu. ft. x 0.35 ACH = 5,600 cubic feet per hour
5,600 cu. ft. / 60 Minutes = 93 cubic feet per minute (CFM)
93 CFM is your ventilation need
ERV/HRV Ventilation Systems 69-2480EF—193
Specifications
FRONT CLEARANCE OF 25 INCHES
M28919A
14-1/2
M33111
Dimensions in inches (mm) of VNT5150, VNT5200, VNT6150 and VNT6200
2
1
L
VNT5150H1000, VNT5150E1000 or VNT6150H1000: H = 22 1/2 in. (572 mm), W = 11 1/2 in. (295 mm), L = 29 1/2 in. (749 mm)
VNT5200H1000, VNT5200E1000 or VNT6200H1000: H = 22 1/2 in. (572 mm), W = 16 1/2 in. (422 mm), L = 29 1/2 in. (749 mm)
• Flexible Duct (2):VNT5150, VNT5200, VNT6150 & VNT6200: 6 in. round for inlet and outlet. Flexible vinyl,
compatible for connection to rigid or flexible ducting with sheet metal screws and/or tape. VNT5070: 5 in. oval for inlet
and outlet. Flexible vinyl, compatible for connection to flexible ducting with sheet metal screw and/or tape.
Standards and Certifications:
CSA22.2 #11310, CSA 439 Standard
UL Standard 1812
RoHS Compliant
HVI Certified
FCC Part 15, Class B
ENERGY STAR (VNT6150H1000 & VNT6200H1000)
Install the ERV/HRV Ventilation System according to national and local regulations, building, and safety codes.
The ERV/HRV unit may be used with one of the following external controls:
T10 Pro Smart Thermostat
• Controls both heating/cooling and ventilation.
• Ventilation programming for time of day or Ashrae standards.
• Optional ventilation lockouts for high/low temp or humidity conditions
using Internet weather when registered to the app.
Prestige™ IAQ Kit
• Controls both heating/cooling and ventilation.
• Wireless sensor for displaying outdoor temperature and humidity.
• Advanced ventilation programming includes economizing and extreme
condition shutdown.
• Maintenance and service reminders.
• High definition color display.
• RedLINK™ Wireless technology
DG115 IAQ Digital Control
• Automatic adjustments maintain fresh air in home.
• Sensor for displaying outdoor temperature and humidity.
• Advanced ventilation programming includes economizing and extreme
condition shutdown.
• Maintenance and service reminders.
• Controls other indoor air quality equipment.
VisionPRO™ Smart or VisionPRO™ RedLINK
• WiFi™ (TH8321WF1001) or RedLINK™ Wireless technology (TH8321R1001)
• Controls both heating/cooling and ventilation.
• Display outdoor temperature and humidity.
• Ventilation programming for time of day or Ashrae standards.
• Optional ventilation lockouts for high/low temp or humidity conditions
• C7089R1013 wireless outdoor sensor for RedLINK model. Internet
weather for Smart model.
Manual Dehumidistat and Automatic Ventilation Controls
• Manual humidity control with intuitive comfort settings.
• Automatic W8150 ventilation control to ASHRAE standard, or for
continuous operation.
Boost Control Digital Timer
• Ventilation boost control for 20/40/60 minutes.
Wireless Vent Boost Remote
• 20/40/60 minute ventilation timer
• Works with RedLINK 2.0 thermostats
ERV/HRV Ventilation Systems 69-2480EF—1913
Install to Fit Your Application
M24745
M28983
NOTE: Prior to installing, serious consideration must be taken to insure this ventilation system will
operate properly if integrated with any other type of mechanical system, i.e. a forced air system,
or an air handling unit. To insure proper operation & compatibilities of both system, it is required
that the airflows of ventilation systems be balanced, by following the procedures found in this
manual.
Limitations: The product is for residential applications only. Must be installed in accordance with all
national and local regulations, building and safety codes. Flex duct is recommended for connecting to the
ERV/HRV collars to reduce vibration noise.
This application uses a devoted duct system for the supply and the exhausting of stale air
accumulated in the home.
Honeywell Home recommends installing fresh air grilles in all bedrooms and living areas and to
exhaust the stale air from the bathroom, kitchen, and laundry room.
ERV/HRV Ventilation Systems 69-2480EF—19
Install to Fit Your Application (continued)
B
Exhaust at the Source and Supply in the Return
STALE AIR FROM LIVING SPACE,
SUCH AS FROM BATHROOM
18 INCHES
6 FEET
OR KITCHEN
TO LIVING
HRV / ERV
SPACE
3 FEET
FORCED AIR
SYSTEM
M28984
This application uses a devoted duct system for the exhausting of stale air accumulated in the home. The
fresh air is introduced into the return air duct and is distributed through the home by the existing supply
air ductwork of the forced air system.
Make sure when using this application that your fresh air duct connection to the forced air system return
air duct is at least 3 feet from the forced air system. You should check with your local code or the forced
air system’s manufacturer.
