Honeywell VisionPRO 8000 Wi-Fi Specification Sheet

33-00096-01
VisionPRO® 8000 with Wi-Fi
FEATURES
• Thermostat aquires weather data through either a wired sensor or an Internet connection, making for a truly universal installation.
• U1 Terminals
One set of universal outputs that are configurable for one IAQ product, such as a Humidifier, Dehumidifier or Ventilator.
• Thermostat S1, S1
Configurable S1 Terminals can be configured for a wired indoor, wired outdoor, or discharge air sensor.
• On-board Humidity sensor
®
PRODUCT DATA
APPLICATION
The VisionPRO® 8000 with Wi-Fi features an effortless, 7-Day programmable touchscreen thermostat that provides control of temperature and one of the following: humidification, dehumidification, or ventilation. Up to 3 Heat/2 Cool heat pump systems or up to 2 Heat/2 Cool conventional systems are supported in residential and commercial applications.
• Customizable Service Reminders
Set up to 10 service reminders. Choose from the pre-set options or customize your own. Reminders can be based on date or the outdoor temperature.
• Selectable for Residential and Light Commercial Applications
One thermostat does it all to meet the needs of Residential and Light Commercial applications. Simply select Residen­tial or Commercial during the installer setup. If Commercial is selected, the thermostat will use commercial language, meet building codes and offer 365 day holiday scheduling.
VISIONPRO® 8000 WITH WI-FI
CONTENTS
®
Application ............................................... 1
Ordering Information ............................... 2
Specifications .......................................... 3
System Installation .................................. 5
When Installing this Product... ......................... 5
Wiring 24 Vac Common .................................... 6
Selecting Discharge Air Temperature Sensor
Mounting Locations .......................................... 6
Selecting Discharge Air Temperature Sensor Mounting
Locations .................................................................. 6
Selecting Thermostat Location ........................ 8
Installing Wallplate ............................................ 8
Make Changes to Installer Setup ..................... 10
Installer Setup (ISU) Table. ..................... 11
Connect to Wi-Fi® Network .................... 37
Installer Tests .......................................... 39
Using the Installer Test ..................................... 39
Operation ................................................. 40
Setting the Time/Date ....................................... 41
Setting the Fan .................................................. 41
Setting System Mode ........................................ 42
Preset Energy-Saving Schedules ............................. 42
Advanced Features ........................................... 52
Adaptive Intelligent Recovery (residential use only) . 52
Compressor Protection ............................................. 52
Staging Control ................................................. 53
Heat Pump and Backup Heat Operation 56
Geothermal Radiant Heat ................................. 56
Indoor Air Quality (IAQ) Control ............. 58
Humidification ................................................... 58
Set up Humidification ................................................ 58
Control Humidification Level ..................................... 60
Dehumidification - Residential ......................... 60
Set up Dehumidification With Cooling System .......... 61
Set up Dehumidification With Whole House Dehumidifier 61
Set up Dehumidification Away Mode ........................ 63
Control Dehumidification Level ................................. 64
Dehumidification - Commercial ....................... 64
Set up Dehumidification With Cooling System .......... 65
Set up Dehumidification With Dehumidifier ............... 66
Control Dehumidification Level ................................. 67
Ventilation .......................................................... 68
Set up Ventilation ...................................................... 69
IAQ Reminders ......................................... 73
Customizable Reminders ....................... 73
Commercial Features .............................. 78
Ramp Rates (Commercial Use) ........................ 81
Economizer and Time of Day (TOD) Operation 81
Pre-Occupancy Purge ....................................... 82
Wired Indoor Sensors ............................. 82
Wiring ....................................................... 84
Wiring IAQ Equipment or a Heat/Cool Stage to the
Universal Terminals .......................................... 86
Wiring C7089U1006 Outdoor Sensor .............. 87
Wiring guide — Wired Indoor Sensors ............ 88
Troubleshooting ...................................... 89
Regulatory Information ........................... 90
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
33-00096—01 2
VISIONPRO® 8000 WITH WI-FI
M34521
4-15/16 (126)
4-5/8 (118)
1-1/8 (29)
3-5/16 (84)
®
SPECIFICATIONS
Thermostat Description:
Feature Description
Powering method Common wire
System types (up to 3 heat/2 cool heat pump and up to 2 heat/2 cool conventional)
Changeover Manual or Auto changeover selectable
System setting Em Heat-Heat-Off-Cool-Auto
Fan setting Auto-On-Circ-Follow Schedule
Ter minal
W - O/B 18 to 30 VAC and
Y (cooling) 18 to 30 VAC 1.00A
G (fan) 18 to 30 VAC 0.50A
W2 - Aux 1 (heating) 18 to 30 VAC 0.60A
Y2 (cooling) 18 to 30 VAC 0.60A
A-L/A (Output) 18 to 30 VAC 1.00A
U1, U1, S1, S1 30 VAC max. 0.50A
Power Consumption of TH8321:
Backlight on: 1.48 VA Backlight off: 0.88 VA
Temperature Setting Range:
Heating: 40 to 90 °F (4.5 to 32 °C). Cooling: 50 to 99 °F (10 to 37 °C).
Gas, oil or electric heat with air conditioning
Warm air, hot water, high-efficiency furnaces, heat pumps, steam and gravity
Cool only
Voltag e
(50/60 Hz)
Max. Current
Rating
1.00A
750 mVDC
Cool Indication:
VisionPRO® 8000 with Wi-Fi
® displays “Cool On” when the
thermostat turns the cooling on.
Heat Indication:
VisionPRO® 8000 with Wi-Fi displays “Heat On” when the
thermostat turns the heating on.
Auxiliary Heat Indication:
VisionPRO® 8000 with Wi-Fi displays “Aux Heat On” when the
thermostat turns the auxiliary heat on.
Interstage Differential:
Comfort:
The thermostat keeps the indoor temperature within 1 degree of the setpoint (droop less control). The thermostat turns on stage 2 when the capacity on stage 1 reaches 90%.
When the interstage differential is set to 1.0 or higher, the ther-
mostat stages the equipment based on how far the indoor temperature is from the setpoint (ISU 303 to 309). See page 16 for more information.
Clock Accuracy: 1 minute per month at 77 °F (25 °C). ± 2
minutes per month over the operating ambient temperature range.
Mounting Means:
Thermostat mounts directly on the wall in the living space
using mounting screws and anchors provided. Fits a hori­zontal 2 x 4 in. junction box.
Temperature Sensor Accuracy:
± 1.5 F at 70 F (0.75 C at 21.0 C)
Humidification Setting Range:
10% to 60% RH.
Dehumidification Setting Range:
40% to 80% RH.
Humidity Display Range:
0% to 99%.
Humidity Sensor Accuracy:
± 5% RH from 30% to 50% RH at 75 F.
Fig. 1. Dimensions of thermostat in in. (mm).
3 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Accessories
Product Part Number
Wired Outdoor Sensor 10k ohm NTC C7089U1006
Wired Wall-mount Indoor Sensor 10k ohm NTC C7189U1005
Wired Flush-mount Indoor Sensor 20k ohm NTC C7772A1004, C7772A1012
Wired Wall-mount Indoor Sensor 20k ohm NTC TR21
Wired Wall-mount Indoor Sensor 10k ohm NTC TR21-A
Cover Plate (covers marks left by old thermostats) THP2400A1019
Wire Saver Module THP9045A1023
Discharge Air Temperature Sensor C7735
33-00096—01 4
SYSTEM INSTALLATION
1-855-733-5465
yourhome.honeywell.com
Honeywell
Golden Valley, MN 55422
RoHs Compliant Conformité RoHs Assembled in Mexico Assemblé au Mexique
TH8321WF1001
1
1524
M35343A
Password (Date Code)
When Installing this Product...
1. Read these instructions carefully. Failure to follow the
instructions can damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to verify the product operation.
Finding Your Password (Date Code)
You will need the thermostat password to:
• Make changes to Installer Setup
• Perform an Installer Test
• Reset Thermostat to Factory Default Settings
The password (date code) is located on the back of the thermostat (see Fig. 2)
VISIONPRO® 8000 WITH WI-FI
RoHs Compliant Conformité RoHs Assembled in Mexico Assemblé au Mexique
1524
1
TH8321WF1001
Residential/Résidentiel
1-800-468-1502
http://yourhome.honeywell.com
Commercial/Commerciale
1-888-245-1051
http://customer.honeywell.com
Honeywell, Golden Valley, MN 55422
M35344
®
Fig. 2. Finding thermostat password.
You can also find the password (date code) by pressing MENU, selecting Dealer Information and then scrolling down to see the Date Code.
5 33-00096—01
VISIONPRO® 8000 WITH WI-FI
MOUNT DISCHARGE SENSOR HERE
M35768
HEAT
EXCHANGER
BLOWER
VENTILATOR
OR
DEHUMIDIFIER
A-COIL
®
INSTALLATION
Model Numbering TH8321
Stages 3H/2C HP
2H/2C CONV
Residential or Commercial
Powered - C Wire (wire saver compatible)
Onboard Humidity Sensor
Number of Universal Relays 1
Number of Universal Sensor Inputs 1
Economizer / TOD Output
Wiring 24 Vac Common
• Single-Transformer System—Connect the common side of the transformer to the C screw terminal of the thermostat. Leave the metal jumper wires in place between R and RC.
• Two-Transformer System—Connect the common side of the cooling transformer to the C screw terminal of the thermostat. Remove the metal jumper wire between R and RC. Connect the hot side of heating transformer to R and connect the hot side of cooling transformer to RC.
Selecting Discharge Air Temperature Sensor Mounting Locations
Refer to the guidelines below and Fig. 3–7 for mounting locations of the Discharge Air Temperature Sensor.
Selecting Discharge Air Temperature Sensor Mounting Location
1. Mount the Discharge Air Temperature Sensor on the
supply duct in a location where the air is mixed well. Mount the Discharge Air Temperature Sensor out of sight of the A-Coil/Heat Exchanger when possible. See Fig. 3.
2. When possible, mount the Discharge Air Temperature Sensor upstream of a Steam Humidifier, a Fan Powered Humidifier or a Dehumidifier that is ducted to the supply. See Fig. 4–5.
3. If space does not allow a Discharge Air Temperature Sensor upstream of a Steam Humidifier or Fan Powered Humidifier, mount the Discharge Air Temperature Sensor downstream of the Humidifier. See Fig. 4.
4. If a Bypass Humidifier is installed, mount the Discharge Air Temperature Sensor downstream of the Bypass Humidifier. See Fig. 6–7.
Selecting Discharge Air Temperature Sensor Mounting Location
1. Install the Discharge Air Temperature Sensor on the duct
in a location where the air is mixed well. See Fig. 3–7.
Fig. 3.
ALTERNATE MOUNTING LOCATION FOR DISCHAR GE SENSO R.
HUMIDIFIER
MOUNT DISCHARGE SENSOR HERE
ABOVE CENTER
VENTILATOR
OR
DEHUMIDIFIER
HEAT
EXCHANGER
BLOWER
OF A-COIL
UPSTREAM OF HUMIDIFIER
M35769
33-00096—01 6
Fig. 4.
VISIONPRO® 8000 WITH WI-FI
M35770
HEAT
EXCHANGER
BLOWER
ALTERNATE MOUNTING LOCATION FOR DISCHARGE SENSOR.
MOUNT DISCHARGE SENSOR HERE
ABOVE CENTER OF A-COIL
UPSTREAM OF DEHUMIDIFIER
DEHUMIDIFIER
HEAT
EXCHANGER
BLOWER
VENTILATOR
OR
DEHUMIDIFIER
MOUNT DISCHARGE SENSOR HERE
BYPASS
HUMIDIFIER
M35771
HEAT
EXCHANGER
BLOWER
VENTILATOR
OR
DEHUMIDIF IER
MOUNT DISCHARGE SENSOR HERE
BYPASS
HUMIDIFIER
M35772
M32995
Fig. 7.
®
Fig. 5.
Fig. 6.