The forced air system’s blower does not have to run when the unit is operating, but is recommended for
maximum effectiveness.
NOTE: For the minimum distance between the fresh air connection and the forced air system, check
with your local building codes and forced air system manufacturer.
NOTE: For dwellings with multiple forced air systems, Honeywell Home recommends one ERV/HRV unit
per system.
NOTE: Refer to the Wiring section (beginning on page 24) for instructions to connect the unit to
operate the forced air system with the ERV/HRV unit.
ERV/HRV Ventilation Systems 69-2480EF—1915
Install to Fit Your Application (continued)
Exhaust and Supply in the Return
C
18 INCHES
6 FEET
HRV / ERV
TO LIVING SPACE
6 FEET
3 FEET
FORCED AIR
SYSTEM
M28985
16
When using this application make sure that there is a minimum of 6 feet between the fresh air and
exhaust air connections of the ERV/HRV unit in the return air duct. Supply air from the ERV/HRV unit
must be at least 3 feet from the forced air system. These distances can be different from one region to
another; you should check with your local code or the forced air system’s manufacturer.
NOTE: For minimum distance between return and forced air system, check with your local building
codes and forced air system manufacturer.
NOTE: Fresh air must always be down-stream from the exhaust air in the return air duct of the forced air
system.
NOTE: Furnace blower is required to operate when ventilation is required. Set the furnace blower to run
continuously, or interlock electrically (low voltage).
ERV/HRV Ventilation Systems 69-2480EF—19
Installation Steps
1
Ensure that you have all of the following installation items:
The ERV/HRV unit should be installed in a mechanical room or as close to an outside wall as possible.
The ERV/HRV unit must always be installed in an area where the air is conditioned to avoid freezing the
condensate line.
The contractor should install the unit in an area that allows the homeowner easy access for maintenance.
It is very important to install an electric receptacle (120 Vac) near the unit, a separate circuit breaker is
also recommended. It is best to have access to a condensate drain near the ERV/HRV unit to avoid having
to use a condensate pump.
NOTE: Installation is not recommended in unconditioned areas such as an attic or crawl space where
NOTE: Ducting in unconditioned areas must be fully sealed and insulated.
ERV/HRV Ventilation Systems 69-2480EF—1917
Installation Area
the temperature can fall below 32 ºF (0 ºC).
Installation Steps (continued)
3a
Hanging the VNT5150, VNT5200, VNT6150 or VNT6200
The ERV/HRV unit enables you to save time and effort by offering a simplified hanging system.
TIP: Removing the core unit makes installation easier since the unit weighs less
without the core inside.
1. Attach straps to joist using the supplied
washers and four 1 in. hex-head hanging
screws.
3. Make final adjustments to ensure that the HRV/ERV is level.
2. Pull on middle of strap while gently lifting unit
upward to raise the unit.
NOTE: If the unit is not level, improper drainage will occur and could lead to moisture and leakage
problems.
18
ERV/HRV Ventilation Systems 69-2480EF—19
Installation Steps (continued)
3b
1. Fix the control module bracket to the top of the
VNT5070 using the supplied mounting screws.
Mounting the VNT5070
2. Slide the control module onto the bracket
using the key holes.
3. Fix the wall mount bracket to two 2x4s or to
a precut sheet of plywood using the supplied
mounting screws.
5. Secure with two sheet metal screws.
NOTE: When these mounting steps are complete, resume normal installation procedures beginning on
page 20, “Installing the flex duct to the ERV/HRV.”
4. Hang the unit on the bracket.
ERV/HRV Ventilation Systems 69-2480EF—1919
Installation Steps (continued)
4
Installing the flex duct to the ERV/HRV
TIP: Honeywell Home recommends using approximately 16 inches of flexible duct (supplied in kit
with VNT5150, VNT5200, VNT6150 and VNT6200) between the unit and the rigid duct for noise
dampening. The flex duct is mounted to the unit the same way as the insulated flex.
1. Insert the vinyl duct over the hooks on the
duct collar and seal with a supplied 30 inch
tie wrap.
2. Insert insulation inside the outer ring of the duct
collar.
20
3. Finish by taping the duct on the collar.
TIP: For the VNT5070 unit, balancing should be
done before taping the insulation onto the
collar. See balancing steps on page 29.
4b. Attach collar onto unit (VNT5070)
IMPORTANT: Always fix and secure each collar using
four of the 5/8 in. screws supplied.
This step is critical in order to prevent
condensation accumulation.
4a. Slide collar onto unit (VNT5150,
VNT5200, VNT6150 and VNT6200)
5. Secure collar with the supplied 5/8 in.
hex-head screws.
TIP: Attach the flex duct to the collar first, and then
attach the collar to the unit.
ERV/HRV Ventilation Systems 69-2480EF—19
Installation Steps (continued)
5
Insert the threaded drain adapter through the bottom of
the unit and hand tighten the plastic nut supplied with
the drain kit.