Installing Discharge Air Temperature Sensor
Use the following steps to mount the Discharge Sensor:
1. Attach plastic cover to the sensor probe.
2. Drill 1/4-inch hole for the sensor probe and mount it to
the ductwork with enclosed screws (see Fig. 8).
3. Connect wires to S1 terminal at the thermostat.
4. Setup the S1 terminal in the Installer Setup at the ther-
mostat.
Fig. 8. Mounting Discharge Air Sensor.
7 33-00096—01
VISIONPRO® 8000 WITH WI-FI
CAUTION
5 FEET
[1.5 METERS]
YES
NO
NO
NO
M19925
®
Selecting Thermostat Location
Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 9.
Fig. 9. Selecting thermostat location.
Do not install the thermostat where it can be affected by: — Drafts or dead spots behind doors and in corners. — Hot or cold air from ducts. — Radiant heat from sun or appliances. — Concealed pipes and chimneys. — Unheated (uncooled) areas such as an outside wall behind
the thermostat.
Installing Wallplate
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
2. Position and level the wallplate (for appearance only).
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and, if drywall, drill
two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
5. Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 11.
6. Insert the mounting screws into the holes and tighten.
C
S1
K
R
C
R
U1
U1
U2
U2
S1
S1
S1
W
O/B
Y
Y
G
G
AUX
W2
-E
Y2
Y2 L/A
A
Fig. 11. Mounting wallplate.
7. Connect common side of transformer to C terminal.
CONVENTIONAL
C
K
RC
R
U1
U1
U2
U2
W2
S1
S1
W
Y
G
Y2
A
S1
S1
O/B
Y
G
AUX
-E
Y2
L/A
1. Press button on top and pull to remove the wallplate.
33-00096—01 8
Fig. 10. Separate wallplate from thermostat.
HEAT PUMP
Fig. 12. Connecting C wire to terminal block.
Wiring the Thermostat
1. Refer to Fig. 13. See Table 9 on page 84 for terminal
designations and “Wiring” beginning on page 84 for more information.
2. Turn on 24 VAC NOW.
Fig. 13. Thermostat wired directly to equipment.
S1
S1
W
Y
G
W2
Y2
A
S1
S1
O/B
Y
G
AUX
-E
Y2
L/A
K
RC
R
U1
U1
U2
U2
C
CONVENTIONAL
HEAT PUMP
MCR34022
Dealer Information
Installer Options
MCR35348
TH8321WF1001 Date Code: 1524
1. Power the thermostat using Rc and C terminals. Refer to Fig. 14.
CONVENTIONAL
VISIONPRO® 8000 WITH WI-FI
Mounting Thermostat on Wallplate
1. Align thermostat at bottom and snap into place as
shown.
Fig. 15. Mount thermostat.
®
C
K
RC
R
U1
U1
U2
U2
HEAT PUMP
W2
S1
S1
W
Y
G
Y2
A
S1
S1
O/B
Y
G
AUX
-E
Y2
L/A
Fig. 14. Inserting wires in thermostat terminal block.
Finding Your Password (Date Code) to Access Installer Options
You need a password (Date Code) to access Installer Options. Installer Options allow you to:
• Make changes to the Installer Setup.
• Perform an Installer Test.
• Reset the thermostat to Factory Default settings.
The password (Date Code) is located on the back of the thermostat. It can also be found by following these steps:
1. Touch Menu.
2. Select Dealer Information.
Fig. 16.
3. Scroll down to see the Date Code.
Fig. 17.
9 33-00096—01
VISIONPRO® 8000 WITH WI-FI
Residential/Résidentiel
1-800-468-1502
http://yourhome.honeywell.com
Commercial/Commerciale
1-888-245-1051
http://customer.honeywell.com
Honeywell, Golden Valley, MN 55422
RoHs Compliant Conformité RoHs Assembled in Mexico Assemblé au Mexique
TH8321WF1001
1
1524
M35344
Password (Date Code)
Scroll to see:
Installer Setup Installer Test Reset To Defaults Device Info
MCR33976
Installer Options
MCR33977
Enter password
0 0 0 0
MCR34015
Installer Setup
Installer Test
®
Thermostat Password (Date Code)
Table 1. Installer Options.
Menu Item Description
Installer Setup Select INSTALLER SETUP to set system
settings one by one.
Installer Test Select INSTALLER TEST to quickly
determine if the heat, cool, fan and thermostat are operating properly. Minimum off timers are ignored during the test.
Reset To Defaults
Select RESET TO DEFAULTS to place all thermostat settings back to the factory settings.
Device Info For Honeywell use only.
RoHs Compliant Conformité RoHs Assembled in Mexico Assemblé au Mexique
M35343A
1524
1
TH8321WF1001
1-855-733-5465
yourhome.honeywell.com
Honeywell
Golden Valley, MN 55422
Fig. 18. Locate password.
The following options are available when you access Installer Options. For more information on each, press Help on the thermostat or see Table 1.
Make Changes to Installer Setup
1. Touch Menu.
2. Select Installer Options.
Fig. 20.
3. Enter password (date code) and touch Done. See “Find-
ing Your Password (Date Code) to Access Installer Options” beginning on page 9 for more information.
Fig. 19.
33-00096—01 10
Fig. 21.
4. Select Installer Setup.
Fig. 22.
5. Follow prompts on the screen to select the desired setup
options. See Table 2 for Installer Setup options.
ISU
Number
Installer Setup
Name Settings Default
101 Application
103 Thermostat Name
104 Thermostat Type
105 Temperature Scale
106 Outdoor Temp
200 Heating System
201 Heating
Equipment
202 Radiant Heat
Stages
203 Radiant Stage 1
Residential Commercial
[Select Thermostat Name]
Non-Programmable Programmable
Fahrenheit Celsius
Wired/Internet No
Conv. Forced Air Heat Pump Radiant Heat Other None (Cool Only)
Heat Pump:
Air to Air Heat Pump Geothermal Geothermal Radiant
0 1 2
None U1
Table 2. Installer Setup (ISU) Table.