Use a wrench to tighten the nut another half turn to
ensure a complete seal.
Install the condensate tubing by pushing the clear
plastic tubing over the drain adapter.
Make a condensate trap by looping the clear plastic
tubing. This loop will prevent foul odors from entering
the unit.
Use a condensate pump if you don’t have access to
the floor drain.
Installing the condensation drain line
Drainless Application
NOTE: If installing an ERV unit (VNT5150E1000, VNT5200E1000, VNT5070E1000) in a region where
the outdoor temperature does not drop below freezing, the condensate drain line does not need
to be installed and the unit may be installed as a drainless application.
1. Insert the threaded drain adapter through the bottom
of the ERV with the drain connection inside of the unit
as shown in the figure.
2. Fit the rubber washer over the drain adapter and then
attach the plastic nut.
3. Hand tighten the plastic nut supplied with the drain kit.
4. Use a wrench to tighten the nut another half turn to
ensure a complete seal.
5. Attach the drain cap to the drain adapter inside the
unit.
ERV/HRV Ventilation Systems 69-2480EF—1921
Installation Steps (continued)
M32372
6
Connecting the power cord
ERV/HRV Power Cord
Insert the power cord on top of the unit. Press firmly
to make sure the power cord is secure.
IMPORTANT: Do not plug the power cord into the
wall receptacle at this time.
Electric Wall Outlet
Honeywell Home recommends that the unit has a dedicated
receptacle with 120 VAC.
Avoid connecting the unit to the wall receptacle with an
extension cord.
Honeywell Home does not recommend the use of an extension cord.
Ensure that the receptacle’s polarization is correct.
NOTE: If the LED light on the ERV/HRV control panel remains green, the motors do not energize, and the
controls do not operate; this can indicate that the polarization in the main AC outlet is inverted.
IMPORTANT: Always consult a qualified technician to ensure proper installation of main power.
7a
Locate the outside hoods at least 18 inches
(0.46 m) above grade and at least 72 inches
(1.83 m) apart.
NOTE: Do not locate the fresh air vent
IMPORTANT: Always consult your
Installing outside hoods for the fresh air and the exhaust
hood close to known sources of
pollutants such as dryer vents.
local code for spacing
requirements in your area.
72 (1,829)
18 (457)
22
ERV/HRV Ventilation Systems 69-2480EF—19
Installation Steps (continued)
7b
Optional Matrix hood (50063805009) installation for fresh air and
exhaust air
NOTE: Only for applications up to 115 CFM maximum speed. Higher airflow rates are limited by higher
static pressures and the potential of cross-contamination between the supply and exhaust air
streams. The Matrix hood design is suitable for smaller spaces commonly found in town homes
and condominiums which require less airflow rates.
NOTE: A 6 in. to 5 in. reducer is required if you are installing the matrix hood (50063805009) with the
VNT5070.
See Matrix hood literature for step-by-step
instructions.
ERV/HRV Ventilation Systems 69-2480EF—1923
Automated Defrost
M33110
The ERV and HRV units are equipped with an automatic defrost feature to eliminate any ice build up on the core.
• Automatic defrost is initiated once every hour when the fresh air supply temperature drops to 23°F (5°C)
or colder.
• The defrost cycle operates by turning off the supply fan while continuing to operate the exhaust fan.
• The exhaust fan speed is adjusted proportionally based on the outdoor temperature, initially operating at
low speed.
• As the outdoor temperature continues to drop, the exhaust fan speed will increase, and will operate at
maximum speed when the outdoor temperature is 4°F (20°C) or less.
• The VNT5070 Series HRV/ERV defrost cycle runs for 5 minutes with the supply fan off followed by
35 minutes of continuous normal operation.
• The VNT5150 Series HRV/ERV defrost cycle runs for 5 minutes with the supply fan off followed by
35 minutes of continuous normal operation.
• The VNT5200 Series HRV/ERV defrost cycle runs for 4 minutes with the supply fan off followed by
40 minutes of continuous normal operation.
• VNT6150H1000 and 6200H1000 HRV cycle runs for 8 minutes with the supply fan off followed by
32 minutes of continuous normal operation.
• Defrost cycles will continue to repeat as long as the temperature is 23°F (5°C) or less.
Wiring
CAUTION: Voltage hazard.
Can cause equipment damage.
Disconnect power from the unit before beginning installation.
Terminal Description
RLY1
NC
CASE GND
NO
LVC – L1
SW3
D1
Z13
Vectouch
INTERLOCK
COM
G
W
B1
TIMER
G
B
SW2
SW1
B
REMOTES
JP2
COM PORT
G
R
JP1
R
24
The wiring terminal block is located behind the control module door on the side of the unit.
To access the terminal block, open the control panel door by swinging it open and to the right as shown above.
ERV/HRV Ventilation Systems 69-2480EF—19
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.