Residential, Commercial
or Both Notes
Residential Both
Thermostat Both The Web Interface displays the name of the
Programmable Both
Fahrenheit Both
No Both Select Wired/Internet to indicate that you are
Conv. Forced Air Both For Dual Fuel, choose Heat Pump.
Air to Air Heat Pump Both This ISU is not displayed when ISU 200 Heating
Both Select the number of radiant heat stages.
Default varies based
Both This ISU is only displayed when ISU 201 on previous selections
VISIONPRO® 8000 WITH WI-FI
thermostat that you enter on this screen.
going to connect a wired outdoor sensor or connect to the internet. This will allow you to configure settings prior to the Internet being connected.
Select No if you are not going to connect to an outdoor sensor or the Internet.
System is set to Conv. Forced Air, Radiant Heat, Other or None (Cool Only).
See “Geothermal Radiant Heat” beginning on page 56.
Heating Equipment is Geothermal Radiant.
Geothermal Radiant Heat must be wired to universal terminal U1.
®
205 Geo Forced Air
206 Reversing Valve
None Cooling Only Heating and Cooling
O (O/B on Cool) B (O/B on Heat)
U1 is a normally open set of dry contacts. U1 requires power from the system transformer or a separate transformer.
Heating and Cooling Both This thermostat has the capability of controlling
Geothermal Radiant Heat, Geothermal Forced Air and Backup Heat.
If this thermostat is not controlling the Geothermal Forced Air System, select None. This setting is typically used if the thermostat is only controlling Geothermal Radiant Heat.
If this thermostat is using the Geothermal Forced Air System for cooling and not for heating, select Cooling Only.
If this thermostat is using the Geothermal Forced Air System for both heating and cooling, select Heating and Cooling.
O/B on Cool Both Only displayed if the equipment type is Air to Air
Heat Pump, Geothermal or Geothermal Radiant.
11 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
207 Cool Stages /
Compressor Stages
202, 207
Heat / Radiant / Backup Heat Stages
208 Cool Stage 3
0 1 2 3
1 - 3
None U1
1 if ISU 101 is Residential
2 if ISU 101 is Commercial
Default is 1 stage if ISU 101 Application is Residential
Default is 2 stages if ISU 101 Application is Commercial
Default varies based on previous selections
Residential, Commercial
or Both Notes
Both Conventional:
Cool Stage 3 is only available if ISU 101 is Commercial.
Cool Stage 3 must be wired to the universal terminal (U1).
Heat Pumps:
Maximum of 2 Compressor Stages for heat pump systems.
Both Maximum of 3 stages for conventional systems.
Maximum of 3 stages for radiant heat.
Maximum of 3 stages for Primary Heat. (Heating system, ISU 200 is set to “Other.”)
Maximum of 2 Backup Heat Stages for systems with more than 1 heating equipment type.
NOTE: Depending on the application, the text
displayed on the screen may show the specific heating equipment type.
Commercial Cool Stage 3 is only available if ISU 101 is
Commercial.
Cool Stage 3 must be wired to the universal terminal (U1).
210 Heat Stage 3
211 Fan Control in
Heat
212 Backup Heat Type
213 Backup Heat
Stages
None U1
No Fan Equip Controls Fan Tstat Controls Fan
None Electric Gas/Oil
0 - 2
U1 are normally open dry contacts when configured for a stage of Cool. U1 requires power from a system transformer or a separate transformer.
Default varies based on previous
Both Heat Stage 3 must be wired to the universal
terminal (U1).
selections
U1 is a normally open dry contact when configured for a stage of Heat. U1 requires power from a system transformer or a separate transformer.
Equip Controls Fan Both No Fan is only displayed when ISU 201 Heating
Equipment is Other.
None Both This ISU is only displayed when ISU 200
Heating Equipment is Radiant Heat or Other.
When ISU 200 Heating Equipment is Radiant Heat, the thermostat keeps the Radiant Heat on when it calls for Backup Heat.
When ISU 200 Heating Equipment is Other, you can select how the backup operates. See ISU
215.
1 Both This ISU is only displayed when a backup heat
source is selected at ISU 212 Backup Heat Type.
Maximum of 2 Backup Heat stages.
33-00096—01 12
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
214 Backup Heat Stg 2
215 Run Backup Heat
with Primary
216 Backup Heat Fan
None U1
No Yes
Equip Controls Fan Tstat Controls Fan
Residential, Commercial
or Both Notes
Default varies based on previous selections
Both The thermostat supports up to 2 backup heat
stages. When there are 2 backup heat stages, backup heat stage #2 must be wired to U1.
U1 is a normally open dry contact when configured for a stage of Heat. U1 requires power from a system transformer or a separate transformer.
No Both This ISU is only displayed when ISU 200
Heating Equipment is Other.
When ISU 200 Heating Equipment is Other, you can select how the Backup Heat operates. The thermostat can be setup to keep the primary heat source on when it calls for Backup Heat or the thermostat can be setup to turn off the primary heat source when it calls for Backup Heat.
When ISU 200 Heating Equipment is Radiant Heat, the thermostat keeps the Radiant Heat on when it calls for Backup Heat.
Tstat Controls Fan Both This ISU is only displayed for conventional
systems when ISU 212 Backup Heat Type is Electric.
217 Backup Heat
Stage 2
218 Backup Heat Type
219 External Fossil
Fuel Kit
None U1
Electric Gas/Oil
No Yes
Backup Heat Fan Operation automatically defaults to Equip Controls Fan when ISU 212 Backup Heat Type is Gas/Oil.
Default varies based on previous selections
Both The thermostat can support up to 2 backup heat
stages for heat pump applications. When there are 2 backup heat stages, backup heat stage 2 must be wired to U1.
U1 is a normally open dry contact when configured for a stage of Heat. U1 requires power from a system transformer or a separate transformer.
Electric Both This ISU is only displayed when ISU 201
Heating Equipment is Air to Air Heat Pump, Geothermal or Geothermal Radiant and there is at least one stage of backup heat.
See “Heat Pump and Backup Heat Operation” beginning on page 56.
No Both This ISU is only displayed when ISU 201
Heating Equipment is Air to Air Heat Pump, Geothermal or Geothermal Radiant and ISU 218 Backup Heat Type is Gas/Oil.
13 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
222 A-L/A Terminal
None Time Of Day Economizer Heat Pump Fault
Residential, Commercial
or Both Notes
None Commercial This ISU is only displayed when ISU 101
Application is Commercial.
Note: When the thermostat is setup for Residential, the L/A terminal operates as described under "Heat Pump Fault". The L/A terminal requires no setup for residential applications.
None: The A-L/A terminal is not used.
Time of Day: The A-L/A terminal is energized
during Occupied periods and when the user overrides the temperature. The terminal is de­energized during Unoccupied periods and in Standby mode.
Economizer: The thermostat controls an economizer module to provide ventilation during Occupied periods and free cooling when outdoor conditions are favorable. The A-L/A terminal is energized during Occupied periods and during a call for cooling in Unoccupied periods. See “Economizer and Time of Day (TOD) Operation” beginning on page 81. Notes: The economizer module determines when outdoor conditions are favorable for free cooling.
300 System
Changeover
Manual Automatic
Manual:
if ISU 101 is Residential
Automatic:
if ISU 101 is Commercial
Heat Pump Fault: When 24 volts is detected on the L/A terminal (compressor monitor), the thermostat displays a message to alert the user when the heat pump requires service. The L/A terminal sends a continuous output to a zone panel when the thermostat is set to Emergency Heat mode. The zone panel will not turn on the heat pump when a zone is set to Emergency Heat mode.
Both Manual: The user must select heating or
cooling as needed to maintain the desired indoor temperature.
Automatic: The user has the option to select Auto for the system setting. In Auto mode, the thermostat controls heating and cooling equipment as needed to maintain the desired indoor temperature.
33-00096—01 14
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
300 Auto Changeover
Deadband
301 Control Options
2° F to 9° F (in 1° F increments)
Basic Options Advanced Options
Residential, Commercial
or Both Notes
3° F Both This ISU is only displayed when ISU 300 is set
to Automatic.
Deadband is the minimum separation between heat and cool settings when the thermostat is setup for Auto Changeover. For example, if the deadband is set to 3° F and the cool setpoint is 75° F, the warmest heat setpoint allowed would be 72° F. If the heat setpoint is adjusted above 72° F, it will automatically adjust the cooling setpoint higher to maintain the 3° F deadband.
When ISU 907 or ISU 910 (Dehum Over Cooling Limit) is set to 1, 2, 3, 4 or 5 F, the thermostat will not show the full Deadband range. For example, if you set a Deadband of 3 F and an Over Cooling Limit of 2 F, the minimum Deadband that you can select will be 5 F. This prevents the heating system from turning on when the thermostat over cools to reach the dehumidification setting.
Basic Options Both Basic Options: The Installer Setup displays
basic temperature control options which include Backup Heat Droop, Backup Heat Upstage Timer, Outdoor Temperature Lockouts and Cycle Rate settings per stage.
302 Finish With High
Cool Stage
302 Finish With High
Heat Stage
No Yes
No Yes
Note: Outdoor Temperature Lockouts only apply to Heat Pump applications.
Advanced Options: The Installer Setup displays both Basic and Advanced Options. Advanced temperature control options include Finish With High Cool Stage, Finish With High Heat Stage, and Temperature Differential settings between all stages.
No Both ISU 301 Control Options must be set to
Advanced to view or adjust Finish With High Cool Stage.
This ISU is only displayed when the thermostat is set for 2 or more cool stages.
When set to Yes, this feature keeps the high stage of the cooling equipment running until the desired setpoint is reached.
No Both ISU 301 Control Options must be set to
Advanced to view or adjust Finish With High Heat Stage.
This ISU is only displayed when the thermostat is set for 2 or more heat stages.
When set to Yes, this feature keeps the high stage of the heating equipment running until the desired setpoint is reached.
15 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
303 Cool Differential
Stage 2
303 Cool Differential
Stage 3
305 Heat Differential
Stage 2
Note: Depending on the application, the text displayed on the screen may show the specific heating equipment type
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort
1.0°F - 4.0°F from setpoint (in
0.5° F increments)
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Residential, Commercial
or Both Notes
Comfort Both ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the thermostat is set to 2 cool stages.
The indoor temperature must rise to the selected differential setting before the thermostat turns on the stage of cooling. For example, if stage 2 is set to 2° F (1.0° C), the indoor temperature must be 2° F (1.0° C) away from the setpoint before stage 2 turns on. When set to Comfort, the thermostat uses the stage of cooling as needed to keep the indoor temperature within 1° F (0.5° C) degree of the setpoint.
Comfort Commercial ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the thermostat is set to 3 cool stages.
The indoor temperature must rise to the selected differential setting before the thermostat turns on the stage of cooling. For example, if stage 3 is set to 2° F (1.0° C), the indoor temperature must be 2° F (1.0° C) away from the setpoint before stage 3 turns on. When set to Comfort, the thermostat uses the stage of cooling as needed to keep the indoor temperature within 1° F (0.5° C) degree of the setpoint.
Comfort Both ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed for conventional systems that have 2 heat stages.
The indoor temperature must drop to the selected differential setting before the thermostat will turn on the stage of heating. For example, if stage 2 is set to 2° F (1.0° C), the indoor temperature must be 2° F (1.0° C) away from the setpoint before stage 2 turns on. When set to Comfort, the thermostat will use the stage of heating as needed to keep the indoor temperature within 1° F (0.5° C) degree of the setpoint.
33-00096—01 16
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
305 Heat Differential
Stage 3
Note: Depending on the application, the text displayed on the screen may show the specific heating equipment type
306 Compressor Heat
Diff. Stage 1
306 Compressor Heat
Diff. Stage 2
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Residential, Commercial
or Both Notes
Comfort Both ISU 301Temperature Control Options must be
set to Advanced to view or adjust this ISU.
This ISU is only displayed for conventional systems that have 3 heat stages.
The indoor temperature must drop to the selected differential setting before the thermostat will turn on the stage of heating. For example, if stage 3 is set to 2° F (1.0° C), the indoor temperature must be 2° F (1.0° C) away from the setpoint before stage 3 turns on. When set to Comfort, the thermostat will use the stage of heating as needed to keep the indoor temperature within 1° F (0.5° C) degree of the setpoint.
Comfort Both ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating Equipment is Geothermal Radiant and ISU 205 Geo Forced Air is set to Heating and Cooling.
The indoor temperature must drop to the selected differential setting before the thermostat will turn on the stage of heating. For example, if stage 1 is set to 2° F (1.0° C), the indoor temperature must be 2° F (1.0° C) away from the setpoint before stage 1 turns on. When set to Comfort, the thermostat will use the stage of heating as needed to keep the indoor temperature within 1° F (0.5° C) degree of the setpoint.
Comfort Both ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating Equipment is Air to Air Heat Pump, Geothermal or Geothermal Radiant and there are 2 compressor stages.
308, 309
Backup Heat Droop Stage 1
Note: “Stage 1" is not displayed if there is only 1 stage of Backup Heat.
Comfort
2.0° F to 15.0° F from setpoint (in 0.5° F increments)
The indoor temperature must drop to the selected differential setting before the thermostat will turn on the stage of heating. For example, if stage 2 is set to 2° F (1.0° C), the indoor temperature must be 2° F (1.0° C) away from the setpoint before stage 2 turns on. When set to Comfort, the thermostat will use the stage of heating as needed to keep the indoor temperature within 1° F (0.5° C) degree of the setpoint.
Comfort Both A backup heat droop can be set on any system
that has more than one heating equipment type.
See “Backup Heat Droop” beginning on page 54.
The Comfort setting is NOT available for Dual Fuel systems. For example, Heat Pumps with Gas Forced Air.
17 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
308, 309
Installer Setup
Name Settings Default
Backup Heat Droop Stage 2
311 Upstage Timer for
Backup Heat
312 Outdoor Lockout
Heat Pump
(Balance Point)
Comfort
2.0° F to 15.5° F from setpoint (in 0.5° F increments)
Off (30, 45, 60, 75, 90) minutes (2, 3, 4, 5, 6, 8, 10, 12, 14, 16)
hours
Off 5° F to 60° F (in 5° F increments)
Residential, Commercial
or Both Notes
Comfort Both ISU 301 Control Options must be set to
Advanced to view or adjust Backup Heat Droop Stage 2.
This ISU is only displayed if there are 2 backup heat stages.
The indoor temperature must drop to the selected droop setting before the thermostat will turn on backup heat stage 2. For example, if backup heat stage 2 is set to 2° F (1.0° C), the indoor temperature must be 2° F (1.0° C) away from the setpoint before backup heat stage 2 turns on. When set to Comfort, the thermostat will use backup heat stage 2 as needed to keep the indoor temperature within 1° F (0.5° C) degree of the setpoint.
Off Both The Backup Heat Upstage Timer starts when the
highest stage of the previous heating equipment type turns on. Backup heat will be used (if needed) when the timer expires. See “Backup Heat Upstage Timer” beginning on page 55.
This ISU is only displayed when Backup Heat Droop Stage 1 is set to 2 F or higher (ISU 308,
309).
Off
Both ISU 312 Heat Pump Outdoor Lockout requires
an outdoor sensor.
(See Notes)
Default is 40 F if ISU 201 Heating Equipment is Air to Air Heat Pump and ISU 218 Backup Heat Type is Gas/Oil.
312 Outdoor Lockout
Backup Heat
Off 5° F to 65° F (in 5° F increments)
Default is Off if ISU 201 Heating Equipment is Air to Air Heat Pump and ISU 218 Backup Heat Type is Electric.
Default is Off if ISU 201 Heating Equipment is Geothermal or Geothermal Radiant.
Heat Pump Outdoor Lockout is optional for any type of heat pump (Air to Air Heat Pump, Geothermal Heat Pump or Geothermal Radiant Heat).
See “Heat pump with outdoor temperature lockouts” beginning on page 56.
Off Both ISU 312 Backup Heat Outdoor Temperature
Lockout requires an outdoor sensor.
This ISU is only displayed if ISU 201 Heating Equipment is Air to Air Heat Pump, Geothermal or Geothermal Radiant and ISU 219 External fossil fuel kit is set to No.
See “Heat pump with outdoor temperature lockouts” beginning on page 56.
33-00096—01 18
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
313 Radiant Cycles
Per Hour Stage 1
Note: “Stage 1" is not displayed if there is only 1 stage of Radiant Heat.
314 Cool /
Compressor Cycles Per Hour Stage 1
Note: “Stage 1" is not displayed if there is only 1 stage.
314 Cool /
Compressor Cycles Per Hour Stage 2
314 Cool Cycles Per
Hour Stage 3
1 to 12 CPH
1 to 6 CPH
1 to 6 CPH
1 to 6 CPH
Residential, Commercial
or Both Notes
3 Both This ISU is only displayed when ISU 201
Heating Equipment is Geothermal Radiant.
The thermostat automatically defaults to the recommended setting for Geothermal Radiant Heat (3 CPH).
Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load.
3 Both This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load.
3 Both This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 2 stages.
Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load.
3 Commercial This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207 Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load.
19 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
315 Heat Cycles Per
Hour Stage 1
Note: Depending on the application, the text displayed on the screen may show the specific heating equipment type. “Stage 1" is not displayed if there is only 1 stage.
315 Heat Cycles Per
Hour Stage 2
Note: Depending on the application, the text displayed on the screen may show the specific heating equipment type.
1 to 12 CPH
1 to 12 CPH
Conv. Forced Air = 5 CPH Heat Pump = 3 CPH Radiant Heat = 3 CPH
Conv. Forced Air = 5 CPH Heat Pump = 3 CPH Radiant Heat = 3 CPH
Residential, Commercial
or Both Notes
Both This ISU is only displayed when ISU 207 Heat
Stages is set to 1 stage.
Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load. The recommended cycle rate settings are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH High Efficiency Gas Forced Air = 3 CPH Oil Forced Air = 5 CPH Electric Forced Air = 9 CPH Hot Water Fan Coil = 3 CPH Hot Water Radiant Heat = 3 CPH Geothermal Radiant Heat = 3 CPH Steam = 1 CPH Gravity = 1 CPH
Both This ISU is only displayed when ISU 207 Heat
Stages is set to 2 stages. Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load. The recommended cycle rate settings are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH High Efficiency Gas Forced Air = 3 CPH Oil Forced Air = 5 CPH Electric Forced Air = 9 CPH Hot Water Fan Coil = 3 CPH Hot Water Radiant Heat = 3 CPH Geothermal Radiant Heat = 3 CPH Steam = 1 CPH Gravity = 1 CPH
33-00096—01 20
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
315 Heat Cycles Per
Hour Stage 3
Note: Depending on the application, the text displayed on the screen may show the specific heating equipment type.
316 Backup Heat
Cycles Per Hour Stage 1
Note: “Stage 1" is not displayed if there is only 1 stage.
1 to 12 CPH
1 to 12 CPH
Conv. Forced Air = 5 CPH Heat Pump = 3 CPH Radiant Heat = 3 CPH
Electric = 9 CPH Gas / Oil = 5 CPH
Residential, Commercial
or Both Notes
Both This ISU is only displayed when ISU 207 Heat
Stages is set to 3 stages.
Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load. The recommended cycle rate settings are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH High Efficiency Gas Forced Air = 3 CPH Oil Forced Air = 5 CPH Electric Forced Air = 9 CPH Hot Water Fan Coil = 3 CPH Hot Water Radiant Heat = 3 CPH Geothermal Radiant Heat = 3 CPH Steam = 1 CPH Gravity = 1 CPH
Both This ISU is only displayed when ISU 207 or 213
Backup Heat Stages is set to 1 stage.
Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load conditions are less than or greater than a 50% load. The recommended cycle rate settings are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH High Efficiency Gas Forced Air = 3 CPH Oil Forced Air = 5 CPH Electric Forced Air = 9 CPH Hot Water Fan Coil = 3 CPH Hot Water Radiant Heat = 3 CPH Geothermal Radiant Heat = 3 CPH Steam = 1 CPH Gravity = 1 CPH
21 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
316 Backup Heat
Cycles Per Hour Stage 2
324 Compressor Off
Time
1 to 12 CPH
Off 1 - 5 minutes
Residential, Commercial
or Both Notes
Electric = 9 CPH
Both This ISU is only displayed when ISU 207 or 213
Backup Heat Stages is set to 2 stages. Gas / Oil = 5 CPH
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load. The recommended cycle rate settings
are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
5 minutes Both The thermostat has a built in compressor
protection (minimum off timer) that prevents
the compressor from restarting too early after a
shutdown. The minimum-off timer is activated
after the compressor turns off.
326 Extended Fan Run
Time in Cool
326 Extended Fan Run
Time in Heat
400 Scheduled
Periods
401 Pre-Occupancy
Purge
0, 30, 60, 90 seconds, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes
0, 30, 60, 90 seconds, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes
2 or 4 periods per day
Off 1 hour 2 hour 3 hour
If there is a call during the minimum-off timer,
the thermostat shows “Wait” in the display.
0 seconds Both After the call for cooling ends, the thermostat
keeps the fan on for the selected amount of time
for increased efficiency. This may re-introduce
humidity into the living space.
0 seconds Both After the call for heating ends, the thermostat
keeps the fan on for the selected amount of time
for increased efficiency.
4 periods per day Both Residential:
4 Periods = Wake, Leave, Return, Sleep
2 Periods = Wake, Sleep
Commercial:
4 Periods = Occupied 1, Unoccupied 1,
Occupied 2, Unoccupied 2
2 Periods = Occupied 1, Unoccupied 1
Off Commercial Runs the fan 1 to 3 hours before each occupied
period to provide a comfortable workplace upon
arrival.
33-00096—01 22
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
402 Type of Override
403 Override Duration
405 Min. Heat
Recovery Ramp Rate
Standard Initiate Occupancy
No Limit 1 to 12 Hours
Off 1° F/hr to 20° F/hr
Residential, Commercial
or Both Notes
Standard Commercial Standard:
The system maintains temperatures programmed for the occupied and unoccupied time periods. Pressing OVERRIDE will allow the user to make a temporary schedule change.
Initiate Occupancy: The system maintains temperature at an energy saving level until the user touches the message center area on the thermostat. Note: The message center displays Press HERE to Start Occupancy. The system will then maintain a comfortable temperature until the occupied period ends. This option is recommended for cost savings when the workplace is used infrequently or arrival times change from day to day (example - schools). After the user touches Press HERE to Start Occupancy, the user will still be able to perform a standard OVERRIDE of the schedule.
3 hours Commercial When the user presses the OVERRIDE button,
the thermostat will maintain the new temperature for at least 1 hour. The user can adjust the Hold Until time from 1 hour to the amount set for the Override Duration (1-12 hours). Default setting is 3 hours. If set to No Limit, the user can adjust the Hold Until time up to 24 hours.
5° F/hr Commercial Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the rate that the heating system can recover at for a cold day in your region. Default setting is 5° F / hour.
If an outdoor sensor is installed, set an Outdoor Temperature that is representative of a cold day in your region to be associated with the Minimum Recovery Ramp Rate. The thermostat will begin recovery at the optimal time based on a calculated ramp rate, allowing the system to recover on time and save energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor temperature. If there is no outdoor sensor, the Minimum Recovery Ramp Rate is used.
23 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
405 Min. Heat
Recovery Outdoor Temp
406 Max. Heat
Recovery Ramp Rate
Off
-20° F to 100°F
Off 1° F/hr to 20° F/hr
Residential, Commercial
or Both Notes
0° F Commercial Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a cold day in your region. Default setting is
5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day
in your region to be associated with the
Minimum Recovery Ramp Rate. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save energy
during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
8° F/hr Commercial Off: The heating system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a mild day in your region. Default setting is
8° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to be
associated with the Maximum Recovery Ramp
Rate. The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature.
33-00096—01 24
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
406 Max. Heat
Recovery Outdoor Temp
407 Min. Cool
Recovery Ramp Rate
Off
-20° F to 100° F
Off 1° F/hr to 20° F/hr
Residential, Commercial
or Both Notes
40° F Commercial Off: The heating system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the rate that the heating system can recover at for a mild day in your region. Default setting is 8° F / hour.
Set an Outdoor Temperature that is representative of a mild day in your region to be associated with the Maximum Recovery Ramp Rate. The thermostat will begin recovery at the optimal time based on a calculated ramp rate, allowing the system to recover on time and save energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor temperature.
3° F/hr Commercial Off: The cooling system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the rate that the cooling system can recover at for a hot day in your region. Default setting is 3° F / hour.
Set an Outdoor Temperature that is representative of a hot day in your region to be associated with the Minimum Recovery Ramp Rate. The thermostat will begin recovery at the optimal time based on a calculated ramp rate, allowing the system to recover on time and save energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor temperature. If there is no outdoor sensor, the Minimum Recovery Ramp Rate is used.
25 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
407 Min. Cool
Recovery Outdoor Temp
408 Max. Cool
Recovery Ramp Rate
Off
-20° F to 100° F
Off 1° F/hr to 20° F/hr
Residential, Commercial
or Both Notes
90° F Commercial Off: The cooling system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the cooling system can recover at
for a hot day in your region. Default setting is 3°
F / hour.
Set an Outdoor Temperature that is
representative of a hot day in your region to be
associated with the Minimum Recovery Ramp
Rate. The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
6° F/hr Commercial Off: The cooling system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based on
the rate that the cooling system can recover at
for a mild day in your region. Default setting is
6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to be
associated with the Maximum Recovery Ramp
Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature.
33-00096—01 26
Table 2. Installer Setup (ISU) Table. (Continued)
VISIONPRO® 8000 WITH WI-FI
®
ISU
Number
Installer Setup
Name Settings Default
408 Max. Cool
Recovery Outdoor Temp
409 Adaptive Recovery
Off
-20° F to 100°F
No Yes
Residential, Commercial
or Both Notes
70° F Commercial Off: The cooling system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the rate that the cooling system can recover at for a mild day in your region. Default setting is 6° F / hour.
Set an Outdoor Temperature that is representative of a mild day in your region to be associated with the Maximum Recovery Ramp Rate.
The thermostat will begin recovery at the optimal time based on a calculated ramp rate, allowing the system to recover on time and save energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate in degrees per hour depending on the outdoor temperature.
Yes Residential No: The system will begin heating or cooling
recovery at the scheduled time.
410 Minimum Cool
Setpoint
410 Maximum Heat
Setpoint
411 Keypad Lockout
500 Wired Sensor on
S Terminals
500 Wired Remote
Indoor Sensor
500 Wired Outdoor
Sensor
500 Wired Discharge
Sensor
50° F to 99° F
40° F to 90° F
Unlocked Partially Locked Fully Locked
No Yes
No Yes
No Yes
No Yes
Yes: The thermostat will begin heating or cooling recovery early to ensure that the temperature is reached at the scheduled time. The thermostat will adjust the start time of the equipment based on how quickly the scheduled temperature was reached on previous days. See page 52 for more information on Adaptive Intelligent Recovery.
50° F Both The user cannot set the temperature below this
level.
90° F Both The user cannot set the temperature above this
level.
Unlocked Both Unlocked: User has access to all thermostat
settings.
Partially Locked: User can modify only temperature settings.
Fully Locked: User cannot modify any settings.
No Both This ISU is only displayed if ISU 106 was
configured to Wired/Internet.
Select Yes if a wired indoor, outdoor, or discharge sensor is wired to S1.
No Both Select Yes if a wired indoor sensor is wired to
S1.
No Both Select Yes if a wired outdoor sensor is wired to
S1.
No Both Select Yes if a wired discharge sensor is wired
to S1
27 33-00096—01
VISIONPRO® 8000 WITH WI-FI
®
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
501 Indoor Sensor
Name
502 Indoor Sensor
503 Indoor Sensor
Type
504
Use [T-Stat Sensor] for Temp Ctrl
505 Outdoor Sensor
509 Discharge Sensor
510 Discharge Sensor
Type
[Select Indoor Sensor Name]
S1
10K 20K
Use T-Stat Sensor for Temp Ctrl ­Yes or No
S1
S1
10K 20K
Residential, Commercial
or Both Notes
Indoor Sensor Both Select a name (location) of the Wired Remote
Indoor Sensor.
Both Confirms type of sensor wired to S1.
10K:
if ISU 101
Both Select 10K or 20K based on the sensor
installed. Refer to resistance values below: Application is Residential
C7189U1005 = 10K ohm
C7772 = 20K ohm
20K:
if ISU 101: Application is Commercial
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A
must be used in combination with a TR21
sensor or another TR21-A sensor for the
thermostat to calculate the correct indoor
temperature reading).
See “Wiring guide — Wired Indoor Sensors”
beginning on page 88 for information on the
sensor type you should select based on how the
sensors are wired. For example, you would
select 20K when you have two TR21-A (10K)
sensors wired in series.
Sensors are Averaged (T-Stat Sensor and Remote)
Both Only displayed when a wired indoor sensor is
configured. Select Yes if you want the
thermostat to average with wired indoor sensor.
Select No if you want to sense temperature only
at the wired sensor.
Both Confirms type of sensor wired to S1.
Both Confirms type of sensor wired to S1.
10K Both Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
511 A-Coil Low Temp.
Cutoff
700 Filter Type
702 Number of Air
Filters
711 Air Filter 1
Reminder
Note: “1” is not displayed if there is only 1 filter.
Off 35° F to 65° F (in 5° F
increments)
None Elec. Air Cleaner Media
1 to 2
Off
Run Time: 10, 20, 30, 45, 60, 90, 120, 150
days
Calendar: 30, 45, 60, 75 days 3, 4, 5, 6, 9, 12, 15 months
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Off Both If an optional Discharge Sensor is used, this
feature can help prevent icing on the air
conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to a
safe level.
Media Both
1 Both
Off Both
33-00096—01 28
Loading...
+ 64 hidden pages